Daintree GE Current WA100-PM User manual

(WA100-PM)
Daintree®
Wireless Adapter
BEFORE YOU BEGIN
Read these instructions completely and carefully.
Save these instructions for future use.
1Installation Process
Installation Guide
WA100-PM |DT113
1. Disconnect power before installation. Turn off all power
toaffectedlightxturesbyturningoffcircuitbreakers.
Conrmthatpowerisoffatalllightxturesbefore
continuing installation.
2. Set the WA100-PM DIP switches to support the device(s)
beingconnectedtoit.SeeDIP Switch Settings (page 2).
3. IMPORTANT: Afxthesmalllabelwith4-5digitsofthe
WA100-PM’sIEEEaddressontheoorPlantoindicate
its location.
4. Mount the WA100-PM in the driver cavity of the light
xture,orexternaltothelightxture,ortoajunctionbox
approved for the application. See Mounting (page 12).
5. Connect low voltage wiring from the WA100-PM to the
driver,switch(es)and/orsensorsasappropriateforyour
application. See Wiring (pages 3-11). Cap any unused wires.
Risk of electrical shock.Disconnectpowerbeforeservicingor
installing product.
Install in accordance with National Electric Code and local codes.
WARNING
Risk of injury. Wear safety glasses and gloves during installation and
servicing.
CAUTION
The Daintree WA100-PM Wireless Adapter forms part of the
DaintreeNetworkedwirelesscontrolssolutionforsmart
commercialandindustrialbuildings.Ittransmitsandreceives
messages over the wireless ZigBee®networkandcontrolslights.
TheWA100-PMisanACpowereddevicethatprovidesOn/Off
switching as well as 0-10V analog dimming control for
LEDdriversandballasts.*Italsoprovidespowerforlowvoltage
occupancysensors,photosensors(daylightharvesters),
wallswitches,andcontrolsignalswhileitprovidesthewireless
adaptationthatenablesthemtocommunicatewiththe
rest of the wireless control solution. The control signals to and
fromtheseconnecteddevicespassbetweentheWA100-PM
and the Wireless Area Controller in Daintree Controls Software
(DCS)webapplication.
Error/Test — On when the Wireless Adapter is in an error state.
Flashes to indicate unit Reset and during Installation Test Mode (red).
Joined —OnwhentheWirelessAdapterhasjoinedaZigBee
®
network.
Flashes to indicate Reset and during sensor Installation Test Mode (green).
Power — On when power is applied to the Wireless Adapter (green).
LED Indicators
6. Connect line voltage wires from the supply circuit to the
WA100-PM and to the driver as shown in Wiring. Cap any
unused wire.
7.Checkloadcircuitsthenturnonthecircuitbreakerstopower
up the WA100-PM. The light connected to the WA100-PM turns
On when power is initially applied (and when power is restored
after a power failure).
8. Ensure the WA100-PM green Power LED is On.
9.PressandholdtheblueRESETbuttonontheWA100-PMfor
3secondstoresettheunit.Releasethebuttonwhenthegreen
JoinedLEDandtheredErrorLEDsbeginashing.
10. Perform the installation test appropriate for your application.
See Installation Tests(pages13-14)
Power
LED
Reset
Button
Joined
LED
Error
LED

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
2
2
4
3
WA100-PM Model Variants
DIP Switch Mode descriptions
DIP Switch settings
ThemodelnumberWA100wastheoriginalversionofthe
adapter and is no longer sold. The WA100-PM model monitors
and measures the power consumption of the connected lighting
load. The WA100-PM reports power measurement data to DCS.
Figure 1: DIP switch location
Figure 2: DIP Switch Table — See DIP switch Mode
descriptions for information about each option.
DIPswitchsettingsenabletheWA100-PMtooperatea
ppropriately for the type of lighting control it provides and
the type of device(s) to which it is connected and adapting
forwirelesscommunication.SetDIPswitchesbasedonlyon
the devices that are physically wired to the WA100-PM.
There are two primary adaptation modes to choose from as
determinedbytheDIPswitch1setting.
• InLightAdapterMode,thesettingsareforthetype
oflightingcontrolthatisavailableontheconnected
driver,and/orthesensortype(s)connectedtothe
WA100-PM.
• IntheSwitchAdapterMode,settingsareforthe
connected switch type and whether the WA100-PM
is connected to a light.
CongureDIPswitchsettingsonlyasshowninthisinstruction.
Incorrect switch settings will cause unexpected operation.
AfteryouchangeDIPswitchsettings,youneedtopresstheblue
Resetbuttonfor3secondstoresettheunit.Releasethebutton
whenthegreenJoinedandredErrorLEDsbeginashing.
Light Adapter Mode
Control Type
On/Off + 0-10V dimming: providesOn/Offcontrolusingitsline
voltage Switched Load connection to the driver(s). It also provides
0-10V dimming control to the driver(s).
On/Off (no dimming): providesOn/Offcontrolusingitsline
voltageSwitchedLoadconnection,anditslowvoltagedigital
outputtoanexternalrelay.Note,bothoutputsareswitchedat
the same time in this driver control mode.
Alternate:providesOn/Offswitchingforonedriverloadusingits
linevoltageSwitchedLoadconnection,anditslowvoltagedigital
outputtoanexternalrelaytoswitchaseconddriverload.This
allowslightinglevelcontrolfornoload(0%),oneortheotherof
thetwoloads,andbothloads(100%).SeeFigure13.
Bi-Level:providesOn/Offswitchingforonedriverwithtwoloads
using its line voltage Switched Load connection and low voltage
digitaloutputanexternalrelaytoswitchthesecondload.This
allowslightingleveltocontrolfornoload(0%),partialload
(accordingtodrivercapability)orfullload(100%).SeeFigure12.
No Driver (sensors only): provides wireless adaptation to
connectedoccupancysensorand/orphotosensoronly.No
driver control.
Sensor
Toprovidewirelessadaptationforsensors,setDIPswitches1,5&
6 according to the type(s) of sensors connected to the WA100-PM.
Range Extender
TheWA100-PMjoinstheZigBeenetworkandactsonlyasa
wirelessrepeatertoimprovethewirelessrangeand/orreliability.
No lights or devices are connected to the WA100-PM.
Occupancy
Photosensor
Both
None
Range Extender*
nolight,nosensor
*Validonlywithrmwarev2.6orhigher
On/Off+0-10Vdimming
On/Off(nodimming)
Alternate Switching
Bi-Level
No Driver (sensors only)
SensorSwitches5&6Mode DriverTypeSwitches1to4
DIP Switch Positions
Light Adapter
OFF
ON
Light + Switch
(driver&switch
are same type)
No Light
(switch only)
Dimming
On/Off(nodimming)
Alternate Switch
Bi-Level
Light OutputSwitches5&6Mode Switch TypeSwitches1to4
Switch Adapter
Figure 2: DIP Switch Table — See DIP switch Mode
descriptions for information about each option.

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
3
5
6
7
Switch Adapter Mode
Occupancy Sensor Time Delays
Wiring
Switch Type
Dimming: operating the connected switch generates
dimmingandOn/Offsignals.
On/Off (no dimming): operating the connected switch
generatesOn/Offsignals.
Alternate: operating the connected switch will switch separate
drivers,providingnoload(0%),partialload(oneortheotherof
thetwoloads,accordingtothedriverloading)orfullload(100%).
Bi-Level: operating the connected switch will switch loads
independentlyinabi-leveldriver(or2drivers),providingno
load(0%),partialload(accordingtothedrivercapabilityor
driver loading) or full load (100%).
Light output ID
Light + Switch (driver and switch are the same type): the
connecteddrivermatchestheoperationalcapabilityofthe
switch.Forexample:
•IftheSwitchtypeis“Dimming,”adimmingswitchand0-10V
dimmabledriverarebothconnectedtotheWA100-PM.
See Figure 10.
•IftheSwitchtypeis“On/Off(nodimming)”anOn/Offswitch
isconnectedtotheWA100-PMdigitalinputandOn/Off
driver(s) are connected to the WA100-PM’s line voltage
SwitchedLoadconnectionand/oranexternalrelay
connected to the WA100-PM’s low voltage digital output.
•IftheSwitchtypeis“Bi-Level,”abi-leveldriverandbi-level
switch connect to the WA100-PM.
No Light (switch only): provides wireless adaptation for the
selected switch type only. No light is connected to the WA100-PM.
Occupancysensortimedelaysmustbesetforminimum.
WhentheDaintreeNetworkediscommissioned,timedelays
aresetintheDaintreeControlsSoftware(DCS)webapplication.
TheseDCS“Offdelays”startcountingdownafterthesensor’s
internaltimedelayexpires.Therefore,setoccupancysensorsfor
the minimum time delay during the WA100-PM installation.
Line voltage wiring connects to the electrical supply circuit and
tothedriver(s).TheBlack(Hot)yingleadandtheRed(Switched
Load)yingleadare14AWG.TheWhite(Neutral)yingleadis
18AWG.
Lowvoltage22AWGyingleadsprovideforconnectionsto
supply low voltage power and carry control signals to and
fromlowvoltagedevicessuchasswitches,dimmers,photocells,
isolated relays and 0-10V analog dimming driver controls. Do
not connect any single low voltage device to more than one
WA100-PM.
While the WA100-PM is in Installation Test mode the low voltage
devices connected to the WA100-PM directly control the lights
wiredtothesameWA100-PM.AfteryouexitInstallationTest
mode,thelightsturnOnandareNOTcontrolledbythedevices
connected to the WA100-PM.
Afterjoiningthewirelessnetwork,thecontrolsignalsfromthe
low voltage devices pass through the WA100-PM and are sent
wirelesslytotheDaintreeNetworked.Dependingonthezone
anddevicecongurationintheDCS,wirelesssignalsfromthe
WAC to the WA100-PM determine the operation of the light(s).
Design Caution
Wirelessadaptersmustalwaysbeprovidedwithuninterrupted
power. Do not install a wireless adapter such as the WA100-PM to
control an electrical circuit that provides power to other wireless
devices or adapters. If power to wireless adapters or devicesis shut
off,controlandcommunicationwiththemisdisabled.
Risk of electrical shock. Disconnectallpowerbeforeinstallationand
duringservicing.DonotopenWA100-PMenclosure;nouser-serviceable
parts inside. All installation and maintenance of line voltage equipment
mustbeperformedbyaqualiedelectrician.TheWA100-PMmustbe
installedinaccordancewithalllocal,state,andnationalelectricalcodes
andrequirements.Wiringconnectorsarenotsupplied.ULrecognized
wiringconnectorsmustbeusedintheinstallation.
CAUTION
Reducing noise on low voltage (0-10V) wiring
• Keep wiring as short as practical
• Keep signal lines separate from mains voltage lines.
• Reducetheareacreatedbythesignallinesand
theGNDreturn(i.e.,keepthemclosetogether).
• IfpossibletwistthesignallinewiththeGNDreturn.

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
4
Figure 3: Wiring Identication
Figure 4: Dimming Light Fixtures
7Wiring Continued
Perform Installation Test Suite 1
DIP Switches
DriverType:
On/Off+0-10V
dimming
WiredSensor:
None
On 1 2 3 4 5 6
(ALL OFF)
OFF
ON

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
5
Figure 5: On/Off (non-dimming) Light Fixtures
ThiscongurationallowstheWA100-PMtoprovideautomatic
On/Offswitchingoflightxtures.
Figure 6: On/Off (non-dimming) Light Fixture(s), Occupancy
Sensor conguration
ThiscongurationallowstheWA100-PMtoprovideautomatic
On/Offswitchingbasedonoccupancy.Setoccupancysensor
for minimum time delay.
7Wiring Continued
Perform Installation Test Suite 1
DIP Switches
DriverType:
On/Off+0-10V
dimming
WiredSensor:
None
On 1 2 3 4 5 6
(#4 ON)
Perform Installation Test Suite 2
DIP Switches
DriverType:
On/Off
(no dimming)
WiredSensor:
Occupancy
On 1 2 3 4 5 6
(#4, 5 ON)
OFF
ON
OFF
ON

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
6
Figure 7: Dimming Driver(s), Occupancy Sensor conguration
ThiscongurationallowstheWA100-PMtoprovideautomatic
0-10VdimmingcontrolandtoswitchdriversOn/Offbasedon
occupancy. Set occupancy sensor for minimum time delay.
Figure 8: Dimming Light Fixture(s), Photosensor conguration
ThiscongurationallowstheWA100-PMtoprovideautomatic
0-10VdimmingcontrolandtoswitchlightxturesOn/Off.
7Wiring Continued
OFF
ON
Perform Installation Test Suite 2
DIP Switches
DriverType:
On/Off
dimming
WiredSensor:
Occupancy
On 1 2 3 4 5 6
(#5 ON)
OFF
ON
Perform Installation Test Suite 8
DIP Switches
DriverType:
On/Off
dimming
WiredSensor:
Photosensor
On 1 2 3 4 5 6
(#6 ON)

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
7
Figure 9: Dimming Light Fixture(s), Photosensor, Occupancy
Sensor conguration
ThiscongurationallowstheWA100-PMtoprovideautomatic
0-10VdimmingcontrolandtoswitchdriversOn/Off.Set
occupancy sensor for minimum time delay.
Figure 10: Dimming Light Fixture(s) and Switch conguration
ThiscongurationallowstheWA100-PMtoprovide0-10Vdimming
controlandtoswitchlightxturesOn/Off.Italsoprovidesmanual
On/Offcontrolthroughalowvoltagemomentarycontactswitch.
7Wiring Continued
OFF
ON
Perform Installation Test Suite 4
DIP Switches
DriverType:
On/Off
dimming
WiredSensor:
Photosensor
On 1 2 3 4 5 6
(#5,6 ON)
OFF
ON
Perform Installation Test Suite 1
DIP Switches
Wired
SwitchType:
dimming
LightOutput::
Driver same as
switch
On 1 2 3 4 5 6
(#1,5 ON)

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
8
Figure 11: Bi-level Switching
ThiscongurationallowstheWA100-PMtoswitchloads
independentlyinabi-leveldriver(or2drivers),providingno
load(0%),partialload(accordingtothedriver/ballast
capability)orfullload(100%).
Figure 12: Alternate Switching
ThiscongurationallowstheWA100-PMtoalternateinswitching
separatedrivers,providingnoload(0%),partialload(accordingto
the driver loading) or full load (100%).
Always connect the smaller proportion of the total load to the
WA100-PM’s RED Switched Load wire.
7Wiring Continued
OFF
ON
Perform Installation Test Suite 1
DIP Switches
Driver:
Bi-Level
WiredSensor:
None
On 1 2 3 4 5 6
(#3,4 ON)
OFF
ON
Perform Installation Test Suite 1
DIP Switches
Driver:
Alternate
Switching
WiredSensor:
None
On 1 2 3 4 5 6
(#3 ON)

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
9
Figure 13: Switching a Branch Circuit
ThiscongurationallowstheWA100-PMtoprovideOn/Off
switchingofabranchcircuit.
Figure 14: 208V 2-Pole (Phase-to-Phase) wiring
ThiscongurationallowstheWA100-PMtoprovideOn/Off
switchingofabranchcircuit.
7Wiring Continued
OFF
ON
OFF
ON
Perform Installation Test Suite 1
DIP Switches
DriverType:
On/Off
(no dimming)
WiredSensor:
None
On 1 2 3 4 5 6
(#4 ON)
Perform Installation Test Suite 1
DIP Switches
DriverType:
On/Off
(no dimming)
WiredSensor:
None
On 1 2 3 4 5 6
(#4 ON)

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
10
Figure 15: Switching Contactors
ThiscongurationallowstheWA100-PMtoprovideOn/Off
switchingcontroltoanexternalcontactor.
7Wiring Continued
OFF
ON
Perform Installation Test Suite 1
DIP Switches
DriverType:
On/Off
(no dimming)
WiredSensor:
None
On 1 2 3 4 5 6
(#4 ON)

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
11
Figure 17: Emergency and Regular Light Fixtures: Wiring
to Dim while Regular Power is Available
Inthisapplication,theWA100-PMispoweredbytheRegular
powercircuitandisinstalledinsidetheRegularLightFixture.
While Regular power is supplied to the RRU-2 the WA100-PM
providesswitchedOn/OffpowertotheRegularLightFixture.
The WA100-PM also controls dimming to the Regular and
EmergencyLightFixture.The0-10Vdimmingcircuitfromthe
WA100-PMisbroughtintotheEmergencyLightFixture.The
EmergencyLightFixtureispoweredbytheEmergency
power circuit.
WhentheRRU-2senseslossofRegularpower,theRRU-2
disconnects the 0-10V output from the WA100-PM and the
EmergencyLightFixtureoperatesatmaximumoutputfromthe
Emergencypowercircuit.(Note:IftheRRU-2isnotinstalled,the
EmergencyFixturewilldimtominimumbecausetheWA100-PM
0-10V output shorts when the adapter loses power.)
7Wiring Continued
Set DIP switches and perform Installation Test appropriate
to 0-10v dimming and connected sensors.
Inthewiringdiagramhere,whileRegularpowerissuppliedtothe
LVSmodelRRU-X-UMtheWA100-PMprovidesswitchedOn/Off
powerand0-10Vdimmingcontroltothexturedriverorballast.
When the RRU-X-UM senses loss of Regular power it passes
Emergencypowerdirectlytothexture.Itdisconnectsthe
WA100-PM switched output and disconnects the WA100-PM
dimmingcontrolsothatthexturewilloperateatmaximum
output during the power failure.
Figure 16: Bypass WA100 switched power and 0-10V
dimming control during power failure

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
12
Figure 18: Secure unused wires
Figure 19: Mounting in driver channel
Figure 20: Mounting with the
included bracket
Figure 21: Mounting external to the top
of a suspended xture
Securing Low Voltage Wires
1.MakesuretheunitisNOTpowered.
2. Cuttheunusedlowvoltagewiresapproximatelyve
inchesfromwheretheyexittheWA100-PMbody.
TheWA100-PMisdesignedsothatitcanbemountedinavariety
ofways.Dependingontheconstructionofthextureanditsability
topropagateradiosignals,itcanbemountedinsidethexturein
theballast/driverchannel.Aprintedbarcodelabelwiththefull
IEEEaddressisincludedwiththeWA100-PM.Afxthislabeltothe
outsideofthexture.Chooseastandardlocationsothatwhen
someonelooksforxturescontainingaWA100-PM,theywill
easilyndit.
UsingtheMountingBracket
ThemountingbracketincludedwiththeWA100-PMandshownin
theillustrationbelowprovidesascrewmountingalternative.
Thebrackethasaslotthatallowswirestoremainconnectedasyou
snapthebracketontotheWA100-PMnipple.TheWA100-PM
canbesecuredattheotherendusingtheintegralscrewtab.
Alternatively,itcanbemountedexternallytoajunctionbox,
enclosure,orxturehousingthrough
a1/2”knockout.
3.Isolatetheendofeachwireusingawirenut,shrinktubing,or
equivalent.
4. Wrap the unused low voltage wires around the side of the
adapterinabunch,andsecuretheminplaceusingawhiteor
clearcabletie.
8
9
Trimming and Dressing
Mounting

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
13
10
Alllightingdevices,includingwirelessadapters,mustbetested
for proper operation.
AftersettingtheDIPswitchesforyourapplication,mounting,
wiringlowvoltage,wiringlinevoltage,poweringupandresetting
theunit,performtherecommendedInstallationTest.The
InstallationTestmodeautomaticallytimesoutafter5minutes
of no activity.
WhiletheWA100-PMisinInstallationTestmode,thelowvoltage
devices connected to the WA100-PM directly control the lights
wiredtothesameWA100-PM.AfteryouexittheInstallationTest
mode,thelightsturnOnandareNOTcontrolledbythedevices
connected to the WA100-PM. After commissioning the Daintree
Networkedsystem,lightingcontrolisdeterminedbyconguration
settings in the Daintree Controls Software.
IMPORTANT NOTICES
Complete Installation Tests
Successful commissioning is dependent on testing each
wireless-adaptedlightingxtureand/orcontroldeviceatthe
timeofinstallation.Findinginstallationissuesordeviceproblems
earliersavessignicanttimeduringthecommissioningprocess.
Record IEEE Addresses
Ifyouhavenotalreadydoneso,besurethateachWA100-PM’s
IEEEaddress(last4or5digits)isrecordedonthefacilityoor
plan.Youcanusethe4or5digitlabelsuppliedwiththe
WA100-PMoryoucanwritethelast4or5digitsontheoorplan.
Thisinformationwillbeusedduringthecommissioningprocess.
Afterthelightinginstallationiscomplete,amarked-upcopyof
thefacilityoorplanshowingtheidentityandlocationofeach
wirelessadapter(includingassociatedlightxtures,switchesand
sensors)shouldbeavailable.Thiswillsimplifyandexpeditethe
commissioning process.
TestSuite1:
On/Off, Dimming, Alternate Switching or Bi-Level Drivers Only
1.PressandimmediatelyreleasetheblueResetbutton.The
redErrorLEDashesonce,thenpausesandrepeats.
2.CheckthattheconnectedlightscycleOnandOff,orcycle
frommaximumtominimumbrightnessthenturnOffper
theDIPswitchconguration.
3.PressandimmediatelyreleasetheResetbuttontoexit
testing.
4.PressandholdtheblueRESETbuttonontheWA100-PM
for3secondstoresettheunit.Releasethebutton
when the green Joined LED and the red Error LEDs
beginashing.
TestSuite2:
Any Driver + Occupancy Sensor
1. PressandimmediatelyreleasetheblueResetbutton.
TheredErrorLEDashesonce,thenpausesandrepeats.
2.CheckthattheconnectedlightscycleOnandOff,orcycle
frommaximumtominimumbrightnessthenturnOff
pertheDIPswitchconguration.
TestSuite2Continued:
3.PressandimmediatelyreleasetheblueResetbuttonagain.
TheredErrorLEDashestwice,
then pauses and repeats.
4. Trigger the occupancy sensor. The light connected to the
driver turns On. When the sensor
times out the light turns Off.
5.PressandimmediatelyreleasetheResetbuttontoexit
testing.
6. PressandholdtheblueRESETbuttonontheWA100-PM
for3secondstoresettheunit.Releasethebutton
when the green Joined LED and the red Error LEDs
beginashing.
Installation Tests
TestSuite3:
Dimming Driver + Occupancy Sensor + Photosensor
1.PressandimmediatelyreleasetheblueResetbutton.The
redErrorLEDashesonce,thenpausesandrepeats.
2. Checkthatthelightsconnectedtothedrivercyclefrom
maximumtominimumbrightnessthenturnOff,then
repeat.
3.PressandimmediatelyreleasetheblueResetbutton.The
redErrorLEDashestwice,thenpausesandrepeats.
4. Trigger the occupancy sensor. The green Joined LED turns
On and the light connected to the driver turns On.
When the sensor times out the Joined LED and light
turns Off.
5.PressandimmediatelyreleasetheblueResetbuttonagain.
TheredErrorLEDashesthreetimes,thenpauses
and repeats.
6. The light connected to the driver turns On.
7. The light’s output is proportional to the amount of light
receivedbythephotosensor.
•Fordimminglights,shineabrightlightatthe
photosensor–thelightgetsbrighter.
Cover the photosensor – the light gets dim.
•Forswitchedlights,coverthephotosensor–thelight
turnsOff.Shineabrightlightatthephotosensor–the
light turns On.
8.PressandimmediatelyreleasetheResetbuttontoexit
testing.
9. PressandholdtheblueRESETbuttonontheWA100-PM
for3secondstoresettheunit.Releasethebutton
when the green Joined LED and the red Error LEDs
beginashing.
TestSuite4:
Any Switch(es) + Any Matching Light Type(s)
1.PressandimmediatelyreleasetheblueResetbutton.The
redErrorLEDashesonce,thenpausesandrepeats.
2.CheckthattheconnectedlightscycleOnandOff,orcycle
frommaximumtominimumbrightnessthenturnOff
pertheDIPswitchconguration.
3.PressandimmediatelyreleasetheblueResetbuttonagain.
TheredErrorLEDashesfourtimes,thenpauses
and repeats.

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
14
TestSuite8:
TestSuite9:
Dimming Driver + Photosensor
1.PressandimmediatelyreleasetheblueResetbutton.The
redErrorLEDashesonce,thenpausesandrepeats.
2.Checkthatthelightsconnectedtothedrivercyclefrom
maximumtominimumbrightnessthenturnOff,
then repeat.
3.PressandimmediatelyreleasetheblueResetbuttonagain.
TheredErrorLEDashesthreetimes,thenpauses
and repeats.
4. The light connected to the driver turns On.
5.Increasetheamountoflightatthephotosensorbyshining
abrightlightatit.Thelight’soutputisproportional
totheamountoflightreceivedbythephotosensor.
• Fordimminglights,shineabrightlightatthe
photosensor–thelightgetsbrighter.Coverthe
photosensor – the light gets dim.
• Forswitchedlights,coverthephotosensor–thelight
turnsOff.Shineabrightlightatthephotosensor–the
light turns On.
6. PressandimmediatelyreleasetheResetbuttontoexit
testing.
7. PressandholdtheblueRESETbuttonontheWA100-PM
for3secondstoresettheunit.Releasethebutton
when the green Joined LED and the red Error LEDs
beginashing.
Occupancy Sensor + Photosensor
1.PressandimmediatelyreleasetheblueResetbutton.The
redErrorLEDashestwice,thenpausesandrepeats.
2. Trigger the occupancy sensor. The green Joined LED turns
On. When the sensor times out the Joined LED
turns Off.
3. PressandimmediatelyreleasetheblueResetbuttonagain.
TheredErrorLEDashesthreetimes,thenpauses
and repeats.
4.ThegreenJoinedLEDbeginstoash.Increasetheamount
oflightatthephotosensorbyshiningabrightlight
atit.ThegreenJoinedLEDashesatafasterrate.
5.PressandimmediatelyreleasetheResetbuttontoexit
testing.
6. PressandholdtheblueRESETbuttonontheWA100-PM
for3secondstoresettheunit.Releasethebutton
when the green Joined LED and the red Error LEDs
beginashing.
TestSuite4:Continued
4.Operatetheswitch(es)connectedtotheWA100-PMand
observethatthelightsturnOn,Off,andDimasexpected.
5.PressandimmediatelyreleasetheResetbuttontoexit
testing.
6.PressandholdtheblueRESETbuttonontheWA100-PM
for3secondstoresettheunit.Releasethebutton
when the green Joined LED and the red Error LEDs
beginashing.
TestSuite5:
TestSuite6:
TestSuite7:
Occupancy Sensor Only
1.PressandimmediatelyreleasetheblueResetbutton.
TheredErrorLEDashestwice,thenpausesandrepeats.
2. Trigger the occupancy sensor. The green Joined LED turns
On. When the sensor times out the Joined LED turns Off.
3.PressandimmediatelyreleasetheResetbuttonto
exittesting.
4. PressandholdtheblueRESETbuttonontheWA100-PM
for3secondstoresettheunit.Releasethebutton
when the green Joined LED and the red Error LEDs
beginashing.
Photosensor Only
1.PressandimmediatelyreleasetheblueResetbutton.The
redErrorLEDashesthreetimes,thenpauses
and repeats.
2.ThegreenJoinedLEDbeginstoash.Increasetheamount
oflightatthephotosensorbyshiningabrightlight
atit.ThegreenJoinedLEDashesatafasterrate.
3.PressandimmediatelyreleasetheResetbuttonto
exittesting.
4. PressandholdtheblueRESETbuttonontheWA100-PM
for3secondstoresettheunit.Releasethebutton
when the green Joined LED and the red Error LEDs
beginashing.
Switch Only (On/Off, Dimming, Alternate Switching or Bi-Level)
1. PressandimmediatelyreleasetheblueResetbutton.
TheredErrorLEDashesfourtimes,thenpauses
and repeats.
2. Operate the switch connected to the WA100-PM. The
green Joined LED turns On for the duration of the switch
activation(appliestoOn,Off,andDimfunctions).
3.PressandimmediatelyreleasetheResetbuttontoexit
testing.
4.PressandholdtheblueRESETbuttonontheWA100-PM
for3secondstoresettheunit.Releasethebuttonwhen
thegreenJoinedLEDandtheredErrorLEDsbegin
ashing.
10 Installation Tests Continued

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
15
11 13
14
After the Installation Test is complete the WA100-PM is ready to
communicate with the Daintree Wireless Area Controller
(WAC)andtheDaintreeControlsSoftware(DCS)web-based
lightingmanagementuserinterface.Uponcommissioning,
theWA100-PM“Join”LEDturnsonsolidandremainsonaslong
astheWA100-PMisincludedintheZigBeeNetwork.
Afterjoiningthenetwork,thelowvoltagedevicesconnectedto
the WA100-PM do not directly control the lights that are
wired to the same WA100-PM. The control signals from the low
voltage devices pass through the WA100-PM and are sent
wirelesslytotheDaintreeNetworked.Dependingonthezone
anddevicecongurationintheDCS,wirelesssignalsfrom
the WAC to the WA100-PM determine the operation of the
light(s).
Formoreinformationaboutconguringthelightingcontrol
network,seetheinstructionsandon-linehelpprovidedwith
theDaintreeControlsSoftwarewebapplication.
The Installation Test procedure fails.
1.ConrmthattheWA100-PMispowered.
2.ChecktheconnectionsfromtheWA100-PMtothedriver(s)
and low voltage control devices.
3. ChecktobesuretheWA100-PMDIPswitchsettings
are correct.
4. PressandholdtheResetbuttonfor3secondstoreset
the WA100-PM.
5. Perform the Installation Test again.
Connected lights do not turn Off during the occupancy sensor
Installation Test.
1. Makesurethesensorisnotdetectingoccupancy.
2. Checktheoccupancysensortimedelayandmakesureitis
set for minimum.
When the Daintree Networked is commissioned, time delays are
set in the Daintree Controls Software system. These DCS “Off delays”
start counting down after the sensor’s internal time delay expires.
Therefore, set occupancy sensors for the minimum time delay
during the WA100-PM installation.
The red Error LED is ashing once every second.
DIPswitchcongurationisinvalid.AtleastoneDIPswitchmustbe
Ontoenableaninterface.
1. Enabletheinterface(s)thatareconnectedbyturning
appropriate DIP switch(es) On.
2. PresstheblueResetbuttonfor3 seconds to reset the unit.
Joining the Zigbee Lighting Control Network
12 Troubleshooting
Thisequipmenthasbeentestedandfoundtocomplywith
thelimitsforaClassBdigitaldevice,pursuanttoPart15of
theFCCRules.Theselimitsaredesignedtoprovidereasonable
protection against harmful interference in a residential
installation.Thisequipmentgenerates,usesandradiatesradio
frequencyenergyand,ifnotinstalledandusedinaccordance
withtheinstructions,maycauseharmfulinterferencetoradio
communications.However,thereisnoguaranteethat
interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television
reception,whichcanbedeterminedbyturningtheequipment
offandon,theuserisencouragetotrytocorrectthe
interferencebyoneormoreofthefollowingmeasures:
• Reorient or relocate the receiving antenna;
• Increasetheseparationbetweentheequipment
and receiver;
• Connect the equipment into an outlet on a circuit different
from that to which the receiver is connected;
• Consultthedealeroranexperiencedradio/TVtechnician
for help.
ProductcomplieswithPart15oftheFCCRules.Operationis
subjecttothefollowingtwoconditions:(1)Thisdevicemaynot
causeharmfulinterference,and(2)Thisdevicemustacceptany
interferencereceived,includinginterferencethatmaycause
undesiredoperation.CANICES-005B/NMB-005B
FCC Warning Message
Industry Canada (IC) Warning Message

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
16
15
Plug load control functionality for the WA100-PM is made
availablewithWA100-PMrmwareprovidedinversion3.5.3.1.
DuringtestingthePlugLoadcycleson/offinsyncwiththe
lightingload.Relaysusedtocontrolplugloadsmustbe
compliantwithUL498(AttachmentPlugandReceptacles)
or equivalent.
Wiring for Combination Plug Load
(Basic Aux Relay) and Dimming Light
Inthewiringdiagrambelow,theWA100-PMisusedto
controlbothadimminglightandaplugloadcircuit.
Wiring for Combination Plug Load (Basic Aux Relay)
and On/Off Light
Inthewiringdiagrambelow,theWA100-PMisusedtocontrol
bothanOn/Offlightandaplugloadcircuit.
Plug Load Applications
OFF
ON
Perform Installation Test Suite 1
DIP Switches
Driver:On/Off+
0-10V dimming.
PlugLoad:
On/Off
WiredSensor:
None
On 1 2 3 4 5 6
(#2,3 On)
Perform Installation Test Suite 1
DIP Switches
Driver:
On/Off
PlugLoad:
On/Off
WiredSensor:
None
On 1 2 3 4 5 6
(#2,4 On)
OFF
ON
*0-10VDimmingoutput,5mAavailable,Upto10LEDdriversor
uorescentballaststypical;thechanceofnoiseonthesignal
increases with more.
**RelaysusedtocontrolplugloadsmustbecompliantwithUL498
(Attachment Plug and Receptacles) or equivalant.

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
17
15
Wiring for Combination Plug Load (Aux Relay with
Input Control Signal) and Dimming Light
Inthewiringdiagrambelow,theWA100-PMisusedto
controlbothadimminglightandaplugloadcircuit.
Plug Load Applications Continued
Perform Installation Test Suite 1
DIP Switches
Driver:
On/Off+0-10V
dimming. Plug
LoadOn/Off
WiredSensor:
None
On 1 2 3 4 5 6
(#2,3 On)
OFF
ON
*0-10VDimmingoutput,5mAavailable,Upto10LEDdriversor
uorescentballaststypical;thechanceofnoiseonthesignal
increases with more.
**RelaysusedtocontrolplugloadsmustbecompliantwithUL498
(Attachment Plug and Receptacles) or equivalant.

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
18
15
Wiring for Combination Plug Load (Aux Relay with Input
Control Signal) and On/Off Light
Inthewiringdiagrambelow,theWA100-PMisusedto
controlbothanOn/Offlightandaplugloadcircuit.
Plug Load Applications Continued
Perform Installation Test Suite 1
DIP Switches
Driver:On/Off
PlugLoad:
On/Off
WiredSensor:
None
On 1 2 3 4 5 6
(#2, 4 On)
OFF
ON
*0-10VDimmingoutput,5mAavailable,Upto10LEDdriversor
uorescentballaststypical;thechanceofnoiseonthesignal
increases with more.
**RelaysusedtocontrolplugloadsmustbecompliantwithUL498
(Attachment Plug and Receptacles) or equivalant.

Installation GuideDaintree®Networked Wireless Adapter (WA100-PM)
Theseinstructionsdonotpurporttocoveralldetailsorvariationsinequipmentnortoprovideforeverypossiblecontingencytobemetinconnectionwithinstallation,operation
ormaintenance.Shouldfurtherinformationbedesiredorshouldparticularproblemsarisewhicharenotcoveredsufcientlyforthepurchaser’spurposes,themattershouldbe
referredtoGECurrent,aDaintreecompany.
Questions:
Web: products.gecurrent.com
Phone: 1-866-855-8629
www.gecurrent.com
©2021CurrentLightingSolutions,LLC.Allrightsreserved.GEandtheGEmonogramaretrademarksofthe
GeneralElectricCompanyandareusedunderlicense.Informationprovidedissubjecttochangewithoutnotice.
Allvaluesaredesignortypicalvalueswhenmeasuredunderlaboratoryconditions.
DT113(Rev.04/28/2021
CAUTION
RISK OF EXPOSURE IF BATTERY IS REPLACED BY AN
INCORRECT TYPE. DISPOSAL OF USED BATTERIES
ACCORDING TO THE INSTRUCTIONS.
WFA100-PM
Input Voltage 120-277VAC,50-60Hz
Switched Output 15Adriver/incandescent@120-277VAC
Relay 1hp@120-230VAC(switchedtoHot/Active)
Low Voltage 24VDC;75mAmaximum
Output
Low Voltage Intel®Atom™ProcessorE3805
Wiring
Memory and 22AWG,600V,UL1015,plenumratedMax.
Storage recommended length of up to 100’ (30m)
Analog Dimming 0-10VDC,5mAmax(sinkorsource),upto
10typical0.5mAsinkingdrivers/ballasts*
Analog Input Photosensor 0-10VDC
Digital Input (2) Activehigh.Occupancysensor,
DimUp/Down(switchmode)
Digital Output LSD(lowsidedriver)auxrelaycontrol,
75mAmaximum(includingattached
sensors)
Radio Properties 2.4GHz,+8dBm,Rangedependent
onRFpropagationvariablessuch
asmetalobstacles
Operating Indoor,drylocation
Environment -4°to149°F(-20°to65°C)
Compliance CSAcertied,plenumrated,
FCCPart15,CAIC
Mounting 1/2”knockout,screwtab,optional
mountingbracketsupplied
Dimensions 9.4”Lx1.7”Wx1.18”H
10.1”Lx1.7”Wx1.18”Hwith
mountingbracket
Specications
*“Driver”referencesinclude“ballasts”unlessotherwisenoted.