IMPORTANT: Ensure that all perforated slots sit firmly on
the notches after tightening up the dome nuts.
356mm
344mm 380mm
Fixed Plant Bracket
MBR-CP56-FPB
Mobile Plant Bracket (Optional)
MBR-CP56-MPB
364mm
145mm 145mm
84mm
208mm
CP56 Luminaire
364mm150mm
208mm
80mm
290mm
Page 1 / 2[email protected] • aus. 1300 287 533 • intl. +613 8681 3633 • www.coolon.com.au
Product must be installed by a suitably qualied person. All documentation is subject to change without notice. Refer to our website for the latest information.www.coolon.com.au
CP56 INDUSTRIAL LED MANUAL EDITION 1.8
CP56-ELV
24VDC IN
Length = 2m
Wiring Diagram
Red (Positive)
White (0 – 10V Dimming)
Black (Negative)
Install arm locks onto protruding studs on both sides of the
housing as shown below.
Step 1
Apply force
to t over
protruding
studs
Apply necessary force to open the bracket in order to fit over the
properly positioned arm locks.
Step 2
MOUNTING BRACKET INSTALLATION
Align perforated slots in mounting bracket against corresponding
notches in the arm locks, then tighten the nut. Ensure that all the
perforated slots sit firmly on the notches after tightening up the
nuts. Recommended tightening torque is 40 Nm.
Step 3
We recommend Loctite® 243™ retaining compound
(not included) to secure the dome nut.
Voltage In
21 – 34VDC
Power
270W @24VDC
IP/IK Rating
IP66 / IK09
Operating Temperature
-20°C ≤ Tamb ≤ 50°C
Electrical Characteristics
Page 2 / 2CP56 INDUSTRIAL LED MANUAL EDITION 1.8
Page 2 / 2[email protected] • aus. 1300 287 533 • intl. +613 8681 3633 • www.coolon.com.au
Product must be installed by a suitably qualied person. All documentation is subject to change without notice. Refer to our website for the latest information.www.coolon.com.au
Under some unique circumstances, a connection of multiple CP56 luminaires may result in the luminaires pulsing on and off (or flashing).
This application note addresses this phenomenon.
The CP56 Industrial LED Luminaire is built using on-board high efficiency switch mode drivers. It is designed to operate at a constant
power, however it reduces its power as the voltage at the input drops below its nominal operating range.
When the CP56 is powered from batteries, this method prevents current increase by reducing voltage when it is below the nominal
voltage which helps reduce battery damage and false tripping of circuit breakers.
The CP56 also has over voltage protection circuitry which ensures its reliable and safe operation on mobile plant equipment.
The Power vs Voltage graph below demonstrates the power consumption of the CP56 with respect to input voltage.
The CP56 is designed to be connected to a low impedance 24VDC source such as a battery or a suitable Power Supply directly using its
2 meter cable.
Often an installation on mobile plant will use multiple CP56 units connected to a single point at the end of a single common cable
between the battery and distribution panel.
For this type of application, this common cable could be 15m long with 35mm² cross section. Such a cable provides low voltage drop,
however, it acts as an inductor with a high-quality factor (Q). The Q factor is defined as a ratio between Impedance at a particular
frequency ωL and DC resistance R.
CP56 APPLICATION NOTE
0
10
20
30
40
50
60
70
80
90
100
Power (%)
Voltage Input (V) Typical over voltage
cut-off level
0 5 10 15 20 25 30 35
Constant
Power Range
Q = ——
ωL
R
The operating frequency of the CP56 drivers are sufficiently high (~300KHz or more). As a result of using a common cable, independent
drivers could start working in sync.
This creates peaks of high current going through the common part of the cable.
As a result of cable inductance voltage spikes are generated at a common point which can exceed the cut-off voltage level and cause a
momentary shut-down of the CP56 on-board driver’s protection circuitry.
Externally this could be observed as a light flicker.
In order to avoid voltage spikes from happening, there are 2 common solution;
1. Independent cables for each CP56 is to be directly connected to the battery (in this case a 2.5 or 4mm² cross
section is sufficient for each luminaire), or
2. A capacitor bank (such as the CL-7DR-1000-24, Coolon 7 Channel DIN Rail Capacitor Bank 1000µF 24V)
should be employed to reduce the voltage spikes when independent cable extensions for individual CP56 units
are impractical.
NOTE: using a normal volt meter or a multimeter at this common point would not show increased voltage as a multimeter performs
averaging of the input voltage. In order to observe the voltage peaks a Digital Storage Oscilloscope (DSO) is needed.
IMPORTANT
• Read through this manual before installation
• Handle the product with care
• The product must be installed by a suitably qualified person
• Turn OFF the power before installation and maintenance
• Make sure the product is securely installed
• The housing might become hot after operation
• Keep optical face clean
Primary use: flood light for commercial and industrial applications.

Popular Light Fixture manuals by other brands

Triarch 29764 instructions

Triarch

Triarch 29764 instructions

Triarch 29761 instructions

Triarch

Triarch 29761 instructions

Modulex MMP-060S Series installation guide

Modulex

Modulex MMP-060S Series installation guide

Kanlux REGIS 4LED OPAL 418PT quick start guide

Kanlux

Kanlux REGIS 4LED OPAL 418PT quick start guide

Lightolier 1101FDM specification

Lightolier

Lightolier 1101FDM specification

Lightolier Lytespan 6415 specification

Lightolier

Lightolier Lytespan 6415 specification

Lightolier Lytespan 22SS3 specification

Lightolier

Lightolier Lytespan 22SS3 specification

Chauvet Intimidator Spot LED 250 user manual

Chauvet

Chauvet Intimidator Spot LED 250 user manual

American DJ ActivePod User instructions

American DJ

American DJ ActivePod User instructions

Cooper Lighting all-pro mst27920les instruction manual

Cooper Lighting

Cooper Lighting all-pro mst27920les instruction manual

Lightolier JS Series specification

Lightolier

Lightolier JS Series specification

GE FCB-XM-3D-CH0078-120V instruction manual

GE

GE FCB-XM-3D-CH0078-120V instruction manual

ECI CabLite ECO Series installation manual

ECI

ECI CabLite ECO Series installation manual

Cooper Lighting AMETRIX Fixture Doors Supplementary instructions

Cooper Lighting

Cooper Lighting AMETRIX Fixture Doors Supplementary instructions

Cooper Lighting RFR Series Specifications

Cooper Lighting

Cooper Lighting RFR Series Specifications

Boost BOOST-LIGHT70 instruction manual

Boost

Boost BOOST-LIGHT70 instruction manual

Ignition Studio Par Zoom Platinum user manual

Ignition

Ignition Studio Par Zoom Platinum user manual

Triarch Indoor Lighting 29643 Assembly instructions

Triarch

Triarch Indoor Lighting 29643 Assembly instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.