manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. CTI
  6. •
  7. Relay
  8. •
  9. CTI FB800E User manual

CTI FB800E User manual

#
'
\
i
'
i
FB
800
E
STATIC
RELAY
261
INSTRUCTION
MANUAL
1
Courtesy of NationalSwitchgear.com
«
-
GSD
8
uiuiii
*
*
*
*
*
*
**
***
***
*
*
*
*
***
***
*
FB
600
E
*
*
*
*
t
k
k
STATIC
RELAY
*
k
INSTRUCTION
MANUAL
*
*
*
*
*
*
*
*
*
**
*
*
*
*
**
*
*
*
**
*
***
*
Carriere
Technical
Industries
Division
of
Derlan
Manufacturing
Inc
.
5621
Finch
Ave
.
E
.
Scarborough
,
Ontario
Canada
Tel
:
Fax
:
M
1
B
2
T
9
(
416
)
297
-
8738
(
416
)
297
-
0421
Part
No
.
FB
600
E
-
M
01
/
91
(
1601
-
0027
)
Rev
.
D
6
Courtesy of NationalSwitchgear.com
FB
600
E
INSTRUCTION
MANUAL
TABLE
OF
CONTENTS
f
1.0
INTRODUCTION
1.1
PRODUCT
DESCRIPTION
1.2
FEATURES
1.3
ACCURACY
1.4
MAXIMUM
INPUTS
.
.
1.5
ENVIRONMENT
.
.
.
.
2
2
4
4
4
2.0
INSTALLATION
2.1
PHYSICAL
DIMENSIONS
2.2
MOUNTING
2.3
EXTERNAL
CONNECTIONS
2.3
.
1
No
Ground
Fault
Detection
2.3
.
2
Zero
Sequence
Ground
Fault
2.3
.
3
Solidly
Grounded
3
Wire
System
/
Residual
Ground
Fault
2.3
.
4
Solidly
Grounded
4
Wire
/
Residual
Ground
Fault
.
.
2.4
CURRENT
TRANSFORMERS
2.5
ACTUATOR
2.6
SYSTEM
GROUNDING
5
6
7
7
8
9
10
11
12
12
3.0
SETUP
AND
OPERATION
3.1
COMMISSIONING
JUMPER
.
.
-
.
3.2
INSTANTANEOUS
TRIP
SETTINGS
3.3
SHORT
TIME
OVERLOAD
SETTINGS
3.4
LONG
TIME
SETTINGS
.
.
.
.
3.5
GROUND
FAULT
SETTINGS
.
.
.
1
13
13
15
16
19
4.0
TESTING
4.1
SECONDARY
INJECTION
TESTING
4.2
PRIMARY
INJECTION
TESTING
.
4.3
INSTANTANEOUS
TRIP
TESTING
4.4
SHORT
TIME
OVERLOAD
TESTING
4.5
LONG
TIME
OVERLOAD
TESTING
4.6
GROUND
FAULT
TESTING
.
..
4.7
FINAL
SETTING
TEST
...
.
22
25
25
25
26
26
27
1
Courtesy of NationalSwitchgear.com
1.0
INTRODUCTION
7
1.1
PRODUCT
DESCRIPTION
The
FB
600
E
is
a
static
.
trip
relay
used
to
cause
a
low
voltage
breaker
to
open
under
fault
conditions
.
Its
primary
application
is
as
a
retrofit
to
600
volt
breakers
for
upgrading
existing
protection
.
By
using
special
CT
'
s
with
both
1
amp
signal
windings
and
a
separate
power
winding
,
the
FB
600
E
relay
requires
no
control
power
to
operate
.
An
output
pulse
from
the
FB
600
E
relay
is
used
to
drive
an
actuator
which
causes
the
breaker
to
trip
.
The
FB
600
E
will
trip
on
overloads
with
separately
adjustable
,
instan
-
taneous
,
short
time
and
long
time
pickup
levels
.
The
short
and
long
delay
times
are
also
adjustable
.
A
long
time
pickup
LED
is
provided
to
assist
in
verifying
the
pickup
threshold
.
To
help
determine
the
cause
of
trip
,
an
indicator
is
provided
for
instantaneous
,
or
short
time
,
trip
and
'
a
separate
indicator
is
used
for
long
time
trip
.
Also
included
with
the
FB
600
E
is
a
ground
fault
trip
and
a
latched
ground
fault
indicator
to
diagnose
the
cause
of
trip
.
1.2
FEATURES
INSTANTANEOUS
OVERLOAD
4
2
/
4
/
6
/
8
/
10
/
12
times
CT
rating
or
defeat
50
ms
maximum
at
>
150
%
of
pickup
setting
(
peak
detector
)
100
ms
maximum
at
>
150
%
of
pickup
setting
(
phase
signal
averaging
)
Pickup
Level
:
Pickup
Time
:
SHORT
TIME
OVERLOAD
Pickup
Level
:
2.5
/
3
/
3.5
/
4
/
4.5
/
5
/
5.5
/
6
/
6.5
/
7
/
7.5
/
8
/
8.5
/
9
/
9.5
/
10
times
CT
rating
or
defeat
Pickup
Time
:
0.15
/
0.25
/
0.4
seconds
at
>
150
%
of
pickup
threshold
LONG
TIME
OVERLOAD
Pickup
Level
:
0.5
/
.
55
/
.
6
/
.
65
/
.
7
/
.
75
/
.
8
/
.
85
/
.
9
/
.
95
/
1
/
1.05
/
1.1
/
1.15
/
1.2
/
1.25
times
CT
rating
or
defeat
Pickup
Time
:
2.5
/
5
/
7.5
/
10
/
12.5
/
15
/
17.5
/
20
seconds
at
6
times
pickup
level
.
Other
times
vary
as
current
squared
.
Actual
times
for
any
overload
condition
can
be
determined
from
the
time
/
overcurrent
curves
,
(
see
fig
.
3.5
)
2
Courtesy of NationalSwitchgear.com
GROUND
FAULT
TRIP
Methods
of
ground
fault
detection
with
the
FB
600
E
are
as
follows
:
Solidly
grounded
3
phase
,
3
wire
systems
.
Residual
connection
(
figure
2.4
)
Solidly
grounded
3
phase
,
3
wire
systems
.
Zero
sequence
connection
(
figure
2.3
)
Solidly
grounded
3
phase
,
4
wire
systems
.
Residual
connection
plus
an
additional
CT
in
the
neutral
conductor
(
figure
2.5
)
Resistance
grounded
3
phase
,
4
wire
systems
.
Use
only
the
zero
sequence
connection
(
figure
2.3
)
a
)
b
)
c
)
d
)
Pickup
Level
:
a
)
ZERO
SEQUENCE
(
SEPARATE
CT
)
.
1
/
.
2
/
.
3
/
.
4
/
.
5
/
.
6
/
.
7
/
.
8
times
G
/
F
CT
rating
or
defeat
i
or
b
)
RESIDUAL
GROUND
FAULT
(
PHASE
CT
SECONDARY
SENSING
)
.
1
/
.
2
/
.
3
/
.
4
/
.
5
/
.
6
/
.
7
/
.
8
times
phase
CT
primary
rating
or
defeat
0.05
sec
minimum
/
0.12
/
0.2
/
0.4
seconds
at
>
150
%
of
pickup
threshold
Pickup
Time
:
*
INDICATORS
i
\
i
:
Long
time
pickup
LED
on
while
long
time
pickup
level
exceeded
.
Latched
instantaneous
or
short
time
trip
indicator
.
Latched
long
time
trip
indicator
.
Latched
ground
fault
trip
indicator
!
i
•
i
I
i
•
TRIP
INDICATORS
Fault
indicators
are
provided
to
determine
the
cause
of
trip
.
Each
indicator
remains
set
after
a
trip
loss
of
control
power
.
Indicators
are
automatically
reset
when
a
load
of
>
40
%
of
the
CT
rating
is
re
-
applied
to
the
breaker
.
i
•
i
i
Instantaneous
/
Short
Time
:
set
if
the
instantaneous
pickup
level
has
been
exceeded
for
50
ms
maximum
(
peak
detector
)
,
100
ms
maximum
(
phase
signal
averaging
)
or
the
short
time
pickup
level
has
been
exceeded
for
the
selected
delay
time
.
Long
Time
:
set
if
the
long
time
or
short
time
pickup
level
has
been
exceeded
for
the
selected
delay
time
.
Ground
Fault
:
set
if
the
ground
fault
pickup
level
has
been
exceeded
for
the
selected
ground
fault
delay
time
.
)
J
3
Courtesy of NationalSwitchgear.com
1.3
ACCURACY
V
Long
Time
/
Short
Time
/
Instantaneous
/
Ground
Fault
pickup
level
:
+
/
-
10
%
Long
/
Short
/
Ground
Fault
trip
time
:
+
/
-
20
%
at
>
150
%
of
pickup
threshold
50
ms
maximum
at
>
150
%
of
pickup
level
(
when
100
ms
maximum
at
>
150
%
of
pickup
level
Instantaneous
trip
:
configured
as
peak
detector
)
,
(
when
configured
as
phase
signal
averaging
)
.
Stated
accuracy
applies
over
the
full
operating
range
of
-
25
to
+
60
°
C
.
CT
input
is
a
50
/
60
Hz
sinewave
.
1.4
MAXIMUM
INPUTS
Phase
/
Ground
Fault
CT
'
s
:
(
terminals
1
/
5
,
2
/
5
,
3
/
5
,
4
/
5
)
4
amps
input
from
secondary
.
.
.
continuous
20
times
rated
current
.
.
.
!
second
1.5
ENVIRONMENT
Operating
temperature
range
:
-
25
°
C
to
+
60
°
C
a
4
Courtesy of NationalSwitchgear.com
2.0
INSTALLATION
•
V
2.1
PHYSICAL
DIMENSIONS
The
FB
600
E
is
housed
in
a
metal
chassis
with
a
hinged
cover
to
protect
its
components
yet
allow
access
to
the
setting
selector
switches
.
Figure
2.1
shows
the
physical
dimensions
of
the
FB
600
E
.
Four
threaded
holes
are
provided
on
-
the
base
to
accept
8
-
32
x
1
/
4
"
screws
for
mounting
the
FB
600
E
to
the
breaker
chassis
.
If
this
orientation
is
not
convenient
other
mounting
holes
must
be
drilled
to
suit
the
mounting
scheme
.
FB
600
E
PHYSICAL
DIMENSIONS
Figure
2.1
8
-
32
-
THflEAO
I
K
in
m
-
<
r
-
<
P
-
I
5.1
"
2.2
"
6.0
“
8.6
"
FB
6
Q
0
E
RELAY
i
5
Courtesy of NationalSwitchgear.com
2.2
MOUNTING
r
To
allow
access
to
selector
switch
settings
,
a
hinged
cover
with
a
spring
release
catch
is
provided
.
This
allows
pickup
levels
and
time
delays
to
be
quickly
set
or
modified
without
the
need
of
tools
.
When
mounting
the
FE
600
E
,
provision
should
be
made
for
the
cover
to
partially
open
to
allow
access
to
the
selector
switches
.
The
latched
trip
indicators
and
external
wiring
terminals
are
mounted
outside
the
hinged
cover
.
Orient
the
relay
on
the
breaker
to
allow
access
to
the
terminal
block
for
relay
testing
and
to
ensure
that
the
indicators
are
visible
when
the
breaker
is
drawn
out
.
?
6
Courtesy of NationalSwitchgear.com
ij
iot
>
ya
ST
*
2.3
EXTERNAL
CONNECTION
^
6
*
2.0
Sic
‘
External
wiring
of
the
FB
600
E
will
depend
on
the
grounding
scheme
used
.
2.3
.
1
No
Ground
Fault
Detection
:
The
simplest
wiring
configuration
is
the
FB
600
E
connected
to
detect
short
circuit
and
overloads
but
no
ground
faults
as
shown
in
figure
2.2
.
Each
of
the
specially
wound
phase
current
transformers
(
CT
'
s
)
has
a
signal
winding
and
a
.
power
winding
thus
eliminating
the
need
for
an
external
control
power
source
.
When
a
trip
condition
occurs
,
a
short
pulse
is
provided
to
the
spring
loaded
actuator
which
triggers
the
breaker
to
open
.
The
CT
signal
winding
common
(
terminals
)
may
be
externally
connected
to
ground
.
However
,
the
power
winding
common
terminal
(
10
)
and
actuator
terminals
(
11
,
12
)
must
not
be
externally
grounded
or
connected
to
signal
common
(
5
)
on
the
FB
600
E
or
it
will
not
operate
correctly
.
Fig
.
2.2
EXTERNAL
WIRING
FOR
NO
GROUND
FAULT
DETECTION
30
SUPPLY
BREAKER
111
Wh
i
te
<
2
T
2
}
-
BREAKER
ACTUATOR
OUTPUT
MR
500
ACTUATOR
f
Rea
<
^
~
T
]
01
SIGNAL
01
C
/
T
$
2
]
02
SIGNAL
02
C
/
T
FB
60
DE
~
3
~
|
03
SIGNAL
~
5
~
~
]
S
IGNAL
COM
.
$
03
C
/
T
jT
]
G
.
F
.
SIGNAL
6
L
1
<
01
}
L
1
C
0
2
D
L
1
C
0
3
D
L
1
CG
.
FO
7
V
V
V
LOAD
L
2
10
*
00
NOT
EXTERNALLY
GROUND
L
2
CTEEM
INAL
1
Gj
7
Courtesy of NationalSwitchgear.com
*
•
V
•
'
I
-
TT
'
—
2.3
.
2
Zero
Sequence
Ground
Fault
:
solidly
grounded
3
wire
systems
,
where
the
On
resistance
grounded
or
phase
conductors
run
in
a
cable
outside
the
breaker
,
the
zero
sequence
ground
fault
detection
scheme
can
be
used
(
figure
2.3
)
.
The
cable
passes
through
the
window
of
a
separate
CT
outside
the
breaker
which
senses
the
zero
sequence
component
of
the
3
currents
.
If
a
ground
shield
is
present
in
the
3
phase
cable
,
it
must
pass
outside
the
window
CT
.
v
?
y
,
of
the
ground
fault
sensing
is
detected
,
the
3
phase
currents
instan
-
Providing
no
ground
fault
taneously
sum
to
zero
and
there
is
no
CT
output
.
Under
ground
fault
this
CT
generates
a
signal
and
power
for
the
FB
600
E
.
The
to
this
external
CT
is
v
;
*
-
a
4
extra
breaker
connecting
fingers
.
conditions
,
wiring
The
CT
signal
winding
common
(
terminals
)
may
be
externally
connected
to
ground
.
However
,
the
power
winding
common
terminal
(
10
)
and
actuator
terminals
(
11
,
12
)
must
not
be
externally
grounded
or
connected
to
signal
common
(
5
)
on
the
FB
600
E
or
it
will
not
operate
correctly
.
EXTERNAL
WIRING
FOR
ZERO
SEQUENCE
GROUND
FAULT
DETECTION
Fig
.
2.3
30
SUPPLY
BREAKER
wn
i
te
T
2
\
-
BREAKER
ACTUATOR
TTL
OUTPUT
MR
60
Q
.
ACTUATOR
*
;
*
Hea
2
~
1
~
|
01
SIGNAL
T
01
C
/
T
T
]
02
SIGNAL
©
02
ic
:
FBBDQE
c
/
r
~
5
~
l
03
SIGNAL
T
]
SIGNAL
COM
.
T
03
C
/
T
ft
:
T
]
G
.
F
.
SIGNAL
>
f
.
>
f
,
%
V
L
1
0
1
)
L
1
0
23
L
1
0
33
L
1
CG
.
F
.
3
30
CABLE
&
T
©
ZERO
SEQUENCE
L
2
£
A
GF
.
C
/
T
NOTE
-
PASS
NEUTRAL
CONDUCTOR
THROUGH
G
.
F
.
C
/
T
IN
4
WIRE
SYSTEMS
*
00
NOT
EXTERNALLY
GROUND
L
2
C
TERM
INAL
103
LOAD
4
8
Courtesy of NationalSwitchgear.com
2.3
.
3
Solidly
Grounded
3
Wire
System
/
Residual
Ground
Fault
:
In
a
3
wire
system
where
it
is
inconvenient
to
run
the
3
phases
through
(
a
separate
ground
fault
CT
,
the
residual
or
common
return
current
of
the
3
phase
CT
'
s
can
be
sensed
for
ground
fault
detection
as
in
figure
2.4
.
Providing
no
ground
fault
is
present
,
the
3
primary
currents
and
hence
phase
CT
secondary
currents
cancel
to
zero
.
When
a
ground
fault
occurs
,
the
current
that
is
sensed
by
summing
the
return
current
in
each
CT
secondary
is
no
longer
zero
and
the
FB
600
E
will
trip
after
the
appropriate
ground
fault
pickup
level
time
delay
has
been
exceeded
.
The
CT
signal
winding
common
(
terminals
)
may
be
externally
connected
to
ground
.
However
,
the
power
winding
common
terminal
(
10
)
and
actuator
terminals
(
11
,
12
)
must
not
be
externally
grounded
or
connected
to
signal
common
(
5
)
on
the
FB
600
E
or
it
will
not
operate
correctly
.
EXTERNAL
WIRING
FOR
3
WIRE
RESIDUAL
GROUND
FAULT
DETECTION
Fig
.
2.4
30
SUPPLY
BREAKER
Wh
i
te
12
}
-
BREAKER
ACTUATOR
OUTPUT
MRSOO
ACTUATOR
#
i
.
~
T
\
01
SIGNAL
01
C
/
T
IE
<
2
9
~
T
\
02
SIGNAL
f
02
C
/
T
FB
600
E
~
3
~
l
03
SIGNAL
31
G
.
F
.
SIGNAL
-
03
C
/
T
M
Q
\
5
~
]
SIGNAL
COM
rrn
6
L
1
(
0
*
0
L
1
C
02
D
L
1
C
0
3
D
L
1
CG
.
F
.
)
V
V
V
3
LOAD
L
2
10
A
*
DO
NOT
EXTERNALLY
GROUND
L
2
CTERWINAL
10
)
9
Courtesy of NationalSwitchgear.com
2.3
.
4
Solidly
Grounded
4
Wire
/
Residual
Ground
Fault
Sensing
:
In
a
4
wire
system
where
it
is
inconvenient
to
run
the
3
phases
and
neutral
through
a
separate
ground
fault
CT
the
wiring
scheme
of
figure
2.5
can
be
used
.
The
residual
current
in
the
return
wire
of
the
3
phase
CT
'
s
is
sensed
.
Under
unbalanced
conditions
this
current
will
not
be
zero
even
with
no
ground
fault
since
the
residual
current
will
flow
in
the
fourth
neutral
wire
.
Consequently
,
a
separate
CT
of
the
same
ratio
as
the
phase
CT
is
used
to
sense
the
neutral
current
and
is
connected
to
exactly
cancel
the
.
phase
CT
residual
current
.
Now
if
a
ground
fault
occurs
,
the
residual
current
will
no
longer
be
cancelled
by
the
neutral
wire
current
and
the
FB
600
E
will
trip
when
the
appropriate
pickup
level
and
time
delay
is
obtained
.
The
CT
signal
winding
common
(
terminals
)
may
be
externally
connected
to
ground
.
However
,
the
power
winding
common
terminal
(
1.0
)
and
actuator
terminals
(
11
,
12
)
must
not
be
externally
grounded
or
connected
to
signal
common
(
5
)
on
the
FB
600
E
or
it
will
not
operate
correctly
.
Fig
.
2.5
EXTERNAL
WIRING
FOR
4
WIRE
RESIDUAL
GROUND
FAULT
DETECTION
30
SUPPLY
BREAKER
t
'
t
t
,
A
White
12
]
-
BREAKER
ACTUATOR
OUTPUT
<
2
MR
6
QQ
ACTUATOR
Tieo
©
r
~
T
]
0
1
SI
GNAL
01
C
/
T
ii
.
d
T
~
l
02
SIGNAL
:
02
C
/
T
FBBOOE
9
"
IH
03
SIGNAL
2
03
*
C
/
T
K
:
]
G
.
F
.
SIGNAL
4
-
:
GF
.
5
SIGNAL
COM
.
L
1
L
1
L
1
C
0
3
^
L
1
CG
.
FO
£
C
/
T
6
K
:
7
1
1
10
L
2
V
V
V
V
LOAD
*
*
DO
NOT
EXTERNALLY
GROUND
L
2
CJERMINAL
10
}
10
Courtesy of NationalSwitchgear.com
2.4
CURRENT
TRANSFORMERS
t
Any
current
transformer
having
both
a
signal
and
power
winding
can
be
used
with
the
FB
600
E
,
Primary
current
ratios
may
cover
any
range
typically
from
100
to
4000
amps
in
suitable
increments
or
CT
'
s
may
have
several
taps
.
A
few
notes
of
caution
are
in
order
regarding
the
CT
'
s
used
in
conjunction
with
the
FB
600
E
.
These
notes
are
:
The
signal
winding
must
have
an
output
of
1
amp
at
the
rated
primary
current
into
a
nominal
resistive
burden
of
0.5
ohms
.
The
power
winding
should
saturate
below
the
CT
rated
amps
and
provide
approximately
10
VA
max
.
The
zero
sequence
ground
fault
CT
is
similar
to
the
phase
CT
.
The
FB
600
E
power
inputs
will
increase
in
burden
with
increased
power
input
.
At
the
worst
case
,
the
FB
600
E
power
inputs
will
burden
the
power
windings
to
a
point
where
the
burden
voltage
is
100
volts
.
Figure
2.6
describes
the
loading
on
the
power
windings
of
the
CT
'
s
.
If
the
power
windings
of
the
CT
'
s
do
not
limit
(
or
saturate
)
their
power
outputs
as
described
in
(
b
)
,
damage
to
the
FB
600
E
may
.
result
.
Carriere
can
provide
specially
designed
CT
'
s
from
stock
which
will
limit
output
power
from
the
power
windings
.
These
Carriere
CT
'
s
are
available
in
several
ratios
.
Please
contact
the
factory
or
a
Carriere
agent
for
more
information
.
In
order
to
ensure
proper
operation
of
all
FB
600
E
functions
,
the
power
windings
must
be
able
to
provide
(
individually
)
at
least
4.5
VA
of
power
.
Carriere
CT
'
s
provide
this
power
at
0.5
x
CT
rating
.
(
a
)
(
b
)
(
c
)
(
d
)
(
e
)
I
Fig
2.6
CT
POWER
WINDING
BURDEN
gsses
gs
*
-
FB
60
DE
Input
Impedance
y
—
+
24
V
Regulated
l
/
V
b
CT
Shunt
Regulator
72
Volt
CMax
}
Power
Winding
?
/
V
100
Volts
(
Maxj
Full
Wave
Rectifier
i
11
Courtesy of NationalSwitchgear.com
.
»
—
-
«
i
*
.
-
-
>
.
-
t
/
•
.
i
.
v
.
*
>
•
'
:
.
*
•
i
•
.
'
f
When
a
trip
condition
is
detected
a
pulse
of
\
DC
.
current
will
be
supplied
to
an
external
actuator
.
The
magnetic
>
f
'
ield
Produced
causes
the
spring
loaded
actuator
to
move
a
plungei
-
thus
,
tripping
the
breaker
.
The
actuator
linkage
mechanism
used
will
depend
'
bn
th
^
|
lyp
?
e
of
breaker
to
which
the
FB
600
E
is
installed
.
/
1
’
,
'
•
•
:
v
-
2.5
ACTUATOR
•
.
•
>
'
-
*
d
-
-
.
,
f
*
mechanism
v
.
i
-
*
2
.
1
•
<
.
,
*
.
k
*
*
v
*
.
/
v
:
N
.
*
.
/
>
vs
-
"
1
2.6
SYSTEM
'
GROUNDING
.
v
.
i
-
•
»
.
V
>
•
jtV
The
CT
signal
windings
,
power
windings
and
actuator
are
connected
to
different
points
in
the
circuitry
of
the
FB
600
E
'
.
Using
a
common
external
ground
for
the
signal
winding
common
-
'
{
terminal
5
)
,
power
winding
common
(
terminal
10
)
or
actuator
(
11
,
12
)
will
cause
the
FB
600
E
to
operate
incorrectly
.
Consequently
,
only
the
CT
signal
winding
common
should
be
connected
to
an
external
ground
as
shown
in
the
wiring
diagrams
of
figures
2.2
-
2.5
.
The
power
winding
common
and
actuator
are
indirectly
referenced
to
ground
internally
by
the
circuitry
.
i
12
Courtesy of NationalSwitchgear.com
i
.
3.0
SETUP
AND
OPERATION
i
3.1
COMMISSIONING
JUMPER
The
jumper
should
be
ON
whenever
the
unit
is
not
ready
,
(
ie
.
all
DIP
switches
have
not
been
programmed
)
.
When
this
jumper
is
in
place
,
the
FB
600
E
will
trip
.
each
time
current
is
applied
to
any
of
the
CT
inputs
.
This
jumper
is
in
place
as
a
failsafe
measure
to
ensure
that
the
unit
is
set
up
before
commissioning
.
(
a
)
!
The
jumper
must
be
removed
after
the
unit
is
set
up
for
commis
-
sioning
.
(
b
)
11
D
41
R
98
R
12
U
12
JU
1
1
Cl
W
4
A
173
Fig
.
3.2
INSTANTANEOUS
TRIP
TIME
DELAY
CURVES
3.2
INSTANTANEOUS
TRIP
SETTINGS
Instantaneous
tripping
without
any
intentional
delay
is
used
to
provide
protection
against
short
circuits
.
Switches
SI
4
and
SI
5
are
used
to
choose
between
phase
signal
averaging
and
peak
detector
and
consequently
the
pickup
time
.
The
pickup
level
is
controlled
by
switches
SI
1
to
SI
3
to
select
a
trip
level
of
2
(
curve
A
)
to
12
(
curve
B
)
times
the
CT
rating
as
shown
in
figure
3.2
.
Various
short
circuit
pickup
levels
can
be
selected
according
to
figure
3.1
.
This
feature
may
be
defeated
by
setting
switch
SIS
off
.
i
023
*
027
-
2
TRIP
TIME
insian
-
A
jtoneousy
L
>
level
V
.
SI
1
-
SI
3
(
SEC
)
V
0.10
phase
signal
averaging
V
v
0.05
peak
detector
i
12
2
CURRENT
(
Multiples
of
CT
Ratio
)
13
Courtesy of NationalSwitchgear.com
Fig
.
3.1
INSTANTANEOUS
TRIP
SWITCH
SETTINGS
INSTANTANEOUS
TRIP
SWITCH
SETTINGS
SWITCHES
SI
12345678
FUNCTION
LEVEL
111
-
-
Oil
1
0
1
T
5
0
0
1
110
0
1 0
2
X
CT
Rating
4
X
CT
Rating
6
X
CT
Rating
4
X
CT
Rating
10
X
CT
Rating
12
X
CT
Rating
:
Instantaneous
Pickup
Level
1
1
1
cr
1
i
0
'
Instant
.
Disable
'
'
SO
1
0
ms
delay
peak
detector
0
1
100
ms
delay
phase
signal
averaging
Trip
Indicator
:
0
=
off
1
=
on
Inst
.
/
Short
Time
no
effect
o o
1 1
o
o o
i
o
*
cT
:
b
\
n
3
14
Courtesy of NationalSwitchgear.com
3.3
SHORT
TIME
OVERLOAD
SETTINGS
Fig
.
3.4
SHORT
TIME
DELAY
TIME
/
OVERCURRENT
CURVES
•
V
Short
time
delay
tripping
is
provided
for
use
in
coordinated
protection
systems
to
shut
down
only
pickup
levels
of
2.5
-
10
times
the
CT
rating
and
time
delays
of
0.15
to
0.4
seconds
can
be
selected
using
switches
SSI
to
SS
8
as
shown
in
figure
3.3
.
This
feature
can
also
be
defeated
for
'
test
purposes
b
.
y
setting
SS
8
off
.
The
effect
o
.
f
these
switches
on
the
time
/
overcurrent
curves
is
•
-
,
jl
.
v
shown
in
f
iguire
3.4
.
Short
Time
Level
SS
1
-
SS
4
TRIP
TIME
(
SEC
)
_
Sv
V
0.40
Short
Time
Deloy
SS
5
-
SS
7
1
'
0.15
I
I
l
l
>
1
.
I
f
10
i
:
2.5
V
-
CURRENT
(
Multiples
of
CT
Rotio
)
?
Fig
.
3.3
SHORT
TIME
SWITCH
SETTINGS
-
f
.
'
f
•
SHORT
TIME
DELAY
'
.
SWITCH
*
-
.
SETTINGS
5
T
.
SWITCHES
SS
1
2
3
4
5
6
7
8
FUNCTION
LEVEL
.
t
--
i
>
-
:
•
•
Short
Time
Pickup
2.5
x
CT
Rating
3
.
x
CT
Rating
3.5
x
CT
Rating
x
CT
Rating
4.5
x
CT
Rating
x
CT
Rating
5.5
x
CT
Rating
x
CT
Rating
6.5
x
CT
Rating
x
CT
Rating
7.5
x
CT
Rating
x
CT
Rating
8.5
x
CT
Rating
x
CT
Rating
9.5
x
CT
Rating
10
x
CT
Rating
1111
0
111
.
1 0
1 1
0
0
1 1
110
1
0
1 0
1
1 0
0
1
000
1
1110
0
110
1 0
1 0
0
0
1 0
110
0
0
1 0
0
1 0
00
0
0
0
0
1
1
1
1
4
1
1
—
5
1
1
-
^
6
1
)
1
7
1
1
8
1
1
9
1
1
1 0
0
1
Short
Time
Delay
0.15
sec
.
@
>
150
%
pickup
level
0.25
sec
.
@
>
150
%
pickup
level
sec
.
@
>
150
%
.
pickup
level
0
1 0
1
0
0
1 1
-
0.4
'
V
'
0
Short
Disable
0
=
off
1
=
on
no
effect
0
o
o
|
oio
15
Courtesy of NationalSwitchgear.com
3.4
LONG
TIME
SETTINGS
To
allow
a
breaker
to
protect
system
components
such
as
transformers
,
motors
,
conductors
,
etc
.
that
fail
due
to
resistive
heating
,
a
set
of
time
overcurrent
curves
that
follow
a
current
squared
characteristic
is
provided
.
When
an
overcurrent
condition
persists
for
a
specified
length
of
time
the
breaker
trips
and
breaks
the
load
.
Trip
times
for
various
levels
of
current
and
curve
settings
are
listed
in
figure
3.5
for
testing
convenience
.
These
curves
are
shown
on
the
time
/
overcurrent
graph
of
figure
3.10
for
coordination
purposes
.
f
A
Fig
3.5
LONG
TIME
OVERLOAD
TRIP
TIMES
FB
600
E
LONG
TIME
PICKUP
DELAYS
(
SECONDS
)
CURRENT
IN
MULTIPLES
OF
LONG
TIME
PICKUP
SL
5
-
7
12
1.5
1.25
CURVE
ERROR
10
8
7
6
5
3
•
2
1.1
1
4
-
20
%
0.50
0.63
0.76
0.72
0.90
1.08
1.13
1.41
1.69
2.88
3.60
4.32
4.50
5.63
6.76
8.00
10.00
12.00
18.00
22.50
27.00
46.08
57.60
69.12
59.50
74.38
89.26
72.00
90.00
108.00
1.47
1.84
2.21
2.00
2.50
3.00
32.00
40.00
48.00
1
0
111
+
20
%
-
20
%
1.01
1.26
1.51
1.44
1.80
2.16
5.76
7.20
8.64
16.00
20.00
24.00
36.00
4
5.00
54.00
92.16
115.20
138.24
119.01
148.76
178.51
144.00
180.00
216.00
2.26
2.82
3.38
2.94
3.68
4.42
4.00
5.00
6.00
9.01
11.26
13.51
64.00
80.00
96.00
2
0
Oil
+
20
%
1.51
1.89
2.27
-
20
%
2.16
2.70
3.24
13.51
16.89
20.27
24.00
30.00
36.00
138.24
172.80
207.36
178.51
223.14
267.77
216.00
270.00
324.00
3.38
4.23
5.08
4.42
5.52
6.62
6.00
7.50
9.00
8.64
10.80
12.96
54.00
67.50
81.00
96.00
120.00
144.00
.
3
101
0
+
20
%
2.02
2.52
3.02
-
20
%
2.88
3.60
4.32
5.89
7.36
8.83
18.02
22.52
27.02
32.00
40.00
48.00
72.00
90.00
108.00
288.00
360.00
432.00
4.51
5.64
6.77
8.00
10.00
12.00
11.52
14.40
17.28
128.00
160.00
192.00
184.32
230.40
276.48
238.02
297.52
357.02
4
m
0
+
20
%
-
>
2.52
3.15
3.78
3.60
4.50
5.40
297.52
371.90
446.28
360.00
450.00
540.00
-
20
%
5.64
7.05
8.46
7.36
9.20
11.04
10.00
12.50
15.00
22.52
28.15
33.78
40.00
50.00
60.00
230.40
288.00
345.60
14.40
18.00
21.60
90.00
112.50
135.00
160.00
200.00
240.00
5
110
0
+
20
%
-
3.02
3.78
4.54
4.32
5.40
6.48
6.77
8.46
10.15
357.02
446.28
535.54
432.00
540.00
648.00
-
20
%
8.83
11.04
13.25
12.00
15.00
18.00
17.28
21.60
25.92
27.02
33.78
40.54
48.00
60.00
72.00
108.00
135.00
162.00
276.48
345.60
414.72
192.00
240.00
288.00
6
010
0
+
20
%
3.53
4.41
5.29
5.04
6.30
7.56
416.53
520.66
624.79
-
20
%
7.90
9.87
11.84
10.30
12.88
15.46
14.00
17.50
21.00
56.00
70.00
84.00
126.00
157.50
189.00
322.56
403.20
483.84
504.00
630.00
756.00
20.16
25.20
3
C
.
24
31.53
39.41
47.29
224.00
280.00
336.00
7
100
0
+
20
%
4.03
5.04
6.05
5.76
7.20
8.64
-
20
%
9.02
11.28
13.54
64.00
80.00
96.00
476.03
595.04
714.05
576.00
720.00
864.00
11.78
14.27
17.66
16.00
20.00
24.00
23.04
28.80
34.56
36.03
45.04
54.05
144.00
180.00
216.00
256.00
320.00
384.00
386.64
460.80
552.96
000
!
8
0
+
20
%
16
Courtesy of NationalSwitchgear.com
Switches
SL
1
to
.
SL
8
are
used
to
select
pickup
current
levels
of
0.5
-
1.25
times
the
CT
rating
and
time
delays
of
2.5
-
20
seconds
(
at
6
times
the
CT
rating
)
as
shown
in
figure
3.6
.
The
short
time
delay
and
instantaneous
trip
settings
should
be
selected
to
ensure
that
the
breaker
trips
without
allowing
a
continuous
current
to
flow
that
is
greater
than
400
%
of
the
CT
rating
(
see
Maximum
Inputs
section
2.5
)
.
The
effect
of
switches
SL
1
to
SL
7
on
the
time
/
current
curves
is
shown
in
figure
3.7
.
Fig
.
3.6
LONG
TIME
DELAY
SWITCH
SETTINGS
.
LONG
TIME
DELAY
SWITCH
SETTINGS
FUNCTION
SWITCHES
SL
-
12345678
LEVEL
Long
Time
Pickup
0.5
x
CT
Rating
0.55
x
CT
Rating
0.60
x
CT
Rating
0.65
x
CT
Rating
0.70
x
CT
Rating
0.75
x
CT
Rating
0.80
x
CT
Rating
0.85
x
CT
Rating
0.90
x
CT
Rating
0.95
x
CT
Rating
1.00
x
CT
Rating
1.05
x
CT
Rating
1.10
x
CT
Rating
1.15
x
CT
Rating
1.20
x
CT
Rating
1.25
x
CT
Rating
1111
0
111
10
11
0
0
1 1
110
1
0
1 0
1
1 0
0
1
0
0
0
1
1110
0
110
i
o
i
o
0
0
1 0
110
0
0
1 0
0
1 0
00
0
0
0
0
1
1
1
1
1
1
1
1
3
1
1
1
1
1
1
1
1
Long
Time
Delay
sec
.
@
6
x
Pickup
Level
sec
.
@
6
x
Pickup
Level
sec
.
@
6
x
Pickup
Level
sec
.
@
6
x
Pickup
Level
12.5
sec
.
@
6
x
Pickup
Level
sec
.
@
6
x
Pickup
Level
17.5
sec
.
@
6
x
Pickup
Level
sec
.
@
6
x
Pickup
Level
2.5
1111
0
111
1 0
1 1
0
0
1 1
110
1
0
1 0
1
1 0
0
1
0
0
0
1
5
7.5
10
1 5
20
Long
Time
Disable
0
0
=
off
1
on
no
effect
[
O
[
D
c
>
o o
1
17
Courtesy of NationalSwitchgear.com
Switches
SL
1
to
SL
4
determine
the
current
pickup
level
required
for
the
breaker
to
trip
.
The
time
to
trip
will
be
determined
by
the
amount
that
the
current
exceeds
the
overload
level
and
the
curve
selected
(
SL
5
to
SL
7
)
.
Long
time
delay
trip
can
be
defeated
for
test
purposes
by
setting
switch
SL
8
off
.
Fig
.
3.7
LONG
TIME
DELAY
CURVES
A
LeveI
SL
1
-
SL
4
TRIP
TIME
C
SEC
}
0
Minimum
pickup
(
0.5
x
CT
rating
)
Minimum
time
(
2.5
sec
.
@
6
x
CT
pick
-
up
)
curve
ABCDE
SL
8
to
SL
1
:
11111111
Minimum
pickup
(
0.5
x
CT
rating
)
Maximum
time
(
20
sec
.
@
6
x
CT
pick
-
up
)
curve
ABGH
SL
8
to
SL
1
:
10001111
Maximum
pickup
(
1.25
x
CT
rating
)
Minimum
time
delay
(
2.5
sec
.
@
6
x
CT
pick
-
up
)
curve
FGDE
SL
8
to
SL
1
:
11110000
Maximum
pickup
(
1.25
x
CT
rating
)
Maximum
time
delay
(
20
sec
.
@
6
x
CT
pick
-
up
)
curve
FGH
SL
8
to
SL
1
:
10000000
.
18
Courtesy of NationalSwitchgear.com

Popular Relay manuals by other brands

ABB C576 operating instructions

ABB

ABB C576 operating instructions

ABB CA-26 Instruction leaflet

ABB

ABB CA-26 Instruction leaflet

Eaton ETR4 W Series Instruction leaflet

Eaton

Eaton ETR4 W Series Instruction leaflet

Pilz PNOZ X2.4V Technical instructions

Pilz

Pilz PNOZ X2.4V Technical instructions

schmersal PROTECT SRB 200EXi-1R Mounting and wiring instructions

schmersal

schmersal PROTECT SRB 200EXi-1R Mounting and wiring instructions

PEGASUS TECHNOLOGY GRAMEYER GCDT-02 Operation and installation manual

PEGASUS TECHNOLOGY

PEGASUS TECHNOLOGY GRAMEYER GCDT-02 Operation and installation manual

Delixi JS14P Series user manual

Delixi

Delixi JS14P Series user manual

Honeywell AQUASTAT L8124A installation instructions

Honeywell

Honeywell AQUASTAT L8124A installation instructions

GE CHC12A instructions

GE

GE CHC12A instructions

Elko HRN-57 manual

Elko

Elko HRN-57 manual

FANOX SIA C Series Installation & commissioning guide

FANOX

FANOX SIA C Series Installation & commissioning guide

KMC Controls FlexStat BAC-12xx36 Series installation guide

KMC Controls

KMC Controls FlexStat BAC-12xx36 Series installation guide

Allen-Bradley Guardmaster 440C-CR30-22BBB Wiring diagram

Allen-Bradley

Allen-Bradley Guardmaster 440C-CR30-22BBB Wiring diagram

Siemens SIRIUS 3RF20 operating instructions

Siemens

Siemens SIRIUS 3RF20 operating instructions

GE D30 series instruction manual

GE

GE D30 series instruction manual

GMI D5096S instruction manual

GMI

GMI D5096S instruction manual

Siemens SIRIUS 3RQ301 0A 0 Series operating instructions

Siemens

Siemens SIRIUS 3RQ301 0A 0 Series operating instructions

Siemens 3TK2810-0 Equipment manual

Siemens

Siemens 3TK2810-0 Equipment manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.