CT-KNX Gateway Protocol
Quickstart
COMM-TEC GMBH SIEMENSSTRASSE 14 TELEFON 07161/30 00-0 WWW.COMM-TEC.DE
D-73066 UHINGEN TELEFAX 07161/30 00-400
Sett ng the F ltertable and commun cat on w th the gateway
a) First set the Interface parameter
b) Press the Green arrow for connecting to the
Gateway
c) type a ? and <Return> in the text field here. If
you are connected you get a list of commands
from the gateway, which shows everything is
working properly.
d) You can test the commands from the first page
for reading and writing here
Setting the Filtertable
Set the option for Echo (1)
Press the transmitt button (6)
Enter the group adress you want to read or
programm in the fiels (2)
Choose the correct Datatype of the variable(3)
Press the button (4) for accepting your selection
Repeat the last 3 steps until all your needed
adresses are entered
If you have entered all needed adresses send
them to the gateway by pressing button (5)
For later use save the content of the filtertable in
a textsheet (7). This is optional not needed
NOTE:
If your Media control system is reconfiguring the
filtertable by itself. You do not need to manually set
the filtertable.
Sample
What you need from a EIB/KNX programmer to set up your Gateway:
Address Type Description Parameters Read or write
1 / 4 / 100 1 Bit Lamp 1 0 – off 1- on write
1 / 1 / 103 4 Bit Lamp 1 Dimmer write
1 / 4 / 102 1 Byte Lamp 1 get value
absolut 0-255 read
1 / 4 / 101 1 Byte Lamp 1 set value
absolut 0 - 255 write