Installation GuideDaintree®Networked General Purpose Adapter (WGA100)
2
3
2Interface Type Descriptions
DIP Switch Settings
Figure 1: DIP switch location
Figure 2: DIPSwitchTable-See Interface Type Descriptions
forinformationabouteachoption.
DIPswitchsettingsenabletheWGA100interfacessothatit
can identify the types of devices connected to it for control,
monitoring, and wireless adaptation. Each of the DIP switches
enablesaseparateinterface.Interfacescanbeenabledinany
combination.
ConguretheDIPswitchsettingsonlyasshowninthisinstruction
for the devices that you connect to the WGA100.
After you change the DIP switch settings, you need to press the
blueResetbuttonfor3secondstoresettheunit.Releasethe
buttonwhenthegreenJoinedandredErrorLEDs
beginashing.
To connect a device to an interface, use the wire leads indicated in
theDIPSwitchTableandinFigure 3:WiringIdentication.
Switch 1. Binary Output: Line voltage On/Off
(Switched Load)
Thisoutputprovidesupto15A/1hpswitchedlinevoltage
(switched to Hot/Active) to the device connected to the
WGA100’s14AWGredwire.Examplesforthisoutputmay
includepoweringanelectricaloutlet,equipmentbench,
contactor, pump or motor when a space is occupied, as
determinedbyDaintreeControlsSoftware(DCS)conguration.
Switch 2. Binary Output: Low voltage, On/Off (LSD)
Thisbinaryoutputisusedtoopenandcloserelaysand
switches.Anexamplewouldbetoturnonaventilationfan,or
energizeadrycontactonasetbackthermostatwhenaroom
is occupied.
Note: WhenbothSwitch1andSwitch2areenabled,DCS
identiestheSwitch1interfaceasBO1,andtheSwitch2
interface as BO2.
Switch 3. Analog Output: 0-10V, level
controllable, multistate
Analogoutputscontrolthespeedorvariablesettingofa
device,suchasamulti-speedfan,oravalveordamperactuator.
Anexampleisahotwatervalveopeningup25%tomaintaina
set-point.
Switch 4. Binary Input: Low voltage (Blue wire)
Abinaryinputindicatesifadeviceisturnedonornot.Some
examplesofabinaryinputwouldbea24VDC/ACsignalfrom
anairowswitch,oravolt-freerelaycontact.Otherexamples
include: high or low pressure switch, high temperature safety,
thermostat,damperendswitch,dirtylterswitch,fanproving
switch,timeclock.
Switch 5. Binary Input: Low voltage (Yellow wire)
ThisinputhasthesamefeaturesastheSwitch4BinaryInput.
Note:WhenbothSwitch4andSwitch5areenabled,DCS
identiestheSwitch4interfaceasBI1,andtheSwitch5
interface as BI2.
Switch 6. Input: 0-10V analog, multistate
Analoginputsareusedtoreadavariablemeasurement.
Typical analog devices include a high or low pressure monitor,
temperature,humidityorpressuresensor,thermistor,4-20mA,
0-10voltorplatinumresistancethermometer(resistance
temperature detector), suction or discharge pressure transducer,
supply air temperature thermistor, supply static pressure sensor,
buildingpressuresensor,roomtemperaturethermistor.
All disabled.
WhenallswitchesareOff,theWGA100isinRangeExtender
mode.ItjoinsaZigBeenetworkandactsasawirelessrepeater
toincreasethewirelessnetworkrangeand/orimprovereliability.
Inputsandoutputsaredisabled.
BinaryOutput:LinevoltageOn/Off(SwitchedLoad) Red(14AWG)
Binary Output: Low voltage, On/Off (LSD) Green (22 AWG)
AnalogOutput:0-10V,levelcontrollable,multistate Violet(22AWG)
BinaryInput:Lowvoltage,binary Blue(22AWG)
BinaryInput:Lowvoltage,binary Yellow(22AWG)
AnalogInput:0-10V,multistate Orange(22AWG)
Allenabled AllswitchesOn.
Allinputs/outputsdisabled. AllswitchesOff.
WGA100isinRangeExtendermodewherebyitjoinsanetworkandactsonlyasa
wirelessrepeatertoincreasethewirelessnetworkrangeand/orimprovereliability.
Wire Color DIP Setting
Interface Type Interfaces can be
enabled in any combination
DIP Switch Positions OFF
ON