manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Computime
  6. •
  7. Control Unit
  8. •
  9. Computime SALUS PL07 User manual

Computime SALUS PL07 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Pump and boiler logic module for KL06 wiring centre
Model: PL07
[EN] XI 2018
Introduction
Technical Information
PL07 module extend a functionality of KL06 wiring centre.
Module is used to control the pump and the boiler using volt-free
COM/NO contacts. When any of thermostats connected to the
KL06 230V reports heat demand, COM/NO contacts are closing.
COM/NO contacts are opening, when thermostats connected to
the wiring centre will stop sending signal for heating.
Product Compliance
This product complies with the essential requirements and
other relevant provisions of the following EU Directives: EMC
2014/30/EU, Low Voltage Directive LVD 2014/35/EU, RoHS
directive 2011/65/EU. The full text of the EU Declaration of
Conformity is available at the following internet address:
www.saluslegal.com.
Safety information
Use in accordance to national and EU regulations. Use the device
as intended, keeping it in dry condition. Product for indoor use
only. Installation must be carried out by a qualied person in
accordance to national and EU regulations.
Before any of operation releated to power supply (connecting
wires, installing the device, etc.), make sure that devices is not
connected to any power source. Installation must be carried out
by a qualied person. Incorrect connection of the wires may
cause damage to the wiring centre. The module can not be
used in conditions of water vapor condensation neither exposed
to water.
Serial connector for PL06 and PL07 modules
It provides communication between the KL06 wiring centre and
the PL07 module. KL06 wiring centre + PL07 module increases
functionality and additionally makes possible to control pump
and boiler. PL07 module is powered from the wiring centre.
ON OFF
34
DelayOverrun
ON OFF
12
123456
fuse
(T2A)
LN LN LN LN LN LN
LN
CON1
Manual
Importer:
SALUS Controls plc
Salus House, Dodworth Business Park
Whinby Road, Barnsley S75 3SP,
United Kingdom
www.salus-controls.com
SALUS Controls is a member of the Computime Group.
Maintaining a policy of continuous product development SALUS
Controls plc reserve the right to change specification, design
and materials of products listed in this brochure without prior notice.
Power Supply from the KL06 wiring centre
Max load 5 (2) A
Outputs 2 x NO/COM relay
Dimensions [mm] 70 x 80 x 20
Make sure that all the wires are properly connected,
mount top cover and power up the wiring centre
- the green„Power”indicator LED will illuminate.
3
Jumpers description
Wiring diagrams
ON-OFF Delay jumper
Is used to activate the delay output for the pump and boiler.
Default is„ON”.
• „ON” position activates the pump and
boiler outputs with a delay of 3 minutes
after the heating signal is supplied
from any of the thermostats connected
to the wiring centre.
• „OFF” position causes immediate
activation of the pump and boiler
outputs.
ON-OFF Overrun jumper
Is used to activate the delay output for the pump when heating
is satised. Default is„ON”.
• „ON” position turns OFF the pump
output with a delay of 3 minutes when
all thermostats stop calling for heat.
• „OFF” position immediately turns OFF
the pump output when all thermostats
stop calling for heat.
PUMP AND BOILER CONTROL
INSTALLATION OF THE ADDITIONAL MODULE
1
Remove the top cover of the wiring centre.
Note: Before connecting module, disconnect the main
power from the KL06 wiring centre.
2
Connect the module to the serial connector.
ON OFF
34
DelayOverrun
ON OFF
12
123456
fuse
(T2A)
LN LN LN LN LN LN
LN
CON1
ON OFF
34
DelayOverrun
ON OFF
12
123456
fuse
(T2A)
LN LN LN LN LN LN
LN
CON1
230 V AC
ON OFF
34
DelayOverrun
ON OFF
12
123456
fuse
(T2A)
LN LN LN LN LN LN
LN
CON1
ON OFF
34
DelayOverrun
ON OFF
12
123456
fuse
(T2A)
LN LN LN LN LN LN
LN
CON1
L
L
N
N
Boiler ON/OFF contacts
(according to the boiler’s
manual)
PE
max 5 (2) A