Cooper Power Systems Kyle GV User manual

Figure 1.
Kyle®Type GW Sectionalizer.
84574KMA
Contents
Safety Information .................................................. 2
Hazard Statement Definitions ............................. 2
Safety Instructions .............................................. 2
Product Information ............................................... 3
Introduction ......................................................... 3
Acceptance and Initial Inspection ........................ 3
Handling and Storage .......................................... 3
Standards ........................................................... 3
Description........................................................... 3
Ratings .................................................................... 4
Dimensions and Weights....................................... 5
Operating Controls and Settings .......................... 6
Manual Operating Controls ................................. 6
Auxiliary Power .................................................... 6
Indicating Devices................................................ 6
Settings ............................................................... 7
Inrush-Current Restraint ...................................... 8
Response Time.................................................... 8
Installation............................................................... 9
Oil Level and Dielectric Strength ......................... 9
Lifting the Sectionalizer........................................ 9
Mounting the Sectionalizer .................................. 9
Grounding the Sectionalizer ................................ 9
High-Voltage Connections ................................... 11
120 Vac Wiring..................................................... 11
Internal Wiring......................................................12
Auxiliary Switch......................................................13
Operating Instructions ...........................................15
Initial Operation....................................................15
Routine Operation................................................15
Automatic Return to Zero Count ..........................15
One-Count-to-Open .............................................15
CT Protector Board ................................................15
Testing .....................................................................16
Test Circuit and Equipment..................................16
Pre-Test Procedure..............................................16
Test Procedures...................................................16
Post-Test Procedures ..........................................19
March 2002 • Supersedes 12/92
Printed in USA
Service Information
Sectionalizers
Type GV and GW
Installation Instructions S270-20-3
Applicable to serial numbers above 2265 for Type GV and 4803 for Type GW
NOTICE: This bulletin is also applicable to Kyle product
serial numbers beginning with the prefix CP57.

Type GV and GW Installation Instructions
2
The instructions in this manual are not intended as a
substitute for proper training or adequate experience in
the safe operation of the equipment described. Only
competent technicians, who are familiar with this equip-
ment should install, operate, and service it.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions.
• Is trained in industry-accepted high- and low-voltage
safe operating practices and procedures.
• Is trained and authorized to energize, de-energize,
clear, and ground power distribution equipment.
• Is trained in the care and use of protective equip-
ment such as flash clothing, safety glasses, face
shield, hard hat, rubber gloves, hotstick, etc.
Following is important safety information. For safe instal-
lation and operation of this equipment, be sure to read
and understand all cautions and warnings.
Safety Instructions
Following are general caution and warning statements
that apply to this equipment. Additional statements, relat-
ed to specific tasks and procedures, are located through-
out the manual.
SAFETY INFORMATION
WARNING: This equipment is not intended to
protect human life. Follow all locally approved
procedures and safety practices when installing or
operating this equipment. Failure to comply may result
in death, severe personal injury and equipment damage.
G102.1
!
DANGER: Hazardous voltage. Contact with
hazardous voltage will cause death or severe
personal injury. Follow all locally approved safety pro-
cedures when working around high- and low- voltage
lines and equipment. G103.3
!
WARNING: Before installing, operating, main-
taining, or testing this equipment, carefully read
and understand the contents of this manual. Improper
operation, handling or maintenance can result in
death, severe personal injury, and equipment damage.
G101.0
!
SAFETY FOR LIFE
Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively
promote safe practices in the use and maintenance of our products through our service literature, instructional training
programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture,
marketing, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working
around high voltage lines and equipment and support our “Safety For Life” mission.
!
SAFETY
FOR LIFE
!
SAFETY
FOR LIFE
This manual may contain four types of hazard
statements:
DANGER: Indicates an imminently haz-
ardous situation which, if not avoided, will
result in death or serious injury.
WARNING: Indicates a potentially haz-
ardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially haz-
ardous situation which, if not avoided, may
result in minor or moderate injury.
CAUTION: Indicates a potentially hazardous situ-
ation which, if not avoided, may result in equip-
ment damage only.
!
!
!
Hazard Statement Definitions
WARNING: Power distribution equipment must
be properly selected for the intended application.
It must be installed and serviced by competent per-
sonnel who have been trained and understand proper
safety procedures. These instructions are written for
such personnel and are not a substitute for adequate
training and experience in safety procedures. Failure
to properly select, install, or maintain power distribu-
tion equipment can result in death, severe personal
injury, and equipment damage. G122.2
!

3
!
SAFETY
FOR LIFE
Introduction
Service Information S270-20-3 provides installation and
operation instructions for the Kyle Type GV and GW
Sectionalizers. Before installing and operating this sec-
tionalizer, carefully read and understand the contents of
this manual.
Read this Manual First
Read and understand the contents of this manual and
follow all locally approved procedures and safety prac-
tices before installing or operating this equipment.
Additional Information
These instructions can not cover all details or variations
in the equipment, procedures, or processes described
nor provide directions for meeting every possible contin-
gency during installation, operation, or maintenance. For
additional information, please contact your Cooper
Power Systems representative.
Acceptance and Initial
Inspection
Each sectionalizer is completely assembled, tested,
inspected, adjusted, and filled to the correct level with
insulating oil at the factory. It is in good condition when
accepted by the carrier for shipment.
Upon receipt, inspect the shipping container for signs of
damage. Unpack the sectionalizer and inspect it thor-
oughly for damage incurred during shipment. If damage
is discovered, file a claim with the carrier immediately.
Check for oil leakage, and tighten all bolts that may have
been loosened during shipment, especially the bolts
attaching the head to the tank.
Handling and Storage
Be careful during handling and storage of the sectional-
izer to minimize the possibility of damage. If the section-
alizer is to be stored for any length of time prior to instal-
lation, provide a clean, dry storage area. Locate the sec-
tionalizer so as to minimize the possibility of mechanical
damage. In particular, protect the bushings and keep the
operator cabinet closed to protect the electronic control
components.
Standards
Kyle sectionalizers are designed and tested in accor-
dance with ANSI standard C37.63 where applicable.
Quality Standards
ISO 9001:2000 Certified Quality Management System
Description
The sectionalizer is a self-contained, circuit-opening
device used in conjunction with source-side protective
devices such as reclosers or circuit breakers, to auto-
matically isolate faulted sections of electrical distribution
systems. The sectionalizer senses current flow above a
preset level, and, when the source-side protective
device opens to de-energize the circuit, the sectionalizer
counts the overcurrent interruption. Depending upon the
coordination scheme, the sectionalizer will open during
the first, second, and third open interval of the fault inter-
rupting device to isolate permanent faults and confine
outages to smaller sections of line.
The sectionalizer does not interrupt fault current but can
be closed into a faulted line. It opens during the open
interval of the backup device. For this reason, it must
always be used in series with a fault-interrupting backup
protective reclosing device. Also, it will reset counts that
do not reach the counts-to-open setting within the
selected reset time due to clearing of temporary faults.
A minimum of 0.5 A of load current flowing through the
sectionalizer will block the generation of a count pulse.
This count-restraint feature prevents the sectionalizer
from counting overcurrents interrupted by down-line
devices.
The sectionalizers are also equipped with an inrush-current
restraint feature which distinguishes between inrush cur-
rents and fault currents. If it is determined that the over-
current through the sectionalizer is inrush current, the
phase and ground current levels of the sectionalizer are
blocked for a duration of 3 seconds upon current detection.
3
S270-20-3
PRODUCT INFORMATION

Tables 1 and 2 show rating information for the Types GV
and GW sectionalizers.
Type GV and GW Installation Instructions
4
Table 1
Basic Sectionalizer Ratings
Type GV Type GW
Nominal Voltage (kV) . . . . . . . . . . . . . . . . . . . . . 14.4 34.5
Rated Maximum Voltage (kV) . . . . . . . . . . . . . . . 15.5 38.0
Impulse Withstand
1.2 x 5.0 microsecond wave
BIL (kV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 150
60 Hz withstand
Dry, 1 minute (kV) . . . . . . . . . . . . . . . . . . . . 50 70
Wet, 10 seconds (kV) . . . . . . . . . . . . . . . . . 45 60
Continuous Current Rating (A) . . . . . . . . . . . . . . 400 400
Rated symmetrical
interrupting current (A rms) . . . . . . . . . . . . . 880 880
Rated making current,
asymmetrical (A rms) . . . . . . . . . . . . . . . . . 20000 15000
Short-time ratings (A rms)
10-seconds symmetrical . . . . . . . . . . . . . . . 4000 3500
1-second symmetrical . . . . . . . . . . . . . . . . . 12500 10000
Momentary maximum,
asymmetrical (A rms) . . . . . . . . . . . . . . . . . 20000 15000
Creepage distance,
standard bushing mm (in) . . . . . . . . . . . . . . 280 (11) 431 (17)
Table 2
Operating Data
Phase-minimum-
actuating current (A) . . . . . . . . 16, 24, 40, 56, 80, 112, 160, 224, 256, 296, 320, 448, 480, 640
Ground-minimum-
actuating current (A) . . . . . . . . 3.5, 7, 16, 20, 28, 40, 56, 80, 112, 160, 224, 320, 448, BLOCK
Number of counts to open . . . . . . . 1, 2, 3
Count reset (seconds) . . . . . . . . . . 15, 30, 60, 90, 120, 180
RATINGS

5
!
SAFETY
FOR LIFE
Figures 2 and 3 show essential dimensional information
for Types GV and GW sectionalizers, along with their
weights and oil capacities.
Note: All dimensions are approximate and are given in mm
(inches).
5
S270-20-3
89 (3.5)
38 (1.5)
641
(25.25)
929 (36.5)
1372 (54)
Tapped Holes (12)
for 1/2–13 Bolts
292
(11.5)
233
(9.25)
1051 (41.5)
Vented
dipstick
435
(17)
292
(11.5)
448
(17.5)
197
(7.75)
Terminal Connectors
No. 6 solid–350 MCM
305
(12)
1203
(47.25)
435
(17)
329
(13)
562
(22)
Ground Connector
No. 8–No.2
Figure 2.
Type GW Sectionalizer.
254
(10)
203
(8)
Terminal Connectors
No. 6 solid–350 MCM
Ground
Connector
No. 8–No. 2
838
(33)
648 (25.5)
1016 (40)
365 (14.5)
197
(7.75)
657 (25.75)
254
(10)
254
(10)
70
(2.75)
32 (1.25)
Vented dipstick
Lifting
lug
244
(9.75)
64
(2.5)
260
(10.25)
324
(12.75)
64
(2.5)
473
(18.75)
365 (14.5)
311
(12.25)
152 (6)
Hole for bolt
16 mm (5/8")
362
(14.25)
448
(17.5)
Figure 3.
Type GV Sectionalizer.
Weight with oil 350 kg (770 lb)
Oil Capacity 160 L (42 gal)
Weight with oil 213 kg (470 lb)
Oil Capacity 72 L (19 gal)
DIMENSIONS AND WEIGHT

Manual Operating Controls
The operating controls for the sectionalizer are located
on the underside of the operator mechanism housing, as
shown in Figure 4.
Manual Opening
The hookstick-operated, manual opening pullring trips
open the sectionalizer with one pull of the yellow pullring.
One-Count-To-Open Lever
The one-count-to-open lever provides the capability of
opening the sectionalizer on the first overcurrent interrup-
tion count. It provides for added safety during downline
hot-line work without disturbing the normal counts-to-
open setting of the sectionalizer. The hookstick-operated
lever locks into position when pulled down, and must be
manually reset to restore normal counts-to-lockout.
Manual Closing
The hookstick-operated, manual closing pullring closes
the sectionalizer when the gray pullring is pulled down
approximately 10 to 12 times. The pullring manually
charges the closing springs and overtoggles the springs
to initiate the closing. (When the sectionalizer closes,
the resistance on the pullring is eliminated.) This is the
only means of closing the sectionalizer.
Auxiliary Power
Auxiliary power (120 Vac, 25 VA, min.) is required for the
cabinet heater and/or potential charging of the trip
capacitor. The input receptacle is located on the underside
of the operator cabinet (Figure 4). A mating connector
plug is also provided with the unit.
Indicating Devices
A contact position indicator and an operations counter
are located under the sleet hood of the operator cabinet.
The yellow contact position indicator is pinned to the
main operating shaft of the sectionalizer to indicate the
OPEN and CLOSED condition of the main contacts.
The operations counter gives a visual indication of the
cumulative number of openings of the unit.
Type GV and GW Installation Instructions
6
Figure 4.
Operating controls on the underside of the operator cabinet.
84575KMA
Provision for
installing auxiliary
switch wiring
receptacles
Manual
Opening
Pullring
120 Vac input
receptacle
(mating plug
also furnished)
Manual closing
pullring
One-count-to-
open Lever
OPERATING CONTROLS AND SETTINGS
IMPORTANT: The potential charging board also includes
a voltage restraint feature which prevents the unit from
counting overcurrent interruptions unless the auxiliary
voltage is also interrupted. Therefore, the auxiliary power
must be obtained from the load side of the backup
protective device so that the board is energized only
when the backup is closed. Failure to follow this pre-
caution will prevent proper operation of the sectionalizer.
WARNING: Do not rely on the open position of
the yellow operating handle; it does not ensure
that the line has been de-energized. Always establish
a visible disconnect. Failure to follow proper safety
practices can result in contact with high voltage, which
will cause death or severe personal injury. G116.0
!
WARNING: Always use a hotstick when work-
ing with this equipment. Failure to do so could
result in contact with high voltage, which will cause
death or severe personal injury. G108.1
!

7
!
SAFETY
FOR LIFE
Settings
The operating characteristics are preset to customer
specifications and tested prior to shipment from the fac-
tory. However, if the sectionalizer is relocated or the
coordination scheme is modified, the operating charac-
teristics can be changed by the user. The settings
should be checked before the unit is put into service.
All settings are located on the printed circuit board in the
operator mechanism cabinet and are accessible when
the cabinet cover is removed. See Figure 6. To access
the settings on an in-service sectionalizer, follow this
procedure to remove the sectionalizer from service.
1. Close all three bypass switches (see Figure 5).
2. Pull down the yellow operating handle with a hot-
stick. The yellow operating handle is located under
the sleet hood (see Figures 3 and 4).
3. Open the source and load disconnect switches (see
Figure 5).
4. Remove the cabinet cover.
Minimum Actuating Current
The minimum actuating current levels for both phase
and ground are determined by the selection of the prop-
er plug-in resistors. (Normally, these settings are approx-
imately 80% of the minimum trip settings of the backup
protective device.)
NOTE: If the backup device is not equipped for ground fault
sensing and tripping, the ground current sensing cir-
cuits of the sectionalizer can be deactivated by using a
shorting resistor labeled BLOCK.
Phase current resistors are identified with the phase
symbol (ø) and the actuating current value in amperes.
Catalog numbers for the available phase current resis-
tors are listed in Table 3.
Ground current resistors are identified with the ground sym-
bol ( ) and the actuating current value in amperes.
Catalog numbers for the available ground current resis-
tors are listed in Table 4.
The minimum actuating current of the sectionalizer for
both phase and ground can be changed by merely
changing the appropriate plug-in resistor.
Label Value Resistance (Ω) Catalog
(A) Minimum Maximum Number
16 264 270 KA176GV16
24 172 176 KA176GV24
40 94.3 96.3 KA176GV40
56 66.3 67.7 KA176GV56
80 47 48 KA176GV80
112 32.6 33.4 KA176GV112
60 22.9 23.5 KA176GV160
224 16.3 16.7 KA176GV224
256 13.8 14.2 KA176GV256
296 11.9 12.3 KA176GV296
320 11.1 11.5 KA176GV320
448 8.1 8.3 KA176GV448
480 7.4 7.6 KA176GV480
640 5.5 5.7 KA176GV640
TABLE 3
Minimum Actuating Resistor (Phase)
Table 4
Minimum Actuating Resistor (Ground)
Label Value Resistance (Ω) Catalog
(A) Minimum Maximum Number
3.5 6.91 k 7.05 k KA177GV3.5
7 1.168 k 1.192 k KA177GV7
16 379.0 387.0 KA177GV16
20 298.0 304.0 KA177GV20
28 200.0 204.0 KA177GV28
40 135.6 138.4 KA177GV40
56 94.3 96.3 KA177GV56
80 66.3 67.7 KA177GV80
112 47.0 48.0 KA177GV112
160 32.6 33.4 KA177GV160
224 22.9 23.5 KA177GV224
320 15.8 16.2 KA177GV320
448 11.2 11.4 KA177GV448
BLOCK 0 0.1 KA177GVBLO
7
S270-20-3
CAUTION: Equipment Damage. The sectional-
izer must be bypassed and disconnected prior to
changing minimum actuating resistor settings. Failure
to comply will cause circuit board damage and may
cause misoperation (unintentional operation) of the
sectionalizer. T277.0
!
Surge
Arrestor
SECTIONALIZER
Bypass Switches
Disconnect
Switches
Surge
Arrester
Disconnect
Switches
Operator
Cabinet
120 Vac Input
Figure 5.
Main Wiring Connections.

Counts-to-Open
The counts-to-open setting is determined by the position
of the COUNTS-TO-OPEN SELECTOR switch. Switch
positions 1, 2, and 3 correspond to 1, 2, or 3 counts to
open. Normally, this setting is one less than the number
of operations to lockout of the backup protective device.
To change the number of counts-to-open setting, merely
change the position of the rotary switch.
Count Reset
The reset setting is determined by the position of the
COUNT RESET switch. Reset times of 15, 30, 60, 90,
120, and 180 seconds are available. This feature resets
to zero any accumulated counts whenever current
through the sectionalizer flows without interruption for
longer than the time programmed.
The reset feature will operate with any current flow from
minimum load (0.5 A) to values below phase or ground
pickup levels.
Inrush-Current Restraint
The inrush-current restraint feature blocks the phase
and ground actuating levels for three seconds after cur-
rent flow through the sectionalizer is restored and the
overcurrent has been determined to be inrush current.
The three second time interval allows for system inrush
parameters to stabilize prior to allowing the sensitivity of
the sectionalizer to return to its programmed state.
Response Time
For backfed motor contribution and unsymmetrical clear-
ing of upline faults, a response time is built into the sec-
tionalizer control to eliminate unwanted counting of
these situations. Upon detection of any current above
the phase or ground actuating setting, the current must
exceed the response-time characteristics as illustrated
in Figure 7. Total clearing time of reclosers and breakers
must exceed the response-time characteristic of the sec-
tionalizer.
Type GV and GW Installation Instructions
8
0.1
.08
.06
.01
.02
.03
.04
.05
50
60
80
100
200
300
400
500
600
800
1000
2000
CURRENT (percent of minimum actuating current)
TIME (sec)
Figure 7.
Maximum Response-Time Characteristics.
Figure 6.
Operating characteristics of the sectionalizer are pro-
grammed on the printed circuit board in the operator
cabinet.
020061KMA
Counts-
to-open
selector
Count
reset
selector
Test
Point
C
Test Point
D

9
!
SAFETY
FOR LIFE
Oil Level and Dielectric Strength
Make sure the oil in the tank is at the proper level by
checking the vented dipstick in the head casting.
Replenish any loss with new, dry transformer oil. Refer
to Figures 2 and 3.
If the switch has been stored for any length of time or is
being relocated, check the dielectric strength of the oil in
accordance with ASTM-approved testing procedures.
Physical properties of the oil used in Kyle®distribution
switchgear is found in Reference Data R280-90-1.
1. In new equipment, the oil must have a minimum
dielectric strength of 26 kV. If less than 26 kV, filter
the oil to restore its dielectric strength to an accept-
able level.
2. If the equipment has been in service and is being
relocated, the minimum dielectric strength of the oil
must be at least 22 kV. If less than 22 kV, or if the oil
is contaminated with carbon or sludge, replace the
oil.
3. Check that the actual settings agree with the section-
alizer nameplate and are correct for the planned
installation.
Lifting the Sectionalizer
Follow all approved safety practices when making hitch-
es and lifting the equipment. Lift the load smoothly, and
do not allow the load to shift.
This unit has two lifting lugs. Both lugs must be used
when lifting. Maximum strength is attained with a verti-
cal lift attached to the lugs. Use a spreader bar with a
fixed attachment point for the hook at the load center.
If a sling is used, it must have a fixed attachment point
at the load center. Rig the load so that the sling height is
equal to or greater than the distance between lifting
lugs. See Figure 8.
Mounting the Sectionalizer
Figures 9 and 10 show installation using Kyle mounting
frames. If other mounting means are used, support the
GV sectionalizer at the four 5/8 inch bolt holes in the
mounting rails on the tank. The GW sectionalizer is sup-
ported at the twelve 1/2-13 threaded holes tapped into
the sides of the head casting.
Grounding the Sectionalizer
Make ground connections to the sectionalizer. Refer to
Figures 2 and 3.
9
S270-20-3
Sling
Height
Distance
Between
Lugs
Figure 8.
Lifting the sectionalizer.
INSTALLATION
WARNING: Do not operate this equipment out
of oil. Oil is the electrical insulating medium with-
in this equipment; operating out of oil will result in
internal flashovers that will damage the equipment
and can cause death or severe personal injury. G104.2
!
CAUTION: This equipment relies on oil to pro-
vide electrical insulation between components.
The dielectric strength of the oil must be checked on a
regular basis, as part of the routine maintenance
inspection, to ensure that it is at or above minimum
dielectric requirements. Use of this equipment with
insulating oil that does not meet minimum require-
ments can result in internal flashovers that will dam-
age the equipment and can cause personal injury. G107.2
!
CAUTION: Follow all locally approved safety prac-
tices when lifting and mounting the equipment. Use
the lifting lugs provided. Lift the unit smoothly and do
not allow the unit to shift. Improper lifting can result in
equipment damage. G106.2
WARNING: Hazardous Voltage. Solidly ground
all equipment. Failure to comply can result in
death, severe personal injury, and equipment damage.
T223.2
!

Type GV and GW Installation Instructions
10
670
(26.5)
362
(14.25)
654
(25.75)
762
(30")
711
(28")
5/8" Bolts (4)
(not furnished)
Holes for
3/4" bolts
Adjustable for
3 1/4 x 4 1/4 to 4 x 5 crossarms
and 1/2 to 4" channels.
KA19H3
Crossarm Hanger
KA116H3
Broadside
Pole Hanger
324 mm
(12.75")
330 mm
(13")
473 mm
(18.5")
378 mm
(14.5")
432 mm
(17")
244 mm
(9.5")
383 mm
(15.25")
324 mm
(12.75")
699 mm
(27.5")
622 mm
(24.5")
489 mm
(19.25")
508 mm
(20")
244 mm
(9.75") 383 mm
(15")
Figure 10.
Mounting hardware for Type GV sectionalizer.
622 mm
(24.5")
978 mm
(38.5")
292 mm
(11.5")
330 mm
(13")
546 mm
(21.5")
32 mm
(1.25")
1346 mm
(53")
537 mm
(21.25")
289 mm
(11.5")
289 mm
(11.5")
Figure 9.
Type GW sectionalizer in the KA146W3 pole-mounting hanger.
Grounding Lug
(two 2/0–250 MCM)
Lifting Holes
Mounting Holes
for 3/4”Bolts
(Bolts not furnished)

11
!
SAFETY
FOR LIFE
High-Voltage Connections
It is desirable to provide the sectionalizer with switches
and protection as shown in Figure 11. Surge protection
on both sides of the sectionalizer is recommended.
However, if provided on only one side, it should be on
the source side. In substations, surge protection should
be provided on the load side of the sectionalizer.
The universal clamp-type terminals used for main line con-
nections accept No. 2 solid through 350 mcm copper or
aluminum cables.
The parallel connector grounding clamp on the tank of
the Type GV and the cover of the GW sectionalizers will
accept No. 8 through No. 2 stranded wire.
120 Vac Wiring
A 120 Vac source voltage is required if the mechanism
cabinet heater and the potential charger for the trip
capacitor are to be energized.
The line voltage is connected to pins B and D of the
source-voltage plug shown in Figure 12.
Internal Wiring
A connection diagram for the GV and GW sectionalizers
is shown in Figures 12 and13.
11
S270-20-3
Surge
Arrestor
SECTIONALIZER
Bypass Switches
Disconnect
Switches
Surge
Arrester
Disconnect
Switches
Operator
Cabinet
120 Vac Input
Figure 11.
Main Wiring Connections.
A
BC
D
E
Figure 12.
125 Vac Input Connector Plug.
Keyway Socket Insert
Socket E
Max wire size No. 12 AWG
Rubber Grommet
accommodates
3/8”to 1/2”dia. cable

Type GV and GW Installation Instructions
12
Figure 13.
Internal Connections Diagram.
1
2
3
4
7
8
14
15
16
17
18
19
20
22
21
BLK
RED
RED
KEY
RED
YEL
WHT
BLK
BLK
ORG
BRO
BLK
BLU
GRN
BLU
+
–
NC
NO
C
BLU
BLU
BLK
GRN
BLK
BLK
One-
Count
Switch
G
RED
YEL
G
C
B
A
A
C
B
C.T.
Protector
NC
NO
CCount
Reset
Switch
Zenar
Diode Zenar
Diode
A
B
C
D
E
F
1
Potential
Charger
Board
ORG
YEL
GRN
WHT
BLK
WHT
2
4
3
Heater
D
B
BLK
WHT
120 Vac
Input Receptacle
WHT
BLK
BLK
WHT
WHT
Bushing
Current
Transfomer
C
A
E
F
G
H
RED BLK
BLK
YEL
BLK
C
A
E
F
G
H
RED
RED
WHT
BLK
YEL
BLK
WHT
BLK
YEL
BLK
BLK
BLK
WHT
WHT
WHT
øC
øA
øB
Surge
Arrester
BLK
Low-Energy
Tripper

13
!
SAFETY
FOR LIFE
Auxiliary Switch (KA46GV3)
The auxiliary switch, mounted to the top of the operator
cabinet, in a weather-proof housing, is used for relaying
or interlocking schemes and remote contact indication.
A three-stage auxiliary switch is provided. Each stage
consists of two independent contact assemblies with
either “a”(normally open) or “b”(normally closed) con-
tacts which can be easily changed in the field. A data
plate attached to the switch cover shows the switch
arrangement. Related switch contact positions are
shown in Table 5.
The switch is permanently wired to two multipin recepta-
cles in the bottom of the operator cabinet. Table 6 shows
the pin arrangement of the the mating plug shown in
Figure 14.
The switch contacts are insulated for 600 V and have a
continuous current rating of 10 A. Their interrupting rat-
ings are shown in Table 7.
Switching positions can be changed from “a”or “b”oper-
ation by repositioning the cams inside each switch sec-
tion. To change any cam position, complete the following:
1. Remove the auxiliary switch cover.
2. Detach the switch from the switch link by removing
the groove pin and C-rings.
3. Remove the machine screws attaching the assembly
to the cabinet.
4. With the switch removed, unfasten the two hex nuts
and lockwashers from the long machine screws that
hold the switch sections together.
5. Starting with the rear switch section, lift the cams off
the operating shaft, replacing the cams in one of the
positions shown in Figure 15.
6. Reposition the switch sections together, reassemble
the auxiliary switch, and remount the switch on the
sectionalizer.
13
S270-20-3
When Sectionalizer Contacts Are Closed Open
Auxiliary “a”contacts are Closed Open
Auxiliary “b”contacts are Open Closed
Table 5
Related Switch Contact Positions
H
A
B
C
D
E
FG
Figure 14.
Auxiliary Switch Connector Plug.
Rubber grommet accommodates 0.750”to 0.812”
O.D. Cable No. 12 AWG Max Conductor size
Pin G Keyway
Pin insert
Table 6
Switch Leads to Receptacle Terminals
Switch Stages Switch Receptacle Switch
Terminal Pin Contact
1A
“b”
Stage 1 2B
3C
“a”Rear
4D
5E Receptacle
“b”
Stage 2 6F
7G
“a”
8H
9A
“b”
Stage 3 10 B Front
11 C Receptacle
“a”
12 D
Table 7
Interrupting Ratings - Switch Contacts
Inductive Non-Inductive Inductive Non-Inductive
Volts ac ac dc dc
(A) (A) (A) (A)
24 dc —— 15 20
48 dc —— 7.5 10
120 ac 60 80 ——
125 dc ——1.5 2
240 ac 30 60 ——
250 dc ——0.45 0.5

Type GV and GW Installation Instructions
14
CONTACT
SECTION
END PLATE
AND GASKET
SQUARE
SHAFT
CAMS
OPEN
POSITION
CLOSED
POSITION 45°
When assembling be sure
that the roll pin hole and
punch mark on the shaft
are in vertical plane with
the punch mark in the end
plate (as shown).
TERMINALS
3, 7, 11, 15 CAMS
TERMINALS
1, 5, 9, 13
TERMINALS
2, 6, 10, 14
TERMINALS
4, 8, 12, 16
CONTACTS
SQUARE
SHAFT
CAM POSITION NO. 1
Both contacts closed.
CAM POSITION NO. 2
Both contacts open.
CAM POSITION NO. 3
One contact open and one
contact closed.
Figure 15.
Cam positions inside the Auxiliary Switch.

15
!
SAFETY
FOR LIFE
Initial Operation
With the sectionalizer connected into the system and the
source-side high-voltage lines energized, the sectional-
izer can be placed into service. Follow approved local
practices, which may involve closing the line disconnect
switches, closing the sectionalizer, and then opening the
bypass circuit.
Routine Operation
Under normal operating conditions, the sectionalizer
counts overcurrent interruptions of the backup protective
device and automatically opens if the counts registered
exceed the control setting. Once open, the sectionalizer
will remain open until manually closed. In addition, the
sectionalizer can be opened manually by one operation
of the yellow pullring of the manual trip rod.
To close the sectionalizer, after either a manual or auto-
matic trip, the gray manual-closing pullring must be oper-
ated approximately 10 to 12 times. (When the sectional-
izer closes, the resistance on the pullring is eliminated.)
This is the only means of closing the sectionalizer.
Automatic Return to Zero Count
A switch operated by the tripping linkage of the section-
alizer mechanism will automatically erase any accumu-
lated counts every time the sectionalizer opens either man-
ually or automatically.
One-Count-to-Open
As an added safety precaution during downline hot-line
work, the sectionalizer can be programmed for one-
count-to-open without opening the operator mechanism
housing and disturbing the normal operating settings.
The one-count-to-open lever overrides the COUNTS-
TO-OPEN SELECTOR switch to provide the capability
of opening the sectionalizer on the first overcurrent inter-
ruption. The hookstick-operated lever locks into position
when pulled down and must be manually reset.
CT PROTECTOR BOARD
Should the control be removed, the CT protector board,
shown in Figure 16, will automatically protect the current
sensing CTs. This is done by limiting the open-circuit
voltages to non-destructive levels.
15
S270-20-3
OPERATING INSTRUCTIONS
Figure 16.
Control Circuitry.
84577KMA
CT
Protector Board
Voltage
Charging Board
Heater
WARNING: This equipment is not intended to
protect human life. Follow all locally approved
procedures and safety practices when installing or
operating this equipment. Failure to comply can result
in death, severe personal injury, and equipment dam-
age. G102.1
!
WARNING: Do not rely on the open position of
the yellow operating handle; it does not ensure
that the line has been de-energized. Always establish
a visible disconnect. Failure to follow proper safety
practices can result in contact with high voltage, which
will cause death or severe personal injury. G116.0
!
WARNING: Always use a hotstick when work-
ing with this equipment. Failure to do so could
result in contact with high voltage, which will cause
death or severe personal injury. G108.1
!

Type GV and GW sectionalizers are carefully tested at
the factory prior to shipment. Well-equipped test facili-
ties, a detailed testing procedure, and trained test per-
sonnel assure that the unit will operate according to pub-
lished data. Permanent records are kept of each sec-
tionalizer’s test performance.
Each sectionalizer leaves the factory ready for installa-
tion. Preinstallation testing is not necessary. However,
should verification of operation prior to installation be
desired, the these procedures should be used.
Test Circuit Equipment
A suggested test circuit is shown in Figure 17. In this
test setup, the test current is obtained by back-feeding a
500:5 A current transformer (T2, located in the primary
loop of one phase of the sectionalizer) from an
adjustable 120 Vac source. The ammeter scales (A)
should be selected to accommodate the appropriate
range of test currents.
Pre-Test Procedure
Before performing any of the test procedures that follow,
make sure the 120 Vac power to the heater and voltage
charging board (Figure 15) is disconnected to disable
the voltage restraint feature. The sectionalizer will not
count as long as the voltage restraint feature (part of the
voltage charging board) is energized.
Test Procedures
While performing the following tests, monitor the conti-
nuity between test points C and D on the circuit board.
(see Figure 6). If no continuity exists between either set
of test points upon closing of the sectionalizer, apply 6 A
of load current by closing switch S1 for 3.5 seconds.
Once continuity has been restored, open S1 and pro-
ceed with the test procedures.
Minimum Actuating Current
The minimum actuating current can be verified by test-
ing at the ± 10 percent values of the phase and ground
actuating current ratings.
For example, the minimum actuating resistor rated at 80 A
is tested at 72 A (no count) and at 88 A (count regis-
tered).
Type GV and GW Installation Instructions
16
T1–VARIABLE AUTO TRANSFORMER
T2–500:5 CURRENT TRANSFORMER
S1–SPST TOGGLE SWITCH
S2–SPST PUSHBUTTON SWITCH
R1–DROPPING RESISTOR, 2 kΩ-10 W
A –AMMETER
A
T2
120 V 60 Hz
T1
S2
S1
R
AC Source
Figure 17.
Test Circuit Schematic.
TESTING
WARNING: This equipment is not intended to
protect human life. Follow all locally approved
procedures and safety practices when installing or
operating this equipment. Failure to comply can result
in death, severe personal injury, and equipment dam-
age. G102.1
!
WARNING: The switchgear and high voltage
transformer must be in a test cage or similar pro-
tective device to prevent accidental contact with the
high voltage parts. Solidly ground all equipment.
Failure to comply can result in death, severe personal
injury, and equipment damage. T221.3
!

Phase Minimum Actuating Current
When checking the phase minimum actuating current,
the ground fault sensing portion of the sectionalizer
must be disabled. Testing an individual phase without
disabling the ground sensing circuits will cause a false
count.
The following procedure is used:
1. Jumper the ground actuating current resistor with a
short lead to disable the ground sensing circuit.
2. Jumper terminals P and D together.
3. Program the sectionalizer for one-count-to-open by
setting the COUNTS-TO-OPEN SELECTOR switch
to 1.
4. Close the sectionalizer by operating the close pull-
ring the required number of times.
5. With the test circuit connected to phase A of the sec-
tionalizer and S1 open, hold S2 closed and slowly
raise the test current from zero to the appropriate
value shown in Column A of Table 8. Hold S2 closed
for at least three seconds.
6. Release S2 to simulate a backup opening. The sec-
tionalizer should not open.
7. Close S2 and adjust the test current to the appropri-
ate value shown in Column B of Table 8.
8. Release S2 to simulate a backup opening. The sec-
tionalizer should count the overcurrent interruption
and open.
9. Repeat steps 3 through 7 for phases B and C.
10. Remove the jumper from terminals P and D.
11. Remove the jumper from across the ground actuat-
ing current resistor upon completion of this portion of
the test.
Ground Minimum Actuating Current
To prevent the possibility of a false count, the phase
sensing portion of the sectionalizer control circuit should
be disabled when the ground minimum actuating current
is being checked. The following procedure is used:
1. Jumper the phase actuating current resistor with a
short lead to disable the phase sensing circuit.
2. Jumper terminals P and D together.
3. Check that the sectionalizer control is set for one-
count-to-open.
4. Close the sectionalizer by operating the close pull-
ring the required number of times.
5. With the test circuit connected to phase A of the sec-
tionalizer and S1 open, hold S2 closed and slowly
raise the test current from zero to the appropriate
values shown in Column A of Table 8. Hold S2
closed for at least three seconds.
6. Release S2 and simulate a backup opening. The
sectionalizer should not open.
7. Close S2 and adjust the test current to the appro-
priate value shown in Column B of Table 8.
8. Release S2 to simulate a backup opening. The sec-
tionalizer should count the overcurrent interruption
and open.
9. Repeat steps 3 through 7 for Phases B and C.
10. Remove the jumper from terminals P and D.
11. Remove the jumper from across the phase actuat-
ing current resistor.
17
S270-20-3
!
SAFETY
FOR LIFE
Table 8
Test Circuit Operating Limits for Actuating Current Settings
Column A Column B
Actuating Sectionalizer Must Sectionalizer Must
Current Setting Not Count Below Count At
(A) (A) (A)
3.5 3 4
7 6.3 7.7
16 14.4 17.6
20 18 22
24 21.6 26.4
28 25.2 30.8
40 36 44
56 50.4 61.6
80 72 88
112 101 124
160 144 176
224 201 247
256 230 282
296 266 326
320 288 352
448 403 483
480 432 528
640 576 704

Count Restraint
The count restraint feature prevents erroneous counts of
overcurrents interrupted by downline protective devices
by blocking the counting operation as long as a mini-
mum of 0.5 A of uninterrupted line current flows through
the sectionalizer.
The operation of the count restraint can be verified by
superimposing an interruptible overcurrent on a constant
minimum line current. The sectionalizer will not count or
open on the interruption of the overcurrent as long as
the minimum line current is not interrupted. To check the
count restraint feature, proceed as follows:
1. Jumper the ground actuating current resistor with a
short lead to disable the ground sensing circuit.
2. Jumper terminals P and D together.
3. Check that the sectionalizer control is set for one-
count-to-open.
4. Close the sectionalizer by operating the close pullring
the required number of times.
5. With the test circuit connected to phase A of the sec-
tionalizer and S1 closed (to simulate a constant load
current of approximately 6 A), hold S2 closed and raise
the test current to slightly above the appropriate values
shown in Column B of Table 8. Hold S2 closed for at
least three seconds
6. Release S2 to simulate a downline device clearing the
overcurrent. The sectionalizer should not open verify-
ing the operation of the count restraint feature.
7. Open S1 and again close and adjust S2 to simulate a
backup device clearing the fault. This time the section-
alizer should count the overcurrent interruption and
open.
8. Remove the jumper from terminals P and D.
Voltage Restraint
When energized at 120 Vac, the voltage charging board
provides fast charging times for the trip energy storage
capacitors. It also acts as a voltage restraint; the sectional-
izer will not count an overcurrent interruption of the protec-
tive device unless the voltage at the control is also inter-
rupted. To check the voltage restraint feature, proceed as
follows:
1. Jumper the ground actuating resistor with a short lead
to disable the ground sensing circuit.
2. Jumper terminals P and D together.
3. Program the sectionalizer for one-count-to-open.
4. Close the sectionalizer.
5. Connect 120 Vac across pins B and D of the 120 Vac
input receptacle.
6. With the test circuit connected to Phase A of the sec-
tionalizer and S1 open, Close S2 and raise the current
slightly above the appropriate value shown in Column
B of Table 8. Hold S2 closed for at least three sec-
onds.
7. Release S2 to simulate a downline device clearing the
overcurrent. The sectionalizer should not open.
8. Disconnect the 120 Vac from the input receptacle.
9. Again close and release S2. The sectionalizer should
open.
10. Remove the jumper from terminals P and D.
Number of Counts-to-Open
The number of counts-to-open can be verified by inter-
rupting, the preset number of times, an overcurrent
through the sectionalizer. For example, with the control
set for three counts, the sectionalizer will open upon the
third overcurrent interruption. Proceed as follows:
1. Jumper the ground actuating current resistor with a
short lead to disable the ground sensing circuit.
2. Jumper terminals P and D together.
3. Program the sectionalizer for three counts-to-open by
setting the COUNTS-TO-OPEN SELECTOR switch to 3.
4. Close the sectionalizer by operating the close pullring
the required number of times.
5. With the test circuit connected to phase A of the sec-
tionalizer and S1 open, close S2 and raise the test cur-
rent to slightly above the appropriate value shown in
Column B of Table 8. Hold S2 closed for at least three
seconds.
6. Open and close S2 a number of times. The sectionaliz-
er should open upon the third opening of S2.
7. To verify the two-counts-to-open setting, set the
COUNTS-TO-OPEN SELECTOR switch to 2and
repeat steps 3 through 5. The sectionalizer should
open upon the second opening of S2.
8. Remove the jumper from terminals P and D.
Type GV and GW Installation Instructions
18

Count Reset
The count reset feature resets the sectionalizer count to
zero whenever current below the actuating level flows
through the sectionalizer for longer than the pro-
grammed reset time without interruption. The reset time
settings have a tolerance of ±10 percent.
It can be verified by interrupting an overcurrent flow
through the sectionalizer one time less than the counts-
to-open setting, then allowing load current to flow for
periods just under and just over the reset setting. The
sectionalizer should open if the overcurrent for the final
count is interrupted within the reset time period (count
has reset to zero). The following procedures may be
used to verify the count reset:
1. Jumper the ground actuating current resistor with a
short lead to disable the ground-sensing circuit.
2. Program the sectionalizer control for two counts-to-
open and set the COUNT RESET SELECTOR to 15
seconds.
3. Jumper terminals P and D together.
4. Close the sectionalizer.
5. With test circuit connected to phase A of the section-
alizer and S1 open, close S2 and raise the test cur-
rent to slightly above the appropriate value shown in
Column B of Table 8. Hold S2 closed for at least
three seconds.
6. Release S2 to simulate a backup protective device
clearing the overcurrent. The sectionalizer will regis-
ter a count.
7. Close S1 for 13.5 seconds.
8. Momentarily close and then release switch S2. The
sectionalizer should open, verifying that the count
reset has not been activated.
9. Reclose the sectionalizer and then close and release
S2 once to register one overcurrent interruption
count.
10. Close S1 for slightly more than 16.5 seconds.
11. Momentarily close and release switch S2. The sec-
tionalizer should not open, verifying that the count
reset has been activated and the first count has
been erased.
12. Again, close and release S2. The sectionalizer
should open.
13. Remove the jumper form terminals P and D.
Inrush-Current Restraint
The inrush-current restraint feature distinguishes
between fault currents and inrush currents. For fault cur-
rent interruptions, the sectionalizer counts and opens
normally. For an inrush-current condition, the phase and
ground minimum actuating current detection is blocked
for three seconds to prevent counting the inrush current.
The three-second time interval allows for system inrush
parameters to stabilize prior to allowing the sensitivity of
the sectionalizer to return to its programmed state.
The operation of the inrush-current restraint can be veri-
fied by simulating a fault condition (the overcurrent is
preceded by an overcurrent interruption) and an inrush
condition (the overcurrent is preceded by a load current
interruption).
The following procedure can be used to verify the
inrush-current restraint feature.
1. Jumper the ground actuating current resistor with a
short lead to disable the ground sensing circuit.
2. Set the COUNTS TO OPEN SELECTOR switch to 1.
3. Manually close the sectionalizer.
4. With the test circuit connected to phase A of the sec-
tionalizer and S1 open, hold S2 closed and raise the
test current to slightly below the appropriate value
shown in Column A of Table 8.
5. Release S2 to simulate a backup opening with only
load current flowing through the sectionalizer when
current was interrupted. The sectionalizer should
not open.
6. Close S2 and in no more than three seconds
adjust the test current to just below twice the appro-
priate value shown in Column A of Table 8 to simu-
late an inrush condition. Release S2. The sectional-
izer should not open, verifying that the inrush
restraint feature has been activated.
7. Reset the inrush restraint as follows:
A. Short test terminals D and P together.
B. Close S1 closed for 3.5 seconds.
C. Open S1 and remove short from Test Terminals D
and P.
8. Close S2 and raise the test current to slightly above
the appropriate value shown in Column B of Table 8.
9. Release S2 to simulate a backup opening with fault
current flowing through the sectionalizer when cur-
rent was interrupted. The sectionalizer should open.
10. Close the sectionalizer.
11. Repeat step 9 to simulate a fault condition.
12. Release S2. The sectionalizer should open verifying
that the inrush restraint has not been activated.
Post-Test Procedures
After testing has been completed, make sure that the
control settings are programmed to the operating param-
eters as originally specified.
19
S270-20-3
!
SAFETY
FOR LIFE

1045 Hickory Street
Pewaukee, WI 53072 USA
www.cooperpower.com
© 2005 Cooper Power Systems or its affiliates.
Kyle®is a registered trademark of Cooper Power Systems or its affiliates..
KA2048-101 Rev: 01
!
SAFETY
FOR LIFE
KDL
6/05
This manual suits for next models
1
Table of contents
Other Cooper Power Systems Industrial Electrical manuals

Cooper Power Systems
Cooper Power Systems VXE15 User manual

Cooper Power Systems
Cooper Power Systems GV Technical specifications

Cooper Power Systems
Cooper Power Systems GW Technical specifications

Cooper Power Systems
Cooper Power Systems RVE Technical specifications

Cooper Power Systems
Cooper Power Systems GH Technical specifications
Popular Industrial Electrical manuals by other brands

SDCEM
SDCEM SBE Series Instruction book

Murata
Murata GRM155R71H681KA01 Series Reference sheet

Murata
Murata GRM219R72A392KA01 Series Reference sheet

Murata
Murata GJM0335C1E2R7BB01 Series Reference sheet

Murata
Murata GRM188R71E562KA01 Series Reference sheet

Murata
Murata GRM1555C1H181GA01 Series Reference sheet