CommPact Control system User manual

Installation Manual
For quick installation information please refer to the CommPact
Quick Start Installation Guide provided on our website: www electronics-line com

ii
Table of Contents
1. Introduction ................................................................................................................................................................................ 1
1.1. Documentation Conventions...................................................................................................................................1
1.2. Specifications..........................................................................................................................................................2
1.3. System Overview ....................................................................................................................................................3
1.4. Hardware Layout.....................................................................................................................................................4
2. System Installation..................................................................................................................................................................... 7
2.1. Pre-Installation Planning .........................................................................................................................................7
2.2. Installation Procedure .............................................................................................................................................8
2.3. Back Tamper ........................................................................................................................................................12
2.4. Internet Communication Setup .............................................................................................................................12
3. Basic System Operation .......................................................................................................................................................... 14
3.1. Front and Back Panel Layouts..............................................................................................................................14
3.2. Front Panel System Status LEDs .........................................................................................................................15
3.3. Front Panel Keypad ..............................................................................................................................................15
3.4. LCD Display ..........................................................................................................................................................16
3.5. Audible Notification ...............................................................................................................................................17
3.6. Setting and Unsetting............................................................................................................................................18
3.7. Additional Setting Options.....................................................................................................................................21
4. Advanced System Operation................................................................................................................................................... 23
4.1. Menu Navigation ...................................................................................................................................................23
4.2. Cancel Report .......................................................................................................................................................24
4.3. Zone Omitting .......................................................................................................................................................24
4.4. User Codes ...........................................................................................................................................................24
4.5. Follow-Me..............................................................................................................................................................27
4.6. Event Log..............................................................................................................................................................27
4.7. Service Menu ........................................................................................................................................................28
5. Telecontrol and Two-Way Audio ............................................................................................................................................. 34
5.1. Incoming Calls ......................................................................................................................................................34
5.2. Outgoing Calls.......................................................................................................................................................36
6. PGM Control.............................................................................................................................................................................. 38
6.1. Keyfob Control ......................................................................................................................................................38
6.2. Telephone Control ................................................................................................................................................38
7. Devices...................................................................................................................................................................................... 39
7.1. Device Descriptors................................................................................................................................................39
7.2. Wireless Devices ..................................................................................................................................................39
7.3. Zones ....................................................................................................................................................................41
7.4. Keyfobs .................................................................................................................................................................45
7.5. Wireless Keypads .................................................................................................................................................46
7.6. Repeaters .............................................................................................................................................................47
7.7. Wireless Sounder .................................................................................................................................................47
8. Entry/Exit Timers and System Tones...................................................................................................................................... 49
8.1. Entry/Exit Delay.....................................................................................................................................................49
8.2. Set on Exit.............................................................................................................................................................49
8.3. Supplementary Entry Delay...................................................................................................................................49
8.4. Entry Deviation......................................................................................................................................................50
8.5. Setting Tones........................................................................................................................................................50
8.6. System Trouble Tones..........................................................................................................................................51

iii
8.7. Tones Options.......................................................................................................................................................52
9. System Options......................................................................................................................................................................... 53
9.1. Code Lockout........................................................................................................................................................53
9.2. Set/Unset Options.................................................................................................................................................53
9.3. Panic Alarm...........................................................................................................................................................54
9.4. AC Loss Delay ......................................................................................................................................................55
9.5. Display Options .....................................................................................................................................................55
9.6. PGM Output Options.............................................................................................................................................56
9.7. "No Set" Indication ................................................................................................................................................58
9.8. Jamming Detection ...............................................................................................................................................58
9.9. "No Motion" Time ..................................................................................................................................................58
9.10. Vocal Messages....................................................................................................................................................59
9.11. Engineer Access ...................................................................................................................................................59
9.12. Daylight Savings....................................................................................................................................................59
9.13. Entry/Exit Trouble..................................................................................................................................................59
9.14. Report Fail Trouble ...............................................................................................................................................60
9.15. Immediate Setting from WUApp ...........................................................................................................................60
10. Communications....................................................................................................................................................................... 61
10.1. System Reporting..................................................................................................................................................61
10.2. Report Cycles........................................................................................................................................................63
10.3. Vocal Message Dialer ...........................................................................................................................................63
10.4. Remote Programming...........................................................................................................................................65
10.5. Service Call ...........................................................................................................................................................67
10.6. Communications Options......................................................................................................................................67
10.7. GSM Options.........................................................................................................................................................70
10.8. TWA Event Report Options...................................................................................................................................72
10.9. Event Options for Central Station Reporting.........................................................................................................74
10.10. Vocal Message Dialer Event Options ...............................................................................................................75
11. Internet Options .......................................................................................................................................................................... 77
11.1. ELAS Connection Parameters ..............................................................................................................................77
11.2. Control System Parameters..................................................................................................................................77
11.3. GPRS Network Parameters..................................................................................................................................78
12. System Initialization ................................................................................................................................................................. 79
12.1. Initialization............................................................................................................................................................79
12.2. Default Program Restore ......................................................................................................................................79
12.3. Clear User Codes..................................................................................................................................................79
12.4. Clear Wireless Transmitters .................................................................................................................................79
Appendix A: Menu Structure ............................................................................................................................................................. 80
Appendix B: Transmitter Installation................................................................................................................................................ 87
PIR Detectors (EL-2645/EL-2645PI)..................................................................................................................................87
Directional PIR (EL-2650XL)..............................................................................................................................................90
Wireless PIR (EL-2652SR) ................................................................................................................................................95
Magnetic Contact (EL-2601)..............................................................................................................................................99
Universal Transmitter (EL-2602)......................................................................................................................................101
Glassbreak Detector (EL-2606) .......................................................................................................................................102
Vibration Detector (EL-2607) ...........................................................................................................................................106
Smoke Detector (EL-2703) ..............................................................................................................................................108
Keyfobs (EL-2711M / EL-2711P / EL-2614E and EL-2714).............................................................................................116
1-Way Wireless Keypad (EL-2620)..................................................................................................................................117
Wireless Indication Keypad (EL-2621).............................................................................................................................118

iv
Flood Detector (EL-2661) ................................................................................................................................................120
Gas Leak Detector (EL-2762)..........................................................................................................................................122
Carbon Monoxide Detector (EL-2764) .............................................................................................................................125
Outdoor Sounder and Strobe (EL-2626AC).....................................................................................................................130
Repeater (EL-2635) .........................................................................................................................................................133
Transmitter Specifications................................................................................................................................................136
Appendix D: Event Table................................................................................................................................................................. 139
Appendix E: Zone Types ................................................................................................................................................................. 142

1 Introduction
CommPact Installation Manual
1
1. Introduction
This manual is designed to help you install the CommPact Control System1. We strongly urge you
to read through this manual, in its entirety, before beginning the installation process so that you can
best understand all that this security system has to offer. This manual is not intended for end user
use. End users are encouraged to read the user manual provided with the system. f you have any
questions concerning any of the procedures described in this manual please contact Electronics Line
3000 Ltd. at (+972-3) 963-7777.
1.1. Documentation Conventions
Throughout the manual, we have tried to include all of the operating and programming functions
using a similar structure and order as they appear in the menu. A detailed explanation of how to
navigate the Control System’s menu is included in p. 23, 4.1 Menu Navigation. n order to simplify
the procedures that appear in the rest of this manual, the following conventions are used:
Table 1-1: Documentation Conventions
Item Description
Select Use the arrow keys to scroll through the options and press '√'
From the Event Log Menu,
select Clear Log. Enter the main menu by pressing 3and entering your user code. Using the arrow
keys, navigate until you reach Event Log and press √. Using the arrow keys,
navigate until you reach Clear Log and press '√'.
From the Service menu,
select Time/Date, Set Date.
The same as above only this time you are navigating through three menu levels.
[7012] The shortcut to a specific menu item from the main menu. In this case, this is the
shortcut for Set Date. These appear in the procedures as an additional aid to menu
navigation.
[#5] A shortcut to a specific item in a sub-menu. For example, [#5] is the shortcut to Bell
enable disable in the sub-menu that is opened once you have selected the detector
you want to program.
√The symbol on a key that appears on the Front Panel keypad
5. Interface Test The text that actually appears on the CommPact LCD display (bold).
Due to the occurrence Important note, please pay attention.
The CommPact Control
System is
Caution: description of a potentially hazardous situation.
Warning Do not test
with flame!
Warning: description of a potentially hazardous situation that is a threat to
human life.
1The terms Control System, Control Panel, and CP refer to the same notion.

1 Introduction
CommPact Installation Manual
2
1.2. Specifications
General
Zones: 32 wireless zones (1 transmitter per zone), 1
hardwire zone (Zone 33).
Wireless Keyfobs: 19 (Controlled or Non-controlled)
Wireless Keypads: up to 4, including one way or two-
way
Repeaters: 4
Wireless Sounder: 1 (2-way)
User Codes: 32
Setting Methods: Full, Part or Perimeter.
Event Log: 1022 event capacity, time and date stamped
Weight: 1.350g
Dimensions: 210x153x40 mm
Communications
Event Reporting Accounts: up to 6, including Central
Station, Follow-Me, and Voice.
Telephone Numbers: 6 event reporting accounts, RP
Callback, Service Call.
Communication Interface Options: GPRS, GSM, PSTN.
Receiver
Type: Super-heterodyne, fixed frequency
Frequency: 418MHz, 868.35 or 433.92 (optional).
Data Encryption: SecuriCode™
Electrical
*
Power Input: 230VAC, 50Hz, 120VAC, 60Hz/9VAC,
15VA (Model 1332)
AC Current Consumption: 30mA (alarm), 17mA
(standby)
DC Current Consumption: 280mA (alarm), 130mA
(standby)
Maximum Auxiliary Output Current Rating : 50mA
Battery low: below 7.15V
Backup Battery Pack: 4.8V 1.3Ah Part No. BT3021
(4 x 1.2 NiMH, size AA, rechargeable cells,)
The maximum charging current for the BT-5780 is 1.8 Ah
Fuse Ratings: 63mA/250V for 230VAC – Part No.
EF1063,
PGM Relay Output Contact Rating: 100mA (max. load)
Built-in Sounder: 93dB @ 10ft
Tamper Switch: N.C.
Operating Temperature: -10°C to 55°C (14°F to 131°F)
* The measurements are with fully charged battery. AC current was measured on fuse F1 and DC current was measured
on fuse F2.
!
Power connection to the unit should be according to the national electrical code for
permanent installation.
The power supply should be fed from a readily accessible disconnect device.
If the unit is permanently wired to the mains power, use a 2-pole disconnect device (15A max.)
and the wires should be min. 0.75mm2in a conduit of at least 16mm.
If the mains power is connected with a plug, the plug should be indicated as the disconnecting
device and the socket shall be max. 2m from the Control System.
Batteries shall be provided by a distributor and replaced by authorized service personnel.
The backup battery pack should be replaced every five years.
Batteries should be stored in a cool, dry place.

1 Introduction
CommPact Installation Manual
3
1.3. System Overview
The CommPact Control System is a full-featured wireless Control System that is expected to
provide a solution to the needs of most residential installations. This system has been developed
based upon a design concept geared towards easy installation and use. With this in mind, the user
interface is based on a simple, menu-driven model that suits the essential requirements of both the
user and engineer alike. You can program the CommPact Control System on-site using the Front
Panel keypad or PC, or off-site via a PC using local programming option of the Remote
Programmer.
The system offers GPRS network connectivity, providing high-speed central station reporting via a
GPRS interface.
The Electronics Line Application Server (ELAS) handles all communication between the system,
service providers and web users enabling monitoring and control to be performed via the Web.
Backup communication is carried out via PSTN or GSM.
Central station communication and remote parameters programming and maintenance employ
GPRS, GSM or standard PSTN communication. SMS messaging provides an innovative method
used for both central station and Follow-Me user monitoring. Additionally, SMS messages can be
sent to the Control System enabling the user to send commands to the system from anywhere on
the planet.
Figure 1-1 shows the components that make up the system and the system’s interaction with
external communication networks for all the available configurations.

1 Introduction
CommPact Installation Manual
4
Figure 1-1: System Architecture
1.4. Hardware Layout
The aim of this section is to acquaint you with the circuit boards that make up the system. The
CommPact Control System housing has two PCBs: the Main Board and the Power Supply and
Connections Board.

1 Introduction
CommPact Installation Manual
5
1.4.1. Main Board
The Main Board is the brain of the system. t coordinates all the Control System activity.
The Main Board (see Figure 1-2) enables GSM and GPRS communication that allows reporting
events to the Central Station send or receive SMS messages, implement cellular Two-Way Audio
and remote software update.
This Board also has a standard dialer for communication via the Public Switched Telephone
Network (PSTN). Backup communication with event reporting, and Two-Way Audio (TWA) are
also available via PSTN.
The Main Board also has connectors to the Built-in Sounder and the Speaker.
Additionally, the Main Board includes a USB port for PC programming.
Figure 1-2: Main Board
1. Built-in Sounder Connector
2. Buzzer
3. LCD Contrast Control
4. USB Port
5. SIM-Card Holder
6. Speaker Connector
7. Flat-Cable Interface Connector to the Power Supply and
Connections Board
8. Sounder Strength Control Jumper (JP1)
Table 1-2: Main Board Jumper Settings
JPI Sounder Strength
(see Figure 1-2, Main Board)
Installed: 105dB
Removed: 85dB
Do not use VoIP phone lines for communication to the central monitoring station.
In certain cases the system may not transmit alarm signals successfully over the
VoIP network.
To reduce the risk of fire, use only o. 26AWG or larger telecommunication wire.
Flat cable (8) is not Removable!

1 Introduction
CommPact Installation Manual
6
1.4.2. Power Supply and Connections Board
As the name suggests, the Power Supply and Connections Board has the AC and battery connectors,
power connection fuses, and the transformer. This Board also serves as the interface to the PGM
programmable output, the Hardwire Zone, Telephone, Telephone Line, and Back Tamper. On the rear
side of the Board, there is a battery switch that allows applying battery power at first installation.
Figure 1-3: Power Supply and Connections Board
1. AC Power Connector
(N=Neutral, L=Live)
2. AC Fuse
3. Terminal Block
4. Back Tamper Connector
5. AC to AC Transformer
6. Front Tamper Switch
7. Flat-Cable Interface Connector to the Main Board
8. Battery Connector
9. PGM Control Jumper (JP1)
Table 1-3: Jumper Settings
JPI PGM (see Figure 1-3, Power Supply
and Connections Board)
Installed: Open Collector
Removed: Dry Contact

2 System Installation
CommPact Installation Manual
7
2. System Installation
The following chapter explains how to install the system and provides guidelines and tips on how
to optimize the installation.
t is recommended that you familiarize yourself with the various circuit boards that make up the
system – see p. 4, 1.4 Hardware Layout.
2.1. Pre-Installation Planning
Before starting the installation procedure, it is worthwhile to draw a rough sketch of the building
and determine the required position for the Control System and each wireless device.
When deciding on the placement for installation, consider the following:
•Mount the Control System in a location with easy access to telephone and power
connections.
•Mount the Control System in a location that provides easy connection to the router.
•For best performance of the GPRS Communication, the Control System should be
mounted in a position where the GSM signal is strong.
•Refer to the following section in order to choose the optimal location for wireless
devices in relation to the Control System.
2.1.1. Wireless Installation Guidelines
n order to optimize wireless communication, consider the following guidelines:
•Whenever possible, mount the Control System centrally in relation to wireless
detectors.
•Avoid installation in close proximity to sources of high noise or radio frequency
interference. For example, metal air conditioner/heater ducts and circuit breaker
boxes.
•Minimize the distance between the Control System and transmitters.
•Minimize the number of obstacles between the Control System and transmitters.
Figure 2-1: Minimizing Obstacles
•Metal based construction materials, such as steel reinforced concrete walls, reduce the
range of radio transmissions.
Figure 2-2: Considering Construction Materials

2 System Installation
CommPact Installation Manual
8
•The reduction of the RF signals’ strength is directly proportional to the thickness of
the obstacle, assuming that the obstacles are of identical material.
Figure 2-3: Considering Thickness of Obstacles
2.2. Installation Procedure
The CommPact Control System Kit consists of:
•Control System
•Quick Start nstallation Guide
•Quick User Guide
•Mounting Guide
•Plastic bag with Cable Clamp, Cable Clamp screw, Housing Screw,
After unpacking the kit and making certain that you have all the necessary equipment, it is
recommended that you install the system as follows:
STAGE 1: Temporarily power up the system and install the S M card.
STAGE 2: Selecting language and defaults
STAGE 3: Register the transmitters.
STAGE 4: Test the chosen mounting location.
STAGE 5: Program the relevant nternet options.
STAGE 6: Permanently nstall the Control System and Transmitters
2.2.1. Stage 1 – Temporarily Power Up the System
n order to register and test transmitters, it is necessary to temporarily power up the Control
System before permanently installing it.
1. nsert a screwdriver between the front and back panels of the housing; carefully twist it
to release the tabs (see p. 8, Figure 2-4).
Figure 2-4: Opening the Housing
2. Thread the Power AC cable through the hole in the back cover. Connect it to the AC
cable connector on the PCB and secure it by Cable Clamp (see p. 9, Figure 2-5).
The Control System is su lied without AC cable. Please use Standard Two-Pin Euro ean
Plug cable only. For the Cable Clam , use the screw and the washer su lied in your kit to
re lace the PCB screw.

2 System Installation
CommPact Installation Manual
9
3. Open the S M card holder on the Main Board; insert the S M card* (see p. 5, Figure 1-2 ).
4. Close the Housing.
5. Plug the Power AC cable into the wall outlet.
In five minutes since ower-u , the sounder will sound. To silence the sounder, ress your
user code (default user code is 1234).
At this stage, do not connect the backup battery. gnore any trouble conditions that
may appear on the LCD Display (e.g. Low Battery).
Figure 2-5: Main Board Wiring Scheme
2.2.2. Stage 2: Selecting Language and Defaults
The Control System supports several languages. Language and defaults settings must be defined
before any configuration parameters are set or any transmitters registered.
Setting language and defaults automatically initializes the Control System. This means that
all rior configuration settings are reset to the default settings and all reviously registered
transmitters are deleted from the Control System.
To select language and defaults:
1. Press '√ʹ.
2. Enter your Engineer code (the default Engineer code is 1111).
3. From the Programming menu, select Devices [971].
4. Select default and press '√ʹ.
5. Select language (Voice + LCD display) and press '√ʹ.
6. Press '√ʹ once more to initialize the Control System
2.2.3. Stage 3 – Register the Transmitters
For the Control System to recognize a device, its transmitter must be registered. n general terms,
transmitter registration means sending two transmissions from a device when the Control System is
in Registration mode.
To register a device:
1. Press '√ʹ.
2. Enter your Engineer code.
3. From the Programming menu, select Devices [91].
4. Select the type of transmitter you want to register. For example, if you want to register a
wireless detector to a zone, select Zones.
*optional feature

2 System Installation
CommPact Installation Manual
10
5. Select the specific device you want to register (for example, Zone 4); the system initiates
Registration mode. During Registration mode, the system waits for two transmissions
from the device.
If a device has already been registered at the selected location, the system will not initiate
Registration mode. If the device has already been registered at another location, attem ts to
register it are ignored by the system. Zones 1-32 are intended for wireless detectors
6. Register the device – refer to each device’s installation instructions in Appendix B for
further details.
7. When two transmissions have been received, Save? is displayed.
Press '√ʹ to confirm registration.
8. Continue entering other parameters for the chosen device.
9. Press Χ to exit menu mode.
2.2.4. Stage 4 – Test the Chosen Mounting Location
Once all of the transmitters are registered, it is recommended that you test the chosen mounting
locations before permanently mounting the Control System and wireless devices. You can test the
transmitter signal strength using the TX Test feature.
To test transmitter signal strength:
1. Press '√ʹ.
2. Enter your Engineer code.
3. Enter [7072] (Service, Transmitters, and TX Test) to initiate TX Test mode.
4. Activate the transmitter you wish to test; the transmitter’s details appear on the Control
System’s LCD. Additionally, between one and four tones are sounded to indicate the
transmitter’s signal strength. f four tones are sounded, the transmitter is in the best
possible location – see p. 30, 4.7.7 Transmitters for further information.
5. After you have tested each transmitter, press Χ to exit TX Test mode.
When using GPRS and/or GSM communication, test the GSM signal strength.
To test the GSM signal strength:
1. Press '√ʹ.
2. Enter your Engineer code.
3. Enter [7091] (Service, RF & GSM level, GSM Signal); RF RSS level measured by the
system's receiver – see p. 31, 4.7.9 GSM Signal Strength for further information.
Check the RF RSS (Received Signal Strength ndication) level using the system’s RSS meter.
To view the RF RSS level reading:
•Enter [7092] (Service, RF & GSM level, RF RSS Level); the RF noise measured by the
system's receiver is displayed – see p. 32, 4.7.10 RF RSS level for further information.

2 System Installation
CommPact Installation Manual
11
2.2.5. Stage 5 – Program Internet Options
The Electronics Line Application Server (ELAS) handles all communication between the system,
service providers and web users, enabling monitoring and control to be performed via the Web.
nternet settings are mostly pre-programmed in the Control System’s default settings. The only
settings you need to program are the Control System’s connection settings and control system
parameters (provided by the ELAS administrator). The following procedures explain how to
program the Control System’s D (CP D) and Password. For further information regarding other
nternet options and settings, see p. 77, 11 nternet Options.
To program the ELAS P Address and Port:
1. Press '√ʹ.
2. Enter your Engineer code.
3. Enter [9571] (Programming, Communications, nternet, and XMP Proxy D).
4. Enter the P address of the ELAS and press '√ʹ.
5. Enter the XML port of the ELAS and press '√ʹ.
For MyELAS, define the IP address as 195.219.118.21 and the Port as 33000.
If the end user is to erform the self registration on-line then the following CPID and CP
Password ste s are not required.
To program the CP D:
1. Press '√ʹ.
2. Enter your Engineer code.
3. Enter [9573] (Programming, Communications, nternet, and CP D).
4. Enter an D using the alphanumeric keypad. The D length must be six up to sixteen characters.
The D must begin with a letter.
5. Press '√ʹ.
To program the Control System’s password:
1. Press '√ʹ.
2. Enter your Engineer code.
3. Enter [9574] (Programming, Communications, nternet, and CP Password).
4. Enter a password using the alphanumeric keypad.
The password length must be six up to sixteen characters. The password must begin
with a letter.
5. Press '√ʹ.
2.2.6. Stage 6 – Permanently Install the Control System and Transmitters
Having chosen and tested the mounting location of the Control System and each transmitter, you
are now ready to permanently install the system.
To permanently install the transmitters, refer to each device’s installation instructions in Appendix
B of this manual or to those supplied individually with each product.
To install the Control System:
1. Place the drilling template against the wall and mark the mounting holes.

2 System Installation
CommPact Installation Manual
12
2. nstall 2 wall anchors and screws leaving 2-3mm out of the wall.
The Control System must be mounted so that it shall withstand a force of at least three times
its own weight.
3. Disconnect (unplug) AC power from the Control System.
4. Open the housing (see p. 8, Figure 2-4).
5. Thread any required cables through the hole in the back cover.
6. Connect the optional Telephone Line, Telephone, Wired Zone, and PGM to their
connectors on the Main Board terminal block – see p. 9, Figure 2-5.
7. Plug the AC power cable into the outlet.
Always connect AC ower before connecting the battery ack. Batteries are su lied
uncharged. When you first connect the battery, it is robable that the system will dis lay a
Low Battery condition. Allow the battery to charge for at least 18 hours before use.
8. Connect the Backup Battery to its connector on the Main Board – see p.6 Figure 1-3.
9. Mount the Control System to the wall by hanging the back cover onto the screws.
Make sure that the back tam er is closed.
10. Close the housing making sure that the front and back covers click shut. Apply the
housing screw at the bottom of the panel.
2.3. Back Tamper
The Back Tamper switch is an optional feature that provides an extra safeguard in the event that the
Control System is removed from the wall.
The Back Tamper switch is located on the rear side of the Control System’s housing and is
constantly depressed while the panel is hanged tightly on the screw.
2.4. Internet Communication Setup
After you have powered up the system, the GPRS startup sequence is initiated. During this
sequence, the parameters programmed in the Control System's nternet Options (see – p. 77, 11
nternet Options) are activated. After the startup sequence is complete, the Control System attempts
to connect to the ELAS GPRS Proxy.
f the Control System is having difficulty connecting to ELAS, a trouble message is displayed. The
following table summarizes the trouble messages for this case.
Table 2-1: ELAS Connection Trouble Message
LCD Display Trouble condition Restored by
SIM CARD TROUBLE SIM card not recognized or incorrectly
programmed
Insertion of recognized SIM card
or correct programming.
MEDIA LOSS GSM Cellular network down Cellular network restore
DEVICE TROUBLE GSM Faulty GSM/GPRS module Replacement of faulty module
MEDIA LOSS GPRS
MODULE
Wrong GPRS settings (APN, Password
etc.) or loss of GPRS service
Correct GPRS settings or restored
GPRS service
XML FAIL Control panel fails to communicate with the
XML Proxy
Successful communication with
XML Proxy
n this case, check that the Control System’s nternet Options are correctly programmed. f
you still experience problems, the P Protocol and GPRS settings must be checked.

2 System Installation
CommPact Installation Manual
13
To check the P Protocol and GPRS settings:
1. Open the PCB Compartment and make sure a S M Card with GPRS support is on the
PCB – see p. 14 Figure 3-2.
2. Close the housing and enter your Engineer code.
3. Enter [95112] (Programming, Communications, Accounts, Account 1, and Protocol).
f the setting is correct, you will see " P Protocol".
4. Exit this menu and Enter [95113] (Programming, Communications, Accounts, Account 1,
nterface). f the setting is correct, you will see "GPRS".
When using a SIM card with a PI code, the engineer has to make sure that the PI code
programmed in the Control System is the same as the SIM card's PI code – see p. 8,
10.7.2 PI Code.

3 Basic System Operation
CommPact Installation Manual
14
3. Basic System Operation
3.1. Front and Back Panel Layouts
The front panel provides a detailed interface for operating and programming the system. The
following diagram will familiarize you with the various elements of the front panel.
Figure 3-1: Front Panel
Next diagram shows the Control System's back panel that provides access to the S M card, the USB
Connector and the battery power switch used at first installation – see Figure 3-2 below.
Figure 3-2: Back Cover
Alphanumeric
Keypad
Setting
Keys
LCD
Display
OK
LED
Arm
Status
LED
Menu
Navigation
Keys

3 Basic System Operation
CommPact Installation Manual
15
3.2. Front Panel System Status LEDs
The two LEDs, OK and Set Status, provide essential information on the status of the system.
Table 3-1: OK LED Indication
OK LED Status Meaning
Off Both AC and Battery power are disconnected.
Green On System Power Status is OK and there is no System Trouble.
Green Flashing Open Zone. Check that the windows and doors are closed and no movement is
detected by the detectors within the protected area.
Yellow On System Trouble.
Yellow Flashing (slow) Backup battery low or low battery from transmitters.
Yellow Flashing (fast) AC loss.
Yellow Intermittent
On/Off
System Trouble in addition to AC loss/Low Battery.
Table 3-2: Set Status LED Indication
LED Status Meaning
Off The system is unset.
Green On The system is set.
Red Flashing An alarm has occurred. Alarm indication is cleared the next time you set the
system or view the relevant setting event in the event log.
Alarm indication is not dis layed after a silent anic alarm.
3.3. Front Panel Keypad
The alphanumeric keypad on the front panel enables you to perform various operation and
programming tasks. Apart from Full, Part, and Perimeter setting, the front panel keypad offers a
number of special functions.
Table 3-3: Front Panel Keypad Functions
Key Symbol used in
the text of this
manual
Special function
1Used to enter symbols in descriptor editing.
0Used to enter symbols in descriptor editing.
Χ Used to cancel the current selection.
Used to return to the previous menu level.
√ Used to enter Menu mode.
Used to select the current menu item.
Used to signify the end of an entered value.
Toggles status in Zone Omit/Un-omit function.

3 Basic System Operation
CommPact Installation Manual
16
In descriptor editing, used to insert a space before the current character
In phone number editing, used to enter "T", ",", "P", "+", "*", "#".
In account number editing, used to enter Hexadecimal digits (A-F).
Toggles item descriptors and default names.
In the event log, toggles the time/date stamp.
Toggles AM and PM when setting the time in 12hr format.
In descriptor and phone number editing, used to delete the current
character
Used to scroll backwards in the current menu level.
For Global Chime and Message Center features, used to access
shortcuts.
+ (Global Chime shortcut)
+ Χ (Record Message shortcut, front panel keypad only)
+ √ (Play Message shortcut, front panel keypad only)
Used to scroll forwards in the current menu level.
During standby, used to scroll through the list of system trouble
conditions.
3.4. LCD Display
The LCD display provides you with a detailed interface for operation and programming.
3.4.1. Standby Mode
Standby mode can be defined as the state the system is in when it is unset and not in Menu mode.
n Standby mode, the set status, system status, or banner is displayed. f system status is normal,
the current time is displayed.
Table 3-4: Set Status
Item Description
UNSET The system is unset.
FULL SET
The system has been set using the displayed setting method.
PART SET
PERIMETER SET
PART SET INST The system has been set using the displayed setting method with the Instant set
feature activated.
PERIM SET INST
FULL SETTING
The system is in the process of setting (displayed during exit delay).
PART SETTING
PERIMETER SETTING
Table of contents