COSMOGAS CR04 User manual

REMOTE TIME CONTROL
“CR04”
INSTRUCTIONS FOR THE INSTALLATIONAND USE OF
THE “CR04” REMOTE CONTROL
62403440 - R01 17-01-2008_GB-IE
PLEASE READ THE MANUAL CAREFULLY: IT CONTAINS IMPORTANT INFORMATION REGARDING
SAFETY, INSTALLATION, USE AND MAINTENANCE OF THE APPLIANCE

2
Table of contents
1 - Main features ........................................................................................................... 3
2 - Operating features................................................................................................... 3
2.1 - LCD Display ............................................................................................................................. 3
2.2- Keys and associatedfunctions.................................................................................................. 3
3 - Initial start-up............................................................................................................4
4 - Introduction .............................................................................................................. 4
5 - Users’ menu............................................................................................................. 4
5.1 - Selecting the operating modes.................................................................................................. 5
5.2-Automatic or manualoperationof the time programmablethermostat........................................5
5.3-Adjusting the domestic hotwatertemperature............................................................................6
5.4-Manualforcingofroomtemperature(overrunfunction)............................................................... 6
5.5- Forcing ofheating programme .................................................................................................. 6
5.6 - Forcing of domestic hot water programme ................................................................................ 6
5.7-Systemparameters’consultation............................................................................................... 7
5.8- Programming the heatingtimes................................................................................................. 8
5.8.1-Calling up anexistingprogramme for heating.................................................................8
5.8.2- Programming ofdomestic hot water timing .................................................................. 10
5.8.3- Calling up anexisting programme fordomestic hot water.............................................10
5.9-Adjusting the systemoperatingparameters ............................................................................. 11
5.10-Date, hour and minute setting................................................................................................ 12
5.11- Memorizing hour/minutes/date andoperatingmode...............................................................12
5.12-Indicationof boiler with burner on........................................................................................... 12
5.13- Indication of presenceof anomalies ......................................................................................12
6 - Installers’ menu...................................................................................................... 13
6.1- Displaying thesystemparameters........................................................................................... 13
6.2 - Displayingand changing thesystem parameters..................................................................... 14
6.2.1-Thermoregulation-Setting the gradient........................................................................ 15
6.2.2-Thermoregulation-Correctionwith room temperature..................................................16
6.2.3-Thermoregulation - Choosing the operatingmodes...................................................... 18
6.2.4-Hour type displayed .....................................................................................................19
6.2.5- Domestic hotwater programme type ........................................................................... 19
6.2.6-Automaticpre-heating..................................................................................................19
6.2.7-Minimumsupplytemperature .......................................................................................20
6.2.8-Maximumsupplytemperature ...................................................................................... 20
6.2.9-Pre-setting of room temperature ..................................................................................20
6.2.10 -Pre-setting ofdomestic hotwater temperature ...........................................................20
6.2.11- Pre-setting of systemsupplytype ............................................................................... 20
6.2.12- Correcting the roomtemperature read .......................................................................20
6.2.13-Factory settings ......................................................................................................... 21
6.3 - Diagnostics............................................................................................................................. 21
6.3.1 - modelsAXIA-Ei, BMS-Ei and BME-Ei .........................................................................21
6.3.2- modelsAXIA-H,ECOPLUS, ECOBI, INKAS, NOVADENS, INKADENS and
CIELODENS..........................................................................................................................22
6.4-Settingthe language ............................................................................................................... 22
6.5- Operating parameters-PAR Menu ......................................................................................... 22
6.6- Operating parameters- PARC Menu.......................................................................................22
6.7- Installation ............................................................................................................................... 23

3
2.2 - Keys and associated functions
The remote control envisages a user interface comprising 7 keys:
K1 depends on operating mode selected
K2 depends on operating mode selected
K3 depends on operating mode selected
K4 depends on operating mode selected
K+ increases value selected
K- decreases value selected
KM selection of the user and installer mode menus
Figure 1 - LCD Display
Figure 2 - Keys and associated functions
Safety instructions
Please read the manual carefully: it contains important information regarding installation and use.
This device must be installed by a professionally qualified technician, observing national and
local legislation, as well as the instructions contained in this manual.
1 - Main features
The CR04 series remote control acts as a time-programmable thermostat, a thermoregulator and a remote
control. Itcan be usedas an initial installation device or as an optional extra,connecting it toCOSMOGAS boilers
appropriately set up for such installation.
· Connection to boiler using 2 non-polarized wires
· Three different user languages supported (English, Italian and French)
2 - Operating features
- LCD Display
- Keys and associated functions
2.1 - LCD Display
The remote control uses an alphamumeric LCD display, whose symbols are shown in the following diagram:

4
3 - Initial start-up
On initial start-up or in any event each time the power supply fails for more than 5 hours, it is necessary to set the
time and day of the week. This is done as follows:
- switch on the power supply to the boiler, the display will come on with the date field flashing; use the K+ and K-
keys to set the correct day of the week;
- press key K2 so that the hour flashes; use the K+ e K- keys to set the correct hour of the day;
- press key K3 so that the minutes flash; use the K+ e K- keys to set the correct minutes;
- press key KM to save the data and return to user mode;
- consult section 5.10 to make further changes to the day and time data.
4 - Introduction
With the exclusion of the:
· “off”, “domestic hot water with heating”, “only domestic hot water”, “only heating” operating modes;
· PROG SAN (DHW programming) PROG RIS (heating programming) programming mode;
· OROL (date and time) programming mode;
the remote control display shows a two-letter code (in the field used to indicate the current day) which identifies
the menu displayed.
5 - Users’ menu
It is possible to carry out the following operations in “User” mode:
- selectionof the operatingmode: “off”,“domestic hotwater with heating”,“only domestichot water”,“only heating”
- automatic or manual operation of time programmable thermostat
- adjustment of domestic hot water temperature
- manual forcing of room temperature (overrun function)
- forcing of heating programme, RIS menu
- forcing of domestic hot water programme, SAN menu
- system parameters’ consultation
- programming of heating and domestic hot water times, PROG menu
- adjustment of system operating parameters, IMP menu
- setting of day, hour and minutes, OROL menu
Figure 3 - Display components
KEY (figure 3)
1 Heating on
2 Dom. hot water on
3 Day
4 Hours and minutes
5 Functionkeys
6 Activate and
deactivate menu mode
7 Room temperature
8 Decrease value
9 Increase value
10 Active key indictors
11 Time-programmable
thermostat histogram
The display has the following aspect in “user” mode:

5
5.1 - Selecting the operating modes
Using key K1, with the remote control positioned in any operating mode, it is possible to select, by rotation, the
possible operating modes of the boiler, such as:
· OFF
· domestic hot water and heating
· only domestic hot water
· onlyheating
OFF
Only the room anti-freeze function with temperature setting equal to 5°C is enabled in this mode. The display
shows:
· current day, hour and minutes
· the value of the room temperature gauged
· the switched off symbol and the wording OFF
Domestic hot water and heating
The domestic hot water and heating functions are enabled in this mode. The display shows:
· current day, hour and minutes
· the value of the room temperature
· the tap symbol and the radiator symbol
· the timer bar (if related function enabled)
Only domestic hot water
The heating function is disabled and the functions relating to the domestic hot water are enabled in this operating
mode.
The display shows:
· current day, hour and minutes
· the value of the room temperature
· the tap symbol
· the timer bar (if related function enabled)
Only heating
The domestic hot water function is disabled and the functions relating to the heating are enabled in this operating
mode.
The display shows:
· current day, hour and minutes
· the value of the room temperature
· the radiator symbol
· the timer bar (if related function enabled)
5.2 - Automatic or manual operation of the time programmable thermostat
Using key K2, it is possible to enable or disable the time-programmable thermostat of the remote control in
cyclical mode. This can be noted from the display of the histogram bar of the time-programmable thermostat
(automatic position), alternatively from the display of the hand (manual position)
The function only becomes available in the “heating with domestic hot water” and “only heating” modes. The
function is not active in the “only domestic hot water” mode.
Consult section 5.8 for the programming of the time-programmable thermostat .
Whenthe remotetime controlis in theMANUAL position(hand designedon thedisplay), just use the K+ oK- keys
for increasing or decreasing the temperature required.

6
5.3 - Adjusting the domestic hot water temperature
Using key K4, with the remote control positioned in any operating mode (excluding OFF mode), it is possible to
select the menu for setting the domestic hot water temperature.
The display shows the wording REG SAN and the domestic hot water temperature value; using keys K+ o K- it is
possible to change these values between 40 and 65 °C.
Use the KM key to save the data and return to the operating mode.
5.4 - Manual forcing of room temperature (overrun function)
This function only becomes available if the “heating mode” is enabled (see section 5.1)
Having activated the automatic functioning of the time-programmable thermostat (see section 5.2) of the remote
control (AUTO mode), using keys K+ o K-, the display will show TEMPER AMBIENTE and the room temperature
value. By pressing K+ o K- once again, it is possible to temporarily change the room temperature required; in this
way, the automatic functioning of the time-programmable thermostat is by-passed (overrun), forcing a manual
setting value, until the following change of status requested of the timer of the time-programmable thermostat.
Return to the operating mode takes place automatically, after 5 seconds, or manually using the KM key.
Ifthe temperaturevalue has beenchanged, thedisplay willshow the handsymbol andthe programming bar of the
timer(seefigure 3,detail11) soas toindicate that thefunctionin questionisunderway (thehandsymbol disappears
the next time the status of the time-programmable thermostat’s timer changes).
5.5 - Forcing of heating programme
Using the KM key, it is possible to access page 1 of the menus and from there, using key K1 (RIS), one accesses
the heating forcing menu.
Once this menu has been selected, it is possible to make the following choice:
· TIMER
Return to the operating mode takes place automatically, after 2 minutes, or manually using the KM key.
By pressing key K4 (TIMER), the TIMER heating mode function is enabled; effectively, the manual functioning of
the time-programmable thermostat is forced for a given period of time set on DURATION using the K+ e K- keys,
at a room temperature value set by pressing key K4 (TMP) and adjusted as always using the keys K+ e K-.
Nowthe running of theboiler will depend onthe room temperature selected and the duration of the time seton the
timer.
Return to the operating mode takes place automatically, after 2 minutes, or manually using the KM key.
Thedisplay shows thewordingTIMER RISfor the durationof the forcedheating set on theTIMER, or, in the event
that the domestic hot water timer function is active, the wording TIMERS.
Once the time set on the TIMER has elapsed, the heating returns to that active before the setting.
Itis possible tointerrupt the function in questionat any giventime; in orderto do this, after havingselected the RIS
– TIMER heating mode (key KM followed by key K1), press key K1 (OFF). The remote control automatically
returns to the operating mode.
5.6 - Forcing of domestic hot water programme
Using key KM, it is possible to access page 1 of the menus and from there, using key K2 (SAN), one accesses the
domestic hot water forcing menu.
This menu is enabled only if the selection parameter of the domestic hot water operating mode (PROG SAN) is
set at 2 or 3 (see section 5.9).
Once this menu has been selected, it is possible to make the following choice:
· AUTO
· TIMER
By pressing key K1 (AUTO), the automatic functioning of the domestic hot water mode is obtained.
In relation to the PROGR SAN parameter set (see section 5.9), the AUTO domestic hot water mode
can adopt 2 different operating features:
- follow an independent timing programme

7
- follow the setting of the timing programme of the heating service
The activation of the AUTO domestic hot water mode is indicated on the display when the clock
symbol lights up.
Itis possible to interrupt thefunction in question at anygiven moment, re-settingthe continualfunction
(always ON) of the domestic hot water mode. In order to do so, after having selected the domestic hot
water mode SAN – AUTO (key KM followed by key K2), press key K1 (ON); the remote control
automatically returns to the operating mode.
Bypressing key K4 (TIMER),the TIMER domestic hotwater operating mode is enabled; in practice,the operating
of the domestic hot water mode is forced for a given period of time.
The display shows the DURATION parameter which can be selected by using key K1 (DURATION);
the flashing off said parameter indicates its selection and the possibility of changing it using the keys
K+ o K-.
The DURATION parameter can adopt a value ranging between 30 minutes and 12 hours.
Return to the operating mode takes place automatically, after 2 minutes, or manually using the KM
key.
The activation of the TIMER domestic hot water mode is indicated on the display when the TIMER
SAN wording lights up, or, in the event that the heating timer function is also active, the TIMERS
wording is shown.
Once the timing has elapsed, the domestic hot water mode returns to that active before the setting of
the TIMER domestic hot water mode.
It is possible to interrupt the function in question at any given moment. In order to do so, after having
selected the domestic hot water mode SAN – TIMER (key KM followed by key K2), press key K1
(OFF); the remote control automatically returns to the operating mode
5.7 - System parameters’ consultation
Using key K3, with the remote time control positioned in any operating mode (excluding OFF mode), it is possible
to immediately access the user information.
Having pressed key K3, the display will immediately show the external temperature; using keys K1 (<<) and K4
(>>), it is possible to display the subsequent information, listed below:
· TMPESTERNA externaltemperature
· PRESSIONE datanot available
· TMPMANDATA boiler unit temperature
· BRUCIATORE datanot available
· TMPSAN domestic hot water temperature (only with water heater)
· PORTATA SAN datanot available
· STATO SAN domestic hot water mode status, 0 inactive 1 active
· TMP RITORNO datanot available
· TMPAMBIENT room temperature
Return to the operating mode takes place automatically, after 2 minutes, or manually using the KM key.

8
5.8 - Programming the heating times
Using key KM and subsequently key K4 (>>), page 2 of the menus is accessed.
Using key K1 (PROG), the programming menu is selected.
Having selected this menu, it is possible to make one of the following choices:
· RIS(HEATINGtimer)
· SAN (DOMESTIC HOT WATER timer)
If the PROGR SAN parameter set (see section 5.9), does not anticipate the management of the SAN timer
(different to 2), one directly accesses the programming of just the timer for the heating.
- press key K1 (RIS), one accesses the menu for programming the heating timer;
-press key K1 (GIO) inorder to set the day one intends to programme(pressing it repeatedly,one will see thatthe
two letters corresponding to the day of the week change continually, updating the day);
- press key K2 (IMP) to access the menu for selecting the temperature raising or lowering bands, comprising the
levels T0, T1 and T2 plus the choice which makes it possible to leave the value unchanged ( - - );
- choose the T0, T1 or T2 temperature level which one intends to set, the display automatically returns to the
previous status;
- using the keys K+ e K-, set the hour for that day during which one wishes it to function in the set timeband; (the
timebands T0,T1 and T2 are displayed on the histogram bar, respectively by means of: nil, a small black square
at the base of the histogram, two small black squares overlapping);
- press key K2 (IMP) once again to select the new temperature timeband and repeat the previous operation in
order to set the operating timeband under T1;
- repeat the above procedure, so as to set the operating timeband under T2.
So as to shift from one part of the timer to another over 24 hours, without changing the setting made previously,
proceed as follows:
- press key K2 (IMP), then press key K1 (- -); the display returns to the clock display, thus move between the
hours using the keys K+ e K- until reaching the desired time;
- repeat the above procedure, selecting a new T0, T1 or T2 temperature level.
Once the programming of the day has been carried out, just press key K3 (COP) in order to copy the same
programmingto thenext day, then presskey K1(GIO) inorder toselect the followingday (whosetime willhave the
same programming made above), then press K3 (COP) once again so as to copy the programming to the next
day, and so on for all the days of the week which one wishes to programme as the same as the others. In order to
programme one day of the week differently, it is sufficient to do so as per the above indications, without it being
copied from a previous day.
In order to save the programme set, just press key KM. The display will return to normal view. If the display shows
the histogram bar 11 as per figure 3, it means that the programme set above is already active. If this is not so,
follow the instructions in section 5.2 to activate it.
5.8.1 - Calling up an existing programme for heating
Theremote controlmakes 5 pre-compiled programmes available,in orderto facilitatethe user when programming
the time. Proceed as follows to access them:
- press key KM and subsequently key K4 (>>), page 2 of the menus is accessed;
- press key K1 (PROG), the programming menu is selected;
Once this menu has been selected, it is possible to make one of the following choices:
· RIS(HEATINGtimer)
· SAN (DOMESTIC HOT WATER timer)
Ifthe PROGRSAN parameterset (seesection 5.9) does not envisagethe managementof theSAN timer(different
to 2), one directly accesses the programming of just the timer for the heating.
- press key K1 (RIS), one accesses the menu for programming the heating timer;
- press key K4 (PRE), one accesses the menu for selecting the pre-set operating programme;
- press keys K+ o K- to select the pre-set programme nearest to one’s requirements;
- press key K1 (OK) in order to load the programme in the memory or press key K2 (ANNULLA) to return to the
previous menu without loading any pre-set programme.
Once the programme has been loaded, the display returns to show the menu of the heating programming mode.

9
Programme 2
Programme 3
Programme 4
Programme 5
Bymeans ofthe procedurefor programmingthe timebands, asper theprevious section,it ispossible tocustomize
the pre-set programme loaded in the memory.
Having loaded and possibly customized the pre-set programme, just press key KM to save it and return to the
main page.
Ifthe display shows the histogram bar 11as per figure 3, it means that the programme set above isalready active.
If this is not so, follow the instructions in section 5.2 to activate it.
The pre-set programmes are as follows:
Programme 1

10
5.8.2 - Programming of domestic hot water timing
Using key KM and subsequently key K4 (>>), access is gained to page 2 of the menus.
Using key K1 (PROG), the programming menu is selected.
Once this menu has been selected, it is possible to make one of the following choices:
· RIS(HEATINGtimer)
· SAN (DOMESTIC HOT WATER timer)
If the choice does not appear, it means that the domestic hot water programme is already active (PROG SAN
parameter as per section 5.9, at 1), or that it is linked to the programming of the heating (PROG SAN parameter
as per section 5.9, at 3).
So as to carry out programming of the domestic hot water independently from the programming of the heating, it
is necessary to set the PROG SAN parameter as per section 5.9, at 2.
- press key K2 (SAN), one accesses the menu for programming the domestic hot water timer (the clock symbol
which appears on the display acts as confirmation that the time programming of the heating is taking place);
- press key K1 (GIO) in order to set the day one intends to programme (by repeatedly pressing it, one will see that
the two letters corresponding to the day of the week change continually, updating the day);
- press key K2 (IMP) in order to access the menu for selecting the on and off timebands for the domestic hot
water service , comprising OFF and ON, plus the choice which makes it possible to leave the value unaltered ( -
- );
-choose thekey correspondingto thefunction oneintends toprogramme (OFF)or (ON), thedisplay automatically
returns to the previous setting;
-using keys K+ eK-, set the timeband,for that day, during which youwish it to operatein the chosen function;(the
OFF and ON timebands are displayed on the histogram bar, respectively by means of: nil, a small black square at
the base of the histogram);
- press key K2 (IMP) once again so as to select the new OFF or ON function timeband and repeat the operation
carried out previously in order to set the new operating timeband.
So as to shift from one part of the timer to another over 24 hours, without changing the setting made previously,
proceed as follows:
- press key K2 (IMP), then press key K1 (- -); the display returns to the clock display, thus move between the
hours using the keys K+ e K- until reaching the desired time;
- repeat the above procedure, selecting a new ON or OFF operating timeband.
Once the programming of the day has been carried out, just press key K3 (COP) in order to copy the same
programmingto thenext day, then presskey K1(GIO) inorder toselect the followingday (whosetime willhave the
same programming made above), then press K3 (COP) once again so as to copy the programming to the next
day, and so on for all the days of the week which one wishes to programme as the same as the others. In order to
programme one day of the week differently, it is sufficient to do so as per the above indications, without it being
copied from a previous day.
In order to save the programme set, just press key KM. The display will return to normal view. If the display shows
the histogram bar 11 as per figure 3, it means that the programme set above is already active. If this is not so,
follow the instructions in section 5.2 to activate it.
5.8.3 - Calling up an existing programme for domestic hot water
Theremote controlmakes 2 pre-compiled programmes available,in orderto facilitatethe user when programming
the time. Proceed as follows to access them:
- press key KM and subsequently key K4 (>>), page 2 of the menus is accessed;
- press key K1 (PROG), the programming menu is selected;
Once this menu has been selected, it is possible to make one of the following choices:
· RIS(HEATINGtimer)
· SAN (DOMESTIC HOT WATER timer)
Ifthe PROGRSAN parameterset (seesection 5.9) does not envisagethe managementof theSAN timer(different
to 2), one directly accesses the programming of just the timer for the heating, therefore set PROGR SAN at 1 or
3.
- press key K2 (SAN), one accesses the menu for programming the domestic hot water timer;
- press key K4 (PRE), one accesses the menu for selecting the pre-set operating programme;

11
Programme 1
Programme 2
Having selected the pre-set programme, it is however possible to customize it as one likes, following the same
indications in the previous paragraph “Domestic hot water programming”.
5.9 - Adjusting the system operating parameters
Using key KM and then key K4 (>>), access is gained to page 2 of the menus.
Using key K2 (IMP), the menu for adjusting the operating parameters is selected.
The menu makes it possible to display, and subsequently change, the parameters which can be accessed by the
user.
Using keys K1 (<<) and K4 (>>), it is possible to display the information listed below:
· TMPAMB T0 adjustment of room temperature value T0 (can adopt valuesranging between7 and 35°C)
· TMPAMB T1 adjustment of room temperature value T1 (can adopt valuesranging between7 and 35°C)
· TMPAMB T2 adjustment of room temperature value T2 (can adopt valuesranging between7 and 35°C)
· PROGR SAN adjustment of domestic hot water programme type (can adopt the values 1, 2 and 3)
· REG RISCALD adjustment of maximum heating supply temperature (can adopt values ranging between
20 and 45°C)
Where:
- T0 is the room temperature level, considered to be saving status
- T1 is the room temperature level, considered to be reduction status
- T2 is the room temperature level, considered to be comfort status
-PROG SAN,if set at 1, meansthat thedomestic hot water function isactive continuallythroughout the entire day;
if set at 2, it means that the operating time programme for the domestic hot water is independent from the heating
time programme; if set at 3, it means that the operating time programme for the domestic hot water is linked to the
heating time programme.
All the parameters can be changed using the keys K+ o K–.
Return to the operating mode takes place automatically, after 2 minutes, or manually by using key KM.
If the MODO FUNZ parameter has been set at 4 (see section 6.2), the adjustment ofTMPAMB T0,TMPAMB T1
and TMP AMB T2 is disabled.
All the afore-mentioned operating parameters are memorized within an Eeprom-type memory, which stores them
even if the power to the remote control is cut.
- press keys K+ o K- to select the pre-set programme nearest to one’s requirements;
- press key K1 (OK) in order to load the programme in the memory or press key K2 (ANNULLA) to return to the
previous menu without loading any pre-set programme.
Oncetheprogrammehas beenloaded,thedisplayreturns toshowthemenu of thedomestichotwater programming
mode. By means of the procedure for programming the timebands, as per the previous section, it is possible to
customize the pre-set programme, loaded in the memory.
Having loaded and possibly customized the pre-set programme, just press key KM to save it and return to the
main page.
Ifthe display shows the histogram bar 11as per figure 3, it means that the programme set above isalready active.
If this is not so, follow the instructions in section 5.2 to activate it.
The pre-set programmes are as follows:

12
5.10 - Date, hour and minute setting
It is possible to adjust or set the date, hour and minutes of the remote control at any given time.
Proceed as follows:
Using key KM and then key K4 (>>), access is gained to page 2 of the menus.
Using key K3 (OROL), the programming menu is selected.
Once this menu has been selected, it is possible to make one of the following choices:
· GIO
· ORA
· MINUTI
Make the choice using keys K1, K2 or K3, then carry out the adjustment using keys K+ o K-. The parameter being
adjusted is shown because it blinks.
The days are shown on the display, in two letters, according to the following scheme:
· DO = Sunday
· LU =Monday
· MA = Tuesday
· ME = Wednesday
· GI = Thursday
· VE = Friday
· SA = Saturday
Return to the operating mode takes place automatically, after 2 minutes, or manually using the KM key.
In relation to the TIPO ORA operating parameter selected (see section 6.2), the display of the hour is between 00
and 23, or, 00 and 12AM/PM.
5.11 - Memorizing hour/minutes/date and operating mode
If the remote time control is electrically powered for an hour and subsequently there is a power cut, it is able to
keep the clock (hour/minutes) and calendar (day) working and memorize all the data, before the power cut, for a
period of time of up to 5 hours.
If the remote control remains without power for more than 5 hours, on start-up said remote control positions itself
automatically in day and hour programming mode; see section 3 for re-setting.
5.12 - Indication of boiler with burner on
The display shows the flame symbol indicating that the boiler’s burner is on.
5.13 - Indication of presence of anomalies
In the presence of anomalies, the display shows the flashing alarm symbol and the wordingANOMALY.
If the anomaly requires re-set action to be taken by the user, the display shows a downwards arrow symbol, in
correspondence with the key K1 (RESET).
Using key K1 it is possible to reset normal running conditions, returning to operating mode, if the cause which
generated the anomaly has been removed.
Pressing key K4, it is possible to directly access the menu displaying the possible signals for the anomalous
performance of the boiler and/or the remote time control.
The type and number of anomalies which may be displayed, is shown in section 6.3, Diagnostics.
Intheeventthatthe roomtemperaturesensoroftheremote timecontrolisindicatedasfaulty,thesupplytemperature
is automatically set at 40°C (in the absence of an external sensor). If an external sensor is present, the supply
temperature is adjusted by means of the setting algorithm of the thermoregulation as per the diagram in figure 4.
Inthe eventthat the externaltemperature sensoris indicatedas faulty, thethermoregulation functionchanges and
automatically becomes set at the room temperature (MODO FUNZ 2 as per section 6.2.3).

13
6 - Installers’ menu
Pressing down key KM for around 10 seconds it is possible to access the menus intended for the installer.
Page 1 makes it possible to make one of the following choices:
· INFO display the system parameters
· IMP display and change the system parameters
· ERR display faults
·>>
Pressing key K4 (>>), access is gained to page 2 of the menus, which makes it possible to make one of the
following choices:
· LING select the language of the remote time control
· PAR menu not available
· PARC menu not available
·>>
Using key K4 (>>), one passes from page 1 to page 2 and vice versa.
Return to the operating mode takes place automatically, after 2 minutes, or manually using the KM key for about
10 seconds
.
6.1 - Displaying the system parameters
Pressing down key KM for about 10 seconds and then using key K1 (INFO), the menu for the display of the
operating parameters of the remote time control is selected.
Using keys K1 (<<) and K4 (>>), it is possible to display the information listed below:
· TMPESTERNA externaltemperature
· PRESSIONE datanot available
· TMPMANDATA boiler temperature
· BRUCIATORE datanot available
· TMPSAN domestic hot water temperature (only with water heater)
· PORTATA SAN datanot available
· STATO SAN domestic hot water mode status (0 inactive, 1 active)
· TMP RITORNO datanot available
· TMPAMBIENT room temperature
· REGAMBIENT room temperature requested
· TEMP CALC supply temperature calculated
· CODICE ID identification number of the remote control version
· VERSIONE number of the version of the remote control’s firmware
Return to the operating mode takes place automatically, after 2 minutes, or manually using the KM key for about
10 seconds
.
Possible values adopted by the afore-mentioned variables:

14
6.2 - Displaying and changing the system parameters
Pressing down key KM for 10 second and then key K2 (IMP), the menu which permits the display, and possible
change,of theoperating parametersof the remote timecontrol, whichcan beaccessed bythe installer,is selected.
Using keys K1 (<<) and K4 (>>), it is possible to display the information listed below:
· CURVA EST Thermoregulation - setting the gradient (see section 6.2.1)
· COMPENSAMB Thermoregulation - correction with room temperature (see section 6.2.2)
· MODOFUNZ Thermoregulation - choosing the operating modes (see section 6.2.3)
· TIPO ORA Hour type displayed (see section 6.2.4)
· PROGR SAN Domestic hot water programme type (see section 6.2.5)
· PRE RISCALD Automatic pre-heating (see section 6.2.6)
· TMPMINRIS Minimum supply temperature (see section 6.2.7)
· REG RISCALD Maximum supply temperature (see section 6.2.8)
· TMPAMBT0 Pre-setting of T0 room temperature (see section 6.2.9)
· TMPAMBT1 Pre-setting of T1 room temperature (see section 6.2.9)
· TMPAMBT2 Pre-setting of T2 room temperature (see section 6.2.9)
· REGSAN Pre-setting of domestic hot water temperature (see section 6.2.10)
· RIEMPIMENTO Pre-setting of system supply type (see section 6.2.11)
· CORR TAMB Correcting the room temperature read (see section 6.2.12)
· IMPFABBRIC Factory settings (see section 6.2.13)
The change of each parameter can be carried out by using the keys K+ o K– within the range permitted by said
parameter (see table below)
Return to the operating mode takes place automatically, after 2 minutes, or manually using the KM key for about
10 seconds
.
All the afore-mentioned operating parameters are memorized within an Eeprom-type memory, which stores them
even if the power to the remote control is cut.
Possible values adopted by the afore-mentioned variables:
(1) It is not possible to set the maximum value of the TMP MIN RIS parameter greater than the minimum of the
REGRISCALD parameter. Viceversa,it isnot possibleto set the minimum valueof theREG RISCALDparameter
lower than the maximum value of the TMP MIN RIS parameter.
(2) The function is subject to the management of said parameter by means of the boiler control board to which the
remote control is connected.

15
6.2.1 - Thermoregulation - Setting the gradient
PressingkeyKM down for10seconds andthenkeyK2 (IMP),the CURVAESTparameterisimmediatelydisplayed.
Using the keys K+ o K- , it is possible to change the setting.
The graph in figure 4, shows the ratio between the external temperature and the supply temperature calculated in
relation to the value assigned to the CURVAEST parameter.
The installer can use this graph in order to establish the exact CURVAEST to be set in relation to the geographic
area where the installation will take place (typically, the curves chosen for Italian regions range between 0.6 and
1.1 for radiant panel systems).
Theadjustment of the supply temperaturein relation tothe externaltemperature is activeonly if the MODOFUNZ
parameter is set at 3 (see section 6.2.3)
Figure 4 - Ratio between supply temperature and external temperature
Normally,the adjustmentof justthe CURVAEST (gradient) as per thegraph infigure 4, isnot enoughto adjust the
supply temperature exactly, in relation to the external temperature. For this purpose, it is possible to adjust the
parallelism of this line as well, taking action directly on the remote time control, requesting a room temperature
other than 20°C. Figure 5 shows how the line (in this case with a CURVA EST gradient = 2.0) can move on a
parallel in relation to the temperature set on the remote control.
To set the temperature on the remote control, see section 5.2, or 5.8.
This type of setting is advisable above all else for radiant panel systems, where the remote control cannot be
positioned as a sensor of a characteristic room temperature, or in situations where there are thermostats which
regulate the temperature zone by zone.
EASTCurve 2.0
EAST Curve 0.8
EASTCurve 0.4
Calculated supply temperature (TEMP CALC) °C
External temperature (TMP ESTERN) °C
EASTCurve
EASTCurve 2.5
EASTCurve 1.6
EASTCurve 1.2
Room temperature requested =
20°C

16
6.2.2 - Thermoregulation - Correction with room temperature
Pressing key KM down for 10 seconds, then key K2 (IMP) and finally key K4 (>>) the COMPENSAMB parameter
is displayed immediately. Using keys K+ o K-, it is possible to change the setting.
When the value of the COMPENS AMB parameter differs from 0, the compensation of the room temperature is
active.
The effect of the room temperature compensation is the automatic parallel shift of the curve as per figure 4.
Inthis way,the parallel translationof the line, which in the previous section wascarried out manually, is now made
automatically on the basis of the temperature registered by the remote control in the room.
The shifting of the curve, defined as Delta, is calculated on the basis of the error between the value of the room
temperature requested and that actually read by the remote control.
The Delta is also influenced by the parameter defined as room compensation (COMPENS AMB) which can be
selected from between 0 and 20 (as can be seen from the graph in figure 6).
The rules for the correct setting of the room compensation value (COMPENS AMB) are:
· the compensation of the room temperature makes it possible to put the heating system in steady state much
faster and automatically compensate the imperfect selection of the CURVA EST;
· the higher its value, the quicker the putting of the heating system in steady state is;
· too high a value may cause the system to react too quickly, involving the consequent sudden igniting and
switching off of the boiler;
· generally, a large heating system, which requires a long period before it reaches steady state, requires a higher
room compensation value with respect to a smaller heating system which requires a shorter period before it
reaches steady state;
· the room compensation works correctly only if the CURVA EST has been correctly chosen.
The room compensation is active only if the MODO FUNZ parameter is set at value 3 (see section 6.2.3)
This type of adjustment is advised for all radiant panel type systems where the remote time control can be
installed in an area where the temperature is characteristic of the entire area to be heated.
Figure 5 - Parallel adjustment of the line as per figure 4.
Calculated supply temperature (TEMP CALC) °C
External temperature (TMP ESTERN) °C
EAST CURVE set at 2.0

17
Figure 6 - Automatic parallel translation of the line
Figure 7 - Room compensation curve
Compensation of the room temperature
·The curves, present in the following graph, show how the delta is calculated on the basis of the COMPENSAMB
value set and the room temperature.
COMPENS AMB = 15 COMPENS AMB = 8
COMPENS AMB = 4
COMPENS AMB = 0
Deltacalculated bythecompensation
ofthe roomtemperature
CURVAESTwithoutinfluence ofroomcompensation
(COMPENS AMB = 0)
Calculated supply temperature (TEMP CALC) °C
External temperature (TMP ESTERN) °C
Delta on calculated supply temperature °C
Current room temperature °C
COMPENS AMB 20
COMPENSAMB 10 COMPENSAMB 6
COMPENSAMB 4
COMPENSAMB 2
Reference conditions:
- CURVAEST 2.0
- Room temperature required 20°C
- Room temperature read 18°C
Roomtemperaturerequired=20°C

18
6.2.3 - Thermoregulation - Choosing the operating modes
The MODO FUNZ parameter is one of the most important to be adjusted. On the basis of the setting of this
parameter, the type of thermoregulation to be used in the system is chosen. Therefore, it is indispensable to
choose the type of thermoregulation carefully, in relation to the type of system owned, in order to achieve the best
degree of comfort envisaged.
Pressing key KM down for more than 10 seconds, then key K2 (IMP), and subsequently key K4 (>>) until MODO
FUNZ is displayed, it is possible to select, using keys K+ e K-, one of the 4 types of thermoregulation available:
1 · room thermoregulation with set supply temperature
2 · room thermoregulation in relation to the room temperature
3 · room thermoregulation in relation to the external temperature, with or without room temperature
4 · thermoregulation with exclusion of the room temperature and two-point adjustment
Room thermoregulation with set supply temperature (MODO FUNZ = 1)
The user sets the room temperature desired and the remote control generates a heat request to the boiler (pump
comes on), every time the room temperature falls below the temperature requested. Vice versa, every time the
roomtemperature rises above that set, the remote control interruptsthe heat request tothe boiler (pump switches
off). In this operating mode, the supply temperature to the radiators is set at the value set on the REG RISCALD
parameter (see section 6.2).
This type of thermoregulation is recommended for a system with radiators or convector fans
Room thermoregulation in relation to the room temperature (MODO FUNZ = 2)
The heating supply temperature is calculated using a PID type algorithm so that the room temperature, read by
the remote control, corresponds with that set by the user; the value calculated corresponds to the value of the
heatingsupply temperature (TEMPCALC parameter, seesection 6.1).Thisvalue however isalways limitedto the
value set on the REG RISCALD parameter (see section 6.2.8).
This type of thermoregulation is recommended for systems with radiators, convector fans or radiant panels where
the temperature of the room where the remote time control is located is characteristic of all the rooms heated.
Room thermoregulation in relation to the external temperature, with or without
room temperature (MODO FUNZ = 3)
The heating supply temperature is calculated using a formula which takes into account the CURVAEST selected
(seesection 6.2.1); thevalue calculated (TEMPCALC parameter,see section 6.1)corresponds with thesetting of
theheating supplytemperature. Thisvalue however isalways limitedto thevalue of theREG RISCALDparameter
set (see section 6.2.8).
In this operating mode, if the COMPENS AMB parameter (see section 6.2.2) is set at zero, the adjustment of the
supply temperature is made without considering the room temperature read by the remote control. Therefore, the
installer will have to find the right angle of the line, adjusting the CURVAEST parameter as per section 6.2.1 and
the right parallelism, adjusting the room temperature as per sections 5.2 and 5.8.
This type of thermoregulation is recommended for a system with radiant panels where the rooms heated are
served by room thermostats which act on the area valves, or in systems where it is not possible to install the
remote control in a place where the room temperature registered is characteristic of the building. In such cases,
the supply temperature is adjusted exclusively in relation to the external temperature according to the ratio shown
in the graphs as per figures 4 and 5.
If the COMPENS AMB parameter (see section 6.2.2) is set at a value other than zero, the room temperature
registered by the remote time control intervenes to correct the supply temperature on the basis of the matters
already illustrated in section 6.2.2 and figures 6 and 7.
This type of thermoregulation is recommended for a system with radiant panels where the temperature of the
room in which the remote time control is located is characteristic of all the rooms heated.
Inall theafore-mentioned cases, whenthe externaltemperature isgreater than thecalculated supplytemperature
(parameter TEMP CALC as per section 6.1), the heating is shutdown.
Thermoregulation with exclusion of the room temperature and two-point

19
adjustment (MODO FUNZ = 4)
Theroom temperatureand theexternal temperaturedo notinteract on the operating modeof thethermoregulation
in question.
Theadjustment of the supply temperatureto the radiatorsis carriedout at twotemperature levels, set respectively
at TMP MIN RIS (minimum supply temperature, see section 6.2.7) and REG RISCALD (maximum supply
temperature, see section 6.2.8).
Themeaningusually attributedto theparametersTMPAMBT0,TMPAMBT1 andTMPAMBT2(room temperature
levels which can be selected for the automatic operating mode of the room thermostat, see section 5.8), changes
as indicated below:
TMP AMB T0 = heating request absent
TMP AMB T1 = heating request present with supply adjustment at value of TMP MIN RIS parameter
TMP AMB T2 = heating request present with supply adjustment at value of REG RISCALD parameter
By means of the programming of the heating timer (see section 5.8), the user establishes when, over a period of
24 hours, to set the boiler going in heating mode (levels T1 or T2) or not (level T0) and what the setting of the
supply temperature must be (TMP MIN RIS or REG RISCALD) for the water of the heating system.
When this thermoregulation operating mode is selected:
- the PRE RISCALD function (see chapter 6.2.6) is automatically disabled;
- the programming of the TMP AMB T0, TMP AMB T1 and TMP AMB T2 parameters as per section 5.9, is
automaticallydisabled;
- during the manual adjustment of the room temperature, as per section 5.2, it permits the adjustment of the
desiredroom temperature, at three levelscorresponding to 0 = TMBAMB T0, 1 = TMPAMB T1 and 2 =TMP AMB
T2.
6.2.4 - Hour type displayed
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until TIPO
ORAis displayed, it is possible to select, using keys K+ e K-, the 12 hours or 24 hours timing display. Setting the
parameter at 1, one obtains the 24 hour display, whilst setting it at 2 the 12 hour display is shown.
6.2.5 - Domestic hot water programme type
Pressing theKM keydown for morethan 10seconds and thenkey K2(IMP) followed bykey K4(>>) until PROGR
SAN is displayed, it is possible to select, using keys K+ e K-, the operating of the domestic hot water function, in
the following manner:
1 = domestic hot water service always active;
2 = possibility of carrying out the time programming of the domestic hot water service independently from the
heatingservice(the function,whenactive,is shownonthe displayusingthe clocksymbol).Forthe programming
of the domestic hot water service, refer to section 5.8;
3 = the domestic hot water service follows the time programming made for the heating service exactly.
Due to how the boiler is conceived, it is advisable to keep the parameter at 1 or 3.
6.2.6 - Automatic pre-heating
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until PRE
RISCALDis displayed,it is possibleto select,using keys K+e K-, the typeof pre-heatingone intendsto carry out.
The parameter can adopt the following values:
1 = pre-heating enabled in adaptive mode;
2 = pre-heating enabled with a ramp of 3°C/hour;
3 = pre-heating disabled.
If this parameter is set at 3, during the time programming of the heating function, the user must bear in mind to
switch on the heating in advance with respect to the effective need, due to the thermal inertia of the plant (high in
the case of radiant panels, low in the case of radiators, uninfluential in the case of convector fans).
So as to avoid having to take these times into consideration, being among other things difficult to calculate and
variablein relationto the seasonand typeof plant,it isadvisable tokeep theparameterat thevalue of1 or2, where
the remote time control carries out an automatic detection of the system’s features (with a frequency of 10
minutes), thus calculating the thermal inertia, or the time necessary for achieving a specific room temperature. In

20
this way, when the time programming is carried out it will be sufficient to introduce the switching on and switching
offof the heatingin correspondencewith thetimeperiod ofeffective need;the remote timecontrol willautomatically
take steps to bring forward the ignitions so as to obtain the desired room temperature, in the time period set.
6.2.7 - Minimum supply temperature
Pressingthe KMkey downfor morethan 10seconds andthen keyK2 (IMP)followed bykey K4(>>) untilTMP MIN
RIS is displayed, it is possible to select, using keys K+ e K-, the minimum supply temperature for the heating. It
is recommended that it be left at 20°C.
Onlyin theevent thatthe MODOFUNZ parameter(see section6.2.3) hasbeen set at 4, theTMP MINRIS mustbe
adjusted to the supply temperature, corresponding to the energy saving timeband TMP AMB T1.
6.2.8 - Maximum supply temperature
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until REG
RISCALD is displayed, it is possible to select, using keys K+ e K-, the maximum supply temperature for the
heating. It is recommended that it be left at 45°C.
In the event that the MODO FUNZ parameter has been set at 1 (see section 6.2.3), the REG RISCALD must be
adjusted to the supply temperature, corresponding to the adjustment temperature.
In the event that the MODO FUNZ parameter has been set at 4 (see section 6.2.3), the REG RISCALD must be
adjusted to the supply temperature, corresponding to the comfort timeband TMPAMB T2.
6.2.9 - Pre-setting of room temperature
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until TMP
AMB T0/T1/T2 is displayed, it is possible to select, using keys K+ e K-, the room temperature values, envisaged
during the time programming of the heating function (see section 5.8). The operation for adjusting TMP AMB T0,
TMP AMB T1 and TMP AMB T2, corresponds with the same regulation as per section 5.9.
Ifthe MODO FUNZ parameter hasbeen set at 4 (seesection 6.2.3) theadjustment ofTMP AMB T0,TMP AMBT1
and TMPAMB T2 is disabled.
6.2.10 - Pre-setting of domestic hot water temperature
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until REG
SAN is displayed, it is possible to select, using keys K+ e K-, the exit temperature of the domestic hot water
between40 and 65°C. Thefunction corresponds with the adjustment of the domestic hot water as per section 5.3.
6.2.11 - Pre-setting of system supply type
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until
RIEMPIMENTO is displayed, it is possible to select, using keys K+ e K-, the following values:
1 = manual
2 = automatic
3 = disabled
If the boiler comes with an automatic valve, for filling the heating circuit, with the RIEMPIMENTO parameter set at
2,the remote timecontrol takes stepsto carry out the fillingof the boilereach time thewater pressure dropsbelow
a pre-established value.
In the event that the parameter is set at 1or 3, the filling of the system must always take place manually (follow the
boiler instruction manual, so as to carry out the filling of the heating circuit’s system).
6.2.12 - Correcting the room temperature read
Pressing the KM key down for more than 10 seconds and then key K2 (IMP) followed by key K4 (>>) until CORR
TAMB is displayed, it is possible to select, using keys K+ e K-, the correction of the reading of the room sensor,
with respect to the actual temperature. If the room temperature read by the remote time control is influenced by
the installation position (e.g. installation on a wall which faces outside, installation on a thermal brigde, etc.) it is
possible to correct the temperature of a value by more or less two degrees, using the CORR TAMB parameter.
Table of contents