Cutler-Hammer VAC-CLAD-W METAL-CLAD User manual

1m:n
CUTLER-HAMMER
E
ffecti
ve
12/97
INSTRUCTIONS
FOR
VAC-CLAD-W
METAL-CLAD
SWITCHGEAR
INDOOR
HOUSINGS
1.8.
32-255

-
----------~,-..,.,---
--
1.8.
32-255
'
Page
1
CAUTION
THE METAL-CLAD SWITCHGEAR DESCRIBED S BOOK HAS BEEN DESIGNED ANDTESTED
TO
OPERATE WITHIN ITS NAMEPLATE RATINGS.
OP:RA
ON
OUTSIDE
OF
THESE RATINGS MAY CAUSE
THE
EQUIPMENTTO FAIL, RESULTING IN BODILY
lNJU
D PROPERTY DAMAGE.
PURPOSE
THIS INSTRUCTION BOOK HAS BEEN PREPA
REo-o
...
E..?
ENGINEERS ANO TECHNICIANS INSTALL,
OPERATE, AND MAINTAIN TYPE VAC-CLAD-W S O ·
..
G=.AR. FOR INFORMATION ON THE APPLICATION OF
THISTYPE OF SWITCHGEAR, REFER TO THE PE
:=>,.r-
ANSI STANDARDS AND
TO
CUTLER-HAMMER
APPLICATION
DATA
32-265.
~
DANGER
SAFETY
ALL SAFETY CODES, SAFETY STANDARDS, AND SAFETY REGULATIONS MUST BE STRICTLY ADHERED
TO WHEN INSTALLING, OPERATING, OR MAINTAJNING
THJS
EQUIPMENT.
...
Eff
ec
ti
ve
1
2/97

Page
2
TABLE OF CONTENTS
DESCRIPTI
ON
SECTION 1 - RECEIVING, HANDLING AND STORING
1.8.
32-255
PAGE
1.1 RECEIVING .....................................................................................................
..
.....................................................4
1.2 HANDLING .......................................
....
......
..
.......................................................................................................4-6
1.3 STORING INDOOR SWITCHGEAR .........................................................................................
..
..
..........................7
RECOMMENDED SAFETY PRACTICES.....................
..
..............................................................................................7
SECTION 2 - INSTALLING SWITCHGEAR
2.1 OUTLINE
OF
INSTALLATION PROCEDURE .........................................................................................................8
2.2 DETAILS OF THE INSTALLATION PROCEDURE.............................................................................................8-15
SECTION 3 - ADJUSTING AND TESTING ................................................................................................................15
SECTION 4 - OPERATION
OF
THE
SYSTEM ............................................................
..
.
..
.......
.'
..................................
16
SECTION 5 - INSPECTION AND MAINTENANCE
5.1 SAFETY PRECAUTIONS ..........................................................................................................................
..
.....
....
16
5.2 ACCESS TO SWITCHGEAR PARTS ....................................................................................................................
16
5.3 INSPECTION AND MAINTENANCE SCHEDULE.........................................................................................
..
17-
18
SECTION 6 - LUBRICATION .............................
..
........................
..
...................................................
..
...............
..
....
..
.
19
...
SECTION 7 • RENEWAL PARTS ....
..
........
..
..
..............................................................................
..
.............................. 19
SECTION 8 • A DESCRIPTION OF
SW
ITCHGEAR
8.1 SAFETY FEATURES ............................................................................................................................................ 19
8.2 INTERRUPTER POLE UNIT MOUNTING ..............................................................................................
..
............
19
8.3 RING-TYPE CURRENTTRANSFORMERS ...................
..
........................
....
..
......................................................
19
8.4 AUTOMATIC SHUTTER ........................................................................................................................................
21
8.5 KEY INTERLOCKS ................
..
.
...
........
..
...............................................................................................................
21
8.6
PAN
ASSEMBLY
..
.....................................................................................
..
.....................................
..
...................
22
SECTION 9 - ACCESSORIES -STANDARD..............................................................................................................
22
9.1 ACCESSORIES -OPTIONAL.
..
........................................................................
..
..
...........................................23-24
SECTION 10 -TAPING ...............
...
......................
....
.......................
..
........
..
...............
..
.
..
.................................
..
..
..
24·
30
Effec
tive
12/97

I.
B.32
-255
LIST OF ILLUSTRATIONS
FIGURETITLE
P
age
3
PAGE
1 HANDLING OF INDOOR SHIPPING GROUP
..
................................................................................................6
2 A TYPICAL 5/15
KV
INDOOR BASE PLAN
...
........................................
..
......................................................
...
.
..
9
2 B TYPICAL 27
KV
INDOOR FLOOR PLAN .........................
..
............
...
............................
..
...............................10
2C TYPE 5 KV ND INDOOR FLOOR PLAN .........................................................................................................
11
3 INSERTION OF DRAW-OUT EXTENSION RAILS .........................................................................................14
3 A LIFTING AND SETTING OF BREAKER IN HOUSING .........
..
.
..
.............
..
........
..
......
...
..
.................................14
4 AUXILIARY WITH FUSE DRAWER
IN
DRAW-OUT POSITION ..
...
..
..
.............
..
..........................................
...
15
5 DRAW-OUT DRAWER FOR
VOLTAGE
TR
ANSFORMERS..................................
..
.....................................
..
.15
6 DRAW-OUT DRAWER FOR CONTROL POWER TRANSFORMER.......
..
.....
..
...
...
..................................
..
....15
7 AUXILIARY COMPARTMENT WITH
SHU
TT
ERS ......................
..
...
..............................
..
..
..
....................
..
.
..
...
20
8 CT BARRIER
...
................................................................................
..
.
..
........................................................
..
20
9 BREAKER
PR
IMARY DISCONNECT SHUTTER .........................
..
...........................
..
..
............
..
...............
..
..20
9 A RING TYPE CT'S .......
..
.............
..
...............
...
............
..
......................
..
...
...............
...
..............................
..
...
.
..
.20
10 MANUAL OPENING OF SHUTTER USI
NG
MAINTENANCE TOOL .......
..
...................
..
.....
..
........
...
..
............
21
11
VC
-W SWITCHGEAR BREAKER
PA
N ASSEMBLY .............................
..
..........
..
.......................................
....
.
21
12 A MAINTENANCE TOOL.........................
..
.....
....
....
..
...........
..
.....
..
...
...
..
.............
..
...............................................22
12 B LEVERING CRANK ........
...
....................
..
............
..
.........
..
....
..
...........................................
..
..
..
....
..
...
...........
..
.22
12 D BREAKER LIFTING YOKE .....................
..
.
..
...........
...
................
..
...................................
..
...............................23
12 E RAIL CLAMPS ·
··
···········
···
····...................
..
...
..
....
.....
....
....
....
..
..
....................
..
.................
..
...............................23
12 F EXTENSION RAILS ..........................
..
.........
..
...
..........
..
...........
..
...................................................
..
................23
13 ZERO SEQUENCE CURRENT TERMINAL CONNECTIONS .............
...
..............................
..
..............
...
...
..
..
25
14 A TYPICAL 5
TO
15 KV TAPING CONNECTIONS ..
..
.
..
................................................................
..
...
.........
..
.....26
14 B TYPICAL 27
KV
TAP
I
NG
...................
..
......
...
......
..
...
..
..
...
.......................................
...
.
...
.......
..
...
...
..
......
..
.... 27-28
15 PORTABLE BREAKER LIFTER OUTLINE DRAWING .........................................................
...
.......
...
.........
..
..29
16 TEST CABINET OUTLINE DRAWING .
..
..
..
.
......
.
..
........................
..
...................
..
..
..
..................
..
..............
..
....
30
Eff
ect
ive
12/
97

Page
4
1.8.
32-255ARC
SECTION 1
RECEIVING, HANDLING AND STORING INDOOR SWITCHGEAR
1.1
RECEIVING INDOOR SWITCHGEAR
The switchgear is shipped to the customer as
completely assembled as possible. Depending on the
number
of
switchgear vertical sections it may be
necessary to ship the
sw
itchgear in several groups to
facilitate handling.
VCP-W breakers are shipped in individual containers.
See breaker I.B. 32-255-1 for breaker handling
instructions.
Each switchgear group and all the cartons and crates
are labeled with the shop order number and a shipping
weight. On one of the groups there will be a shipping
packet, securely attached, that contains the shipping
lists and storage and handling drawings.
When the switchgear
ar
rives at the installation site,
check it to make sure all the parts described on the
shipping list have been received.
Do
this before
discarding the packing material to prevent losing parts.
If the switchgear has been damaged, file a claim as
IF:."l•N
soon as possible with the carrier and notify the nearest
Cutler-Hammer representative.
It the switchgear
is
going to be installed as soon as it
has been received, unpack it and handle it accord
in
g
to
the procedure outlined
in
the following paragraphs. If the
switchgear is to be stored, inspect it to make sure the
shipment is complete and undamaged. Repack it so it
will be protected until it has been installed. (SEE
SECTION ON STORAGE
OF
EQUIPMENT.}
1.2 HANDLING INDOOR SWITCHGEAR
Table 1 gives the approximate werghts of the various
combinations of switchgear and the various rating of
breakers. The vertical section refers to the way the
breaker compartment and the auxiliary compartment
are arranged in front of the switchgear.The
combinations are: breaker over breaker B/B; breaker
over auxiliary B/
A;
auxili
ary
over breaker
NB
;and
auxiliary over auxiliary
NA.
Effective
12/97

1.8.
32
-
255
Pages
TABLE 1
TYPICAL WElGHTS (POUNDS)
TYPE
OF
MAJ
, - s
INDOOR
VERT
I
CAL
VERTICAL
RA
GS
SECTION
SECTION
(A
M?E'=1=3
(LESS
BREAKER)
1200 2400
BREAKER
/ 2000 2500
BREAKER
3000 2600
BREAKER
/ 1200
23
00
AUXILIARY
2000 2400
3000
2500
1200 2300
AUXILIARY
/ 2000
2d-OO
BREAKER
3000 2500
AUXILIARY
/ 1200
2000
AUXILIARY
2000 2100
3000 2500
~
TYPE
OF
CURRENT
BREAKER BREAKER
RATING
ELEMENT
ELEMENT
BREAKER
AMPERES
(S
TATIC
)
(IM
PAC
T)
50VCP
-
W250
1200 350 525
2000 410 615
3000 525 788
50
VCP-W350
1200 460 690
2000 490 735
3000 525 788
75
VCP
-
W500
1200 375 563
2000 410 615
3000 525 788
150
VCP
-
W500
1200 350 525
2000 410 615
3000 525 7
88
1
50
VCP-W
750 1200 350 525
2000 410 615
3000 525
78
8
150
VCP-W1000
1200 460 690
2000 490 735
3000 525 788
Effect
i
ve
12/97

Page
6
Lift
in
g members are bolled to the top
of
each shipping
group. Put a crane hook through each of the four holes
to li
ft
and move the group. After the group has been
moved into installation position remove the lifting
members and discard them.
If a crane is not available, move the group Into
installation position
on
rollers. Skids run the length
of
the group. If the group
is
to be skidded sideways, the
front and back skids are enough. If it is to be moved
across its depth (from front to back), put in several short
skids across the depth
of
the group and roll it into
position on these. Jacking Plates may be bolted to the
sides
of
a shipping group to facilitate lifting the
switchgear,
to
place rollers, and slide switchgear in
place
._
These must be sized to handle the heaviest
shippi
ng
group.
1.
8.32
-2
55
NOTE: NEVER MANEUVER THE SWITCHGEAR
DIRECTLY ON THE ROLLERS.
ALWAYS USE THE SKIDS TO PROTECT THE
SWITCHGEAR FROM BEING DISTORTED OR
DAMAGED.
Handle all switchgear whether crated
or
uncrated with
great care.The instrument panel on the front of the
vertical sections contains delicate instruments, relays
and meters that can be damaged by rough handling. If
the switchgear is not put into service right away, cover
it
to keep clean. SEE SECTION ON STORING
OF
EQUIPMENT.
_..,t,,~!--
--
- -
~~-~C;iii"IO,e,,r-
Rear Lifting Angle
~
~-----
-l\r-:-;;,i~-.,,,,.c...---+-- Spreaders (2)
CJ 1
CJ
D
D D D
Fig. 1 Handling of Indoor Shippi
ng
Group
Front Lifting Angle
Un
it Depth X y z
96.25
24
.5
52
.
94
14.
88
86
.25
14
.0 52.
94
14.88
DETACHABLE
JACK
ING PLATES
Rear
Sk
id
,,,,....._
__
Middle
Sk
id
~l-----
Tie Member
Front
Skid
Effective
12/97

1.8.
32-255
1.3 STORING
INDOOR
SWITGHGEAR
Packaging for shipping is not suitable for storage Pa"'
of the original packaging may be discarded when
switchgear is removed from the carrier. Switchgear be
runs, beca_use
of
their open connection ends, are
particularly vulnerable to moisture and dirt during
storage.
Ifthe switchgear must be stored for a while, prepare a
suitable storage space. Keep it indoors
in
a heated
bu
ilding that is clean and dry.The floor should
be
smooth and level to prevent strain and distortion in the
equipment. Be sure the space is well-drained so there
is no standing water. Store the switchgear on its skids o
keep it off the floor and to allow airto move under it
freely. -
Take
steps to protect the switchgear against dampness
cement dust, corrosive atmospheres, and extreme
temperature changes.
To
control condensation, make
sure the equipment is well ventilated. Install temporary
space heaters if necessary.
Switchgear should be checked periodically for
a,ny
signs
of deterioration.
Storing the switchgear outdoors is not recommended.
It is the responsibility of the purchaser to assure
protection during storage.
STORAGE
OF
SPARE PARTS AND MISCELLANEOUS
EQUIPMENT
All parts should be stored with the same care as the
main switchgear.
Summary
of
storage procedures:
1.
Check the ventilation of the switchgear itself and of
protective coverings. Serious damage can result from
a non-ventilated tarpaulin.
2. Check the ventilation of enclosed storage areas of
buildings.
3. Check for adequate heat, when in doubt provide
heat.
4. Check for distortion.
5. Check for damage and standing water.
6. Check weather protection including open doors,
windows, drafts, etc
_.
·
Effective
1
2/97
oc
door storage.
set
:>e"odically.
Page
7
;"
.::..
CC~
DETAILED INSTRUCTIONS ON STORING
C-
G=A.R
REFER TO DRAWING 7009214, A
=-
:-iE
'JRAWING IS ATTACHED TO EACH
:: =S
~TC
HGEAR.
& DANGER
RECO
E
DED
S
-:TY
PRACTICES
The only peo e s'" ""'1 be allowed to install,
operate,
or
nar:a.
...
,..
ec
...
·oment are those who meet
the quali
1ca
'?:J-
-ere":S
described in the National
Electr
ic
Sa•e
Cooe
To
perform o - on
·-
l)'P8
of equipment, one must be
trained and
exoe
erceo
woncmg
with high-voltage
circurts. e,
~
o
:le~
1ar
with the construction
and ope
of
tt s equprnent and aware
of
the
hazards
Before a.
e'.T'p·
ng
·o
do
any maintenance, always be
sure o de-energize botn tne primary and secondary
circu
ts.
Never leave a breaker in an intermediate position in its
compartment. Always crank the breaker into the fully
connected
or
withdrawn position.
Before removing a bolted-on cover first make sure that
all the circuits have been de-energized.
Never try to disconnect
or
open the secondary circuit of
a current transformer that
is
carrying load current.
In
this situation the transformer develops a dangerous
high voltage. Before attempting work eitherde-energize
the circuit by opening the breaker or short-circuit the
secondary of the current t
ra
nsformer.

Page
8
SECTION 2
INSTALLING INDOOR SWITCHGEAR
2.1
OUT
LINE
OF
INSTALLATION PROCEDURE
1. Prepare the installation foundation. It is
recommended that fl
oor
channels be imbedded in
the foundation to maintain a level surface.
2.
Al
the factory the switchgear system may have
been divided into groups to facilitate shipping. At
the installation site the groups must be rejoined
to
form the switchgear system. Align the groups, side
by
side, on the
ti
e bolt holes.
3.
Bolt the groups together through the tie bolt holes.
4. Bblt or weld the base members of the vertical
section frame, front and rear, to the foundation
channels.
5. Remove all shipping braces.
6. Connect the ground bus.
7. Install
the
primary bus supports, insulated phase
conductors, and rubber snubbers removed for
shipping.
8. Reconnect the wiring between shipping groups.
Run the control wiring for remote apparatus through
the conduits in the foundation (
or
on top of the
ver
tical sections).
9. Replace the metal barriers in the bus
compartments.
10. Connect the main power cables and fully insulate
the terminals for the voltage class (SEE SECTION
10
& FIG. 14 FOR GUIDELINES).
11
. Replace the rear covers
on
all the vertical sections.
12
. Check the operation
of
the levering-in system in the
breaker compartments.
13
. Check the potential transformers and the control
power transformers in the auxiliary compartments.
14. Perform loading check on both control and primary
circuits to assure the system is ready for operation.
2.2 DETAILS OFTHE INSTALLATION PROCEDURE
1. PREPARE THE FOUND
AT
ION
REVIEW THE INSTRUCTION.BOOKS AND
DRAWINGS
CA
RE
FULLY.
A. Locate the switchgear so there is enough aisle
space at the front and rear of the system.The
amount
of
space recommended is shown in Fig. 2.
1.8.
32-255
B. Leave enough space so the doors can be opened
and the breakers and transformers can
be
pulled
out for inspection and
ma
intenance. Leave enough
space at the rear so there will be room to install the
cables and
to
perform whatever inspection and
maintenance that may be necessary.
THE MINIMUM CLEARANCES ARE SHOWN IN FIG. 2.
REFER TO THE FLOOR PLAN DRAWING FURNISHED
WITH EACH ORDER.
C. Make sure the foundation is flat and level.
D. Design the foundation so
it
will be strong enough to
support the weight of the switchgear without
sagging. Table 1 gives the weights
of
the various
ratings
of
switchgear and breakers.
Be
sure
to
take
into account the shock
or
impact weight that occurs
when the breaker trips and when it closes.The
impact weight is 1.5 times the weight of the breaker.
The weights
in
the tables are only an approximation.
The actual weight will vary, depending on the type
and
th
e amount of equipment in the switchgear. Use
adequate safety factors.
E. The recommended foundation consists
of
steel
channels embedded in a level concrete floo
r.
The
channels must lie in a flat and level plane. (A slope
of 0.125 inch in 3 feet in any direction is
acceptable.) In no case may the non-supporting
areas of the foundation be higher than the tops
of
the steel channels.
The anchor bolts, channels, and other materials are
to be furnished by the purchaser
of
the switchgear.
A 4-inch structural channel is recommended as the
minimum size for the average indoor switchgear
system.
If unit substation transformers
or
high voltage
switches are
pa
rt of the Installation, be sure the
floor steel underthe transformer conforms
to
the
specifications
of
these manufacturers.
F. Install the conduits in the foundation.
When
th
e primary and secondary cables enter the
switchgear from below, the conduits that carry them
are embedded
in
the foundation.A floor plan
drawing is furnished with each order. Use this
drawing to determine the conduit layout, the circling
of
the steel around single phase conductors rated
600 amps
or
more should
be
avoided to prevent
overheating due to induced currents.
Effective
12/97

1.8.
32-255
TYPICAL
~,#$##&
0
LIN(
CO
MPT
B
US
CO
HPT
B
KR
CON
TR
Cll
CO
H
PT
961'5
J
E,
Ml
'I
.
..
so
..
56
3
:X.,""X)
:J 3~ E PLAN
---
__;~
32
MIN.
___
__,.
0
0)
FIG. 2A 5/15
KV
TYPICAL FLOOR PLAN
Effe
c
tive
12/9
7
0
SUGGESTED
LOCATIONS f'OR
.
:lO
I
NCH
SOLIS
CR V
[LDI
NG
G\
Sf.COI
DARY
CO
N
TR
OL
\V
VJRl'II,;
CClNDU
I -
OPEN
JN~S.
CONDUJ
r PROJECTION MUSl
NDT
DCCED I I
NCk
.
,;,.
HINIHUM rRONT
CL
E
ARANCE
~/
IIHEN
USING
CUT
L
ER-HAMMER
PORT~BLE
LI
rT
ER
('.;'\
MINIMUM
LEr-
OR R!G
HT
V •IHCi(D PANEL
CL
E
AR~NCE
©
.COK
DED
H
INI
H
UM
<>:..-.
Cl.[ARANCE
f:\
r1
..
:s,co
Ftl1.JNDA
TION
'=.}
::..P-ta:
1'-'C.I.UDI 'IG
r
..LIPS~:
MUST
BE
T
...
T
Al:
U:VEL
AND
,..
~.£
P\J,'<
{'::';\
•~
S'U....
I•
USED,
~
,.LT
oCl"
O:ca:D
lHIS
:loC'C!J::N
:El>
SVITCHGEAR
Q
rt
IS.0
TQJ',DATIOH
\:!/c
.
,~_i~
36
!N01
::LC...
~
EXTEND
Gi
IP9'J,.-...:,r
CH.;,/)
t.CN])UJ
1
~
;,v-_:c:;
11:N
·s
1 'CJT
o=
z
;..a<s
SEE
S>O'
.,:,lC;o-
!~
~LA'I
r:,;
~1,.
Lct.,\TlO,,.,S.
r;;,.~S~D
~
~
s; o,.s PROVIDED
A!:
S:-0". ,
Et
Sf~B:ll.
ON
S-tJ>
[R:,CD
~C-IIJ'<A.
S X
!t
,'S
€,
~
J
CH
~
1 I
MJM
C~M
"EL
SUPP_
IE
D
BY
CUSTMER.
t:7\
:':JJF
....
"!IJH
ll"t:CR
~
S,.l""OC£~
~T
BE
, •
Lc..s-
3 ,NCt<S
l"ICJ'
ALTERNATE
SECCl'4=t
CONDJll
LOCAT
!DI\
TCP
ENTRANCE
l<NIJCK[)JTS
rOR
I IN.
OR
1.2:S
CONDUI
TS
.
_l
6
..
__
___,_
7
Pag
e9

..
Page
10
Ll1'(
CC><PT
BUS
(
[NP!
l!KP
C
OMl>l
TYPICAL INDOOR BASE PLAN
~,,//
f
,,/
,,/
,'.~///
,,///
4
G)
36
MIN
96
25
32
MIN-
-
--+-
---
26
-----+-32
MlN
- -
--I.
0 8
70
MIN
0
FIG.
28
27
KV
TYPICAL INDOOR FLOOR PLAN
1.8.
32-255
([)
sur.Gcs-
rn
L
JCAr101s
rOR
5C
:
NCH
BOLTS
OR
V[LDING
/';'\
SECONDARY
CCJNTRCl.
\::.)
JIRING CCINOUJl
OPEN
I
NGS
,
CCN
DU
IT
PROJEC
11
ON
..US1
~OT
EXCCCD
I I
NCH.
r.:\
MINIHUII rRCN
I.
CLE
A
RANCE
\:.,I
WHEN
USING
1w)
PCRTADLE
Ll >T(R
0 M
:N
IHU"I LEFT
CR
RIGHT
HI
NGE:D
PANEL CL( A
Rl'NC[
0
R£C:ll*£1'0Ct
IIINIHJ>
REAR
CLEARANCE
© f
.N
IS~D
FC1JNDA1
,r,-,,
SURrAC,
t:NCLUDING
rLOJR
1TEEL>
MUST
BE
FLAT
AND
LEVEL
AND
:N
TRJE
PLANE
r:;).. FLOOR STEEL
I,
USED
,
V,Y
HUST
NJT
(XC[El)
THIS
DIHCIISJO,,
UNDER
S\IITCHGEAR
~
F"INISH,
D fCUNDATl:JN
'5'cv1THIN
05
INCH
CL[<UWICC>
~UST
(Xl[ND
U
NlJCR
sv1-0iC£aR
MlNl"IUM
1.50
IN:H
IC
MAXJ"""
3 Jl'ICH(S
17:"\
P~lMARY
( H V. )
CONDUll
\V
PRC.JCCT
JIN
MUST
,o-
EXC£(0
2 INCHES.
SEE
SHCJ'
!JlD[R
DAS[
PL
AN
roR
CONDUIT LOCATIONS.
r.;-,,
CUSl
OME:R
' S
GROUNO
\.:J
PROVISIONS.
PROV! D[O
AS
SHO
JN
BY
SY~IIOL
Ill<
SHOP
CJRDCR
ScCTIDNAL
SIDE
Vl[VS
@ 4 I NCH
MI
\I I
MUM
CHANN
E_ SLPPL!ED
BY
CUSTOMER
.
ALTERNAT(
SECO
NDARY
CCNDUll
LCX:AT!CN
TOF (NTRANC.E
KNOCKOUTS FOR I
38
IN
CR
I
75
C(),IDUI TS
Effective
1
2/97

1.8
.
32-255
Page
11
LINC
C:J~PT
B
US
COHP'
BKR
9625
0
26
HIN.
• • 50
19
I 25
56
TYPICAL IND
OO
BASE PLAN
22
--
-
--<
3
IJL
56
26
J
22MIN
©
70 H
lf\
0
FIG.
2C
5
KV
ND
TYPICAL FLOOR
PLAN
Eff
ec
bve
12/97
O SU
GGES
T
ED
LOCATIONS
ro
P.
50 lflCH
BDL
TS
QR
SELCINC,
(';\
SECONDARY
Cil'ITROL
\::..)
VIRING CO.DU
il
OPEf\lN
GS
:
ONO
U
IT
PROJECT ION H
UST
'IDT
EXCE£D
I I
NCH
(';\
'1
:NIMU1 rRONl
CU
ARAl'C
(
~
VHEN USING
CU
'L[R-HAMM[R
DQRTA
BLE
L !I
T[R
8
©
'1
INI
HU1
LffT
OR
RIGHT
1ltr.,(0
PANEL
CLL
ARAllC(
~C!JH
'IDIO
[D
M
INI
MUM
'EP~
C-E
A~AN
C(
Q
q.,1Sli0l
~OU
'IDATION
\.:.;
~ACE
( 11\CLLDII\G
r~
ST
E!:L
> t'UST
3E
i L
Al
A"'IID
_[VE.L
~ND
I
"1JE
PLIINE
r.;:,.
rLOCP
STEQ
Ir J S
ED
.
\:Y
~I
NOT
E>CEED THIS
Jf'4(>,SID1
UND
ER Siil TC'iGEAR
r.:;;,..
rf
.SrED
rOU,,DATIQN
\:..:J
c. J
..
"41N
06
.
HCH
CU::AP
...
C:
..us-
CXT!:ND
/;;\_
P',:;l
..
•'i
Y
(M
I , C°"DU1 T
'.::.,/
Pq()JEC'
10,,
HUST
1\
01
EXCC!::I
2 INCHCS SEE
S,<J!> ORDER B"SC: Pl.AA
r~
CO.!IUI-LDCATID~S
r;;\
CVS
'04CP'
S
:.ROUND
\J
PPOVIS;Cl'IS.
PROVIDCD
AS Sl-0\/N BY SYMilDL
[),I
Sl'IJP OPDEP seer
l(J,jl\l
~!DE
v:cus
(v
4 INCH MINIM
UM
CHANN
EL
SUPPL
Tr
D
BY
cus-OMER
.
,.;.,
rouNDAT ION
UNDER
~
SUI
TC
,<
G[AP
'1UST
BE
AT
LEAST
J lNC.<ES
THICK.
AL
T[R
NATC
SECO
NDARY
CrtiOL
IT
LO
C
AT
!
[),j
T
OP
ENTRANC(
KNJCKOUTS
raR
I I
'I
DR
I
25
CONDUI
-s

'-,
Page
12
2. ALIGN THE SHIPPING GROUPS SIDE BY SIDE ON
THE
FOUNDATION.
A. Remove the crating and packaging material from
the groups of switchgearthat are going to be
installed.
B.
Let the shipping skids remain on each group until
the group has been moved into i
ts
final installa-
tion position. (The skids help protect the
switchgear and reduce the risk that it will be
damaged
or
distorted during the move.)
C. If an odd number of groups is to be installed,
install the middle one first. Then install the other
-groups, working outfrom the mi
dd
le.
If an even number of groups is to
be
installed, start
with either group on either side of the middle shipping
break.
If a unit substation
or
a
power
center is being in-
stalled, line up the powertransformer and the adja-
cent switchgear group first.
Set
them in the position
called for
on
the drawing of the base plan.Then
install the rest
of
the groups.
D. Handling the switchgear by crane is the preferred
method.
Move the first group into position. Line up the bolt
holes in the base
of
the vertical sections with the bolt
ho
les
in
the steel channels in the foundation.
A few inches in front of the line-up draw a base line
along the length of the intended location
of
switchgear. As
the
groups are maneuvered into place,
keep the front of each group parallel to the base line.
E. A bolt
at
each end of the wooden skids holds
them
to
the base ofthe group. Lift and remove
the bolts, and discard the skids.
F.
Set the group into its installation
pos
ition. Use a
level
to
make sure the group is level both across
its width and along its length. Use a plumb line to
make sure the group is plumb.
(To
level
or
plumb
the group use shims
arthe
points where the
vertical sections will be bolted
to
the floors.}
Move each group i
nto
po_sition and repeat the
preceding steps.
G. If no crane is avail~ble the groups may be moved
on
the skids and rollers.
1.
8.
32-255
3. BOLT
THE
GROUPS TOGETHER THROUGH THE
TIE
BOLT HOLES.
A. Remove the back covers from the vertical sec-
tions at the shipping group. Insert and tighten tie
bolts in the rear upright members.
8. Open
the
front panels on these vertical sections.
Insert
and
tighten tie bolts between the front
upr
ight members.
4. BOLT OR
WELD
THE ENTIRE SWITCHGEAR
SYSTEMTO THE CHANNELS IN THE
FOUNDATION.
Checkthe system
aga
in to make sure
it
is level and
plumb.
5. REMOVE ALL
THE
SHIPPING BLOCKS
OR
BRACES.
A.
Examine all
the
meters, relays, etc. and remove
any shipping blocks or braces.
The
time dials on
the relays are set at zero
in
the
factory
so
the
rel
ay
contacts will
be
closed during
shipping.
6. CONNECT
THE
GROUND BUS.
A.
The
ground bus in
the
switchgear is assembled in
sections.There is a
joint
in each housing.
Solderless terminals are provided on the ground
bus (See the shop order drawing for their loca-
tion). Use these terminals to connect the ground
bus
to
the station ground. Make the connection
as direct
as
possible. It should be large enough
to
carry
the
ground fault current of the installa-
tion. Never house it in a metal conduit.
8. The standard ground bus is a .25-inch X 2-inch
copper bus
bar
bolted to the cross members
of
the frame in the bottom of each enclosure.The
ground bus runs through the center of each
section through the length
of
the entire
switchgear system.Where the system is split
for
shipping, a splice plate (and hardware) is fur-
nished
to
bridge the shipping break when the
system is installed.
NOTE:THE IMPORTANCE
OF
ADEQUATE
GROUNDING
CANNOT
BE
OVERSTRESSED. FOR
THE DESIGN AND INSTALLATION
OF
A GROUNDING
SYSTEM REFER
TO
"ELECTRIC POWER
DISTRIBUTION FOR INDUSTRIAL PLANTS"
Effective
12/97

1.8.
32-255
(IEEE STD.141);"GROUNDING
OF
INDUSTRI
AL
POWER
SYSTEMS
" (IEEE PUBLICATION
141
.
FORMERLY AIEE 953); AND "THE NATIONAL
ELECTRIC CODE
",
ART
I
CLES
100,
200
, AND
2SC
FOR GENERATING STATIONS AND LARGER
SUBSTATIONS,
THE
GROUND
RESISTANCE S
HOv
.........
BE
ONE
OHM
OR
LESS. FOR INDUSTRIAL PLA S
AND
SMALL SUBSTATIONS, THE GROUND
RESISTANCE SHOULD
BE
LESS
THAN
FIVE
OH
S.
(THE NATIONAL ELECTRIC CODE STATES
THATTP::
GROUND
RESISTANCE SHOULD NEVER EXCEED 25
OHMS
.)
7. RECONNECT
THE
HI
GH
VOLTAGE
BUS
WrER
::
IT
WAS DISMANTLED BETWEEN GROUPS.
A. Remove the horizontal and vertical
meta
l
ba-ne~
from the cable compartment. Remove the
ma
...
bus barrier. (Also remove
any
other
componeMs
such
as
potheads, surge suppressors,
etc
.
tha
·
interfere with access
to
the bus compartme1:t.
B. Obtain the section
of
bus th
at
was re
mo
ea
c
separate
the
groups for shipping.
Ea
ct,
SectxYI
s
labeled and shipped in the carton w1
t!l
e
details.
C.
The
surfaces
in
the bus
jo
ints are n
or
s Iv
er
plated. Clean the plated surfaces
of
the
bus
section
by
brushing them lightly with crocus cloth
only if necessary.Then wipe clean.
D. Slide the section of bus through the supports in
the side of the vertical section. Slide the rubber
snubber along the bus until it fits inside the
opening in the bus support.
When
the bus
se
ction is disconnected for shipping, the
splice plates and hardware are l
eft
bo
lted
to
the
end
of
the bus in each
of
the adjoining vertical secti
ons
.
Sandw
ic
h the end
of
the
disconnected section between
the
splice plates and fit the other end
of
the section
be
tween the splice plates on the end of the bus in the
adjacent section. Boltthe splice plates together on each
end
of
the bus section.
Repeat these steps for each section
of
bus
at
each
shipping break.
Tighten the
bo
l
ts
in the splicl= plate to the torques
shown in table 2. ·
Cover joint with insulating
boot
(or tape) provided.
8. RECONNECT
THE
WIRING WHICH WAS
DISCONNECTED AT
THE
FACTORY FOR
SHIPPING. THE WIRING IS LABELED.
A. Connect t
he
wiring to the remote apparatus and
to
the terminal blocks mounted within the front
of
the vertical sections.
Elfective
12/97
9
R::PLA
CE
THE METAL BARRIERS AND
AN
Y
OTH
ER
PARTS THAT MAY HAVE BEEN
R=M
OVED TO
GIVE
ACCESS
TO
THE
BUS
COM
PARTMENTS.
) CONNECT
THE
MAIN POWER CABLES.
Page
13
Before connecting a cable, determine its phase.
"'lle
swi
tchgear
system is usually supplied with
connec
tions for phasing
1-2
·3
left to ri
ght
(viewed
ram the front). Check the shop order drawing to
make
sure because
somet
imes another phasing
ay
have been specified.
3 I two systems are to be
para
ll
eled, make sure
e phase rotation and the phase angle a
re
the
same.
Th
ey
must
be
the same to prevent damag-
~
the equipment.
The
phase rotation must
conform
to
the
phase rotation on the shop or
der
drawing
so
that
the instruments, meters, and
relays
will operate
properly
.
C. Vlhe'l forming cables
to
fit inside
th
e cable
compartm
e
nt
. avoid bending it sharply
or
kinking
ai<e
sure
it doesn't re
st
on
sharp
corners
or
edges
that could
dama
ge t
he
insulation.
Teble 2 • BoltTightness for Bus Connections
Bolt Material Torque In Foot-Pounds for Bolt Size
.25-20 .31-1B .38-16 .50-
13
.62-
11
High Strength Steel 5 12
20
50
95
Sil
icon
Bronze 5 10
15
40
55
D.
Follow the instructions of the
ca
ble manufacturer
to determine
what
minimum bending rad
ii
is
permitted. Fo
ll
ow
the
instructions on insulating
the joints so the insulation will ta
per
properly
through
the
cor
rect gradient.
Th
e insulation will
vary
with the type and size
of
cable
and
with the
service voltage for which it w
as
des
igned.
E. Solderless connectors are usually furnished.
The
connection must be insulated according to the
recommendation
of
the cable manufacturer.
F. If potheads
or
other
types
of
terminators are
furnished, follow
the
instructions of the
manufacturer when connecting
the
cable to them.
U
se
the flexible connectors to connect the aerial
lugs
to
the
co
nductor
s.
This will keep strain oft
the insulators of
th
e pothead
or
the
termina
t
or
.
Tape
(or
otherwise insulate) the entire
joint
(incl
ud
ing
the
flexible connectors).
SEE SECTION 10.

Pa
ge
14
G. If zero sequence current transformers are us
ed
,
pass the power cables through the transformer.
Connect it
to
the terminals
or
to a pothead (See
standard drawing 7008222
or
Figure 13).
11
.REPLACE THE REAR COVERS ON A
LL
THE
VERTICAL SECTIONS.
12
.Insert draw-out extension rails per figure 3 to install
breakers.
13.Install the breakers per figure
3A
using optional
portable lifter shown,
or
other device.
14
.Test breaker and cell interface persection 4 of
breaker I.B. 32-255-1.
15.Check the voltage transformers control power
transformers and draw-out fuses in the auxiliary
compartments.
A.
The transformers or draw-out primary fuses are
mounted
in
separate drawers
in
th
e auxiliary
compartments. (See figures 4,5, & 6.) They are
adjusted in the factory and shipped installed in
the switchgear.
B.
Insert extension rails into each si
de
of the
auxiliary compartment
per
figure 3.Turn the two
drawer handles and pull the drawer out
of
the
compartment.tRollers on the sides
of
the draw-
ers ride on the extension rails
.)
C. Check to
ma
ke sure the primary contacts and
secondary contacts are engaged when the
drawer is closed. Use the "lighting out"
or
"ring-
ing" method.They should engage when drawer is
with
in
1.0 i
n.
of being closed.
D. Check the fuses for continui
ty.
Make sure there is
proper contact in the fuse clips.
E. Suspended from inside the top
of
the compart-
ment are three flexible, grounding straps. As the
drawer is pulled open watch insi
de
to make sure
they contact the fuses and ground them.
F.
Make sure the mechanical interlock (or the key
interlock) is working properly for control power
transformers. When the interlock is working, it
should be impossible to pull the drawer out
without first opening the main secondary breaker.
FIG.3 INSERTION
OF
DRAW-OUT
EXTENSION RAILS
1.8.
32-255
FIG. 3A LIFTING
AND
SETTING
OF
BREAKER IN
HOUSING
Effecti
ve
12/97

1.
8.
3
2-255
FIG. 4 TYPICAL AUXILIARYWITH DRAWERS
IN
DRAW-OUTPOSITION
FIG.5 DRAW-OUTDRAWER FOR
VOLTAGE
TRANSFORMER
Effe
ctive
1
2197
FIG. 6 DRAW-OUT DRAWER FOR CONTROL
POWER TRANSFORMER
& DANGER
SECTION 3
ADJUSTING AND TESTING
Page
15
1. After the switchgear has been installed and
connected to the apparatus it is to control, give it a
final check before it is put into service. (Make sure
the apparatus being controlled is not connected to
the system while the tests are being carried out.)
The testing equipment will depend on the size and
type of installation. Use portable voltmeters. Rig up
some simple device for "ringing "or"lighting out''
circuits.
2.
Examine all wiring circuits to make sure they have
not been damaged or loosened during shipment
or
installati
on
.
3. Make sure all the connections are correct before the
equipment is operated. "Light out" connections
between the switchgear and remote apparatus such
as instrument transformers, auxiliary switches and
remote control and interlock circuits.
4. Coordinate the settings of the relays with other parts
of the system in accordance with the standards or
operating practice of the purchaser.

Pag
e16
5. If the covers are removed from meters,
re
lays,
or
other devices for installation or test, handle them
carefully. Replace the covers as soon as po
ss
ible to
keep outdust and dirt.
6. Perform a loadi
ng
check of the control c
ir
cuits.
A. Before energizing the control circuits, check the
control bus with an ohmmeter to make sure there
are no short circuits in the control wiring. If an
ohmmeter is not available, conne
ct
a small fuse
in
ser
ies with the source of the comrol power.
This will protect the control
wiring
against dam-
age. (The fuse should be one-'ourth
th
e normal
rating
of
the circuit.)
& DANGER
SECTION 4
OPERATION
OF
THE
SYSTEM
1. Install the circuit breakers and check their operation.
2. Study and be sure to understand the diagrams
furnished
wi
th each switchgear system.
3. NOTE: AS CHECKS ARE BEING MADE THE
BREAKERS SHOULD BE
IN
THE TEST POSITION
WITH THE SECONDARIES MADE
UP.
4. A green light on the hinged instrument panel on the
front
of
the breakercompartment shows the breaker
is open. A red light shows the breaker is closed. In a
D-C control scheme the red light supervises the trip
coil and indicatesthe trip coil circuit has continuity.
5. The details
of
the breaker control schemes vary from
o
ne
installation to another. They comply with the
requirements set forth by IEEE, NEMA, and ANS
I.
All of the schemes are designed to coordinate
electrically with the mechanical design of the
breaker. & DANGER
SECTION 5
INSPECTION AND MAINTENANCE
5.1 SAFETY PRECAUTIONS
When inspecting, repairing, and performing mainte-
nance on metal-clad switchgear, the fact that dangerous
voltages may exist must be kept in mind; and precau-
tions must be taken to ensure that personnel do not
come in contact with energized high voltage parts.
F
ai
lure to do
so
could result in personal injury or
property damage.
1.8.
32-255
SOME COMMON GENERAL PRECAUTIONS FOR
HIGH VOL
TAG
E WORK ARE:
1. All connections should be considered energized until
the crew expecting to work on them is assured that
the circuits are de-energized, and until every pos-
sible precaution has been taken to see that there is
no chance
of
a circuit being energized while the
crew is working.
2. Switches which have been opened to de-energize a
circuit to perm
it
work on equipment should be locked
or blocked open and a suitable visible warning
device placed on them.
3. Do not work on parts normally carrying current
at
high voltage until these parts have been discon-
nected and grounded to the ground bus. Provision
should be made by the purchaser for connecting
adequate flexible ground leads to every part
of
the
switching equipment.
4. A good
an
d
re
liable ground connection is necessary
for every switchgear installation. It should be of
sufficient capacity to take care
of
any abnormal
condition that might occur on the system and
sh
ould
be independent of the grounds used for any other
apparatus.SEE GROUND BUS CONNECTIONS.
& DANGER
5.2 ACCESSTO SWITCHGEAR PARTS
1. HIGH
VOLTAG
E PARTS
VAC-CLAD-W METAL-CLAD SWITCHGEAR
is
designed so that internal compartments provi
de
metal isolation between the circuit breaker compart-
ment, the main bus, and the primary line termina-
tions. Access to high voltage parts is provided by
removable covers and barriers which should not be
removed unless the parts to be exposed
ar
e de-
energized.
2. MAIN CONTACTS AND CURRENT
TR
ANSFORMERS
Both the station
ary
main disconnecting contacts and
the
ri
ng-type current transformers are located behind
the glass polyester
CT
barrier.
Upper and/
or
lower contacts and transformers are
easily exposed (See figure 10). For this reason
caution must be exercised. Do not expose any
contacts
or
transformers
un
less all upper and lower
high voltage parts are de-energized.
Fa
ilure to do
so
could cause personal injury
or
property damage.
E
ffective
12/97

1.8.
32-255
3. DISCONNECTING TRANSFORMERS AND FUSES
Simply opening the drawer automatically discon-
nects and grounds the moving high-voltage parts.
Shutters automatically cover the primary discon-
nects.
CAUTION: DO NOT
ATIEMPT
TO REMOVE THE
BACK,COVERS, THE DISCONNECTING ASSEM-
BLIES OR
SHUTIERS
UNLESS THE HIGH
VOLT-
AGE CIRCUITTO THE COMPARTMENT IS DE-
ENERGIZED AND PRECAUTIONS TO PREVENT
RE-ENERGIZINp HAVE BEEN TAKEN. FAILURE
TO DE-ENERGIZE
THE
CIRCUITAND TO TAKE
PRECAUTIONS TO PREVENT RE-ENERGIZING -
COULD RESULT IN BODILY INJURY OR ELEC-
TROCUTION
. WHEN ENERGIZED, CIRCUIT
CARRIES LETHAL HIGH VOLTAGES.
4. CONTROL EQUIPMENT
With the exception of apparatus such
as
curre
nt
transformers and rear mounted heaters,
co
ntrol
equipment and wiring is generally accessible
wiihout
exposing high voltage parts.
& DANGER
5.3 INSPECTION AND MAINTENANCE SCHEDULE
To
assure high quality service, a definite maintenance
schedule, systematically followed, is essential. Plant,
operating, and local conditions vary to such an extent
that the schedule must be prepared to suit
the
condi-
tions. However, the following general requirements
should be helpful in setting up the program.
CAUTION: BEFORE
ATIEMPTING
ANY INSPECTION
OR MAINTENANCE BE SURE THAT
ALL
PRIMARY
AND CONTROL CIRCUI
TS
HAVE BEEN DE-ENER-
GIZED AND GROUNDED AS REQUIRED
AND
THAT
PROPER STEPS HAVE BEEN TAKEN TO
BE
SURE
THAT
THEY
WILL REMAIN DE-ENERGIZED UNTIL
ALL WORK IS COMPLETED. FAILURE TO DO SO
COULD RESULT IN BODILY INJURY OR ELECTRO-
CUTION.WHEN ENERGIZED, CIRCUIT CARRIES
LETHAL HIGH VOLTAGES.
1. INDIVIDUAL DEVICES
The maintenance schedule for individual devices
such
as
circuit breakers, relays, etc. should be
based upon recommendations contained
in
the
individual instruction book for
the
device. These
operations should be coordinated with
the
overall
program to result
in
the least operating
inconvenience and circuit shutdown.
E
ff
ective
1
2/
97
Page
17
2
OV
ERALL INSTALLATIONS
n e switchgear installation should be given a
t
'"IOrou
gh overall maintenance check at
the
end
of
.
,..
e first year in service because it provides an
opport
unity to evaluate conditions at an early point
in
·, e fe of the equipment. Where conditions are
ab
'lOrmal, more frequent inspection and
ma
nt
enance is necessary, where conditions
::.rra
,t.
a
lo
nger period of time between
- r
·e,ance
periods may
be
used.The following
_ _ '"e aaention:
-
3'..5ES
~
rn
CONNECTIONS
:).:
::-e
~
ze
:>
rim
ary
circuits and remove cover
: "·
:s
'-Y"'
• e
pnmary
compartments. Before
Ear. ;g
ta
•
:.e
-
=.
GGER" readings between phases
er.
o ;r
nd
'lS08Ct for signs of overheating
or
ea
•e'leO
"SU
a·
O'l
. ~em
ov
e dust from buses,
corr
ectlO'lS. suppor.s
and
enclosure surfaces. A
v
aCUJm
cieaner with a long
no
zzle will be of assis-
~ce
.Wipe clean with a warm soap water solution,
w1o
e d
ry.
After buses have been dusted and wiped clean, take
"MEGGER" readings again between the buses and
ground and between phases. Keep a record of these
readings for future reference in determining when
trends
oc
c
ur
that would indicate a lowering of the
insulation resistance.
Periodic high potential tests are
not
required and are
recommended only after repair of high voltage buses
or
installati
on
,
or
when the trend
of
megger readings
indicates it to be advisable. This field test should be
made before the
ma
in cables are connected and
sh
ould not exceed 14.25 KV, 60
HZ
, 1 minute, for
4.
76
KV
sw
itc
hgear
;
27
KV, 60
HZ
, 1 minute, for 8.
25
KV
and
15
.0 KV
sw
itchgear; and
45
KV,
60
HZ, 1
minute, for 27 KV switchgear.Transformer primary
fuses should
be
removed
and
surge protective
devices such
as
capacitors and arresters
disconnected during high potential tests.
4. MAIN DISCONNECTING CONTACTS AND
SUPPORTS
Remove each break
er
from its co
mpa
rtment.
De-energize primary circuits and expose primary
contacts and their supports. Wipe clean with a cloth
moistened in a non-flammable solvent. Inspect for
abnormal wear or overheating. Discoloration of the
surfaces is
not
harmful unless corrosion
due
to
atmospheric conditions is severe, leaving deposits
on
the
surface. If necessary, these can be removed
by a light application
of
crocus cloth. Check each
breaker while it is out of the housing for all items
recommended in the instruction book applying to
that particular type
of
breaker. SEE INSTRUCTION
BOOK 32-255-1.

Page
18
5. OTHER DISCONNECTING CONTACTS
Inspect all primary and secondary disconnecting
contacts such as those on draw-out transformers for
abnormal wear, fatigue, or overheating. Replace if
necessary. Otherwise treat the same as main
disconnecting contacts above.
6.
CONTROL CONTACTORS
Contacts should be inspected and dressed or
replaced when the surface becomes pitted. Unless
repetitive duty has been experienced, little attention
should be required.
7. INSTRUMENTS, RELAYS AND OTHER PANEL
MOUNTED DEVICES
Individual devices should
be
maintained according
to
the specific instructions supplied for each device.
Remove all relay covers and inspect the interiors for
dust ordirt. This operation can most readily be
performed
by
relay test personnel
dur
ing period
relay tests.
8. SECONDARY WIRING
Check all wiring connections for tightness including
those at the current and potential transformers
and at the terminal blocks where circuits leave the
switchgear. Make sure that all secondary wiring
connections are properly connected
to
the
switchgear ground bus where so indicated.
9. MECHANICAL PARTS
Visually cheak and manually operate mechanical
moving parts such as the shutter,TOC and MOC
switch assemblies, the position interlock, hinged
door
s, and the draw-out features
of
the transformers
and fuses. Examine mechanical mating parts such
as the breaker secondary contacts blocks, side rails
and trippers.
10.VENTILATION
Check all labyrinths, grillwork, and air passages for
obstructions and accumulations of dirt.
11
.BATTERY AND CHARGING EQUIPMENT
The
control battery is such-
an
important item in
switchgear operation that it must be given special
periodic attention
if
it
is
to give reliable service for a
long period
of
tim
e.
Periodic inspections and tests
are recommended in the battery supplier(s)
instructions. At the same time the battery is checked,
inspect the battery charger and remove
accumulations of dust and dirt. On all chargers
having a manual transfer switch for setting
the
1.8.
32-255
charging rate, check carefully
to
be sure that the
selector switch is returned
to
the value appropriate
for a floating charge at the end
of
the periodic
inspection. Serious damage to the control battery
can occur if the charger is left on a high charging
rate for an extended period
of
time.
12.RECORDS
The condition of each switchgear unit
at
the time of
inspection should
be
listed in a permanent record
to
become a guide for anticipating the need for
replacements
or
for special attentiqn between the
regul
ar
maintenance periods. Megger tests are
suggested for checking the insulation. A series of
these tests will indicate any tendency toward a
reduction in dielectric strength
of
the insulation.
Megger readings should be taken before and after
cleaning the equipment and, where possible, under
similar conditions at successive perio
ds
. Records
should include the megger reading, t
he
temperature
and the humidity.The readings will vary with the
extent and design
of
the bus structure. In contrast
with a small installation, the longer switchgear
assemblies will have a more extensive bus structure
with a greater number of insulators and thereby, a
longer number of
par
allel insulation resistance paths
to
ground which will tend
to
decrease megger
readings. This vari
at
ion in insulation resistance
between different switchgear assemblies
emphasizes the value of a series of readings which
can be charted
to
establish a
nor
mal insulation level
so that progressive weakening
of
the insulation can
be
recognized.
13
.ABNORMAL CONDITIONS
Local conditions such as high humidity, salt-laden
atmosphere, corrosive gases, heavy dust,
or
severe
circ
ui
t operating conditions, are considered to be
abnormal; and will require more frequent inspec-
tions.
It should be emphasized that a series of inspections
should be made at quarterly intervals until the
progressive facts of the local conditions can be
analyzed to determine a schedule which will
ma
in-
tain the equipment in satisfactory condition.
In some locations conditions may be
so
bad that the
frequency
of
maintenance will interfere with operat-
ing and production schedules. In such cases,
consideration should be given to the possibility of
enclosing the switchgear equipment in a relatively
tight room and
to
supplying a sufficient quantity of
clean air
to
ma
intain a positive pressure in the room.
Under such conditions maintenance schedules may
then be established on a more normal basis. Such
an arrangement might also provide for cooling the
air
where the
amb
ient temperature is relatively high,
thus further improving operating conditions.
Effective
12/97

1.8.
32-255
SECTION 6
LUBRICATION
& DANGER
VAC-CLAD-W
SW
ITCHGEAR is designed so that
lubrication is not required under normal conditions.
However, abnormal local conditions such as high
humidity, salt-laden atmosphere, corrosive gase
s,
or
severe circuit operating conditions may demand the use
of lubricants.
In
such cases a dry
or
powder lub
ri
cant
should be used on moving or mating mechanical parts
and a
thiniilm
of vaseline on disconnection contacts.
The application of the lubricants should be held to a
minimum to reduce the accumulation
of
the du
st
and
dirt.
SECTION 7
RENEWAL PARTS
When ordering renewal or spare pa
rt
s, include as much
information as possible. In many cases the style number
of the new part can be obtained from identification on
the old part. Always include a description of the part.
Specify the rating, housing number and shop order
number
of
the metal-clad housing in which the part is to
be
used.
SECTION 8
A FURTHER DESCRIPTION OF VAC-CLAD-W
SWITCHGEAR
8.1
SAFETY FEATURES
Westinghouse VAC-CLAD-W SWITCHGEAR is
manufactured with several built-in interlocks.These
interlocks are intended to protect persons working on
the equipment. Never make these interlocks inoperative.
Doing so can damage proper
ty
and cause severe injury.
FOLLOWING ARE TWO
OF
THE INTERLOCKS:
1. CODING PLATES
A coding plate is fastened to the bottom front edge
of the breaker compartment. There is also a coding
plate fastened
to
the front of the breaker. Itthe
breaker has a lower interrupting rating than the
rating
of
the compartment,
or
if the voltage and
continuous current characteristics don't match, the
coding plate on the compartment will prevent
the
entrance
of
the breaker into the compartment.
E
ffective
12/97
Page19
NOTE: EVEN WITH THE CODING PLATES IT IS
POSSIBLE TO PUT TO THE COMPARTMENT A
BREAKER WHOSE CONTROL WIRING IS NOT
COORDINATED WITH THAT
OF
THE COMPARTMENT.
ALWAYS CHECK THE SHOP ORDER DRAWING TO
MAKE SURE THE CONTROL WIRING OFTHE
BREAKER AND THE COMPARTMENT ARE BOTH
THE SAME.
2. AUTOMATIC SHUTTER
An automatic shutter, shown in figure 9, covers the
primary disconnecting contacts when the breaker is
withdrawn from the operating position.The shutter
prevents persons who are working
on
the
switchgear from accidentally touching the primary
contacts. Shutters also cov
er
the station
ary
d1SC01111ects
for draw-out
tr
ansf
or
me
rs and primary
h.ses.
8.2 INTERRUPTER POLE UNIT MOUNTING
Each mounting is made
of
two glass polyester
mouldings backed up by a steel barrier.
(SEE IB 32-255-1 FOR FURTHER DETAILS.)
CONTACT STUD
May be flat, as shown, or round, dependent on
amperage rating. (SEE FIGURE 9A.)
8.3 RING-TYPE CURRENTTRANSFORMERS
The ring-type current transformers are mounted so they
slip over the
pr
imary contact insulating tube on the rear
wall
of
the breaker compartment. There is space for a
maximum, of four standard accuracy transformers
per
phase (2 on each side
of
the breaker). A polyester CT
barrier, shown in figure 8, restricts unconscious access
to the CT's.
They are mounted so
th
ey can be reached from the
fr
ont of the enclosure (SEE FIGURES 9 & 9A
).
This
makes it possible to add
or
to change transformers
when the switchgear is de-energized without handling
high voltage connections
or
breaking the primary
insulation. The polari
ty
marks on the transformers show
the relative instantaneous polarity in the primary and
secondary windings.The diagrams show how to
connect the transformers to give polarity needed to
operate relays and instruments.
CAUTION:
DO
NOT MANUALLY RAISE
OR
REMOVE
SHUTTER UNLESS MAIN CONTACTS ARE
DE-ENERGIZED AND SAFETY PROCEDURES HAVE
BEEN INITIATED TO MAKE SURE THE CIRCUITS
CAN NOT BE RE-ENERGIZED. FAILURE TO
EXERCISE CAUTION MAY RESULT IN BODILY
INJURY AND PROPERTY DAMAGE.
Table of contents
Other Cutler-Hammer Power Supply manuals