Control Techniques Commander SE SE11200025 User manual

RGB ELEKTRONIKA AGACIAK CIACIEK
SPÓŁKA JAWNA
Jana Dlugosza 2-6 Street
51-162 Wrocław
Poland
biuro@rgbelektronika.pl
+48 71 325 15 05
www.rgbautomatyka.pl
www.rgbelektronika.pl
DATASHEET
www.rgbautomatyka.pl
www.rgbelektronika.pl
OTHER SYMBOLS:
SE23400150
CONTROL TECHNIQUES

YOUR
PARTNER IN
MAINTENANCE
At our premises in Wrocław, we have a fully equipped servicing facility. Here we perform all the repair
works and test each later sold unit. Our trained employees, equipped with a wide variety of tools and
having several testing stands at their disposal, are a guarantee of the highest quality service.
OUR SERVICES
ENCODERS
SERVO
DRIVERS
LINEAR
ENCODERS
SERVO AMPLIFIERS
CNC
MACHINES
MOTORS
POWER
SUPPLIERS
OPERATOR
PANELS
CNC
CONTROLS
INDUSTRIAL
COMPUTERS
PLC
SYSTEMS
Repair this product with RGB ELEKTRONIKA ORDER A DIAGNOSIS ∠
Buy this product at RGB AUTOMATYKA BUY ∠

www.controltechniques.com
EF
User Guide
Commander SE
Sizes 1 to 5
Variable speed drive for 3 phase induction motors
from 0.25kW to 37kW
Part Number: 0452-0061
Issue Number: 8

General Information
The manufacturer accepts no liability for any consequences resulting from inappro-
priate, negligent or incorrect installation or adjustment of the optional operating pa-
rameters of the equipmentorfrom mismatchingthevariablespeed drive (Drive) with
the motor.
The contentsof this User Guideare believed to be correct atthe time of printing. In
the interests of a commitment to a policy of continuous development and improve-
ment, the manufacturer reserves the right to change the specification of the product
or its performance, or the contents of the User Guide, without notice.
All rights reserved. No parts of this User Guide may be reproduced or transmitted
in any form or by any means, electrical or mechanical including photocopying, re-
cording or by an information storage or retrieval system, without permission in writ-
ing from the publisher.
Drive software version
This product is supplied with thelatest version of user-interface and machine control
software. If this product is to be used in a new or existing system with other Com-
mander SE Drives, there may be some differences between their software and the
software in this product. These differences may cause this product to function dif-
ferently. This may also applyto Drives returned from a ControlTechniques Service
Centre.
If there is any doubt, contact a Control Techniques Drive Centre.
Copyright © December 2001 Control Techniques Drives Limited
Issue Code: 8
Software: V02.00.00 onwards

Commander SE User Guide
Issue Number 8
Contents
1 Safety Information 1
1.1 Warnings, Cautions and notes 1
1.2 Electrical safety - general warning 1
1.3 System design and safety of personnel 1
1.4 Environmental limits 2
1.5 Compliance with regulations 2
1.6 Motor 2
1.7 Adjusting parameters 2
2Options 3
3 Technical Data 4
3.1 Power dependant rating data 4
3.2 General data 12
3.3 RFI Filters 14
4 Installing the drive 16
4.1 Safety information 16
4.2 Planning the installation 16
4.3 Mechanical installation 17
4.4 Electrical installation 23
4.5 Electromagnetic compatibility (EMC) 27
5 Terminals 34
5.1 Power terminal connections 34
5.2 Control terminal connections 35
5.3 Serial communication connections 36
5.4 Control terminal specifications 37
6 Handling and Programming 40
6.1 Display and keypad 40
6.2 Display Messages 41
6.3 Selecting and changing parameters 41
6.4 Saving parameters 42
6.5 Security codes 42
6.6 Setting a security code 42
6.7 Unlocking a security code 43
6.8 Set security back to zero (0) - no security 43
6.9 Setting to default values 43
6.10 Level 1 and level 2 parameter descriptions 43
7 Getting Started - Bench Testing 61
7.1 Terminal control 61
7.2 Keypad control 63
8 Diagnostics and Protective Features 65
8.1 Trip codes 65
8.2 Alarm warnings 67
8.3 HF-Hardware fault trip codes 67

Commander SE User Guide
Issue Number 8
9 Parameter List 68
10 Advanced Functions 69
10.1 Speed control 69
10.2 Ramps 69
10.3 Torque control 69
10.4 Stopping 69
10.5 Programmable I/O 69
10.6 Motor protection 69
10.7 Monitoring 69
10.8 Auxiliary functions 69
10.9 Second motor selection 69
11 UL Listing Information 70
11.1 Common UL information 70
11.2 Power dependant UL information 70

Commander SE User Guide
Issue Number 8
Declaration of Conformity
Control Techniques, The Gro, Newtown, Powys, UK. SY16 3BE
The AC variable speed drive products listed above, have been designed and manufactured in
accordance with the following European harmonised, national and international standards:
*Applies to Size 1 units only.
**SE11200025, SE11200037, SE11200055: input choke required. All other units where input
current <16A: for professional use only.
***Applies to the following models: SE11200025 - SE11200075, SE2D200075, SE2D200110,
SE23400075 - SE23400220, SE23400300, SE23400400, SE33400550, SE33400750.
These products comply with the Low Voltage Directive 73/23/EEC, the Electromagnetic
Compatibility (EMC) Directive 89/336/EEC and the CE Marking Directive 93/68/EEC.
These electronic Drive products are intended to be used with appropriate motors,
controllers, electrical protection components and other equipment to form complete end
products or systems. Compliance with safety and EMC regulations depends upon installing
and configuring Drives correctly, including using the specified input filters. The Drives
must be installed only by professional assemblers who are familiar with requirements for
safety and EMC. The assembler is responsible for ensuring that the end product or system
complieswithalltherelevantlawsinthecountrywhereitistobeused.RefertothisUser
Guide. A Commander SE EMC Data Sheet is also available giving detailed EMC information.
SE11200025 SE11200037 SE11200055 SE11200075
SE2D200075 SE2D200110 SE2D200150 SE2D200220 SE23200400
SE23400075 SE23400110 SE23400150 SE23400220 SE23400300 SE23400400
SE33200550 SE33400550 SE33200750 SE33400750 SE43401100 SE43401500
SE43401850 SE53402200 SE53403000 SE53403700
EN60249 Base materials for printed circuits
IEC60326-1 Printed boards: general information for the specification writer
IEC60326-5 Printed boards: specification for single- and double-sided printed boards with plated-
through holes
IEC60326-6 Printed boards: specification for multilayer printed boards
IEC60664-1 Insulation co-ordination for equipment within low-voltage systems: principles, requirements
and tests
EN60529 Degrees of protection provided by enclosures (IP code)
UL94 Flammability rating of plastic materials
UL508C Standard for power conversion equipment
*EN50081-1 Generic emission standard for the residential, commercial and light industrial environment
EN50081-2 Generic emission standard for the industrial environment
EN50082-2 Generic immunity standard for the industrial environment
EN61800-3 Adjustable speed electrical power drive systems - Part 3: EMC product standard including
specific test methods
**EN61000-3-2 Electromagnetic compatibility (EMC). Limits. Limits for harmonic current emissions
(equipment input current <16A per phase)
***EN61000-3-3 Electromagnetic compatibility (EMC). Limits. Limitation of voltage fluctuations and flicker in
low-voltage supply systems for equipment with rated current < 16A
W. Drury
Executive VP Technology
Date: 1 November 2001

1Commander SE User Guide
www.controltechniques.com Issue Number 8
1 Safety Information
1.1 Warnings, Cautions and notes
AWarning contains information which is essential for avoiding a safety hazard.
ACaution contains information which is necessary for avoiding a risk of damage to
the product or other equipment.
ANote contains information which helps to ensure correct operation of the product.
1.2 Electrical safety - general warning
The voltages used in the drive can cause severe electrical shock and/or burns, and
could be lethal. Extreme care is necessary at all times when working with or adjacent to
the drive.
Specific warnings are given at the relevant places in this User Guide.
1.3 System design and safety of personnel
The drive is intended as a component for professional incorporation into complete
equipment or a system. If installed incorrectly, the drive may present a safety hazard.
The drive uses high voltage and currents, carries a high level of storedelectrical energy,
and is used to control equipment which can cause injury.
Close attention is required to the electrical installation and the system design to avoid
hazards, either in normal operation or in the event of equipment malfunction. System
design, installation, commissioning and maintenance must be carried out by personnel
who have the necessary training and experience. They must read this safetyinformation
and this User Guide carefully.
The STOP function of the drive does not remove dangerous voltages from the output of
the drive or from any external option unit.
Careful consideration must be given to the functions of the drive which might result in a
hazard, either through their intended functions or through incorrect operation due to a
fault.
In any application where a malfunction of the drive could lead to damage, loss or injury,
a risk analysis must be carried out, and where necessary, further measures taken to
reduce the risk.
The STOP and START controls or electrical inputs of the drive must not be relied
upon to ensure safety of personnel. If a safety hazard could exist from
unexpected starting of the drive, an interlock that electrically isolates the drive
from the AC supply must be installed to prevent the motor being inadvertently
started.
To ensure mechanical safety, additional safety devices such as electro-mechanical
interlocks and overspeed protection devices may be required. The drive must not be
used in a safety critical application without additional high integrity protection against
hazards arising from a malfunction.
Under certain conditions, the drive can suddenly discontinue control of the motor. If the
load on the motor could cause the motor speed to be increased (e.g. in hoists and
cranes), a separate method of braking and stopping must be used (e.g. a mechanical
brake).
WARNING
CAUTION
NOTE

Commander SE User Guide 2
Issue Number 8 www.controltechniques.com
1.4 Environmental limits
Instructions in this User Guide regarding transport, storage, installation and use of the
drive must be complied with, including the specified environmental limits. Drives must
not be subjected to excessive physical force.
1.5 Compliance with regulations
The installer is responsible for complying with all relevant regulations, such as national
wiring regulations, accident prevention regulations and electromagnetic compatibility
(EMC) regulations. Particular attention must be given to the cross-sectional areas of
conductors, the selection of fuses or other protection, and protective earth (ground)
connections.
This User Guide contains instruction for achieving compliance with specific EMC
standards.
Within the European Union, all machinery in which this product is used must comply
with the following directives:
• 97/37/EC: Safety of machinery.
• 89/336/EEC: Electromagnetic Compatibility.
1.6 Motor
Ensure the motor is installed in accordance with the manufacturer’s recommendations.
Ensure the motor shaft is not exposed.
Standard squirrel cage induction motors are designed for single speed operation. If it is
intended to use the capability of the drive to run a motor at speeds above its designed
maximum, it is strongly recommended that the manufacturer is consulted first.
Low speeds may cause the motor to overheat because the cooling fan becomes less
effective. The motor should be fitted with a protection thermistor. If necessary, an
electric forced vent fan should be used.
1.7 Adjusting parameters
Some parameters have a profound effect on the operation of the drive. They must not
be altered without careful consideration of the impact on the controlled system.
Measures must be taken to prevent unwanted changes due to error or tampering.

3Commander SE User Guide
www.controltechniques.com Issue Number 8
2Options
The following options are available for Commander SE;
•Quickey for rapid parameter transfer (SE55)
• Standard and low earth leakage footprint / side mounting RFI filters and low cost
panel mounting RFI filters
• Universal Keypad, IP65, hand held or door mounting plain text, LCD display
•SESoftWindows
™based set-up software for advanced programming
• +10V to -10V analog input card for bi-directional input reference (SE51)
• Cable screening bracket and screening clamps to provide a convenient way of
connecting supply, motor and control cable screens to ground (SE11, 12, 13, 14 &
15) (SE15 for Size 5 control cables only)
• EMC Data Sheets
• Through hole mounting plate drawings to allow heatsink to be put outside main
cubicle (Size 2 ~ 4 only)
• EIA232 to EIA485(2 wire) converter for connecting betweenthe driveand PC when
using SE Soft (SE71 Communications lead)
• Fieldbus Communications:
Profibus DP (SE73)
Device Net (SE77)
CAN Open (SE77)
Interbus (SE74)
•Commander SE Advanced User Guide: (See Chapter 10 Advanced Functions on
page 69 for a list of advanced functions).
• AC input line reactors
• Braking resistors and mounting plate (Size 2 ~ 4 only)
For further details on the above options and availability, contact your local Control
Techniques Drive Centre or Distributor.

Commander SE User Guide 4
Issue Number 8 www.controltechniques.com
3 Technical Data
3.1 Power dependant rating data
Model code explanation
SE 1 1 2 xxxxx Drive kilowatt rating: 00025 = 0.25kW etc.
Drive voltage rating: 2 = 230V, 4 = 400V
Number of input phases: 1 = 1∅,3=3∅,D=1∅and 3∅
Frame size.
Table 3.1 Commander SE Size 1
* See section 3.1.1.
** For an explanation of inrush current, see section 3.1.2.
Table 3.2 Recommended supply fuses and cables
MODEL SE11200...
025 037 055 075
AC supply voltage and frequency Single phase 200 - 240V +/- 10% 48 - 62Hz
Input displacement factor (cos φ) >0.97
Nominal motor power - kW 0.25 0.37 0.55 0.75
Nominal motor power - hp 0.50 1.0
Output voltage and frequency 3 phase, 0 to input voltage, 0 to 1000Hz
100% RMS output current - A 1.5 2.3 3.1 4.3
150% overload current for 60 secs - A 2.3 3.5 4.7 6.5
Typical full load input current - A* 5.6 6.5 8.8 11.4
Typical inrush current - A** (duration <10ms) 100
Drive power losses at 230Vac at 6kHz switching
frequency - W 18 24 37 56
Weight - kg/lb 1.1/2.4 1.25/2.75
Cooling fan fitted No
MODEL SE11200...
025 037 055 075
Recommended input supply fuse - A 6 10 16
Control cable mm² ≥0.5
AWG 20
Recommended input cable mm² 1.0 1.5
AWG 16 14
Recommended motor cable mm² 1.0
AWG 16

5Commander SE User Guide
www.controltechniques.com Issue Number 8
Table 3.3 Commander SE Size 2, 200V dual rated units
* See section 3.1.1.
** For an explanation of inrush current, see section 3.1.2.
Table 3.4 Recommended supply fuses and cables
Table 3.5 Braking resistors
* Based on recommended braking resistor value.
Before fitting a braking resistor please read the information on Braking, and the
Warnings on High Temperatures and Overload Protection at the end of this
section.
MODEL SE2D200...
075 110 150 220
AC supply voltage and frequency Single or 3 phase 200 to 240V +/- 10%, 48 to 62Hz
Input displacement factor (cos φ) >0.97
Nominal motor power - kW 0.75 1.1 1.5 2.2
Nominal motor power - hp 1.0 2.0 3.0
Output voltage and frequency 3 phase, 0 to input voltage, 0 to 1000Hz
100% RMS output current - A 4.3 5.8 7.5 10.0
150% overload current for 60 secs - A 6.5 8.7 11.3 15.0
Typical full load input current - A* 1ph/3ph 11.0 5.5 15.1 7.9 19.3 9.6 26.2 13.1
Typical inrush current - A**(duration <10ms) 55 35
Drive power losses at 230Vac at 6kHz switching
frequency - W 54 69 88 125
Weight - kg/lb 2.75 / 6
Cooling fan fitted No Yes
MODEL SE2D200...
075 110 150 220
1ph 3ph 1ph 3ph 1ph 3ph 1ph 3ph
Recommended input supply fuse - A 16 10 20 16 25 16 32 20
Control cable mm² ≥0.5
AWG 20
Recommended input cable mm² 1.5 1.0 2.5 1.5 2.5 1.5 4.0 2.5
AWG1416121412141012
Recommended motor cable mm² 1.0 1.5
AWG 16 14
Recommended braking resistor cable mm² 1.0 1.5
AWG 16 14
MODEL SE2D200...
075 110 150 220
Minimum braking resistor value - Ω50 40
Recommended braking resistor value - Ω100 75 50
Resistor peak power rating - kW* 1.8 2.4 3.5
NOTE

Commander SE User Guide 6
Issue Number 8 www.controltechniques.com
Table 3.6 Commander SE Size 2, 200V Three phase units
* See section 3.1.1.
** For an explanation of inrush current, see section 3.1.2.
Table 3.7 Recommended supply fuses and cables
Table 3.8 Braking resistors
* Based on recommended braking resistor value.
Before fitting a braking resistor please read the information on Braking, and the
Warnings on High Temperatures and Overload Protection at the end of this
section.
MODEL SE23200400
AC supply voltage and frequency 3 phase 200 to 240V +/- 10%, 48 to 62Hz
Input displacement factor (cos φ) >0.97
Nominal motor power - kW 4
Nominal motor power - hp 5
Output voltage and frequency 3 phase, 0 to input voltage, 0 to 1000Hz
100% RMS output current - A 17.0
150% overload current for 60 secs - A 25.5
Typical full load input current - A* 21
Typical inrush current - A** (duration <10ms) 35
Drive power losses at 230Vac at 6kHz switching
frequency - W 174
Weight - kg/lb 2.75 / 6
Cooling fan fitted Yes
MODEL SE23200400
Recommended input supply fuse - A 32
Control cable mm² ≥0.5
AWG 20
Recommended input cable mm² 4.0
AWG 10
Recommended motor cable mm² 2.5
AWG 12
Recommended braking resistor cable mm² 2.5
AWG 12
MODEL SE23200400
Minimum braking resistor value - Ω30
Recommended braking resistor value - Ω30
Resistor peak power rating - kW* 5.9
NOTE

7Commander SE User Guide
www.controltechniques.com Issue Number 8
Table 3.9 Commander SE Size 2, 400V Three phase units
* See section 3.1.1.
** For an explanation of inrush current, see section 3.1.2.
Table 3.10 Recommended fuses and cables
Table 3.11 Braking Resistors
* Based on recommended braking resistor value.
Before fitting a braking resistor please read the information on Braking, and the
Warnings on High Temperatures and Overload Protection at the end of this
section.
MODEL SE23400...
075 110 150 220 300 400
AC supply voltage and frequency 3 phase 380 to 480V +/- 10%, 48 to 62Hz
Input displacement factor (cos φ) >0.97
Nominal motor power - kW 0.75 1.1 1.5 2.2 3.0 4.0
Nominal motor power - hp 1.0 2.0 3.0 5.0
Output voltage and frequency 3 phase, 0 to input voltage, 0 to 1000Hz
100% RMS output current - A 2.1 3.0 4.2 5.8 7.6 9.5
150% overload current for 60 secs - A 3.2 4.5 6.3 8.7 11.4 14.3
Typical full load input current - A*400V, 50Hz/480V, 60Hz 3.6 4.8 6.4 9.3 11 14
Typical inrush current - A** (duration <10ms) 90 60
Drive power losses at 480Vac at 6kHz switching
frequency - W 43 57 77 97 122 158
Weight - kg/lb 2.75 / 6
Cooling fan fitted No Yes
MODEL SE23400...
075 110 150 220 300 400
Recommended input supply fuse - A 10 16 20
Control cable mm² ≥0.5
AWG 20
Recommended input cable mm² 1.0 1.5 2.5
AWG 16 14 12
Recommended motor cable mm² 1.0 1.5
AWG 16 14
Recommended braking resistor cable mm² 1.5
AWG 14
MODEL SE23400...
075 110 150 220 300 400
Minimum braking resistor value - Ω100 75
Recommended braking resistor value - Ω200 100
Resistor peak power rating - kW* 3.4 6.9
NOTE

Commander SE User Guide 8
Issue Number 8 www.controltechniques.com
Table 3.12 Commander SE Size 3, 200V units
* See section 3.1.1.
** For an explanation of inrush current, see section 3.1.2.
Table 3.13 Recommended fuses and cables
*It is recommended that 6mm2/ 8AWG cable is used to minimise volt drops when cable
length greater than 100m are used
Table 3.14 Braking Resistors
* Based on recommended braking resistor value.
Before fitting a braking resistor please read the information on Braking, and the
Warnings on High Temperatures and Overload Protection at the end of this
section.
MODEL SE33200...
550 750
AC supply voltage and frequency 3 phase 200 to 240V +/-10%, 48 to 62Hz
Input displacement factor (cos φ)>0.97
Nominal motor power - kW 5.5 7.5
Nominal motor power - hp 7.5 10.0
Output voltage and frequency 3 phase, 0 to input voltage, 0 to 1000Hz
100% RMS output current - A 25.0 28.5
150% overload current for 60 secs - A 37.5 42.8
Typical full load input current - A* 22.8 24.6
Typical inrush current - A** (duration <10ms) 44
Drive power losses at 230Vac at 6kHz switching
frequency - W 230 305
Weight - kg/lb 6 / 13.2
Cooling fan fitted Yes
MODEL SE33200...
550 750
Recommended input supply fuse - A 30
Control cable mm² >0.5
AWG 20
Recommended input cable mm² 4.0*
AWG 10*
Recommended motor cable mm² 4.0*
AWG 10*
Recommended braking resistor cable mm² 4.0
AWG 10
MODEL SE33200...
550 750
Minimum braking resistor value - Ω12.0
Recommended braking resistor value - Ω15.0
Resistor peak power rating - kW* 11.8
NOTE

9Commander SE User Guide
www.controltechniques.com Issue Number 8
Table 3.15 Commander SE Size 3, 400V units
* See section 3.1.1.
** For an explanation of inrush current, see section 3.1.2.
Table 3.16 Recommended fuses and cables
Table 3.17 Braking Resistors
* Based on recommended braking resistor value.
Before fitting a braking resistor please read the information on Braking, and the
Warnings on High Temperatures and Overload Protection at the end of this
section.
MODEL SE33400...
550 750
AC supply voltage and frequency 3 phase 380 to 480V +/-10%, 48 to 62Hz
Input displacement factor (cos φ)>0.97
Nominal motor power - kW 5.5 7.5
Nominal motor power - hp 7.5 10.0
Output voltage and frequency 3 phase, 0 to input voltage, 0 to 1000Hz
100% RMS output current - A 13.0 16.5
150% overload current for 60 secs - A 19.5 24.8
Typical full load input current - A* 13.0 15.4
Typical inrush current - A** (duration <10ms) 80
Drive power losses at 480Vac at 6kHz switching
frequency - W 190 270
Weight - kg/lb 6 / 13.2
Cooling fan fitted Yes
MODEL SE33400...
550 750
Recommended input supply fuse - A 16 20
Control cable mm² >0.5
AWG 20
Recommended input cable mm² 2.5
AWG 12
Recommended motor cable mm² 2.5
AWG 12
Recommended braking resistor cable mm² 2.5
AWG 12
MODEL SE33400...
550 750
Minimum braking resistor value - Ω39.0
Recommended braking resistor value - Ω50
Resistor peak power rating - kW* 13.8
NOTE

Commander SE User Guide 10
Issue Number 8 www.controltechniques.com
Table 3.18 Commander SE Size 4, 400V units
* See section 3.1.1.
** For an explanation of inrush current, see section 3.1.2.
*** 3kHz for 18.5kW
Table 3.19 Recommended fuses and cables
Table 3.20 Braking Resistors
* Based on recommended braking resistor value.
Before fitting a braking resistor please read the information on Braking, and the
Warnings on High Temperatures and Overload Protection at the end of this
section.
MODEL SE4340...
1100 1500 1850
AC supply voltage and frequency 3 phase 380 to 480V +/-10%, 48 to 62Hz
Input displacement factor (cosφ) >0.97
Nominal motor power - kW 11 15 18.5
Nominal motor power - hp 15 20 25
Output voltage and frequency 3 phase, 0 to input voltage, 0 to 1000Hz
100% RMS output current - A 24.5 30.5 37
150% overload current for 60 secs - A 36.75 45.75 55.5
Typical full load input current - A* 23 27.4 34
Typical inrush current - A** (duration <10ms) 40
Drive power losses at 480Vac at 6kHz***
switching frequency - W 400 495 545
Weight - kg/lb 11 / 24.2
Cooling fan fitted Yes
MODEL SE4340...
1100 1500 1850
Recommended input supply fuse - A 32 40
Control cable mm² >0.5
AWG 20
Recommended input cable mm² 4.0 6.0
AWG 10 8
Recommended motor cable mm² 4.0 6.0
AWG 10 8
Recommended braking resistor cable mm² 6.0
AWG 8
MODEL SE4340...
1100 1500 1850
Minimum braking resistor value - Ω24
Recommended braking resistor value - Ω40 30 24
Resistor peak power rating - kW* 17.2 23 28.7
NOTE

11 Commander SE User Guide
www.controltechniques.com Issue Number 8
Table 3.21 Commander SE Size 5 units
* See section 3.1.1.
** For an explanation of inrush current, see section 3.1.2.
Table 3.22 Recommended fuses and cables
Table 3.23 Braking resistors
* Based on recommended braking resistor value.
Before fitting a braking resistor please read the information on Braking, and the
Warnings on High Temperatures and Overload Protection at the end of this
section.
MODEL SE5340...
2200 3000 3700
AC supply voltage and frequency Three phase 380 - 480V +/- 10% 48 - 62Hz
Input displacement factor (cos φ)>0.97
Nominal motor power - kW 22 30 37
Nominal motor power - hp 30 40 50
Output voltage and frequency 3 phase, 0 to input voltage, 0 to 1000Hz
100% RMS output current - A 46 60 70
150% overload current for 60 secs - A 69 90 105
Typical full load input current - A* 40 52 66
Typical inrush current - A** 28
Typical inrush current duration - ms 49
Drive power losses at 480Vac at 3kHz switching
frequency - W 730 950 1090
Weight - kg/lb 22 / 49
Cooling fan fitted Yes
MODEL SE5340...
2200 3000 3700
Recommended input supply fuse - A 60 70 80
Control cable mm² 0.5
AWG 20
Recommended input cable mm² 10 16 25
AWG 6 4 4
Recommended motor cable mm² 10 16 25
AWG 6 4 4
Recommended braking resistor cable mm² 10 16 25
AWG 6 4 4
MODEL SE5340...
2200 3000 3700
Minimum braking resistor value - Ω10
Recommended braking resistor value - Ω20 12
Resistor peak power rating - kW* 34.5 57.5
NOTE

Commander SE User Guide 12
Issue Number 8 www.controltechniques.com
Braking Resistors - High Temperatures
Braking resistors can reach high temperatures. Locate braking resistors so that
damage cannot result. Use cable having insulation capable of withstanding high
temperatures.
Braking Resistors - Overload Protection
It is essential that an overload protection device is incorporated in the braking
resistor circuit. This is described in section 5.1.1 Thermal Protection Circuit for
an Optional Braking Resistor.
3.1.1 *Input current
The input current values given could be exceeded where the supply fault current is
greater than 5kA or the phase voltages are not balanced. In these cases, input line
reactors are recommended. See section 4.4.3 Useoflinereactorson page 26.
3.1.2 **Temperature effects on inrush currents
Size1-4
Due to the design of the inrush circuit, the inrush current will be lower on the first power
up of the drive after a period of non-use and when the drive is cold. The inrush current
will increase when the time between power ups is short and the internal ambient
temperature within the drive is high.
3.2 General data
IP Rating
NEMA Enclosure Rating
WARNING
WARNING
Size 1: IP20
The Ingress Protection rating is applicable to the drive when
the supplied rubber grommets are fitted into the gland plate.
Sizes 2, 3 & 4: IP20
The Ingress Protection ratingis applicable to the drivewhen
the supplied rubber grommets are fitted into the gland plate
and the drive is mounted on a solid flat surface.
Size 5: IP00 - Gland plate not fitted
IP10 - Gland plate fitted, cable glands not fitted (unused holes
covered)
IP20 - Gland plate fitted, cable glands fitted (blanking caps
covering unused holes)
Size 1: The drive has a NEMA 1 enclosure rating when a suitable
method of cable entry is used, e.g. conduit
Sizes 2, 3 & 4: ThedrivehasaNEMA1enclosureratingwhenmountedona
solid flat surface and a suitable method of cable entry is used,
e.g. conduit
Size 5: ThedrivedoesnothaveaNEMA1enclosurerating.
NEMA1isanenclosureconstructedforindoorusetoprovideadegreeofprotectionto
personnel against incidental contact with the enclosed equipment and to provide a
degree of protection against falling debris.

13 Commander SE User Guide
www.controltechniques.com Issue Number 8
If the drive is not mounted as indicated, hazardous live parts will be exposed and
the IP Rating or NEMA 1 enclosure rating of the drive will be invalid.
WARNING
Input phase
imbalance: Phase imbalance not to exceed 2% negative phase sequence
Ambient
temperature: -10°Cto+40°C(14°Fto104°F) at 6kHz switching frequency.
-10°Cto+50°C(14°Fto122°F) at 3kHz switching frequency
with derating on some models.
-10°Cto+40°C(14°Fto104°F) at 3kHz switching frequency for
SE4, 18.5kW and SE Size 5.
See Commander SE Advanced User Guide for Derating
Curves.
Storage temperature: -40°Cto+60°C (-40°Fto140°F) for 12 months max
Altitude: Reduce the normal full-load current by 1% for every 100m
(325ft) above 1000m (3250ft) to a maximum of 4000m
(13000ft).
Humidity: Maximum relative humidity 95% (non-condensing)
Materials: Flammability rating of main enclosure:UL94-5VA (Size 1 to 4)
Flammability rating of main enclosure:UL94-V0 (Size 5)
Grommets:UL94-V1
Vibration (random):
Vibration
(sinusoidal)
Unpackaged - tested to 0.01g²/Hz (equivalent to 1.2g rms) from
5 to 150Hz for 1 hour in each of 3 axes in accordance with
IEC68-2-34 and IEC68-2-36.
Unpackaged - tested from 2-9Hz, 3.5mm displacement; 9-
200Hz 10m/s2acceleration; 200-500Hz, 15m/s2acceleration.
Duration - 15 minutes in each of 3 axes. Sweep rate 1 octave/
minute.
Test in accordance with IEC68-2-6.
Bump: Packaged - tested to 40g, 6ms, 100 times/direction for all 6
directions as in IEC68-2-29
Unpackaged - tested to 25g, 6ms, 100 times/direction for all 6
directions in accordance with IEC68-2-29
Frequency
accuracy: 0.01%
Resolution: 0.1Hz
Output frequency
range: 0to1000Hz
Starts per hour: By using the electronic control terminals: Unlimited
By switching of the supply: 20 starts per hour maximum (3
minute intervals between starts)
Power up delay: 1.5 seconds maximum (Allow at least 1 second for Sizes 1 to 4
and 1.5 seconds for Size 5 before monitoring the state of the
status relay contacts, communicating with the drive via serial
communications etc.)
This manual suits for next models
24
Table of contents
Other Control Techniques Inverter manuals

Control Techniques
Control Techniques Commander SE Series User manual

Control Techniques
Control Techniques Mini Maestro Drive User manual

Control Techniques
Control Techniques Commander SK Assembly instructions

Control Techniques
Control Techniques Emerson EV2100 Series User manual

Control Techniques
Control Techniques Digitax ST Assembly instructions

Control Techniques
Control Techniques FXM5 User manual