manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. CTI
  6. •
  7. Relay
  8. •
  9. CTI FB800E User manual

CTI FB800E User manual

Popular Relay manuals by other brands

Woodward BU1-DC2 manual

Woodward

Woodward BU1-DC2 manual

ABB SSR32 product manual

ABB

ABB SSR32 product manual

Siemens SIRIUS 3UG4633 operating instructions

Siemens

Siemens SIRIUS 3UG4633 operating instructions

Siemens SIRIUS 3TK2824 A.20 Series Original operating instructions

Siemens

Siemens SIRIUS 3TK2824 A.20 Series Original operating instructions

Shelly Pro Series user manual

Shelly

Shelly Pro Series user manual

GE MVAX 11 Technical manual

GE

GE MVAX 11 Technical manual

ABB RELION REF615R manual

ABB

ABB RELION REF615R manual

Kemo Electronic B197 quick guide

Kemo Electronic

Kemo Electronic B197 quick guide

Seg MRM3 manual

Seg

Seg MRM3 manual

Basler BE1-700C manual

Basler

Basler BE1-700C manual

CD Automation REVEX 2PH 280A user manual

CD Automation

CD Automation REVEX 2PH 280A user manual

ABB SPAJ 142 C User manual and technical description

ABB

ABB SPAJ 142 C User manual and technical description

Ruelco 1S04 Operation manual

Ruelco

Ruelco 1S04 Operation manual

Basler V3E Z1P B2C1F instruction manual

Basler

Basler V3E Z1P B2C1F instruction manual

GE DGP instruction manual

GE

GE DGP instruction manual

Kyongbo Electronics GDR-D01 user manual

Kyongbo Electronics

Kyongbo Electronics GDR-D01 user manual

Eaton easyE4 series Application note

Eaton

Eaton easyE4 series Application note

Siemens BD2-AK03X/FS Series installation instructions

Siemens

Siemens BD2-AK03X/FS Series installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

#
'
\
i
'
i
FB
800
E
STATIC
RELAY
261
INSTRUCTION
MANUAL
1
Courtesy of NationalSwitchgear.com
«
-
GSD
8
uiuiii
*
*
*
*
*
*
**
***
***
*
*
*
*
***
***
*
FB
600
E
*
*
*
*
t
k
k
STATIC
RELAY
*
k
INSTRUCTION
MANUAL
*
*
*
*
*
*
*
*
*
**
*
*
*
*
**
*
*
*
**
*
***
*
Carriere
Technical
Industries
Division
of
Derlan
Manufacturing
Inc
.
5621
Finch
Ave
.
E
.
Scarborough
,
Ontario
Canada
Tel
:
Fax
:
M
1
B
2
T
9
(
416
)
297
-
8738
(
416
)
297
-
0421
Part
No
.
FB
600
E
-
M
01
/
91
(
1601
-
0027
)
Rev
.
D
6
Courtesy of NationalSwitchgear.com
FB
600
E
INSTRUCTION
MANUAL
TABLE
OF
CONTENTS
f
1.0
INTRODUCTION
1.1
PRODUCT
DESCRIPTION
1.2
FEATURES
1.3
ACCURACY
1.4
MAXIMUM
INPUTS
.
.
1.5
ENVIRONMENT
.
.
.
.
2
2
4
4
4
2.0
INSTALLATION
2.1
PHYSICAL
DIMENSIONS
2.2
MOUNTING
2.3
EXTERNAL
CONNECTIONS
2.3
.
1
No
Ground
Fault
Detection
2.3
.
2
Zero
Sequence
Ground
Fault
2.3
.
3
Solidly
Grounded
3
Wire
System
/
Residual
Ground
Fault
2.3
.
4
Solidly
Grounded
4
Wire
/
Residual
Ground
Fault
.
.
2.4
CURRENT
TRANSFORMERS
2.5
ACTUATOR
2.6
SYSTEM
GROUNDING
5
6
7
7
8
9
10
11
12
12
3.0
SETUP
AND
OPERATION
3.1
COMMISSIONING
JUMPER
.
.
-
.
3.2
INSTANTANEOUS
TRIP
SETTINGS
3.3
SHORT
TIME
OVERLOAD
SETTINGS
3.4
LONG
TIME
SETTINGS
.
.
.
.
3.5
GROUND
FAULT
SETTINGS
.
.
.
1
13
13
15
16
19
4.0
TESTING
4.1
SECONDARY
INJECTION
TESTING
4.2
PRIMARY
INJECTION
TESTING
.
4.3
INSTANTANEOUS
TRIP
TESTING
4.4
SHORT
TIME
OVERLOAD
TESTING
4.5
LONG
TIME
OVERLOAD
TESTING
4.6
GROUND
FAULT
TESTING
.
..
4.7
FINAL
SETTING
TEST
...
.
22
25
25
25
26
26
27
1
Courtesy of NationalSwitchgear.com
1.0
INTRODUCTION
7
1.1
PRODUCT
DESCRIPTION
The
FB
600
E
is
a
static
.
trip
relay
used
to
cause
a
low
voltage
breaker
to
open
under
fault
conditions
.
Its
primary
application
is
as
a
retrofit
to
600
volt
breakers
for
upgrading
existing
protection
.
By
using
special
CT
'
s
with
both
1
amp
signal
windings
and
a
separate
power
winding
,
the
FB
600
E
relay
requires
no
control
power
to
operate
.
An
output
pulse
from
the
FB
600
E
relay
is
used
to
drive
an
actuator
which
causes
the
breaker
to
trip
.
The
FB
600
E
will
trip
on
overloads
with
separately
adjustable
,
instan
-
taneous
,
short
time
and
long
time
pickup
levels
.
The
short
and
long
delay
times
are
also
adjustable
.
A
long
time
pickup
LED
is
provided
to
assist
in
verifying
the
pickup
threshold
.
To
help
determine
the
cause
of
trip
,
an
indicator
is
provided
for
instantaneous
,
or
short
time
,
trip
and
'
a
separate
indicator
is
used
for
long
time
trip
.
Also
included
with
the
FB
600
E
is
a
ground
fault
trip
and
a
latched
ground
fault
indicator
to
diagnose
the
cause
of
trip
.
1.2
FEATURES
INSTANTANEOUS
OVERLOAD
4
2
/
4
/
6
/
8
/
10
/
12
times
CT
rating
or
defeat
50
ms
maximum
at
>
150
%
of
pickup
setting
(
peak
detector
)
100
ms
maximum
at
>
150
%
of
pickup
setting
(
phase
signal
averaging
)
Pickup
Level
:
Pickup
Time
:
SHORT
TIME
OVERLOAD
Pickup
Level
:
2.5
/
3
/
3.5
/
4
/
4.5
/
5
/
5.5
/
6
/
6.5
/
7
/
7.5
/
8
/
8.5
/
9
/
9.5
/
10
times
CT
rating
or
defeat
Pickup
Time
:
0.15
/
0.25
/
0.4
seconds
at
>
150
%
of
pickup
threshold
LONG
TIME
OVERLOAD
Pickup
Level
:
0.5
/
.
55
/
.
6
/
.
65
/
.
7
/
.
75
/
.
8
/
.
85
/
.
9
/
.
95
/
1
/
1.05
/
1.1
/
1.15
/
1.2
/
1.25
times
CT
rating
or
defeat
Pickup
Time
:
2.5
/
5
/
7.5
/
10
/
12.5
/
15
/
17.5
/
20
seconds
at
6
times
pickup
level
.
Other
times
vary
as
current
squared
.
Actual
times
for
any
overload
condition
can
be
determined
from
the
time
/
overcurrent
curves
,
(
see
fig
.
3.5
)
2
Courtesy of NationalSwitchgear.com
GROUND
FAULT
TRIP
Methods
of
ground
fault
detection
with
the
FB
600
E
are
as
follows
:
Solidly
grounded
3
phase
,
3
wire
systems
.
Residual
connection
(
figure
2.4
)
Solidly
grounded
3
phase
,
3
wire
systems
.
Zero
sequence
connection
(
figure
2.3
)
Solidly
grounded
3
phase
,
4
wire
systems
.
Residual
connection
plus
an
additional
CT
in
the
neutral
conductor
(
figure
2.5
)
Resistance
grounded
3
phase
,
4
wire
systems
.
Use
only
the
zero
sequence
connection
(
figure
2.3
)
a
)
b
)
c
)
d
)
Pickup
Level
:
a
)
ZERO
SEQUENCE
(
SEPARATE
CT
)
.
1
/
.
2
/
.
3
/
.
4
/
.
5
/
.
6
/
.
7
/
.
8
times
G
/
F
CT
rating
or
defeat
i
or
b
)
RESIDUAL
GROUND
FAULT
(
PHASE
CT
SECONDARY
SENSING
)
.
1
/
.
2
/
.
3
/
.
4
/
.
5
/
.
6
/
.
7
/
.
8
times
phase
CT
primary
rating
or
defeat
0.05
sec
minimum
/
0.12
/
0.2
/
0.4
seconds
at
>
150
%
of
pickup
threshold
Pickup
Time
:
*
INDICATORS
i
\
i
:
Long
time
pickup
LED
on
while
long
time
pickup
level
exceeded
.
Latched
instantaneous
or
short
time
trip
indicator
.
Latched
long
time
trip
indicator
.
Latched
ground
fault
trip
indicator
!
i
•
i
I
i
•
TRIP
INDICATORS
Fault
indicators
are
provided
to
determine
the
cause
of
trip
.
Each
indicator
remains
set
after
a
trip
loss
of
control
power
.
Indicators
are
automatically
reset
when
a
load
of
>
40
%
of
the
CT
rating
is
re
-
applied
to
the
breaker
.
i
•
i
i
Instantaneous
/
Short
Time
:
set
if
the
instantaneous
pickup
level
has
been
exceeded
for
50
ms
maximum
(
peak
detector
)
,
100
ms
maximum
(
phase
signal
averaging
)
or
the
short
time
pickup
level
has
been
exceeded
for
the
selected
delay
time
.
Long
Time
:
set
if
the
long
time
or
short
time
pickup
level
has
been
exceeded
for
the
selected
delay
time
.
Ground
Fault
:
set
if
the
ground
fault
pickup
level
has
been
exceeded
for
the
selected
ground
fault
delay
time
.
)
J
3
Courtesy of NationalSwitchgear.com
1.3
ACCURACY
V
Long
Time
/
Short
Time
/
Instantaneous
/
Ground
Fault
pickup
level
:
+
/
-
10
%
Long
/
Short
/
Ground
Fault
trip
time
:
+
/
-
20
%
at
>
150
%
of
pickup
threshold
50
ms
maximum
at
>
150
%
of
pickup
level
(
when
100
ms
maximum
at
>
150
%
of
pickup
level
Instantaneous
trip
:
configured
as
peak
detector
)
,
(
when
configured
as
phase
signal
averaging
)
.
Stated
accuracy
applies
over
the
full
operating
range
of
-
25
to
+
60
°
C
.
CT
input
is
a
50
/
60
Hz
sinewave
.
1.4
MAXIMUM
INPUTS
Phase
/
Ground
Fault
CT
'
s
:
(
terminals
1
/
5
,
2
/
5
,
3
/
5
,
4
/
5
)
4
amps
input
from
secondary
.
.
.
continuous
20
times
rated
current
.
.
.
!
second
1.5
ENVIRONMENT
Operating
temperature
range
:
-
25
°
C
to
+
60
°
C
a
4
Courtesy of NationalSwitchgear.com
2.0
INSTALLATION
•
V
2.1
PHYSICAL
DIMENSIONS
The
FB
600
E
is
housed
in
a
metal
chassis
with
a
hinged
cover
to
protect
its
components
yet
allow
access
to
the
setting
selector
switches
.
Figure
2.1
shows
the
physical
dimensions
of
the
FB
600
E
.
Four
threaded
holes
are
provided
on
-
the
base
to
accept
8
-
32
x
1
/
4
"
screws
for
mounting
the
FB
600
E
to
the
breaker
chassis
.
If
this
orientation
is
not
convenient
other
mounting
holes
must
be
drilled
to
suit
the
mounting
scheme
.
FB
600
E
PHYSICAL
DIMENSIONS
Figure
2.1
8
-
32
-
THflEAO
I
K
in
m
-
<
r
-
<
P
-
I
5.1
"
2.2
"
6.0
“
8.6
"
FB
6
Q
0
E
RELAY
i
5
Courtesy of NationalSwitchgear.com
2.2
MOUNTING
r
To
allow
access
to
selector
switch
settings
,
a
hinged
cover
with
a
spring
release
catch
is
provided
.
This
allows
pickup
levels
and
time
delays
to
be
quickly
set
or
modified
without
the
need
of
tools
.
When
mounting
the
FE
600
E
,
provision
should
be
made
for
the
cover
to
partially
open
to
allow
access
to
the
selector
switches
.
The
latched
trip
indicators
and
external
wiring
terminals
are
mounted
outside
the
hinged
cover
.
Orient
the
relay
on
the
breaker
to
allow
access
to
the
terminal
block
for
relay
testing
and
to
ensure
that
the
indicators
are
visible
when
the
breaker
is
drawn
out
.
?
6
Courtesy of NationalSwitchgear.com
ij
iot
>
ya
ST
*
2.3
EXTERNAL
CONNECTION
^
6
*
2.0
Sic
‘
External
wiring
of
the
FB
600
E
will
depend
on
the
grounding
scheme
used
.
2.3
.
1
No
Ground
Fault
Detection
:
The
simplest
wiring
configuration
is
the
FB
600
E
connected
to
detect
short
circuit
and
overloads
but
no
ground
faults
as
shown
in
figure
2.2
.
Each
of
the
specially
wound
phase
current
transformers
(
CT
'
s
)
has
a
signal
winding
and
a
.
power
winding
thus
eliminating
the
need
for
an
external
control
power
source
.
When
a
trip
condition
occurs
,
a
short
pulse
is
provided
to
the
spring
loaded
actuator
which
triggers
the
breaker
to
open
.
The
CT
signal
winding
common
(
terminals
)
may
be
externally
connected
to
ground
.
However
,
the
power
winding
common
terminal
(
10
)
and
actuator
terminals
(
11
,
12
)
must
not
be
externally
grounded
or
connected
to
signal
common
(
5
)
on
the
FB
600
E
or
it
will
not
operate
correctly
.
Fig
.
2.2
EXTERNAL
WIRING
FOR
NO
GROUND
FAULT
DETECTION
30
SUPPLY
BREAKER
111
Wh
i
te
<
2
T
2
}
-
BREAKER
ACTUATOR
OUTPUT
MR
500
ACTUATOR
f
Rea
<
^
~
T
]
01
SIGNAL
01
C
/
T
$
2
]
02
SIGNAL
02
C
/
T
FB
60
DE
~
3
~
|
03
SIGNAL
~
5
~
~
]
S
IGNAL
COM
.
$
03
C
/
T
jT
]
G
.
F
.
SIGNAL
6
L
1
<
01
}
L
1
C
0
2
D
L
1
C
0
3
D
L
1
CG
.
FO
7
V
V
V
LOAD
L
2
10
*
00
NOT
EXTERNALLY
GROUND
L
2
CTEEM
INAL
1
Gj
7
Courtesy of NationalSwitchgear.com
*
•
V
•
'
I
-
TT
'
—
2.3
.
2
Zero
Sequence
Ground
Fault
:
solidly
grounded
3
wire
systems
,
where
the
On
resistance
grounded
or
phase
conductors
run
in
a
cable
outside
the
breaker
,
the
zero
sequence
ground
fault
detection
scheme
can
be
used
(
figure
2.3
)
.
The
cable
passes
through
the
window
of
a
separate
CT
outside
the
breaker
which
senses
the
zero
sequence
component
of
the
3
currents
.
If
a
ground
shield
is
present
in
the
3
phase
cable
,
it
must
pass
outside
the
window
CT
.
v
?
y
,
of
the
ground
fault
sensing
is
detected
,
the
3
phase
currents
instan
-
Providing
no
ground
fault
taneously
sum
to
zero
and
there
is
no
CT
output
.
Under
ground
fault
this
CT
generates
a
signal
and
power
for
the
FB
600
E
.
The
to
this
external
CT
is
v
;
*
-
a
4
extra
breaker
connecting
fingers
.
conditions
,
wiring
The
CT
signal
winding
common
(
terminals
)
may
be
externally
connected
to
ground
.
However
,
the
power
winding
common
terminal
(
10
)
and
actuator
terminals
(
11
,
12
)
must
not
be
externally
grounded
or
connected
to
signal
common
(
5
)
on
the
FB
600
E
or
it
will
not
operate
correctly
.
EXTERNAL
WIRING
FOR
ZERO
SEQUENCE
GROUND
FAULT
DETECTION
Fig
.
2.3
30
SUPPLY
BREAKER
wn
i
te
T
2
\
-
BREAKER
ACTUATOR
TTL
OUTPUT
MR
60
Q
.
ACTUATOR
*
;
*
Hea
2
~
1
~
|
01
SIGNAL
T
01
C
/
T
T
]
02
SIGNAL
©
02
ic
:
FBBDQE
c
/
r
~
5
~
l
03
SIGNAL
T
]
SIGNAL
COM
.
T
03
C
/
T
ft
:
T
]
G
.
F
.
SIGNAL
>
f
.
>
f
,
%
V
L
1
0
1
)
L
1
0
23
L
1
0
33
L
1
CG
.
F
.
3
30
CABLE
&
T
©
ZERO
SEQUENCE
L
2
£
A
GF
.
C
/
T
NOTE
-
PASS
NEUTRAL
CONDUCTOR
THROUGH
G
.
F
.
C
/
T
IN
4
WIRE
SYSTEMS
*
00
NOT
EXTERNALLY
GROUND
L
2
C
TERM
INAL
103
LOAD
4
8
Courtesy of NationalSwitchgear.com