DAB PUMPS ACTIVE DRIVER M/M 1.1 User manual

ACTIVE DRIVER M/M 1.1
ACTIVE DRIVER M/T 1.0 - ACTIVE DRIVER M/T 2.2
ACTIVE DRIVER T/T 3.0 - ACTIVE DRIVER T/T 5.5
DICHIARAZIONE DI CONFORMITÀ
La Ditta DAB PUMPS s.p.a. - Via M. Polo,14 - Mestrino (PD) - ITALIA - sotto la propria
esclusiva responsabilità dichiara che i prodotti summenzionati sono conformi a:
Direttiva della Compatibilità elettromagnetica 2004/108/CE e successive modifiche.
Direttiva Bassa Tensione 2006/95/CE e successive modifiche.
DÉCLARATION DE CONFORMITÉ
La société DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALY – sous sa propre
responsabilité exclusive déclare que les produits susmentionnés sont conformes à:
Directive de la Compatibilité électromagnétique 2004/108/CE et modifications successives.
Directive Basse Tension 2006/95/CE et modifications successives.
DECLARATION OF CONFORMITY
The Company DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALY – under is own
exclusive responsibility declares that the products listed above comply with:
Directive on Electromagnetic Compatibility 2004/108/CE and subsequent modifications.
Directive on Low Voltage 2006/95/CE and subsequent modifications.
KONFORMITÄTSERKLÄRUNG
Die Firma DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALIEN – erklärt
eigenverantwortlich, dass die vorstehend beschriebenen Produkte den folgenden Richtlinien
entsprechen:
Richtlinie zur elektromagnetischen Verträglichkeit 2004/108/CE und folgende Änderungen.
Niederspannungsrichtlinie 2006/95/CE und folgende Änderungen.
CONFORMITEITSVERKLARING
De firma DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALY – verklaart onder
haar eigen, exclusieve verantwoording dat de hieronder genoemde producten voldoen aan:
Richtlijn elektromagnetische compatibiliteit 2004/108/CE en successievelijke wijzigingen.
Laagspanningsrichtlijn 2006/95/CE en successievelijke wijzigingen.
DECLARACIÓN DE CONFORMIDAD
La empresa DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALIA – declara bajo su
total responsabilidad que los productos anteriormente mencionados cumplen la:
Directiva de Compatibilidad Electromagnética 2004/108/CE y sucesivas modificaciones.
Directiva de Baja Tensión 2006/95/CE y sucesivas modificaciones.
FÖRSÄKRAN OM CE-ÖVERENSSTÄMMELSE
Företaget DAB PUMPS s.p.a. – Via M. Polo 14, Mestrino (PD) – ITALIEN – förklarar på eget
ansvar att ovannämnda produkter är i överensstämmelse med:
EMC-direktivet 2004/108/EEG jämte ändringar.
Lågspänningsdirektivet 2006/95/EEG jämte ändringar.

ACTIVE DRIVER M/M 1.1
ACTIVE DRIVER M/T 1.0 - ACTIVE DRIVER M/T 2.2
ACTIVE DRIVER T/T 3.0 - ACTIVE DRIVER T/T 5.5
ǻǾȁȍȈǾ ȈȊMMOPĭȍȈǾȈ
Ǿ İIJĮȚȡİȓĮ DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALY – įȘȜȫȞİȚ
ȞʌİȪșȣȞĮ ʌȦȢ IJĮ ʌȡȧȩȞIJĮ ʌȠȣ ĮȞĮijȑȡȠȞIJĮȚ ʌĮȡĮʌȐȞȦ,İȞĮȡμȠȞȓȗȠȞIJĮȚ μİ:
ɌȘȞ ȠįȘȖȓĮ ʌİȡȓ μĮȖȞȘIJȚțȒȢ ıȣμȕĮIJȩIJȘIJĮȢ 2004/108/EOK țĮȚ μİIJȑʌİȚIJĮ IJȡȠʌȠʌȠȚȒıİȚȢ.
ȉȘȞ ȠįȘȖȓĮ ʌİȡȓ ȤĮμȘȜȒȢ IJȐıȘȢ 2006/95/EOK țĮȚ μİIJȑʌİȚIJĮ IJȡȠʌȠʌȠȚȒıİȚȢ.
UYGUNLUK BEYANNAMESø
- Via M. Polo, 14 – Mestrino (PD) – ITALY – adresinde yerleúik DAB PUMPS s.p.a. ùirketi,
sadece kendi sorumlulu÷u altnıda sözü geçen ürünlerin aúa÷idaki yönetmeliklere uygun old÷unu
beyan etmektedir:
2004/108 sayılı elektromanyetik Uygunluk Yönergesi ve daha sonraki de÷iúiklikler.
2006/95 sayılı Alçak Gerilim Yönergesi ve daha sonraki de÷iúiklikler.
VYHLÁSENIE O ZHODE
SpoloþnosĢDAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – Taliansko, vyhlasuje na
vlastnú výhradnú zodpovednosĢ, že výrobky uvedené v d’alšom texte zodpovedajú.
Smernici Elektromagnetická kompatibilita þ. 2004/108 a nasledujúcim úpravám.
Smernici Nízke napätie þ. 2006/95 a nasledujúcim úpravám.
ɁȺəȼɅȿɇɂȿ Ɉ COOTBETCTBɂɂ
Ɏɢɪɦɚ DAB PUMPS s.p.a. – ȼɢɹ M. ɉɨɥɨ, 14 – Ɇɟɫɬɪɢɧɨ (ɉȾ) – ɂɌȺɅɂə – ɩɨɞ
ɫɨɛɫɬɜɟɧɧɭɸ ɢɫɤɥɸɱɢɬɟɥɶɧɭɸ ɨɬɜɟɬɫɬɜɟɧɧɨɫɬɶ ɡɚɹɜɥɟɬ,ɱɬɨ ɜɵɲɟɭɤɚɡɚɧɧɵɟ ɢɡɞɟɥɢɹ
ɫɨɨɬɜɟɬɫɬɜɭɸɬ:
Ⱦɢɪɟɤɬɢɜɟ ɩɨ ɗɥɟɤɬɪɨɦɚɝɧɢɬɧɨɣ ɫɨɜɦɟɫɬɢɦɨɫɬɢ 2004/108 ɢ ɩɨɫɥɟɞɭɸɳɢɦ ɢɡɦɟɧɟɧɢɹɦ.
Ⱦɢɪɟɤɬɢɜɟ ɩɨ ɇɢɡɤɨɦɭ ɧɚɩɪɹɠɟɧɢɸ 2006/95 ɢ ɩɨɫɥɟɞɭɸɳɢɦ ɢɡɦɟɧɟɧɢɹ.
DECLARAğIE DE CONFORMITATE
Întreprinderea DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALIA – pe exclusiva
proprie răspundere declarăcăprodusele mai sus menĠionate sunt conforme cu:
Directiva CompatibilităĠii electromagnetice 2004/108 úi următoarele modificări.
Directiva de JoasăTensiune 2006/95 úi următoarele modificări.
ΔϘΑΎτϣ ΓΩΎϬη
ϰϟ· ΔϘΑΎτϣ ϩϼϋ ΓέϮϛάϤϟ ΕΎΠΘϨϤϟ ϥ΄Α Ρ˷ήμΗ ΔλΎΨϟ ΎϬΘϴϟϭΆδϣ:
-Ϣϗέ ΔϴΎΑήϬϜϟ ΔϴδϴτϨϐϤϟ ΔϘΑΎτϤϟ ϥϮϧΎϗ2004/108ϭϪΑ ΔϘΣϼϟ ΕϼϳΪόΘϟ.
-Ϣϗέ ξϔΨϨϤϟ ΪϬΠϟ ϥϮϧΎϗ2006/95ϪΑ ΔϘΣϼϟ ΕϼϳΪόΘϟϭ.
Mestrino (PD), 16/05/2007
Attilio Conca
Legale Rappresentante
Legal Representative

ENGLISH
37
GENERAL INDEX page
1. GENERAL 39
2. WARNINGS 39
2.1 Skilled personnel 39
2.2 Safety 39
2.3 Responsibility 39
2.4 Particular warnings 39
3. APPLICATIONS 39
4. TECHNICAL DATA AND LIMITATIONS OF USE 40
5. ELECTRICAL CONNECTIONS OF THE A.D. TO THE ELECTROPUMP 40
6. CONNECTION TO THE POWER SUPPLY LINE 40
7. HYDRAULIC CONNECTIONS 41
7.4 Risk of frost 41
8. CHARACTERISTICS – INTERPRETATIONS – OPERATION 41
8.1 Characteristics and interpretations 41
8.2 Operation: keyboard factory settings 44
8.3 First switch-on operations (only with A.D. as accessory) 44
8.4 Operation: Parameters for the user (MODE and SET keys for 2 seconds) 45
8.4.1 SP: Setting the setpoint pressure (in bar) 45
8.5 Operation: Parameters for the installer (MODE and SET and - keys for 5 seconds) 45
8.5.1 rC: Setting the rated current of the electropump (excluding A.D. M/M 1.1) 45
8.5.2 rt: Setting the direction of rotation (excluding A.D. M/M 1.1) 45
8.5.3 Fn: Setting the rated frequency (pre-set value 50Hz) 45
8.5.4 od: Setting the operating mode of the A.D. 45
8.5.5 rP: Setting the fall in pressure for restarting 46
8.5.6 Ad: Setting the interconnection address (excluding A.D. M/M 1.1) 46
8.5.7 Eb: Enabling booster (pre-set value 2) (excluding A.D. M/M 1.1) 46
8.6 Operation: Technical Assistance displays and settings
(MODE and SET and + keys for 5 seconds)
46
8.6.1 tb: Setting the reaction time of the water lack blockage 46
8.6.2 GP: Setting the gain of the proportional coefficient of the PI 46
8.6.3 GI: Setting the gain of the integral coefficient of the PI 47
8.6.4 FS : Setting the maximum rotation frequency of the electropump. 47
8.6.5 FL : Setting the minimum frequency 47
8.6.6 Ft: Setting the low flow rate threshold 47
8.6.7 CM: Method of exchange (pre-set value 1) (excluding A.D. M/M 1.1) 47
8.6.8 AE : Enabling the anti-block/anti-frost function 48
8.6.9 Setting pump start 48
8.6.10 SF : Setting the starting frequency 48
8.6.11 St : Setting the starting time 48
8.6.12 Setup of the auxiliary digital inputs IN1; IN2; IN3 with the parameters i1; i2; i3
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
48
8.6.13 Active Driver M/T 2.2 = setting the set point P1 function of input 2 49
8.6.14 O1: setting output 1 function (active alarm)(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
O2: setting output 2 function (pump operating)(excluding A.D. M/M 1.1 and A.D. M/T
1.0)
49
9. DISPLAYS 49
9.1 Displays of the main values (MODE key) 49
Fr: Display of the current rotation frequency (Hz) 49
UP: Display of pressure (in bar) 49
C1: Display of electropump phase current (A)
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
49
UE: Display of the version of the software with which the appliance is equipped 49
9.2 Monitor display (SET and - key for 2 seconds) 49
UF: Display of flow 49
ZF: Display of zero flow 49
FM: Display of the maximum rotation frequency (Hz) 49

ENGLISH
38
tE: Display of the temperature of the power stages (°C) 49
bt: Display of the temperature of the electronic card (°C) 49
GS: Display of running status 49
FF: Display of fault history (+ and - to scroll through the alarms) 49
10.
ACCESS TO MANUAL MODE OF THE MACHINE
(SET and + and - keys for 5 seconds)
50
10.1 rt: setting the direction of rotation 50
10.2 Starting the electropump 50
11. GENERAL SYSTEM RESET (MODE and SET and + and – keys) 50
12. RESTORING THE FACTORY SETTINGS (SET and + keys) 50
13. ERROR AND STATUS CONDITIONS 50
13.1 bL: Blockage due to water lack 51
13.2 bP: Blockage due to fault of the pressure sensor 51
13.3 LP: Blockage due to low supply voltage (excluding A.D. M/M 1.1 and A.D. M/T 1.0) 51
13.4 oF/ot :
Blockage due to current overload in the output stages with temperature of the stages
higher than 45°C
52
13.5 SC: Blockage due to direct short circuit between the phases of the output terminal 52
13.6 Manual reset of error conditions 52
13.7 Self-reset of error conditions 52
14. INDICATIONS ON THE DISPLAY 53
INDEX OF TABLES Page
Table 4. Technical data and limitations of use 40
Table 8.1. Characteristics and interpretations 41
Table 8.2. Operation: keyboard factory settings 44
Table 8.6.12 Table summarising the configuration of digital inputs IN1, IN2, IN3 48
Table 8.6.14 Assigning the parameters that associate functions with the digital outputs OUT1, OUT2 49
Table 10. Access to manual mode of the machine: Use of the keys 50
Table 13. Error and status conditions: Warnings in the fault log 51
Error and status conditions: Error conditions 51
Table 13.7. Automatic resets of error conditions 52
Table 14. Indications on the display 53
INDEX OF FIGURES page
Fig. 1 Logic-functional diagram of the connections of the alarm output terminals 42
Fig. 2 Connection diagram for 2 ACTIVE DRIVERS for exchange function 42
Fig. 3 Logic-functional diagram of the connections of the user input terminals 43

ENGLISH
39
1. GENERAL
Read this documentation carefully before installation. Installation and functioning must comply
with the safety regulations in force in the country in which the product is installed. The entire
operation must be carried out in a workmanlike manner.
Failure to comply with the safety regulations not only causes risk to personal safety and damage to
the equipment, but invalidates every right to assistance under guarantee.
2. WARNINGS
2.1 Skilled personnel
It is advisable that installation be carried out by competent, skilled personnel in
possession of the technical qualifications required by the specific legislation in force.
The term skilled personnel means persons whose training, experience and instruction, as well as
their knowledge of the respective standards and requirements for accident prevention and working
conditions, have been approved by the person in charge of plant safety, authorizing them to perform
all the necessary activities, during which they are able to recognize and avoid all dangers. (Definition
for technical personnel IEC 60634).
2.2 Safety
Use is allowed only if the electric system is in possession of safety precautions in accordance with the
regulations in force in the country where the product is installed (for Italy, IEC 64/2).
2.3 Responsibility
The Manufacturer does not vouch for correct operation of the ACTIVE DRIVER or for any damage
that it may cause if it has been tampered with, modified and/or run outside the recommended work
range or in contrast with other indications given in this manual. The Manufacturer declines all
responsibility for possible errors in this instructions manual, if due to misprints or errors in copying.
The Manufacturer reserves the right to make any modifications to products that it may consider
necessary or useful, without affecting the essential characteristics.
2.4 PARTICULAR WARNINGS
Before working on the electrical or mechanical part of the system, always turn off the mains voltage.
Wait at least five minutes after the power supply to the machine has been switched off before opening
the appliance. The condenser of the continuous intermediate circuit remains charged with dangerously high
voltage even after the mains voltage has been switched off.
Only firmly wired mains connections are admissible. The appliance must be earthed (IEC 536 class 1, NEC
and other relevant standards).
Mains terminals may carry dangerous voltage even when the motor is stopped.
In determined calibration conditions, after a power cut the converter may start automatically.
Pay attention: the motor terminals U, V and W (for the Active Driver M/M 1.1 the motor terminals R
and S) may carry dangerous voltages even when the converter is not operating.
Do not operate the appliance in direct sunlight.
This appliance may not be used as an “EMERGENCY STOP mechanism” (see EN 60204, 9.2.5.4).
3. APPLICATIONS
The ACTIVE DRIVER is supplied already set up for installation in the following models:
ACTIVE DRIVER M/T: fed with a single-phase line, controls electropumps with a 230V standard
three-phase asynchronous motor.
ACTIVE DRIVER M/M: fed with a single-phase line, controls electropumps with a 230V standard
single-phase asynchronous motor.
ACTIVE DRIVER T/T: fed with a three-phase line, controls electropumps with a 400V standard
three-phase asynchronous motor.

ENGLISH
40
4. TECHNICAL DATA AND LIMITATIONS OF USE
A.D. M/M 1.1 A.D. M/T 1.0 A.D. M/T 2.2 A.D. T/T 3.0 A.D T/T 5.5
Max phase current of the motor: 8,5 A 4,7 A 9,3 A 7,5 A 13,3 A
Line voltage (+10% / -20%): 230 V
single-phase
230 V
single-phase
230 V
single-phase
400 V
three-phase
400 V
three-phase
Line frequency: 50-60 Hz 50-60 Hz 50-60 Hz 50-60 Hz 50-60 Hz
Electropump voltage: 230 V
single-phase
230V
three-phase
230 V
three-phase
400 V
three-phase
400 V
three-phase
Weight of the unit
(packing excluded): 4 Kg. 3,8 Kg. 3,8 Kg. 5 Kg. 5Kg.
Work position: Any position Any position Any position Facing upward
Facing upward
Max fluid temperature: 50°C 50°C 50°C 50°C 50°C
Max working temperature: 60°C 60°C 60°C 60°C 60°C
Max. pressure: 16 bar 16 bar 16 bar 16 bar 16 bar
Regulating range:
from 1 to 6 bar from 1 to 9 bar from 1 to 15 bar from 1 to 15 bar from 1 to 15 bar
Maximum dimensions (LxHxD): 22x28x18 cm 22x28x18 cm 22x28x18 cm 22x28x18 cm 22x28x18 cm
Fluid input hydraulic coupling: 1 ¼” male 1 ¼” male 1 ¼” male 1 ¼” male 1 ¼” male
Fluid output hydraulic coupling: 1 ½”female 1 ½”female 1 ½”female 1 ½”female 1 ½”female
Degree of protection: IP 55 IP 55 IP 55 IP 55 IP 55
Protections: dry running
overload
excess temperature of the electronics
abnormal feeding voltages (excluding A.D. M/M and A.D. M/T 1.0)
direct short-circuit between the output phases
5. ELECTRICAL CONNECTIONS OF THE ACTIVE DRIVER TO THE ELECTROPUMP
5.1 Ensure that all the terminals are fully tightened, paying particular attention to the earth
terminal .
5.2 Check that all the connecting cables are in excellent conditions, with the external sheathing unbroken.
5.3 The motor of the installed electropump must comply with the data in the table in Chapter 4.
The user connected to the ACTIVE DRIVER M/M 1.1 must not exceed 8,5 A as phase current.
The user connected to the ACTIVE DRIVER M/T 1.0 must not exceed 4,7 A as phase current.
The user connected to the ACTIVE DRIVER M/T 2.2 must not exceed 9,3 A as phase current.
The user connected to the ACTIVE DRIVER T/T 3.0 must not exceed 7,5 A as phase current.
The user connected to the ACTIVE DRIVER T/T 5.5 must not exceed 13,3 A as phase current.
5.4 Connect the electropump to the output cable of the ACTIVE DRIVER, paying particular attention to the
earth connection.
The incorrect connection of the earth lines to a terminal other than the earth terminal
may cause irremediable damage to the whole appliance!
The incorrect connection of the power supply line on output terminals intended for the
load may cause irremediable damage to the whole appliance!
6. CONNECTION TO THE POWER SUPPLY LINE
6.1 Connect the ACTIVE DRIVER to the power supply line by means of the power socket.
(See values in chapter 4).
6.2 If an extension to the power cable is used the following minimum sections must be respected:
Section of each lead (mm²) Maximum length of the line (metres)
1.5 15
2.5 30
4 60
6.3 The ACTIVE DRIVER is already provided with current protections. If a magnetothermal switch is
installed in line, it must have a max. capacity of 16A.
6.4 The connection of the line to the ACTIVE DRIVER must include the earth line. The total earth resistance
must not exceed 100 Ohm.

ENGLISH
41
6.5 To protect the system it is recommended to install a differential switch with correct
dimensions, type:
Class A, with adjustable dispersion current, selective, protected against sudden tripping.
The automatic differential switch must be marked with the following two symbols:
7. HYDRAULIC CONNECTIONS
7.1 Always install a check valve on the pipe upstream from the ACTIVE DRIVER.
For the purposes of operation of the ACTIVE DRIVER it does not matter whether the valve is fitted on
the suction or on the delivery of the pump.
7.2 The hydraulic connection between the ACTIVE DRIVER and the electropump must not have any
derivations.The dimensions of the pipe must be suitable for the electropump installed.
7.3 The ACTIVE DRIVER works at constant pressure. This regulation is appreciated if the
hydraulic system downstream from the system is of suitable dimensions.
Systems made with pipes that have too narrow a section introduce load losses which the
appliance cannot compensate; the result is that the pressure is constant on the device but not on
the user.
7.4 RISK OF FROST: pay attention to the place where the ACTIVE DRIVER is installed!
If the place of installation reaches a temperature below 0°C, the following precautions must be
taken:
If the ACTIVE DRIVER is operative it is absolutely necessary to protect it suitably
against frost and to leave it constantly fed.
If it is disconnected from the power supply, the anti-frost function is no longer active!
If the ACTIVE DRIVER is not operative it is advisable to turn off the power supply,
disconnect the appliance from the pipe and completely empty out all water left inside it.
It is not sufficient just to remove pressure from the pipe, because some water is
always left inside.
8. CHARACTERISTICS – INTERPRETATIONS – OPERATION
The ACTIVE DRIVER is an innovative integrated system for controlling electropumps with variable
speed, able to keep a constant pressure while the flow rate varies.
The ACTIVE DRIVER is composed of an inverter, a pressure sensor and a flow sensor.
With the exclusion of models M/M 1.1 and M/T 1.0 the ACTIVE DRIVER is provided with 3 inputs and
2 outputs so as to be able to realise certain interface solutions with more complex installations.
Figure 1 shows the logical function diagram for the connection of the user input terminals.
Figure 2 shows the logical function diagram for the connection of the alarm output terminals.
Figure 3 shows the connection diagram for 2 ACTIVE DRIVER units, for the exchange function.
8.1 CHARACTERISTICS AND INTERPRETATIONS
Ref. FUNCTION
L – N
SINGLE-PHASE
R – S – T
THREE-PHASE
Power supply line connection terminals.
Line earth system connection terminal.
U - V – W
THREE-PHASE
R – S
SINGLE-PHASE
Three-phase pump connection terminals.

ENGLISH
42
Ref. FUNCTION
Pump earth system connection terminal.
1
Power supply terminal: + 12V DC – 50Am.
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
2
=IN 3 Connection terminal of input i3 for general disabling command.
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
3
=IN 2 Connection terminal of input i2 for selecting set point 1.
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
4
Common connection terminal I
3
– I
2
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
6
=IN 1 Connection terminals of input i1 for protection against dry running.
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
J22
7
Connection terminal: 0V DC (GND).
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
o1
Remote alarm connection terminal. (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
250 Vac – 6 A max resistive load – 3 A max inductive load
J14 o2
Pump operating connection terminal. (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
250 Vac – 6 A max resistive load – 3 A max inductive load
J9
Connection terminals for interconnection and exchange.
ATTENTION: For interconnection cables with a length of more than 1 m, it is
recommended to use screened cable with the braiding connected to earth (central pin
number 2) on both appliances.
ATTENTION: Scrupulously respect the connection sequence between the two
appliances! (excluding A.D. M/M 1.1) (see fig.2)
Fig. 1
Fig. 2
For functionality and programming:
see table on page 49 “Assigning the parameters that associate functions with the digital outputs OUT1,
OUT2”
3
2
1
3
2
1
J 9 J 9
Primary
Active Driver
Secondary
Active Driver
ACTIVE DRIVER M/T 2.2
o2
o1
J 14
1
4
2
3

ENGLISH
43
Fig. 3
– Example of possible use of the user inputs -
Control with clean contact Control with external voltage
For functionality and programming:
see table on page 48 “Table summarising the configuration of the digital inputs IN1, IN2, IN3"
Example: Use IN 1
When IN 1 is activated the pump is
blocked and the signal “F1” is given
ex. IN 1 could be connected to a
float
Example: Use IN 2
When IN 2 is activated the regulating
pressure becomes “P1”
(switch over active setpoint:
SP or P1)
Example: Use IN 3
When IN 3 is activated the pump is
blocked and the signal “F3” is given
ex. IN 3 could be connected to a
safety pressure switch with manual
reset
Supplied with
direct voltage
(Max. 48V) or
alternate voltage
(Max. 50Vrms)
Supplied with
direct voltage
(Max. 48V) or
alternate voltage
(Max. 50Vrms)
Supplied with
direct voltage
(Max. 48V) or
alternate voltage
(Max. 50Vrms)
Clean contact
Jumper
Clean contact
Jumper
Clean contact
Jumper
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
7
AC/DC
1
2
3
4
5
6
7
AC/DC
1
2
3
4
5
6
7
AC/DC
J22
J22
J22

ENGLISH
44
8.2 OPERATION: KEYBOARD FACTORY SETTINGS
(ref. Table no. 14 page 53)
MODE The MODE key allows you to move on to the next items in the individual menus.
SET The SET key allows you to quit the current menu and return to normal operating status.
+
Press to increase the currently modifiable parameter.
Each time it is pressed, the value of the parameter is displayed for at least 6 seconds, after which the
identifying symbol appears.
–
Press to decrease the currently modifiable parameter.
Each time it is pressed, the value of the parameter is displayed for at least 6 seconds, after which the
identifying symbol appears.
When the + key or the – key is pressed, the selected value is modified and saved immediately. Even the
accidental shut-down of the machine during this phase does not cause the loss of the newly set parameter. The
SET key is used only to return to the display of the machine status. It is not fundamental to press the SET key
in order to save the changes made.
8.3 FIRST SWITCH-ON OPERATIONS (only with ACTIVE DRIVER as accessory)
(ref. Table no. 14 page 53)
After having correctly carried out the installation of the hydraulic and electric system, power can be
supplied to the ACTIVE DRIVER.
The letters “ZF” will appear on the display and after a few seconds the error condition “EC” will be
shown.
To start the ACTIVE DRIVER it is necessary to set the current value shown on the data plate (in A) and
the frequency (in Hz) of the electropump used.
Below are described some steps for setting the main parameters and making the first start-up.
8.3.1 Setting the rated current “rC”
In normal operating status, hold down simultaneously the MODE and SET and - keys until "rC" appears on
the display.
Using the + and – keys you can respectively increase and decrease the value of the parameter, according to the
indications on the data plate of the electropump motor.
If the set parameter is lower than the correct one, during operation the error message “oC” will appear as soon
as the set current has been exceeded for a certain time.
If the set parameter is higher than the correct one, the overload protection will trip incorrectly beyond the
motor safety threshold.
An incorrect configuration of the electric motor of the electropump may cause damage to the
motor.
If SET is pressed to leave the menu without setting “Fn”, the set current value is activated but
the ACTIVE DRIVER is not unblocked because the frequency has not been set and the letters
“EC” will still be displayed.
8.3.2 Setting the rated frequency “Fn”
From the parameter “rC”, press the MODE key once, the electropump rated frequency “Fn” will appear
on the display.
The frequency “Fn” must be set as shown on the data plate of the electropump using the + and – keys.
The next time MODE or SET is pressed, the set current and frequency values are activated and the
ACTIVE DRIVER is unblocked, unless other error or blocking conditions have occurred.
An incorrect configuration of the working frequency of the electropump may cause damage to
the electropump.
8.3.3 Setting the direction of rotation
From the parameter “Fn” press the MODE key to make the current and frequency settings active and
move on to the next item “rt”. At this point the ACTIVE DRIVER is ready to start.
Switch on a user to start the electropump turning.
If the direction of rotation is correct, proceed to set the Setpoint pressure, otherwise invert the direction of
rotation of the motor using the + and – keys (function active even with the motor switched on).
8.3.4 Setting the setpoint pressure
In normal operating status, hold down simultaneously the MODE and SET keys until "SP" appears on the
display. In these conditions the + and – keys respectively allow you to increase and decrease the desired
pressure value.
The regulating range is from 1 to 15 bar depending on the ACTIVE DRIVER model.
Press SET to return to normal operating status.

ENGLISH
45
8.4 OPERATION : PARAMETERS FOR THE USER (ref. Table no. 14 page 53)
Access keys MODE and SET for 2 seconds
8.4.1 SP : Setting the set point pressure ( in bar )
From normal operating status, hold down the MODE and SET keys simultaneously until the letters SP
appear on the display. In these conditions the +and –keys allow you respectively to increase and
decrease the desired pressure value.
The regulating range is from 1 to 6 bar for the S.D. M/M 1.1, from 1 to 9 bar for the A.D. M/T 1.0 and
from 1 to 15 bar for the other models.
Press SET to return to normal operating status.
As well as the working pressure the ACTIVE DRIVER allows you to set one other value:
rP: expresses in bars the decrease in pressure, with respect to SP, that makes the pump restart.
8.5 OPERATION : PARAMETERS FOR THE INSTALLER (ref. Table no. 14 pa
g
e 53)
Access keys MODE and SET and – for 5 seconds
If an error or malfunction occurs during this phase, the display is not changed. Depending on
the type of error, the electropump may switch off. However it is still possible to make the desired
calibration. To know the type of error that has occurred you must return to the mode in which
you see the operating status by pressing the SET key.
From normal operating status, hold down the MODE and SET and –keys simultaneously until the
letters “rC” appear on the display. In these conditions the +and –keys allow you respectively to
increase and decrease the value of the parameter while the MODE key allows you to move on to the
next parameter in cyclic mode. Press SET to return to normal operating status
.
8.5.1 rC : Setting the rated current of the electropump (excluding A.D. M/M 1.1)
This parameter must be set the same as the current on the motor data plate (Amps) in the configuration
in which it is used (power supply 230V for A.D. M/T - power supply 400V for A.D. T/T).
8.5.2 rt : Setting the direction of rotation (excluding A.D. M/M 1.1)
Possible values: 0 and 1
If the direction of rotation of the electropump is not correct, it is possible to invert the direction of
rotation by changing this parameter.
If it is not possible to observe the direction of rotation of the motor, proceed as follows:
- Open a user and observe the frequency (parameter Fr with MODE key from GO) and the current
(parameter C1).
- Without changing the amount of water taken, change the parameter rt and observe the frequency Fr
and the current C1 again.
- The correct parameter rt is the one which, with the same amount of water taken, requires a lower
frequency Fr and current C1.
8.5.3 Fn : Setting the rated frequency (pre-set value 50Hz)
This parameter defines the rated frequency of the electropump and it may be set at 50Hz or 60Hz.
However the frequency must be set as indicated on the data plate of the
electropump motor.
Press the + or – keys to select the two frequencies 50Hz or 60Hz.
An incorrect setting of the rated frequency may cause damage to the
electropump.
Each change of Fn is interpreted as a change of system and so FS, FL and FP will automatically assume
the default values.
8.5.4 od: Setting the operating mode of the ACTIVE DRIVER
Possible values: 1 and 2
The ACTIVE DRIVER leaves the factory in mode 1 for working without expansion vessels or with
small vessels. If there is an expansion vessel near the ACTIVE DRIVER, with a half-inch or larger
fitting, you must change to mode 2.

ENGLISH
46
8.5.5 rP: Setting the fall in pressure for restarting
Expresses, in bars, the fall in pressure that makes the pump restart.
rP may be set from a minimum of 0.1 to a maximum of 1.5 bar.
rP is equipped with a limiting system depending on the combination of the SP value so as to have in any
case a minimum restarting pressure of 0.3 bar.
8.5.6 Ad : Setting the interconnection address (excluding A.D. M/M 1.1)
With the ACTIVE DRIVER system it is possible to realise booster sets composed of two elements
communicating by means of serial interconnection (see fig.3). In this type of installation it is necessary
for the two units to have a different identifying address (Ad).
The admissible values are: “- -”, 1 and 2:
- When “Ad” is “- -” the communication is disabled.
- When “Ad” is “1” it is called Secondary ACTIVE DRIVER (booster).
- When “Ad” is “2” it is called Primary ACTIVE DRIVER (leader).
Attention: If two interconnected ACTIVE DRIVER units are set with the same “Ad” value, the
communication does not work and there may be malfunctions in regulation.
When the communication does not work (due to incorrect setting of the “Ad” value, for wiring
problems, or other reasons), the two ACTIVE DRIVER units will work as though they were two
completely independent machines, but they will indicate the impossibility of dialogue by making the
display blink when the states “Go” or “Sb” are shown.
When the “Ad” values are correctly set, some regulating parameters are aligned. In particular the
secondary ACTIVE DRIVER copies the following values from the primary ACTIVE DRIVER:
- SP : Setting of the set point pressure.
- rP : Setting of the restarting pressure drop.
- Eb : Enabling of the booster pump.
- CM : Method of exchange.
- dP : Setting of the pressure differential at low flow rates.
- P1 : Setting of the input function 2 set point P1.
Note: During operation it is possible to change all the parameters of the ACTIVE DRIVER on each of
the two machines.
8.5.7 Eb : Enable booster (pre-set value 2) (excluding A.D. M/M 1.1)
When two ACTIVE DRIVER units are interconnected with each other, in the case where only one
ACTIVE DRIVER is not able to satisfy the user, there is the possibility of activating the two
electropumps at the same time.
Eb = 1 : The leader-booster operating mode is disabled, so only one electropump at a time will
be active.
If during operation the leader electropump is not able to satisfy the user, the booster
electropump will not be switched on.
Eb = 2 : The leader-booster operating mode is enabled, so 2 electropumps can be activated at the
same time.
If during operation the leader electropump is not able to satisfy the user, the booster
electropump will also be switched on and will work at the maximum frequency, while
the leader machine will continue to modulate the rotation frequency according to the
user.
8.6 OPERATION : TECHNICAL ASSISTANCE DISPLAYS AND SETTINGS
Access keys MODE and SET and + for 5 seconds (ref.Table no. 14 pa
g
e 53
)
8.6.1 tb: Setting the reaction time of the water lack blockage
The setting of the reaction time of the water lack blockage allows you to select the time (in seconds)
taken by the ACTIVE DRIVER system to indicate the lack of water in the electropump. The variation
of this parameter may be useful if it is known that there is a delay between the moment in which the
electropump is switched on and the moment in which it actually starts delivering.
8.6.2 GP: Setting the gain of the proportional coefficient of the PI
For nearly all systems, the GP parameter set in the factory is the optimum one. However, if there
should be any problems in regulation, this setting may be adjusted. Indicatively it may be said that, for
example, the presence of great swings in pressure or of a slow response of the system to variations in
pressure may be compensated by high GP values. Instead the occurrence of “vibrations” in pressure
(extremely rapid pressure swings around the set point value) may be attributed to too high a GP value.

ENGLISH
47
8.6.3 GI: Setting the gain of the integral coefficient of the PI
The integral value must be increased when the system is not very elastic, that is where there is absence
of any expansion. On the contrary, in systems with deformable pipes or with delays due to considerable
distances between the electropump and the ACTIVE DRIVER, the integral value must be lowered.
To obtain satisfactory pressure regulations, you generally have to adjust both GP and GI. In
fact it is the correct agreement between these two parameters which allows the optimum
pressure regulation.
8.6.4 FS :
Setting the maximum rotation frequency of the electropump.
The ACTIVE DRIVER allows the electropump to be fed for short periods at a frequency higher than the
rated frequency, limiting the maximum frequency sent to the electropump in the event of an excessive
increase in temperature.
The value of the set maximum frequency (FS) can therefore be reached with the motor cold and it
decreases to Fn (rated frequency) as the temperature rises in the windings.
The ACTIVE DRIVER also allows a maximum working frequency to be set that is lower than the rated
frequency Fn. In this case, in whatever regulating condition, the electropump will never be run at a
frequency higher than the set rated frequency.
The maximum FS is Fn + 20%, while the minimum FS is Fn – 20%.
FS will align automatically with Fn whenever a new Fn is set.
When increasing the supply frequency, pay attention not to exceed the Max. phase current of the
motor, otherwise there is a risk of blockage due to current overload in the output stages oF.
8.6.5 FL : Setting the minimum frequency
FL is used to set the minimum frequency at which the electropump is to be run.
The minimum value may be assumed to be 0Hz, the maximum value is 60% of Fn.
For example, if Fn=50Hz, FL may be regulated between 0Hz and 30Hz.
FL will align automatically with Fn whenever a new Fn is set.
8.6.6 Ft: Setting the low flow rate threshold
The ACTIVE DRIVER system possesses a flow sensor. Whenever the electropump is switched off a
new zero is acquired. The ACTIVE DRIVER switches off the electropump when the flow rate reading is
lower than 0 flow (ZF) + the set Ft parameter.
8.6.7 CM : Method of exchange (pre-set value 1) (excluding A.D. M/M 1.1)
When two ACTIVE DRIVER units are interconnected to work in exchange it is possible to choose
between two different strategies for alternating the switching on of the two electropumps.
CM = 0 : The primary ACTIVE DRIVER is always the regulation leader and the secondary
ACTIVE DRIVER will be active as a booster (if Eb=2) or as a reserve (if Eb=1). If the
secondary machine remains unused for 23 hours, it becomes the leader until it has
accumulated one minute of regulation.
If during operation the leader electropump is unable to satisfy the user and the
secondary electropump is set as a booster (Eb=2), the latter will work at maximum
frequency, while the leader ACTIVE DRIVER will continue to modulate the rotation
frequency according to the user.
If the user decreases, the booster machine is switched off, while the leader machine
continues regulating.
CM = 1 : The primary and secondary ACTIVE DRIVER alternate in being the regulation leader.
The exchange takes place each time the leader ACTIVE DRIVER goes into stand-by
mode or after 2 hours of continuous activity.
If during operation the leader electropump is unable to satisfy the user and the
secondary electropump is set as a booster (Eb=2), the latter will work at maximum
frequency, while the leader ACTIVE DRIVER will continue to modulate the rotation
frequency according to the user.
If the user decreases, the leader machine goes into stand-by and becomes the booster
(off), while the booster machine becomes the leader (and starts regulating at variable
speed).
For each of the two exchange modes, if one of the machine breaks down, the other becomes the leader
and carries out regulation at constant pressure up to its maximum available power.

ENGLISH
48
8.6.8
AE : Enabling the anti-block/anti-frost function
It starts rotation of the motor-impeller assembly so as to avoid mechanical blockages due to low temperature or to
long inactivity. When the function is enabled, if the ACTIVE DRIVER measures a temperature that is too low and
with a risk of frost, it automatically starts to turn the electropump at a low number of revs (25Hz). Instead, if the
temperature is within a safety range and the ACTIVE DRIVER records long inactivity, to avoid blockages of
formations of residue it makes the electropump perform an unblocking cycle every 23 hours.
ATTENTION: Since a starting frequency close to the rated value is necessary for a certain time in order to ensure
the starting of a single-phase pump, whenever the anti-frost function starts up with the users closed there may be an
increase in the pressure of the system.
It is important to ensure that the electropump installed has a maximum head that the system can withstand.
Otherwise it is advisable to deactivate the anti-frost function.
8.6.9
Setting pump start
The minimum frequency at which a single-phase pump can be started is an extremely variable parameter, depending
on the pump model used. It has therefore been made possible to set the starting frequency and the time during which
that frequency must be maintained in order to guarantee the correct operation of any model. The pre-set values of SF
and St are a good compromise, but if the pump does not start, or starts with difficulty or slowly, increase SF or St
until good pump operation is reached. If there are problems of excess pressure at starting, it will instead be necessary
to decrease the SF or St parameters. In this case it is recommended to vary one parameter at a time in small steps and
to check operation. The phenomenon of excess pressure at starting is typically found only for very low SP vales (1.0-
1.5 bar) and it may be limited, but not completely eliminated, by decreasing the parameters indicated above.
8.6.10
SF : Setting the starting frequency
This is the frequency at which the pump has to be started for the time St.
The pre-set value is 45 Hz and it may be varied between Fn and Fn-50% using the “+” and “-“ keys.
If a FL higher than Fn-50% has been set, SF will be limited to the value of the minimum frequency FL.
For example, for Fn=50 Hz and FL=0, SF may be set between 50 and 25 Hz; instead, if Fn=50 Hz and
FL=30 Hz, SF may be set between 50 and 30 Hz.
8.6.11
St : Setting the starting time
The parameter St represents the period of time during which the frequency SF is supplied before passing the
frequency control to the automatic system PI. The pre-set value of St is 1 second and it is the best value in the
majority of cases. However, if necessary, the parameter St may be varied from a minimum of 0 seconds to a
maximum of 3 seconds.
8.6.12 Setup of the auxiliary digital inputs IN1; IN2; IN3 with the parameters i1; i2; i3
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
The function assigned to each of the digital inputs IN1; IN2; IN3 may be activated or modified by means
of the parameters i1; i2; i3.
The setup of the parameters i1,i2,i3 may always assume the values:
0 => function disabled
1 => function active on high active input (see fig.3)
2 => function active on low active input (see fig.3)
ATTENTION: the parameter i3 alone may also assume the values 3,4 and 5 (as indicated in the table)
Table summarising the configuration of the digital inputs IN1, IN2, IN3
Parameter Value
0 1 2 3 4 5
With the
intervention of the
command the
system goes into
block and alarm
status with
indication F1 on
the display.
i1
Each function is
disabled
F1 never
appears.
Protection
against dry
running
With input IN1
closed.
Protection
against dry
running
With input IN1
open.
- - - - - -
With the
intervention of the
command the
active set point =
P1.
i2
Each function is
disabled
F2 never
appears.
Active set point
=P1
With input IN2
closed.
Active set point
=P1
With input IN2
open.
- - - - - -
With the
intervention of the
command the
ACTIVE DRIVER
is deactivated with
indication F3 on
the display.
i3
Each function is
disabled
(default)
F3 never
appears.
ACTIVE DRIVER
disabled
With input IN3
closed.
ACTIVE DRIVER
disabled
With input IN3
open.
ACTIVE DRIVER
disabled.
With input IN3
closed
+ eliminate
blockages and
reset.
ACTIVE
DRIVER
disabled.
With input IN3
open
+ eliminate
blockages and
reset.
Eliminate
blockages and
reset.

ENGLISH
49
8.6.13 ACTIVE DRIVER M/T 2.2 (excluding A.D. M/M 1.1 e A.D. M/T 1.0)
Setting the set point P1 function of input 2
When the parameter i2 is set at a value other than zero, with the input 2 it is possible to select one of
the two settable set points. The first is SP. The second is P1. The regulating range is from 1 to 9 bar.
8.6.14 O1: Setting output 1 function ( “active alarm” ) (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
O2: Setting output 2 function ( “pump operating ) (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
Assigning the parameters that associate functions with the digital outputs OUT1; OUT2
Assigning the
parameters
Value
0 1 2 3
o1 Each function is disabled.
Contact always open
Each function is disabled.
Contact always closed
In case of blocking errors
the contact closes (default)
In case of blocking errors
the contact opens
o2 Each function is disabled.
Contact always open
Each function is disabled.
Contact always closed
When the electropump is
operating the contact closes
(default)
When the electropump is
operating the contact
opens
9. DISPLAYS
9.1 DISPLAYS OF THE MAIN VALUES (ref.Table no. 14 page 53)
Access key MODE
From normal operating status, pressing the MODE key displays the following values:
Fr: Display of the current rotation frequency (in Hz).
UP: Display of pressure (in bar).
C1: Display of the phase current of the electropump (in A).
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
UE: Display of the version of the software with which the appliance is equipped.
9.2 MONITOR DISPLAYS (ref. Table no. 14 page 53)
Access keys SET and – for 2 seconds
From normal operating status, pressing the key SET and – enters the MONITOR function where the
following values are displayed:
(NB: to scroll through the values press the MODE key)
UF: Display of the flow
Display of the instantaneous flow.
Parameter to be used only as a reference in programming.
ZF: Display of zero flow
Display of the reading of the flow sensor on which zero was acquired (with electropump switched off).
During normal operation the ACTIVE DRIVER will use this parameter to switch off the electropump.
FM: Display of the maximum rotation frequency (in Hz)
tE: Display of the temperature of the power stages (in °C)
bt : Display of the temperature of the electronic card (in °C)
GS: Display of running status
SP = pump operating to maintain pressure “SP”.
P1 = pump operating to maintain pressure “P1” (input 2 active).
AG = pump operating for “anti-frost”.
FF: Display of fault history (+ and – to scroll through the alarms)
There is a queue of 16 positions for containing the last 16 faults which have occurred during system
operation. By pressing the – key you can go back in history and stop at the oldest fault present, whereas
by pressing the + key you can go forward in history and stop at the most recent fault present.
The decimal point identifies the last fault to have occurred in chronological order.
The history contains at the most 16 positions. Each new fault is inserted in the most recent position
(decimal point). For each fault after the sixteenth, the oldest one in the queue is erased. The history of the
faults is never erased but only updated as new faults occur. Manual reset and switching off of the
appliance do not erase the history of faults.

ENGLISH
50
10. ACCESS TO MANUAL MODE OF THE MACHINE
(ref. Table no. 14 page 53)
Access keys SET and + and – for 5 seconds
During this phase all the controls and protection systems of the ACTIVE DRIVER are
disabled!
Use of the keys
Keys pressed Action
SET and + and – Press them together for a few moments until the display shows MA
+ Increases the frequency and rotation of the electropump
– Decreases the frequency and rotation of the electropump
MODE
Moves on to the next item in the following menu
FP = Setting of the test frequency in manual mode (Hz) at the set FS value
UP = Display of pressure (bar)
C1 = Display of the electropump phase current (A)
rt = Setting of the direction of rotation
UF = Display of flow
ZF = Display of zero flow
MODE and – The electropump runs at the set frequency as long as the keys are held down
MODE and – and
+
(for 2 seconds)
The electropump remains operating at the set frequency.
The electropump may be switched off by pressing SET (when SET is pressed a second time
it takes you out of the Manual Mode menu).
SET and – Changes the direction of rotation of the electropump (active only with the pump running).
SET Press to stop the electropump or to leave manual mode.
10.1 rt : setting the direction of rotation
In manual mode, irrespective of which heading you are under, you can always invert the direction of
rotation by simultaneously holding down the SET and – keys for 2 seconds, this command is active only
with the pump running.
10.2 Starting the electropump .
Pressing the MODE and – and + keys simultaneously stops the electropump at the frequency FP.
The running status remains until the SET key is pressed.
When the electropump is ON the display blinks quickly.
When the electropump is OFF the display blinks slowly.
In manual mode, pressing the SET key takes you out of the menu, but if the electropump has been
started, pressing the key stops only the electropump; when the electropump is stopped, pressing SET
takes you out of the menu.
11. GENERAL SYSTEM RESET (ref. Table no. 14 page 53)
Access keys MODE and SET and + and –
To restart the appliance without disconnecting the power supply press the 4 keys simultaneously.
MODE and SET and + and –
12. RESTORING THE FACTORY SETTINGS (ref. Table no. 14 page 53)
Access keys SET and +
for 2 seconds when switching on
The factory settings are indicated in table no. 14 on page 53.
To reset the factory values:
Switch off the appliance, press and hold down the SET and +keys while switching on the appliance again,
release the two keys only when the letters EE appear. In this case the ACTIVE DRIVER restores the factory
settings. When it has finished setting all the parameters the ACTIVE DRIVER returns to normal operation.
In this phase, in the models in which RC is active, the motor current is set at 0 as factory
default, so when you try to start the electropump it will immediately give the error EC. Go to
the installer’s display and settings menu (keys MODE and SET and – for 5 seconds ) and set the
correct motor data plate current (parameter rC as in paragraph 8.5.1.)
13. ERROR AND STATUS CONDITIONS (ref. Table no. 14 page 53)
The ACTIVE DRIVER is equipped with protection systems to preserve the pump, the motor, the
supply line and the ACTIVE DRIVER itself.
If one or more protections trip, the one with the highest priority is immediately notified on the display.
Depending on the type of error the electropump may switch itself off, but when normal conditions are restored
the error status may be cancelled immediately or only after a certain time, following an automatic reset.

ENGLISH
51
In cases of blockage due to water lack (bL), blockage due to current overload in the electropump (oC), blockage
due to current overload in the output stages (oF), blockage due to direct short circuit between the phases of the
output terminal (SC), you may try to exit the error conditions by pressing the + and – keys simultaneously. If the
error condition remains, you must take steps to eliminate the cause of the malfunction.
In the case of excess temperature, the protection intervenes in two ways:
blockage on reaching too high a temperature,
limitation of the maximum frequency as the temperature rises.
Another type of protection is adopted on:
the power device,
the supply capacitors,
the printed circuit.
These protections intervene when a potentially dangerous temperature is reached, limiting the maximum rotation
frequency FS to small steps.
Once the alarm is over the protection is automatically disabled and normal operating conditions are restored. The
invention of one of these three protections or a combination of them may at the most decrease the frequency FS by
20%.
The three protection systems do not cause and do not generate an error message, but they keep a trace of their
intervention by generating a warning in the fault log.
If the temperature on the final output stages or on the printed circuit is not limited with this system, the blockage for
excess temperature will intervene.
During the intervention of these protections a rotation frequency FR less than the expeted one
may be displayed.
Warning in the fault log
Display indication Description
Lt Warning due to intervention of protection system on power devices
LC Warning due to intervention of protection system on capacitors
Lb Warning due to intervention of protection system on printed circuit
Error conditions
Error and status conditions
Display indication Description
bL Blockage due to water lack
bP Blockage due to absence of pressure sensor
LP Blockage due to low supply voltage
HP Blockage due to high rectified voltage
ot Blockage due to overheating of the power stages
ob Blockage due to overheating of the printed circuit
oC Blockage due to current overload in the electropump motor
oF Blockage due to current overload in the output stages
oF/ot Blockage due to current overload in the output stages with temperature of the stages
higher than 45°C
SC Blockage due to direct short circuit between the phases of the output terminal
EC Blockage due to non setting of the rated current (rC) or of the rated frequency (Fn)
E0...E7 Blockage due to internal error 0...7
F1 Blockage due to input 1 status
F3 Blockage due to input 3 status
13.1
bL : Blockage due to water lack
In conditions of zero flow the system switches off the pump. If, by mistake, a pressure set-point is set which
is higher than the maximum pressure that the electropump can supply, the system indicates “blockage due to
water lack” (bL) even if there is really no lack of water. Then you must lower the switch-off pressure to a
reasonable value that normally does not exceed 2/3 of the head of the installed electropump.
13.2
bP : Blockage due to fault of the pressure sensor
If the ACTIVE DRIVER is unable to detect the presence of the pressure sensor, the electropump remains
blocked and the error signal “bP” is given. This status begins as soon as the problem is detected and ends
automatically 10 seconds after correct conditions have been restored.
13.3 LP :Blockage due to low supply voltage (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
When the line voltage at the supply terminal falls below 180V, the ACTIVE DRIVER goes into block
status due to low line voltage. This is reset only automatically when the voltage at the terminal rises
above 200V.
If the dimensions of the wiring are not suitably large, this block may occur when the electropump is
started even if higher voltages are measured with the machine in stand-by mode.

ENGLISH
52
13.4 oF/ot: Blockage due to current overload in the output stages with temperature of the stages higher
than 45°C
The letters “oF” and “ot” are shown alternately on the display, indicating that a current higher than the safety
threshold has been detected in the output stages and that the temperature of the stages is higher than 45°C.
This means that it might be possible to restart the electropump once the stages have cooled down. The
operating principle of this protection is as follows: since single-stage pumps are characterised by a high
starting current, to make it possible to protect the stages both at starting and during normal operation, 2
different protection thresholds have been introduced.
Moreover, the protection threshold for starting decreases as the temperature of the output stages increases, so
that it will be easier to have a blockage for current overload when trying to start a single-phase pump when
the stages are too warm.
13.5 SC : Blockage due to direct short circuit between the phases of the output terminal
The ACTIVE DRIVER is equipped with protection against the direct short circuit which may occur
between the phases U, V, W of the “PUMP” output terminal. When this block status is indicated, you
are advised to eliminate the short circuit and to check the wiring carefully to ensure it is unbroken and
the installation in general. Once these checks have been made you can try to reset operation by
simultaneously pressing the +and – keys; anyway, this will have no effect until 10 seconds have
passed from the moment in which the short circuit occurred.
Whenever a short circuit occurs, an event counter is increased and saved in the permanent memory
(EEPROM).
AFTER THE HUNDREDTH SHORT CIRCUIT THE MACHINE BLOCKS PERMANENTLY
AND IT WILL NO LONGER BE POSSIBLE TO UNBLOCK IT!
13.6 MANUAL RESET of error condition
In error status the operator can reset the error by forcing a new attempt, pressing the +and –keys
simultaneously.
13.7 Self-reset of error conditions
For some malfunctions and block conditions, the system makes attempts at automatic reset of the
electropump.
The following table shows the sequences of the operations performed by the ACTIVE DRIVER for the
different types of blockage.
Automatic resets of error conditions
Display indication Description Sequence of automatic reset
bL Blockage due to water lack
- An attempt every 10 minutes for a total of 6 attempts
- An attempt every 1 hour for a total of 24 attempts
- An attempt every 24 hours for a total of 30 attempts
bP Blockage due to fault of the
pressure sensor - Reset 10 seconds after correct conditions return
LP Blockage due to low supply
voltage
- Reset when voltage returns to a value in the range
220V - 20% + 10%
HP Blockage due to high
voltage
- Reset when the internal voltage returns in acceptable
conditions
Ot Blockage due to overheating
of the power stages
- Reset when the temperature of the power stages falls
below 70°C again
OC Blockage due to current
overload - An attempt every 10 minutes for a total of 6 attempts
oF
Blockage due to current
overload in the output
stages
- An attempt every 10 minutes for a total of 6 attempts
oF/ot
Blockage due to current
overload in the output
stages with temperature of
the stages higher than 45°C
- An attempt every 10 minutes or when the temperature
has fallen by 10°C. The counting of the attempts is
shared with that of the blockage oF.

ENGLISH
53
14
.
INDICATIONS ON THE DISPLAY
Identifying s. Description Factory parameters
Indications on the display in normal operation
A.D.
M/M 1.1
A.D.
M/T 1.0
A.D.
M/T 2.2
A.D.
T/T 3.0
A.D.
T/T 5.5
Go Electropump operating
Sb Electropump waiting
User displays and settings
(keys MODE and SET 2 seconds )
SP Setting the set-point pressure ( in bar ). Default: 3 bar 3.0 bar 3.0 bar 3.0 bar 3.0 bar 3.0 bar
Installer displays and settings
(keys MODE and SET and – 5 seconds )
rC Setting the rated current of the electropump ( in A ) 0.0 A 0.0 A 0.0 A 0.0 A
rt Setting the direction of rotation 00 00 00 00
Fn
Setting the rated rotation frequency of the electropump.
( in Hz )
50 50 50 50 50
od Setting the operating mode 01 01 01 01 01
rP Setting the pressure drop for restarting ( in bar ) 0.5 bar 0.5 bar 0.5 bar 0.5 bar 0.5 bar
Ad Setting the interconnection address
(necessary on sets of several electropumps with exchange)
“- -” “- -” “- -” “- -”
Eb Enabling the booster 02 02 02 02
Technical assistance displays and settings
(keys MODE and SET and + 5 seconds )
tb Setting the reaction time of the water lack blockage ( in s. ) 10 s 10 s 10 s 10 s 10 s
GP Setting the gain of the proportional coefficient of the PI 1.0 1.0 1.0 1.0 1.0
GI Setting the gain of the integral coefficient of the PI 1.0 1.0 1.0 1.0 1.0
FS Setting the maximum rotation frequency of the electropump
( in Hz )
50 50 50 50 50
FL
Setting the minimum rotation frequency of the electropump.
( in Hz )
0 0 0 0 0
Ft Setting the low flow rate threshold 15 15 15 15 15
CM Exchange method on sets of 2 electropumps 01 01 01 01
AE Setting the enabling of the anti-block/anti-frost function 01 01 01 01 01
SF Setting the starting frequency 45
St Setting the starting time 1.0
i 1 Setting the function of input 1 (float) 01 01 01
i 2 Setting the function of input 2 (set point selection) 01 01 01
i 3 Setting the function of input 3 (enable ) 01 01 01
P1 Setting the auxiliary setpoint pressure (in bar)
- in function of input 2 -
2.5 bar 2.5 bar 2.5 bar
o1
Setting the function of output 1 (default value: 2; function: ON alarm )
02 02 02
o2
Setting the function of output 2 (default value: 2; function: ON operating )
02 02 02
Displays of the main values
(MODE key)
Fr Display of the current rotation frequency (in Hz)
UP Display of pressure (in bar)
C1 Display of the phase current of the electropump (in A)
UE Display of the version of the software with which the appliance is
equipped
DISPLAY (keys SET and – for 2 seconds )
UF Display of the flow
ZF Display of zero flow
FM Display of the maximum rotation frequency (in Hz)
tE Display of the temperature of the power stages (in °C)
bt Display of the temperature of the electronic card (in °C)
GS Display of running status
FF Display of the log of errors and blockages
Access to manual mode
(keys SET and + and – 5 seconds )
FP Setting the test frequency in manual mode (in Hz)
the set value FS
40 40 40 40 40
UP Pressure display (in bar)
C1 Display of electropump phase current (in A)
rt Setting the direction of rotation
UF Display of flow
ZF Display of zero flow
System reset
(keys MODE and SET and + and – )
ZF General reset ( ZF appears when leaving reset and restarting )

ENGLISH
54
14. INDICATIONS ON THE DISPLAY
Identifying s. Description Factory parameters
Restoring the factory settings
(keys SET and + for 2 seconds when switching on)
A.D.
M/M 1.1
A.D.
M/T 1.0
A.D.
M/T 2.2
A.D.
T/T 3.0
A.D.
T/T 5.5
EE Saving and reading the factory settings on the EEprom
Error and status conditions
bL Blockage due to water lack
bP Blockage due to absence of pressure sensor
LP Blockage due to low supply voltage
HP Blockage due to high supply voltage
ot Blockage due to overheating of the power stages
oC Blockage due to current overload in the electropump motor
oF Blockage due to current overload in the output stages
oF/ot Blockage due to current overload in the output stages
with temperature of the stages higher than 45°C
SC Blockage due to short circuit in the output stages
EC Blockage due to non setting of the rated current (rC) or of the rated
frequency (Fn)
E0…E7 Internal error 0…7
F1 Status / Alarm input 1
F3 Status / Alarm input 3
Other manuals for ACTIVE DRIVER M/M 1.1
1
This manual suits for next models
4
Table of contents
Popular Control System manuals by other brands

Advantech
Advantech AIIS-5410P user manual

Emerson
Emerson TraxOil OM3-020P operating instructions

Wireless Solution
Wireless Solution W-DMX TRX Implementation guide

Bosch
Bosch Rexroth NYCe 4000 instruction manual

Extron electronics
Extron electronics TLP Pro 720M user guide

SOMFY
SOMFY SOLIRIS Uno installation guide