Delixi JS14P Series User manual

JS14P Series Time Relay
User Manual
□ Please carefully read this User Manual before
installing and operating the product. and keep this
manual properly for future reference

- 1 -
I. Overview
1.1 Scope of Application
JS14P series time relay is suitable for AC 50/60Hz automatic control circuit with the voltage 380V and below and
with the DC volage 240 and below. and is used to connect or disconnect the circuit at a predetermined time.
The product is an upgraded product such as JS14 and JS20. It uses integrated circuit and preset digital key switch.
featuring with small size. light weight. high precision. long life and high versatility.
Standard: GB/T 14048.5
1.2 Model definition
Rated control supply voltage Us: see 3.3
Delay time: see table
Installation form: no code means device type; M means panel type
Delay type model and specification code: no code means power-on delay;
D means power-off delay
Digital type
Design No.
Time relay
Spec. and Code
Delay range
Multiply
selection
Setting method
Delay time
JS14P. JS14P-M
JS14P-01
JS14P-01/М
0.1-9.9s
1-99s
х0.1
х1
2-digit setting
switch
JS14P-02
JS14P-02/М
0.1-9.9s
0.1-9.9min
х0.1
х6
2-digit setting
switch
0.1-9.9s, 1-99s, 10-999s,
0.1-9.9min, 1-99min,
10-990min, 0.1-9.9h, 1-99h,
0.01-9.99s, 0.1-99.9s, 1-999s,
10-9990s, 0.1-99.9min,
1-999min, 10-9990min,
0.1-99.9h, 1-999h, One machine
with multiple delays 0.1s~99h,
One machine with multiple
delays 0.01s~999h
JS14P-03
JS14P-03/М
1-99s
0.1-9.9min
х1
х6
2-digit setting
switch
JS14P-04
JS14P-04/М
0.1-9.9min
1-99min
х6
х60
2-digit setting
switch
JS14P-05
JS14P-05/М
0.1-99.9s
1-999s
х0.1
х1
3-digit setting
switch
JS14P-06
JS14P-06/М
1-999s
10-9990s
х1
х10
3-digit setting
switch
JS14P-07
JS14P-07/М
0.1-99.9min
1-999min
х6
х60
3-digit setting
switch
JS14Р-D JS14Р-DМ
Delay time
0.1s-9.9s, 1s-99s, 0.01s-9.99s, 0.ls-999s, 1s- 599s

- 2 -
1.3 Normal Working Conditions and Installation Conditions
1.3.1 Working environment: the altitude does not exceed 2000 meters; the ambient temperature is not higher than
+40°C and not below -5°C; the voltage variation range of the rated control power supply is 85%-110% of the
rated voltage; Installed in places where there is no explosive medium or the medium does not contain gas or
conductive dust that causes metal corrosion or damage to the insulation free from the rain or snow erosion.
1.3.2 Vertical or horizontal installation.
II. Structure Features and Working Principle
This series of time relays all uses medium-scale integrated circuits. LED light-emitting diode indication. digital
toggle switch preset. featuring with convenient setting. stable and reliable operation. high delay precision. and
small size.
III. Technical Features
3.1 Rated insulation voltage Ui: AC380V
3.2 Rated impulse withstand voltage Uimp: AC2.5kV
3.3 Rated control power supply voltage Us: AC: 380V, 220V, 127V, 110V, 36V, 24V, 12V; DC: 220V, 127V,
110V, 36V, 24V, 12V; AC/DC24V~48V; AC/DC100V~240V.
3.4 The rated operating voltage Ue / rated operating current under the usage category Ie:
AC-15 Ue: AC380V, Ie: 0.95A; Ue: AC240V, Ie: 1.5A; Ue: AC120V, Ie:3A;
DC-13 Ue: DC250, Ie: 0.27A; Ue: DC125V, Ie: 0.55A
3.5 Resistive current Ith: 5A
3.6 Contact capacity: AC250V 3A; (resistive);
3.7 Pollution level: 3
3.8 Setting error: ≤1%;
3.9 Repetitive error: ≤1%;

- 3 -
3.10 Mechanical life: ≥1 million times
3.11 Electrical life: ≥100,000 times
3.12 Cooperation with the short circuit protective device (SCPD): The RT16-00, 6A fuse with “1” type basic
protection is recommended as SCPD; that is, the relay shall not cause danger to the persons or equipment in case
of short circuit, and it is not allowed to work continuously before the repair or replacement of parts. If the fuse
protective device of the different model is selected, the original cooperation may fail.
IV. Outline and Installation Dimensions
Unit: (mm)
8-φ4 holes are for back-panel wiring
Time relay
JS1P, JS14P-D Outline dimensions drawing Device type installation dimensions drawing
(or a 35mm standard mounting rail used)
JS1P-M, JS14P-D/M Outline dimensions drawing Panel type mounting hole sizes drawing

- 4 -
Time relay
Multiple
Panel type mounting hole sizes drawing
JS14P-01~07/M Panel type outline dimensions drawing
8-φ4 holes are for back-panel wiring
Time relay
Multiple
JS14-01~07 Device type outline dimensions drawing Device type installation dimensions drawing
(or a 35mm standard mounting rail used)
V. Installation and Operation Instructions
5.1 Please install the product according to the size of the mounting hole.
5.2 Properly connect the wire according to the wiring diagram. After each wiring terminal is connected. the
connecting wire shall be sleeved with an insulating bush firmly. When installing the plug and socket. please align
with the pins to prevent accidents caused by short circuit of the power supply.
5.3 Check that the power supply voltage must be consistent with the rated power supply voltage of the product;

- 5 -
5.4 Power-on delay type: Please present all required delay time before use. and then turn on the power; at this time
the relay delay starts; when the preset time expires. the delay contact is converted to realize timing control.
5.5 Power-off delay type: preset the required delay time. and then turn on the power; at this time. the relay delay
contact will pull in. and the charging capacitor starts to charge; when the charging time exceeds 5 seconds. cut off
the control power supply of product. and at this time the relay starts to delay; when the delay time reaches the
preset value. the relay delay contact is converted to the release state to realize the timing control; this state will be
maintained until the relay contact pulls in again when the next startup.
5.6 Operation Precautions:
1) Be sure to weld the control line of the terminal block when wiring;
2) It is forbidden to install or dismantle the energized product.
3) The operating voltage of the relay shall be within the rated operating voltage range during operation.
4) The equipment that may cause major economic losses or personal safety is designed to make the technical
characteristics and performance values have sufficient allowance. and safety measures such as double circuit
protection should be adopted.
JS14P-01~07, JS14P device type wiring diagram
JS14P-01-07M, JS14P-M wiring diagram
JS14P-D wiring diagram
JS14P-D/M wiring diagram

- 6 -
VI. Common Faults and Troubleshooting
6.1 Not work after startup
The power terminal is not wired and the wiring is improperly connected or disconnected. and the power supply is
not connected.
6.2 The relay works abnormally after power-on
Check the relay wiring connection and digital setting are correct; check the product for broken line or short
circuit.
6.3 Troubleshooting
In case of failure of product. first cut off the power. and then find the cause of the failure; operate the product
according to the Installation and Operation Instructions after checking that the line works normally.
If the product has the poor quality problem. please contact the local dealer or our company.
VII. Transport and Storage
The product shall be free from the rain or snow erosion or squeezing during storage and transportation. and shall
be stored in well ventilated places where the relative humidity (25℃±5℃) does not exceed 90%. the lower limit
of the temperature is -25℃. and the upper limit of the temperature is +55℃.
VIII. Unpacking and Inspection
Open the outer carton and check that there is the Operation Instruction in the packing box.
IX. Ordering Notice
Please specify the model and specification of the product when ordering. For Any special requirement. please
contact the manufacturer.
X. Company Commitment
Under the condition that users follow the use and storage conditions and the product are well sealed. within 24
months from the production date. our company will provide repair and replacement service free of charge for any
damage or abnormal operation due to poor manufacture quality. A paid repair will be provided if the warranty
period expires. For any damage due to one of the following situations. a paid repair will be given even if within
the warranty period:

(1) Improper operation. maintenance. or storage;
(2) Modified without permission or improper repair;
(3) Damage due to falling off or caused during installation after purchase;
(4) Force majeure such as earthquakes. fires. lightning strikes. abnormal voltages. and secondary disasters;
(5) The electrical life of the product exceeds 100.000 times; The mechanical life is more than one million times.
If you have any question. please contact the dealer or our company’s customer service department.
Customer Service Hotline: 400-826-8008
Certificate
DELIXI GROUP CO., LTD.
Name: Time Relay
Model: JS14P Series
This product complies with the GB/T 14048.5 standard.
passes the inspection and is allowed to be shipped
Inspector: Check 01
Production date: See label on inner box
Manufacturer: Zhejiang Delixi Electrical Co., Ltd.
Address: No. 155. Zhandong Road. Liushi Town. Yueqing City. Zhejiang P/C: 325604
Tel: (86-577) 61778888
Fax: (86-577) 61778000
Customer Service Hotline: 400-826-8008
www.delixi-electric.com
The second edition of this User Manual was issued in Aug. 2021.
This manual suits for next models
14