Coopers Kyle FXB Operating and installation instructions

Kyle®Type FXB Microprocessor-Based
Electronic Recloser Control
Front Panel Programming Instructions
Reclosers
Service Information
Safety Information ..................................................... 2
Product Information .................................................. 3
Introduction ............................................................... 3
FXB Control Front Panel .......................................... 4
LCD User Interface..................................................... 4
Menu System .............................................................. 4
Control Security ......................................................... 4
Control Panel LED Indicators ................................... 6
Fault Target LEDs ........................................................ 6
Status LEDs ................................................................. 6
Control Panel Keyboard Functions.......................... 7
Using Hot Keys ............................................................ 7
Manual Operation ...................................................... 8
Using Manual-Operation Switches............................... 8
Viewing Menus ..........................................................10
Editing Parameters ...................................................10
Editing the Password ...................................................11
Editing Control Date/Time ............................................11
Editing TCCs ................................................................12
Warnings and Errors..................................................13
Resetting Max Demand Current Settings ................14
Contents
S280-78-3
Printed in USA
1
May 2005 • Supersedes 10/02
Figure 1.
Kyle®Type FXB Microprocessor-Based Electronic Recloser Control.
97KM-A

Type FXB Microprocessor-Based Electronic Recloser Control Front Panel Programming Instructions
2
The instructions in this manual are not intended as a sub-
stitute for proper training or adequate experience in the
safe operation of the equipment described. Only compe-
tent technicians, who are familiar with this equipment
should install, operate, and service it.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions.
• Is trained in industry-accepted high- and low-voltage
safe operating practices and procedures.
• Is trained and authorized to energize, de-energize,
clear, and ground power distribution equipment.
• Is trained in the care and use of protective equipment
such as flash clothing, safety glasses, face shield,
hard hat, rubber gloves, hotstick, etc.
Following is important safety information. For safe instal-
lation and operation of this equipment, be sure to read
and understand all cautions and warnings.
Safety Instructions
Following are general caution and warning statements
that apply to this equipment. Additional statements, relat-
ed to specific tasks and procedures, are located through-
out the manual.
SAFETY INFORMATION
WARNING: This equipment is not intended to
protect human life. Follow all locally approved pro-
cedures and safety practices when installing or operat-
ing this equipment. Failure to comply may result in
death, severe personal injury and equipment damage.
G102.1
!
DANGER: Hazardous voltage. Contact with haz-
ardous voltage will cause death or severe per-
sonal injury. Follow all locally approved safety proce-
dures when working around high- and low-voltage lines
and equipment. G103.3
!
WARNING: Before installing, operating, main-
taining, or testing this equipment, carefully read
and understand the contents of this manual. Improper
operation, handling or maintenance can result in death,
severe personal injury, and equipment damage. G101.0
!
SAFETY FOR LIFE
Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively
promote safe practices in the use and maintenance of our products through our service literature, instructional training pro-
grams, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, mar-
keting, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working
around high voltage lines and equipment and support our “Safety For Life” mission.
!
SAFETY
FOR LIFE
!
SAFETY
FOR LIFE
This manual may contain four types of hazard
statements:
DANGER: Indicates an imminently haz-
ardous situation which, if not avoided, will
result in death or serious injury.
WARNING: Indicates a potentially hazardous
situation which, if not avoided, could result in
death or serious injury.
CAUTION: Indicates a potentially hazardous
situation which, if not avoided, may result in
minor or moderate injury.
CAUTION: Indicates a potentially hazardous situ-
ation which, if not avoided, may result in equip-
ment damage only.
!
!
!
Hazard Statement Definitions
WARNING: Power distribution equipment must
be properly selected for the intended application.
It must be installed and serviced by competent person-
nel who have been trained and understand proper safe-
ty procedures. These instructions are written for such
personnel and are not a substitute for adequate training
and experience in safety procedures. Failure to proper-
ly select, install, or maintain power distribution equip-
ment can result in death, severe personal injury, and
equipment damage. G122.2
!

S280-78-3
3
!
SAFETY
FOR LIFE
Introduction
Service Information S280-78-3 provides front panel key-
pad programming information for the FXB microprocessor-
based electronic recloser control. These instructions are
designed to assist engineers and qualified technicians
with programming the FXB control. These individuals
must be familiar with the functions and programming
parameters required for specific recloser installations.
The information contained in this manual is organized
into the following major categories: Safety Information,
Product Information, Front Panel Keypad Programming,
Control Security, Control Panel LED Indicators, Keypad
Functions, Manual Operating Controls, Viewing Menus,
Editing Parameters, and Warnings and Errors. Refer to
the table of contents for page numbers.
These instructions contain a listing of program settings
and detailed operating descriptions. The settings and
detailed operating descriptions are also listed on the
control information label, located inside the cabinet door.
Read This Manual First
Read, understand, and follow the contents of these
instructions, plus Service Information S280-78-1, FX,
FXA, and FXB Microprocessor-Based Electronic Recloser
Control Installation Instructions and Service Information
S280-78-2 FX, FXA, and FXB Microprocessor-Based
Electronic Recloser Control Programmer’s Software
User’s Manual, and follow all locally approved procedures
and safety practices before installing or operating this
equipment.
Additional Information
These instructions cannot cover all details or variations in
the equipment, procedures, or process described nor
provide directions for meeting every possible contin-
gency during installation, operation, or maintenance.
When additional information is desired to satisfy a prob-
lem not covered sufficiently for the user's purpose,
please contact your Cooper Power Systems Division
sales engineer.
Acceptance and Initial
Inspection
Each Type FXB control is completely assembled, tested,
and inspected at the factory. It is carefully calibrated,
adjusted, and in good condition when accepted by the
carrier for shipment.
Upon receipt, inspect the carton for signs of damage.
Unpack the control and inspect it thoroughly for damage
incurred during shipment. If damage is discovered, file a
claim with the carrier immediately.
Handling and Storage
Be careful during handling and storage of the control to
minimize the possibility of damage. If the control is to be
stored for any length of time prior to installation, provide
a clean, dry storage area. If storage is in a humid atmos-
phere, make provisions to keep the control circuitry ener-
gized.
Note: To energize the control, apply ac power to the ac sup-
ply input terminal block located in the lower right hand
corner of the back panel of the control cabinet. Refer to
the Customer Connection for Ac Power section in this
manual.
ANSI Standards
Kyle reclosers are designed and tested in accordance
with ANSI standards C37.60 and C37.85 and ANSI
guideline C37.61.
Quality Standards
ISO 9001:2000-Certified Quality Management System
PRODUCT INFORMATION

Type FXB Microprocessor-Based Electronic Recloser Control Front Panel Programming Instructions
4
The FXB control front panel (see Figure 2) offers exten-
sive user interface status as well as control interrogation
through the menu-driven keypad and LCD display.
The FXB control, equipped with discrete SCADA (avail-
able as an accessory), allows 23 different status monitor-
ing points.
LCD User Interface
The FXB control LCD user interface consists of the fol-
lowing elements:
• A row of five manual-operation buttons or keys (located
below the 4-line x 20-character LCD display) that are used
to navigate through the menu system and to view or edit
control parameters. These keys are UP, DOWN, EDIT,
ENTER, and ESC.
• A text-based 4-line x 20-character LCD display (located
above the first row of five manual operation buttons or keys).
• A second row of five operation buttons or “hot keys” that are
used to perform specific functions. These hot keys are
OPER COUNTER, RMS CURRENT, DISPLAY TEST,
BATTERY TEST, and RESET TARGETS.
Specific usage of the LCD keys is described in the
Viewing Menus, Editing Parameters, and Using Hot Keys
sections of these instructions.
Menu System
The LCD menu system (see Figure 3) consists of the fol-
lowing levels:
• Level 1 Main Menu Items.
• Level 2 Sub-Menu which contains items within each
main menu item.
• Level 3 Page Menu which may contain up to four
parameters within each submenu item.
Where possible, menus and parameters have been
grouped to follow the arrangement of the Cooper Power
System Kyle®Distribution Switchgear FX, FXA, and FXB
Programmer software. The following formatting rules
have been established for displaying menu labels and
parameters on a single LCD line:
• All text may use up to a maximum of 19 characters.
The 20th character is reserved to indicate menu
direction/mode by using special characters.
• All menu labels are left justified.
• Parameters that have a value with units use the fol-
lowing format:
[Parameter Label - left justified]
[Parameter Value]
[Units - right justified]
• Parameters that have a value with no units use the
following format:
[Parameter Label - left justified]
[Parameter Value - right justified]
For an overview of the FXB menu system, see Figure 3.
Control Security
FXB control security provides limited access to functions
appropriate to responsibility levels of personnel. The
four-digit security code (or password) prohibits unautho-
rized keypad access to programming and other operating
parameters. No programming commands are accepted
by the control unless the operator enters the appropriate
four-digit security code. Provide the necessary security
codes to programming personnel.
The FXB is programmed at the factory with a standard
security code (or password) of AAAA. This code is
changeable to any 4-digit number via the front panel
under CONFIGURATION at the Password screen. See
the Editing Password section of these instructions for
more information.
A security password is not required for interrogation of
the control to display all operating parameters and read-
only functions of the control front panel.
Note: The security code is stored in nonvolatile random-
access memory (RAM). Therefore, it will never be lost,
even if ac power is lost and the battery is discharged.
FXB CONTROL FRONT PANEL
IMPORTANT: Security is provided and designed so that
only personnel completely familiar with the operation of
the control may gain access. Faulty programming could
lead to unintentional control performance.

S280-78-3
5
!
SAFETY
FOR LIFE
Figure 2.
Type FXB recloser control front panel and unit interior.
970032KM
Status LED Indicators
Manual Operating
Control Keypad
(and Hot Keys)
Battery Test
Terminals
Display Switch
Backup Control
Battery Power Capacitor
Pulse/Maintain
Switch*
RS232 Port
Supervisory ON/OFF
Switch*
TRIP/CLOSE
Switches
AC Supply Input
Terminal Block
SGF/SEF Blocked
Keypad (optional)
Fault Target
LED Indicators
Hot Line Tag
LED Indicator*,
and/or Manual
ON/OFF Switch*
*Provided on controls
equipped with the option-
al SCADA feature
4-line by 20-character
LCD display screen
Control
Recloser
Communications
Password
Minimum Trips
Operations to Lockout
Reclose/Reset Time
Time Current Curves
Cold Load Pickup
High Current Lockout
General
Interrupter Duty
RMS Currents
Demand Currents
Max. Demand Currents
Target Counters
State
Metering Configuration
Event XX Entry XX
FXB MENU SYSTEM
Configuration Basic Parameters Adv. Parameters Meters/Counters Event Recorder Load Profile
Figure 3.
The FXB menu system.

Type FXB Microprocessor-Based Electronic Recloser Control Front Panel Programming Instructions
6
Control Panel LED Indicators
Light-emitting diode indicators, or LEDs (see Figure 4),
are arranged along the left side of the control front panel
and provide a visual report of control and recloser oper-
ating status. The LEDs are grouped to display fault tar-
gets and status functions.
Fault Target LEDs
Bushing 1-2, Bushing 3-4, Bushing 5-6, Ground/Earth,
and SGF/SEF (Sensitive Ground/Earth Fault, an optional
fault target feature) indicate the detection of fault current
on individual phases or ground.
Status LEDs
RECLOSER CLOSED: Indicates that the recloser con-
tacts are in the CLOSED position.
RECLOSER OPEN: Indicates that the recloser contacts
are in the OPEN position.
CONTROL LOCKOUT: Indicates that the control has
operated to lockout.
CONTROL OK: Indicates that the control’s continuous
self-diagnostics have detected no EEPROM malfunc-
tions.
CURRENT ABOVE MINIMUM TRIP: Indicates that line
current is above the programmed minimum trip current.
GROUND TRIP BLOCKED: Indicates whether or not
ground trip blocked has been activated by either the front
panel switch or via the supervisory control.
NON-RECLOSING ACTIVE: Indicates whether non-
reclosing has been activated either by the front panel
switch or via supervisory control.
ALTERNATE MINIMUM TRIP ACTIVE: Indicates
whether alternate minimum trip has been activated by the
front panel or via supervisory control.
SGF/SEF BLOCKED: Indicates whether the Sensitive
Ground/Earth Fault Blocked feature has been activated
by the front panel or via supervisory control.
Figure 4.
Kyle®FXB Fault Target LEDs (above left) and Status LEDs (right).

S280-78-3
7
!
SAFETY
FOR LIFE
Figure 5.
FXB control Hot Keys (second row).
Control Panel
Keyboard Functions
Located below the 4-line x 20-character LCD display are
two rows of five manual-operation buttons or keys. The
second row of five operation buttons are referred to as
Hot Keys (see Figure 5) and are used to perform specific
control functions. The Hot Keys are
OPER COUNTER, RMS CURRENT, DISPLAY
TEST, BATTERY TEST, and RESET TARGETS.
Using Hot Keys
The use of Hot Keys (see Figure 5) quickly displays the
LCD menu range for the selected key. Hot Keys also pro-
vide a quick alternative to using a computer interface or
scrolling through the LCD menus.
UP Arrow: This key is used to scroll UP through the pro-
gramming menu.
DOWN Arrow: This key is used to scroll DOWN through
the programming menu.
EDIT: This key, for programmable functions, will (with the
use of the UP and DOWN scroll keys) allow a different
parameter to be selected and changed.
ESC (Escape): This key allows user to back out of each
submenu or menu and return to the main programming
menu. Pressing this key while in the edit mode will imme-
diately return the user to the viewing mode.
OPER. COUNTER (Operations Counter): This key dis-
plays the operations counter value on the LCD display (i.e.,
OPERATIONS XX). This value updates once every second
or until the ESC key is pressed to escape from this menu.
RMS CURRENT: Pressing this key displays the four
instantaneous currents on the LCD display. The currents
update once every second or until the ESC key is pressed
to escape from this menu.
DISPLAY TEST: Pressing this key toggles all LEDs on
the front panel on and off three times then returns each
LED to its current status. The DISPLAY TEST hot key
also tests each segment on the LCD display and returns
it to its previous state.
BATTERY TEST: This key starts the battery test
sequence. The battery is measured with no load, then the
voltage is displayed via the LCD. A 15 Ωload is then
applied directly across the battery. Five seconds later, the
loaded battery voltage is displayed on the LCD screen
with a Battery OK or Battery Not OK message. This
message remains on the screen until the ESC key is
pressed to escape from this menu.
RESET TARGET: Pressing this key turns off all Fault
Target LEDs that are currently on. This function can be
performed at any time without affecting the LCD menu
system. Pressing this key has no effect if all Fault Target
LEDs are off.
Hot Keys:
the five manual-
operation buttons
in the second row

Manual operation of the FXB control occurs through the
use of the front-panel manual-operation switches. The
switches are
•SGF/SEF BLOCK (optional)
•NON-RECLOSING
•GROUND TRIP BLOCKED
•ALTERNATE MINIMUM TRIP
•SUPERVISORY ON
•HOT LINE TAG
•MANUAL CONTROL SWITCH
Refer to Figure 6 as needed to locate each key.
Using Manual-Operation Switches
The use of manual-operation switches (see Figure 6)
provides designated control commands to the recloser.
The switches also provide an alternative to using a com-
puter interface or scrolling through the LCD menus.
SUPERVISORY ON: The SUPERVISORY ON feature is
provided on controls equipped with the optional SCADA
accessory. If the SUPERVISORY ON switch is on, it
allows supervisory operation of the control. Conversely, if
the SUPERVISORY ON switch is not on, it prevents
supervisory operation of the control.
HOT LINE TAG: HOT LINE TAG prevents all closing
operations by opening control contacts in series with the
recloser low-voltage closing-circuit coil. If the feature is
activated while the recloser is closed and the control is in
the reset (home) position, a fault will cause one trip oper-
ation to lockout.
GROUND TRIP BLOCKED: Ground-fault trip operation of
the control is disabled when the GROUND TRIP BLOCK
switch is set in the block position. Blocking ground-trip
operations is useful during known periods of three-phase
load imbalance and is recommended while performing
single-phase load imbalance, testing, or switching.
NON-RECLOSING: By setting the operating mode
switch to NON RECLOSING, the FXB control will block
reclosing after an automatic trip (one trip operation to
lockout) on TCC #1 for phase and ground. When set in
the NORMAL RECLOSING mode, the FXB control will
operate on its programmed operating sequence.
SGF/SEF BLOCK: This switch controls the detection of
and recloser tripping operations for Sensitive
Ground/Earth fault currents below the normal pro-
grammed SGF/SEF minimum trip level (optional feature).
ALTERNATE MINIMUM TRIP: This switch permits
switching to alternate preprogrammed phase, ground,
and sensitive ground-fault minimum-trip values.
TRIP (LOCKOUT) AND CLOSE SWITCHES: Pressing
the green TRIP switch opens the recloser, and the con-
trol locks out. Pressing the red CLOSE button returns the
recloser to the reset condition, and the recloser closes.
While the switch is in the close position, the control is still
free to trip and lockout if closed into a fault.
Type FXB Microprocessor-Based Electronic Recloser Control Front Panel Programming Instructions
8
MANUAL OPERATION

S280-78-3
9
!
SAFETY
FOR LIFE
Figure 6.
Location of FXB manual-operation switches.
SUPERVISORY
ON
GROUND TRIP
BLOCKED
NON-
RECLOSING
HOT LINE TAG
ALTERNATE
MINIMUM TRIP
CLOSE red
TRIP
(LOCKOUT) green
SGF/SEF
BLOCKED
(optional)

Viewing Menus
Accessing the menus for viewing purposes is accom-
plished by using the UP, DOWN, ENTER, and ESC
(ESCAPE) keys. The direction of available menus is indi-
cated to the user by display of special characters; down
arrow, up arrow, and up and down arrow; on the last col-
umn of the first LCD line. The initial state of the menu
system displays the first item from the main menu, CON-
FIGURATION; this is called the home position. From this
point the user can proceed as follows:
1. Press the UP and DOWN key to view other main menu
items.
2. Press the ENTER key to access the first submenu
from the selected main menu item.
3. Press the ESC key to go back to the home position if
the menu is not already there.
Once the first submenu item from a selected main menu
item is displayed, the user can proceed as follows:
1. Press the UP and DOWN key to view other submenu
items.
2. Press the ENTER key to access the first page menu
from a selected submenu item.
3. Press the ESC (escape) key to go back to the previ-
ously selected main menu item.
Once the first page menu item from a selected submenu
item is displayed, the user can proceed as follows:
1. Press the UP and DOWN key to view other page
menu items.
2. Press the ESC (escape) key to go back to the previ-
ously selected submenu item.
The FXB function tree (Figure 3) illustrates the sublevels
of the FXB Menu System. The first row contains the six
main menu items: Configuration, Basic Parameters,
Advanced Parameters, Meters/Counters, Event
Recorder, and Load Profile. Under each of these main
menu items is a number of submenus demonstrating
what type of information can be obtained or changed at
the next level or page menu.
Editing Parameters
The EDIT key becomes active when a page menu is
being displayed and at least one parameter from the
menu has the write or reset attribute. For example, the
RMS currents are read-only parameters, so the EDIT key
has no effect when they are displayed.
To edit a parameter, proceed as follows:
1. Press the EDIT key. A left arrow character is dis-
played on the last column of the LCD line to indicate
which parameter to select for editing.
2. Press the UP or DOWN key to select which parame-
ter to edit.
3. Press the EDIT key. The left arrow character changes
to a blinking up & down arrow character to indicate
that the parameter can now be edited.
4. Press the UP or DOWN key to select the desired
parameter value. For parameters that have a wide
range of values such as Minimum Trips, a speed
increment/decrement feature has been implemented.
If the UP or DOWN key is held pressed-in for up to
approximately 3 seconds, the parameter value is
updated at a rate of approximately 10 times per sec-
ond. After 3 seconds of continuously pressing either
key, the parameter value is increased or decreased,
respectively, by approximately 5% of its remaining
range and updated at a rate of approximately 10
times per second.
5. Once the desired parameter has been selected,
press the ENTER key to perform the change and then
exit from the edit mode. If the previously selected
parameter is rejected by the control, the message
PARAMETER REJECTED is displayed. Press the
ESC (escape) key to clear the message, then return
to the view mode. For example, the range of valid
minimum trips depend on the CT ratio, so it is possi-
ble to have a minimum trip setting that would be con-
sidered invalid at the time a CT ratio change is
attempted.
When the LCD becomes active, the first parameter to be
edited requires the user to enter the active password.
To enter the password, proceed as follows:
1. Press the EDIT key. The blinking up and down
arrow character is displayed to indicate that the active
PASSWORD can now be entered. Then use the UP
and DOWN key to select an alphanumeric number.
2. Press the ENTER key. This will store the first character
and set up the selection of the next character. Since
the password consists of four characters, select and
enter the second, third, and fourth characters. The
user can only see the character being selected. Other
characters are displayed as asterisks (*).
3. After selecting the fourth character, press the
ENTER key. If the password just entered is the same
as the active password, the LCD returns to the view
mode and the previous sequence for editing parame-
ters can now be followed. If not the same, the message
INVALID PASSWORD is displayed.
4. If the ERROR message is displayed, press the
ESC key to clear it and return to the view mode.
If the user has changed the password but is unable to
remember it, contact your Cooper Power Systems repre-
sentative.
Type FXB Microprocessor-Based Electronic Recloser Control Front Panel Programming Instructions
10

Editing the Password
The FXB is programmed at the factory with a standard
security code (or password) of AAAA.
The password parameter can be found under CONFIGU-
RATION/ PASSWORD, refer to Figure 7.
To edit the Password, proceed as follows:
1. Press the EDIT key. The blinking up and down
arrow character is displayed to indicate that a NEW
PASSWORD can be entered. Then use the UP and
DOWN key to select an alphanumeric character.
2. Press the ENTER key. This will store the first char-
acter and set up the selection of the next character.
Since the password consists of four characters, select
and enter the second, third, and fourth characters. The
user can only see the character being selected; other
characters are displayed as asterisks (*).
3. After selecting the fourth character, press the ENTER
key. The blinking up and down arrow character is displayed
to indicate that password VERIFICATION can now be
entered. Select and enter the first through fourth characters.
4. After selecting the fourth character, press the ENTER
key. If the VERIFICATION password is the same, the mes-
sage PASSWORD CHANGED is displayed and the newly
entered password becomes the active password. If not the
same, the message VERIFY FAILED is displayed and
the old password remains as the active password.
5. Press the ESC key to clear the message and return
to view mode.
Edit mode for the password can be terminated at any
time by pressing the ESC key.
Editing Control Date/Time
Control Date/Time parameters can be found on the first
page menu under CONFIGURATION/CONTROL.
To edit these parameters, proceed as follows:
1. Press the EDIT key. The blinking up & down arrow
character is displayed to indicate that the MONTH can
now be edited. Then, use the UP or DOWN key to
select the MONTH.
2. Press the ENTER key. The blinking up & down
arrow character is displayed to indicate that the DAY
can now be edited. Then, use the UP or DOWN key
to select DAY.
3. Press the ENTER key. The blinking up & down
arrow character is displayed to indicate that the
YEAR can now be edited. Then use the UP or DOWN
key to select the YEAR.
4. Press the ENTER key. The blinking up & down
arrow character is displayed to indicate that the
HOUR can now be edited. Then, use the UP or
DOWN key to select the HOUR.
5. Press the ENTER key. The blinking up & down
arrow character is displayed to indicate that the
MINUTE can now be edited. Then, use the UP or
DOWN key to select the MINUTE.
6. Press the ENTER key to perform the changes and
exit the edit mode.
S280-78-3
11
!
SAFETY
FOR LIFE
Configuration
Password
New Password****
Password A***
Verification A***
Password Changed
Enter
Enter
Edit
Enter
Enter
Figure 7.
Password Editing Flowchart.

Type FXB Microprocessor-Based Electronic Recloser Control Front Panel Programming Instructions
12
Editing TCCs
The TCC page menu can be found under BASIC PARA-
METERS/TIME CURRENT CURVES. If a standard curve
is required for a phase or ground operation, the editing pro-
cedure consists of only the selection of the desired curve
from the standard library. If a modified curve is required,
the following TCC modifiers are available for editing:
•MULT/ADDER OFF/ON
•MULTIPLIER 0.100-2.000
•ADDER 0.000-0.200 (sec)
•MIN RESP TIME (MRT) OFF/ON
•MR TIME (MRT) 0.013-1.000 (sec)
•HI CURRENT TRIP (HCT) OFF/ON
•HCT TIME 0.016-0.150 (sec)
•HCT RATIO 1.00-29.00
NOTE: Communication between the control and the keypad is
temporarily interrupted when reading a TCC and the
screen will go blank.
To edit a TCC for phase or ground operation, proceed as
follows:
1. Press the EDIT key. The blinking up & down arrow
character is displayed to indicate that the CURVE
TYPE can now be edited. Then, use the UP or DOWN
key to select STANDARD or MODIFIED.
2. Press the ENTER key. The blinking up & down arrow
character is displayed to indicate that a TCC from the
standard Kyle library can now be edited. Then, use
the UP or DOWN key to select the TCC.
If the CURVE TYPE was selected as STANDARD, con-
tinue with step 11.
3. If the CURVE TYPE was selected as MODIFIED,
press the ENTER key twice. The blinking up & down
arrow character is displayed to indicate that the
MULT/ADDER can now be edited. Then use the UP
or DOWN key to select ON or OFF.
4. If the MULT/ADDER selected was ON, press the
ENTER key. The blinking up & down arrow character
is displayed to indicate that the MULTIPLIER can now
be edited. Then, use the UP or DOWN key to select
the MULTIPLIER.
If the MULT/ADDER selected was OFF, continue with
step 6.
5. If the MULT/ADDER was selected as ON, press the
ENTER key. The blinking up & down arrow character
is displayed to indicate that the ADDER can now be
edited. Then, use UP or DOWN key to select the
ADDER.
6. Press the ENTER key. The blinking up & down arrow
character is displayed to indicate that the MIN RESP
TIME can now be edited. Then, use the UP or DOWN
key to select ON or OFF.
If MIN RESP TIME was selected as OFF, continue with
step 8.
7. If MIN RESP TIME was selected as ON, press the
ENTER key. The blinking up & down arrow character
is displayed to indicate that the MR TIME can now be
edited. Then, use the UP or DOWN key to select the
MR TIME.
8. Press the ENTER key. The blinking up & down arrow
character is displayed to indicate that the HI CUR-
RENT TRIP flag can now be edited. Then, use the UP
or DOWN key to select ON or OFF.
If HI CURRENT TRIP was selected as OFF, continue
with step 11.
9. If HIGH CURRENT TRIP was selected as ON, press
the ENTER key. The blinking up & down arrow char-
acter is displayed to indicate that the HCT TIME can
now be edited. Then, use the UP & DOWN key to
select the HCT TIME.
10. If HIGH CURRENT TRIP was selected as ON, press
the ENTER key. The blinking up & down arrow char-
acter is displayed to indicate that the HCT RATIO can
now be edited. Then, use the UP or DOWN key to
select the HCT RATIO.
11. Press the ENTER key to perform changes. The com-
pletion of these changes will take a few seconds. The
following messages are displayed sequentially to
indicate progress in the transaction: CALCULATING
TCC, WRITING TCC, READING TCC, and TCC edit-
ing is now complete.

S280-78-3
13
!
SAFETY
FOR LIFE
Warnings and Errors
Warnings and errors may occur after a TCC is calculat-
ed. A warning means that the TCC was generated, but
something is unusual. An error means that the TCC was
not generated.
Warnings and Errors are as follows:
CURVE CLIPPED WARNING
The TCC time exceeded the minimum or maximum time
that is allowed in the graph workspace of the TCC Editor.
Time must be greater than or equal to 0.008 and less
than or equal to 100 seconds.
HCT IGNORED WARNING
The selected HCT time was ignored because using it
would have resulted in non-monotonic curve.
MRT BELOW CURVE WARNING
The selected MRT had no effect because the TCC
always times longer than the MRT.
CALCULATION ERROR
This system error occurs if the FXB cannot allocate
enough memory to calculate TCC.
Edit mode for TCC modifiers can be terminated at any
time by pressing the ESC key.
The TCC calculation generates data for 50 or 60 Hz fre-
quencies automatically. The data that is generated for a
modified TCC is not stored by the FXB. Names for mod-
ified TCCs are automated. For example, the standard
curve “Kyle-101 60”will have the name “Kyle-101 60
mod”when it has been modified.

Resetting Maximum Demand
Current Settings
1. Using the DOWN arrow on the front panel of the FXB
control, scroll to Meters/Counters menu and press
ENTER.
2. Using the DOWN arrow, scroll to MAX DEMAND
CURRENTS and press ENTER. The following infor-
mation will be displayed:
3. Press the EDIT key one time. The password dialog
box will be displayed. Enter your password if it has
been changed from the factory set password
“AAAA”. If the password has not been changed,
press the ENTER key 4 times.
4. Press the EDIT key twice. A blinking cursor will be
displayed to the right of the text.
5. Press the DOWN arrow to reset the value to 0.
6. Press the EDIT key. An left-facing arrow will be dis-
played to the right of the text. Using the DOWN arrow,
scroll to MAX PH 1-2.
7. Press the EDIT key. The left-facing arrow wil turn into
a blinking cursor to the right of the text.
8. Press the DOWN arrow to reset the value to 0.
9. Follow steps 6 through 8 to reset the remaining
Maximum Phase Demands.
Type FXB Microprocessor-Based Electronic Recloser Control Front Panel Programming Instructions
14
MAX GND ____________ 2 3 A M P
MAX Ph 1-2 ____________ 4 AMP
MAX Ph 3-4 ____________ 6 AMP
MAX Ph 5-6 ____________ 5 AMP
MAX GND ____________ 2 3 A M P
MAX Ph 1-2 ____________ 4 AMP
MAX Ph 3-4 ____________ 6 AMP
MAX Ph 5-6 ____________ 5 AMP
MAX GND ____________ 0 A M P
MAX Ph 1-2 ____________ 4 AMP
MAX Ph 3-4 ____________ 6 AMP
MAX Ph 5-6 ____________ 5 AMP
MAX GND ____________ 0 A M P
MAX Ph 1-2 ____________ 0 AMP
MAX Ph 3-4 ____________ 6 AMP
MAX Ph 5-6 ____________ 5 AMP
MAX GND ____________ 0 A M P
MAX Ph 1-2 ____________ 4 AMP
MAX Ph 3-4 ____________ 6 AMP
MAX Ph 5-6 ____________ 5 AMP
MAX GND ____________ 0 A M P
MAX Ph 1-2 ____________ 4 AMP
MAX Ph 3-4 ____________ 6 AMP
MAX Ph 5-6 ____________ 5A

S280-78-3
15
!
SAFETY
FOR LIFE

Type FXB Microprocessor-Based Electronic Recloser Control Front Panel Programming Instructions
KDL
5/05
1045 Hickory Street
Pewaukee, WI 53072
www.cooperpower.com
©2005 Cooper Power Systems or its affiliates.
Kyle®is a registered trademark of Cooper Power Systems or its affiliates.
KA2048-443 Rev: 03
!
SAFETY
FOR LIFE
Table of contents