ComAp InteliVision 5 User manual

InteliVision 5, InteliVision 5 RD
InteliVision 5 Display
Controller Display Unit for InteliGen-NT, InteliSys-NT, InteliMains-NT
SW version 1.1, December 2011
Reference Guide
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 1
ComAp, spol. s r.o.
Kundratka 2359/17, 180 00 Praha 8, Czech RepublicCopyright © 2010 ComAp, spol. s r.o.
Tel: +420 246 012 111, Fax: +420 246 316 647Written by Martina Ťopková

Table of Contents
Introduction.............................................................................................................................................. 4
Available Related Documentation....................................................................................................... 5
Firmware and PC Software Supporting InteliVision 5......................................................................... 5
Fast Navigation........................................................................................................................................ 6
Main Icons Description........................................................................................................................ 6
Icons at the Top of InteliVision 5 Display........................................................................................ 6
Icons at the Bottom of InteliVision 5 Display ..................................................................................6
Communication Error.......................................................................................................................... 7
How to View a Controller Status ......................................................................................................... 8
How to View a Breaker Status ............................................................................................................ 8
How to Control Circuits Breakers?...................................................................................................... 8
How to Connect InteliVision 5 to IGS-NT?.......................................................................................... 9
How many InteliVisions 5 can be Used?............................................................................................. 9
How to Log in? .................................................................................................................................. 10
How to Enter a Password?................................................................................................................ 10
How to Change a Password?............................................................................................................ 12
How to Log out?................................................................................................................................ 12
How to Change a Gen-set Mode?..................................................................................................... 13
How to Find Alarms?......................................................................................................................... 13
How to Change Setpoints? ............................................................................................................... 14
How to Reprogram InteliVision 5?..................................................................................................... 15
How to Change Display Brightness?................................................................................................. 16
Operator Interface ................................................................................................................................. 17
LED and Buttons........................................................................................................................... 17
Navigation Buttons........................................................................................................................ 17
Context Buttons ............................................................................................................................ 18
Control Buttons............................................................................................................................. 18
Measurement Screens...................................................................................................................... 19
Setpoints Screens............................................................................................................................. 24
Numerical Value Change.............................................................................................................. 24
String Selection............................................................................................................................. 25
String Edit ..................................................................................................................................... 25
Time and Date Edit....................................................................................................................... 26
Combined Setpoints...................................................................................................................... 26
Unauthorized access message.....................................................................................................27
AlarmList Screen............................................................................................................................... 28
Where to Find Alarms:.................................................................................................................. 28
History Screen................................................................................................................................... 30
Help/Others Menu............................................................................................................................. 31
Language...................................................................................................................................... 31
User/Password.............................................................................................................................. 31
Communication............................................................................................................................. 32
Controller info................................................................................................................................ 32
Modules info.................................................................................................................................. 32
IV5 Info.......................................................................................................................................... 33
IV5 Settings................................................................................................................................... 33
Service Screen.............................................................................................................................. 33
Other features ................................................................................................................................... 35
User buttons.................................................................................................................................. 35
Support of the internal buzzer (IV5-RD) ....................................................................................... 35
Unauthorized access message.....................................................................................................36
Access level indication.................................................................................................................. 36
Message “Controller is locked”..................................................................................................... 36
Change of all label color............................................................................................................... 37
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 2

Installation.............................................................................................................................................. 38
Terminals and Dimensions................................................................................................................ 38
How to Connect InteliVision 5 to IG-NTx-BB .................................................................................... 39
How to Connect InteliVision 5 (Detail of InteliVision 5 Socket)......................................................... 39
How to Connect InteliVision 5 to IS-NTx-BB..................................................................................... 40
Technical Data....................................................................................................................................... 41
HW Modification................................................................................................................................ 41
Power Supply.................................................................................................................................... 41
Operating Conditions ........................................................................................................................ 41
Standard Conformity......................................................................................................................... 41
Dimensions and Weight.................................................................................................................... 41
Communication Interface.................................................................................................................. 42
LCD Display ...................................................................................................................................... 42
List of Possible Events .......................................................................................................................... 43
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 3

InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 4
Introduction
InteliVision 5 is the 5,7” colour display unit for ComAp InteliGen-NT, InteliSys-NT and InteliMains-NT
controllers. It is designed as a Plug and Play solution and it presents simple solution with high visibility
of all engine and gen-set data, monitoring information in colourful direction.
The new screens correspond to wide variety of daily usage and offer significant step ahead.
The compact size, robustness and user-friendly design introduce valuable solution for every day
usage where more information on the screen and display size is preferred alternative.
The same cut-out across all Comaps’ products helps InteliVision 5 to be easily used as a replacement
of or alternative to IG-Display. Regardless of the size it can be also used as an alternative to IS-
Display or InteliVision8.
InteliVision 5 is designed to be connected to the single controller only.
InteliVision 5 is offered in two hardware modifications:
•a local display unit (InteliVision 5)
•a remote version (InteliVision 5 RD) - unit with galvanic separated RS-485, analogue input and
binary output and internal buzzer.
InteliVisoin 5 and InteliVision 5 RD differ only by HW. All SW features, setting and programming are
the same for the both versions.

Available Related Documentation
PDF files Description
IGS-NT-2.6-Installation Guide.pdf Installation guide for IG-NT(C), IS-NT, IM-NT,
IG-NT(C)-BB, IS-NT(C)-BB, IM-NT-BB, IV5, IV8
IGS-NT-SPTM-2.6-Reference Guide.pdf Reference Guide for IGS-NT-SPTM
IGS-NT-SPI-2.6-Reference Guide.pdf Reference Guide for IGS-NT-SPI
IGS-NT-MINT-2.6-Reference Guide.pdf Reference Guide for IGS-NT-MINT
IGS-NT-COMBI-2.-Reference Guide.pdf Reference Guide for IGS-NT-COMBI
IGS-NT-COX-2.6-Reference Guide.pdf Reference Guide for IGS-NT-COX
IGS-NT-2.6-New Features.pdf New Features List of IGS-NT
Firmware and PC Software Supporting InteliVision 5
Firmware – InteliVision 5 is supported from following versions:
Mhx file
IS-NT-2.6
IG-NT-2.6
IM-NT-2.9
PC Software – InteliVision 5 is supported from following versions:
PC Software
GenConfig-2.6
InteliMonitor-2.6
Installation Package – InteliVision 5 is supported from following versions:
Installation Package
IGS-NT-Install-Suite-2.6
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 5

Fast Navigation
This chapter provides information on how to quickly find important data. To be more familiar with
InteliVision 5 menu, see Operator Interface chapter.
Notation : InteliVision 5 and InteliVision 5 RD differ only by HW modification (see chapter HW
Modification). All below described features, setting and programming
Main Icons Description
Icons at the Top of InteliVision 5 Display
- Terminal is locked; no user is logged in
- Terminal is NOT locked; user is logged in
- Access lock is active; display is locked for security reasons
- Remote communication; when any remote connection to controller is active
Icons at the Bottom of InteliVision 5 Display
- Mains icon; green/red = voltage, frequency are/are not in the limits
- Load icon; green/grey = voltage, frequency are in the limits/no available power source
- Gen-set icon; green/grey = voltage, frequency are in the limits/out of the limits or not
started
- Red exclamation mark; a new alarm occur in the alarm list
- Red button; breaker failure MCB/GCB fail
- Green button; closed breaker
- Button contour; opened breaker
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 6

Icons Referring to Specific Screens
- Menu screen
- Measurement screens
- Setpoints screen
- Alarm list screen
- History screen
- Help/Others screen
Communication Error
Communication error occurs when no control unit is connected to the display or communication is
interrupted. In that case the following screen appears:
When the communication between unit and display is fixed, the red stripe disappears and InteliVision
5 initializes communication with the unit.
Hint:
The control unit is identified by InteliVision 5 and only valid numbers of terminal addresses are
displayed. For the maximum number of connected InteliVision 5 see How many InteliVisions 5 can be
used?
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 7

How to View a Controller Status
Controller status is displayed in the left bottom part of the screen. Status depends on the external
conditions and it is updated immediately when any condition is changed.
Hint:
For more information about controller status see relevant Reference guide e.g. IGS-NT-SPtM-2.5.pdf
How to View a Breaker Status
Breakers status is present in all default controller screens. Single line diagram defines Mains and gen-
set condition.
Status is represented with following colours:
- represent breaker failure e.g. MCB fail
- represents closed breaker
- represents opened breaker
Pressing corresponding button results in following actions:
Open MCB (GCB) – command Open MCB (GCB)
Close MCB (GCB) – command Close MCB (GCB)
Hint:
Mode button and command buttons are disabled when active lock is active. SW button link has gray
link around (when no colour background is used) and dark green or dark red when breaker status is
highlighted.
How to Control Circuits Breakers?
Breakers can be controled in MAN mode only. Breaker control button is placed in bottom part of
InteliVision 5 display. See picture bellow:
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 8

How to Connect InteliVision 5 to IGS-NT?
InteliVision 5 is connected to the controller via RS-485 line. Connection is fixed after the unit is
powered up and the control unit is detected. Communication error screen disappears. InteliVision 5
identifies connected controllers and configuration is read automatically without any additional dialogue.
When terminal address has to be changed for any reason:
1. Press Menu button and choose Help/Others menu
2. Use ↑or ↓for Communication item and press Enter
3. Use ↑or ↓and choose appropriate Terminal Adr and press Enter, see picture below.
InteliVision 5 will reboot and the new terminal address will be used. Loss of communication is
presented with the first screen, with SW version, HW version and release date. Communication
timeout error is displayed with terminal address dialogue.
When InteliVision 5 is connected to IS-NTC BB, there can be connected up to 3 IV5. When “terminal
Adr.“ dialog is chose, all terminals are automatically detected . Available NT terminal addresses are
displayed by green color. Color of active (occupied) NT terminals is red.
Hint
For the information how to connect InteliVision 5 to the controller go to the Installation guide 2.5 or
Terminals and dimension chapter.RS 485 terminators have to be used to assure proper functionality.
To avoid electrical disturbances on long distances or where electrical disturbance is present use
InteliVision 5 RD.
How many InteliVisions 5 can be Used?
Unit Number of displays Display address
IG-NT(C) –BB 2 1 and 2
IS-NTC – BB 3 1, 2, 3
IM-NT-BB 2 1 and 2
IG-NT(C) 1 2
IS-NT-BB 3 1, 2 ,3
IM-NT 1 2
Hint
For how to set up InteliVision 5 address see How to Connect InteliVision 5 to IGS-NT?
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 9

How to Log in?
To enter a controller user:
1. Press Menu button.
2. Use ↑or ↓to choose Help/Others and press Enter
3. Use ↑or ↓to choose Users/Password menu item
4. Use ↑or ↓to go to Users field and press Enter.
5. Use ↑or ↓to set the correct user and press Enter. See the picture below:
Hint
The controller is unlocked only when proper password is inserted.
When user is log in. Green lock is displayed in the right upper corner and appropriate access level is
indicated. See figure below.
How to Enter a Password?
To enter a controller password:
1. Press Menu button.
2. Use ↑or ↓to choose Help/Others and press Enter
3. Use ↑or ↓to choose Users/Password menu item
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 10

4. Use ↑or ↓to go to EnterPassword field and press Enter.
5. Use →or ←to select the digit and use ↑or ↓to set the number you need to enter. See the
picture below:
It is possible to set Password protection feature.
Hint:
Password protection features should be activated in InteliMonitor in Password Menu. In default the
feature is inactive.
In case when Password protection choice is activated and a user inserts wrong password for six times
(the number of attempts can change according to new controller SW version) to log into the controller,
the controller is automatically locked for next login. When the controller is locked and user tries to login
into the controller, message (see figure below).
"Controller is locked. Try entering correct password after X min" is displayed.
Message informs about time remaining for unlocking of controller. The time in message is not
actualized. For actual time, user should open login dialog again.
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 11

How to Change a Password?
To change a controller password:
1. Log in, see the chapter How to log in and How to enter a password.
2. Press Menu button.
3. Use ↑or ↓to choose ChangePassword and press Enter button
4. Use →or ←to select the digit and use ↑or ↓to set the number you need to enter. See the
picture below:
How to Log out?
To log out:
1. Press Menu button.
2. Use ↑or ↓to choose Help/Others, press Enter
3. Use ↑or ↓to choose Users/Password menu item and press Enter
4. Use ↑or ↓to choose Logout and press Enter.
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 12

How to Change a Gen-set Mode?
To Change a Gen-set Mode:
1. Press Mode context button (See the picture).
2. Use ↑or ↓to choose menu item and press Enter
How to Find Alarms?
To find alarms:
1. Press Menu button
2. Use ↑or ↓to choose menu item AlarmList and press Enter.
3. Or use context button AlarmList to jump directly to Alarm list.
Hint:
In the first measurement screen controller will jump to the alarm list immediately when any alarms
occurs.
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 13

How to Change Setpoints?
To change setpoints:
1. Press Menu button.
2. Use ↑or ↓to choose Setpoints item, press Enter
3. Use ↑or ↓to choose required setpoints group and press Enter.
4. Use ↑or ↓to choose requested setpoint and press Enter.
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 14

How to edit setpoints see Setpoints Screens chapter.
How to Reprogram InteliVision 5?
To reprogram InteliVision 5 use GenConfig PC SW.
1. Run GenConfig
2. Connect communication cable (appropriate type according to the module used) between the
controller and PC.
3. Select direct connection
4. Go to menu CONTROLLER -> PROGRAMMING AND CLONNING -> DISPLAY GC FONT CHANGE /FW
UPGRADE.
5. Follow instructions given by a message which appeared and finally press WRITE TO DISPLAY.
Hint
For more details see Communication Guide and GenConfig Reference Guide.
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 15

How to Change Display Brightness?
The brightness of display can be changed by holding Menu button and repeated pressing ↑or ↓. See
the picture below:
hold
press
or press
Two modes are available in InteliVision 5.To switch between Day or Night mode hold Menu button
only. Pictogram for day or night appears on the screen.
To change day or night brightness intensity:
1. Hold Menu button until day / night mode on the screens appear
2. Press and hold Menu button with ↑or ↓to change brightness intensity
Hint:
Brightness setting has priority in this order: controller forced brightness InteliVision’s 5 analogue input,
keyboard. When the analogue input is used, small pictograms in brightness sub-menu appears.
Display backlight could be switched off (standby) due to Backlight Time. For recover any button has to
be pressed (see IV5 Settings) or in case of new incoming alarm, the display awakes from standby
mode and backlight of the display is activated.
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 16

Operator Interface
This chapter provides general information on how to operate the InteliVision 5 display. This manual is
intended for everybody who is concerned with operation and controls of the gen-set.
1
4 2
3
LED and Buttons
1. Status - Status LED indication (green = InteliVision 5 is running)
2. Navigation buttons - Arrows for movement + Menu and Enter button
3. Context buttons - Control or select submenu/sub-options buttons
4. Control buttons - Horn reset, Fault reset, Stop and Start buttons
Navigation Buttons
There are four navigation buttons:
1. ↑- Movement up
2. ↓- Movement down
3. Menu - Jump to menu/sub-menu page or escape from any dialog window
4. Enter - Confirms a value or opens a value adjustment within setting dialogs
Hint:
To leave the menu, use Menu button.
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 17

Context Buttons
There are five context buttons with predefined meaning:
1. Mode button - Jump to the controller mode window
2. History - Jump to history screen
3. Alarm - Jump to Alarm list
4. GCB control - GCB control (close/open GCB)
5. MCB control - MCB control (close/open MCB)*
Hint:
MCB control button is present only in application where MCB is controlled.
Context buttons may be modified by users to fulfill customer’s requirements (see chapter User
definable SoftKeys buttons).
Control Buttons
There are four control buttons:
1. Start - Starts the gen-set
2. Stop - Stops the gen-set
3. Fault reset - Acknowledges faults and alarms (active only in Alarm screen)
4. Horn reset - Deactivates the horn (audible alarm)
4 1
3 2
Hint:
Start and Stop buttons work in MAN or SEM mode only. START and STOP buttons are independent
on the InteliVision 5 screen, menu or sub-menu.
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 18

Measurement Screens
On Measurement screen you can see and check various values. Measurement screens appear after
the InteliVision 5 and controller are powered up and initialize sequence disappears. The first
Measurement screen always appears when no user activity is captured during fifteen minutes.
Arrows ↑or ↓are used for measurement screens browsing.
IGS-NT Measurement screens come after each other in following order:
1. Main screen - Main
2. Generator overview - Gen
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 19

3. Mains overview - Mains
4. Power overview – Power
5. Alternator overview - Gen-set power
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 20