Specification
Certification: UL Listed for USA and Canada:
– Hazardous locations
Class I, Div 2, groups A, B, C & D. Class 1, Zone 1
Class II, Div 2, groups F & G, AExd IIC T4/T5.
UL listing No. E187894.
– Ordinary locations: Visual Signal Device.
UL listing No. S8128
CENELEC EN50014 & EN50018.
ATEX Cert. No. Baseefa 04ATEX0009X.
Material: Body: Glass reinforced polyester.
Lens: Glass.
Backstrap: stainless steel 316.
Wire Guard (optional): Stainless steel wire.
Cast Guard (optional): Aluminium LM25M.
Finish: Natural black or epoxy painted to customer specification.
Voltage: 24, 48V d.c.
110, 120, 230, 240, 254V a.c.
Tube Energy: 15 Joules.
Tube Life: >1 x 106 flashes.
Flash Rate: 60, 80, 120 fpm.
Certified -67°F to +104°F (T6) -55°C to +40°C (T6)
Temperature: -67°F to +131°F (T5) -55°C to +55°C (T5)
Weight: Pipe mount: 5.75lb./2.6kg; Direct mount: 6.5lb./3.0kg.
Ingress NEMA 4x &6, IP66 & IP67.
Protection:
Entries: Supplied as 2 x ¾" NPT (direct mount) or ¾" (pipe mount) as
standard.
Other options available:
Up to 3 x ½" NPT or 3 x ¾" NPT (direct mount);
½" NPT (pipe mount) – contact sales office to order.
Terminals: Direct mount: 12 x 14AWG
Pipe mount: 8 x 14AWG
Finish Code
Natural Black N
Red R
Blue B
Yellow Y
Green G
White W
Special Finish S
Color Code
Red R
Blue B
Green G
Amber A
Yellow Y
Clear C
Fpm Code
60 06
80 08
120 12
Voltage Code
24V d.c. 024
48V d.c. 048
110V a.c. 110
120V a.c. 120
230V a.c. 230
240V a.c. 240
254Va.c. 254
Guard Code
None N
Cast C
Wire W
Configuration Options:
The following code is designed to help in the selection of the correct unit. Build up the reference number by inserting the
code for each component into the appropriate box.
Lens Lens Unit Other
Model Certification Voltage Flashrate Color Guard Fixing Options Finish
XB15
Unit Fixing Code
Pipe mount P†
Direct mount D†
Direct w/backstrap B†
Option Code
None N
Tag label T
Duty label D
Relay initiate* R
Blanking Plug P
Multiplying Factor for Colored Lenses:
Red Blue Amber Green Yellow
0.15 0.12 0.51 0.49 0.86
Certification Code
UL UL
UL (ordinary UW
location)
†Contact Sales
Office if ½" NPT
is required.
*Suitable for 24V d.c.
supplies only.
Electrical Ratings:
d.c a.c
Voltage 24 48 110 120 230 240 254
Current (mA) 780 670 400 400 200 200 170
Effective Candela - 330
Tube Energy (Joules) 15 15 15 15 15 15 15
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Made in USA
273 Branchport Avenue
Long Branch, NJ 07740
Phone: (800) 631-2148
Fax: (732) 222-2588
www.cooperwheelock.com
XB15 04/07
Series Model Number Order Code Decription
XB15 XB15UL02406RWPNN 109203-001 330 candela Red Lens, Black finish, 24 VDC
XB15 XB15UL02406RWBNN 109203-002 330 candela Red Lens, Black finish, 24 VDC
XB15 XB15UL02406CWBNR 109203-205 Clear Lens, 330 candela, 24 VDC, Pipe mount, Black finish
XB15 XB15UL12006AWBNN 109202-005 Amber Lens, 330 candela, 120 VAC, backstrap mount, Black
finish
XB15 XB15UL12006AWPNN 109202-006 Amber Lens, 330 candela, 120 VAC, Pipe mount, Black
finish
XB15 XB15UL12006RWBNN 109202-007 Red Lens, 330 candela, 120 VAC, backstrap mount, Black
finish
XB15 XB15UL12006RWPNN 109202-208 Red Lens, 330 candela, 120 VAC, Pipe mount, Black finish
Standard Models
Relay Initiate:
Available on all units – suitable for 24V d.c. supplies only.
Labels: Tag/Duty label option.