emergency operation
In case that wireless remote control switch is unusable by batteries shortage, etc., perform
1) Proceed the “TEST RUN” mode by using “Operation & Installation Manual” for the wireless remote
control switch.
!Turn OFF all power sources before setting the dip switches.
2) Emergency Operation Setting (Refer to the figure of the item 3 “Optional Functions”.)
(1) Switch “COOL”: Press “COOL” so that the cooling operation is started.
Press “COOL” again so that the cooling operation is stopped.
(2) Switch “HEAT”: Press “HEAT” so that the heating operation is started.
Press “HEAT” again so that the heating operation is stopped.
NOTE:
During the emergency operation, the LED (yellow) blinks (0.5 second ON / 0.5 second OFF).
3) Alarm Code Indication
•In case that some trouble occures because of activation of safety device, etc., “RUN” (red lamp)
blinks (0.5 second ON / 0.5 second OFF).
•Refer to the Installation Manual for outdoor unit about Alarm Code List.
•Alarm Code indicates the blinking times of “DEF” (green lamp) and “FILER” (yellow lamp) as shown
bellow.
“DEF” (green lamp): The blinking is shown at the 2 digit of Alarm Code
“FILTER” (yellow lamp): The blinking is shown at the 1 digit of Alarm Code
(Alphabet Code: A=10 times, B=11 times, C=12 times, .....)
4. Others
as follows.
- Example -
•“Run” (red lamp) blinking (1 second ON / 1 second OFF) indicates abnormal transmitting between
Indoor Units and Outdoor Unit.
"FILTER" (yellow lamp)
Alarm
3 5
"DEF" (green lamp)
"DEF" blinks 3 times (0.5 second ON / 0.5 second OFF)
"FILTER" (yellow lamp) blinks 5 times (0.5 second ON / 0.5 second OFF)
5