CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.1/ 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
FEATURES
•CONVERTER+CASAMBI+BUS
•REPEATER CASAMBI
•Input: 230Vac
•Command: APP CASAMBI
•CASAMBI FUNCTION: SMART SWITCHING
•Signal converter from Casambi to DALI o DMX, in MASTER Variant
•Signal repeater, in REPEATER Variant
•Possibility to control DALI or DMX device, by Casambi APP
•Extended temperature range
•100% Functional test –5 Years warranty
➢PRODUCT CODE
CODE
Input Voltage
Input Command
Output Command
CBU-MASTER-DALI-IP
230Vac
APP CASAMBI
DALI (DT6 –DT8)
CONVERTER
CBU-MASTER-DMX-IP
230Vac
APP CASAMBI
DMX
CONVERTER
CBU-REPEATER-IP
230Vac
APP CASAMBI
REPEATER
REPEATER
The management of Addresses (DALI Variant) or Channels (DMX Variant) depends on the Casambi module configuration.
➢PROTECTION
CBU-MASTER-DALI/DMX
REPEATER
OVP
Over voltage protection
✓
✓
IFP
Input fuse protection
✓
✓
➢TECHNICAL SPECIFICATION
CBU MASTER & CBU REPEATER
Nominal Voltage
230 Vac
Voltage Range
100…240 Vac
Mains Frequency
50/60 Hz
Nominal Power @230V1
3W max
Power loss in standby mode
<500mW
Operating Frequencies2
2402 –2480 MHz
Maximum output power2
7dBm
Storage Temperature
min: -40 –max: +60 °C
Ambient Temperature1
min: -25 –max: +60 °C
Type of connector
Plug-In Screw Terminals
Wiring of connector
Power: 2,5mm2 solid & stranded –30/12 AWG
Bus: 1,5mm2 solid & stranded –30/14 AWG
Wire strip lenght
Power: 7,5mm / Bus: 6mm
Clamping range of cable gland
min: 5mm –max: 10mm
Protection grade
IP66
Mechanical dimensions
90 x 90 x 65 mm
Casing material
Plastic
Weight
88g
Only for BUS DALI
I out (only for DALI)
Guaranteed current to the bus = 150mA / Max bus current = 250mA
V out (only for DALI)
15V
1
Maximum value, dependent on the ventilation conditions.
2
The parameters are derived from the configuration of the Casambi module.
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.2/ 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
➢TECHNICAL NOTE
INSTALLATION:
•CAUTION: The product may only be connected and installed by qualified personnel. All applicable regulations, legislation, and building
codes in force in the respective countries must be observed. Incorrect installation of the product can cause irreparable damage to the
product and the connected LEDs.
Pay attention when connecting the LEDs: polarity reversal results in no light output and often damages the LEDs.
•Isolate the mains supply before the installation or adjusting the device. Installation and maintenance must be performed in the absence
of AC Voltage.
•The product must be installed inside a switchgear/controlgear cabinet and/or junction box protection against overvoltage.
•If required, the product must be protected by a suitably sized fuse.
•The external supply must be protected. The product must be protected by a properly sized Miniature Circuit Breaker (MCB) with
overcurrent protection.
•The product must be installed in a vertical or horizontal position with the label/top cover facing upwards or vertically. Other positions are
not permitted. The bottom position is not permitted (label/top cover facing down).
•Keep separated 230Vac (LV) circuits and not SELV circuit from safety extra low voltage (SELV) circuit.
•It is absolutely forbidden to connect, for any reason, directly or indirectly, the 230Vac mains voltage to the BUS terminals.
•If required, the product must be dissipated correctly.
•Use the product in harsh environments could limit the output power.
•Maintenance must be performed only by a qualified electrician in compliance with current regulations.
•Before powering the device, the cover of the product must be correctly placed in its seat and closed by securing all 4 closing hooks. The
device must absolutely not be powered without the cover of the product or with the cover of product not properly closed.
COMMAND and OUTPUT
•The length and type of cables connecting to the bus (DMX, DALI other) must comply with the specifications of the respective protocols and
the regulations in force. They must be insulated from any wiring or non-SELV voltage parts. It is recommended to use double insulated
cables.
•ALL device and control signal connect at the BUS (DMX DALI other) must be SELV type (the device connected must be SELV or supply SELV
signal).
WARNING: Do not compromise the correct functioning of the device, the product must not be in any way shielded and/or installed inside
metal and aluminium boxes.
As any other Casambi product, should not be placed in a metal enclosure or next to large metal structures. Metal will effectively block all
radio signals which are crucial to the operation of the product.
➢SYMBOLOGIES
All products are manufactured in compliance with European Directives, as reported in the EU Conformity Declaration.
Independent lamp Controlgear: lamp controlgear consisting of one or more separate elements so designed that it can
be mounted separately outside a luminaire, with protection according to the marking of the lamp controlgear and
without any additional enclosure
IP66
It represents the degree of protection guaranteed by the casing of a product and is defined by IEC 60529
At the end of its useful life the product described in this datasheet is classified as waste from electronic equipment, and
cannot be disposed together with the municipal undifferentiated solid waste.
Warning! Incorrect disposal of this product may cause serious damage to the environment and human health. Please be
informed about the correct disposal procedures for waste collecting and processing provided by local authorities.
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.3/ 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
➢MECHANICAL DIMENSIONS
INFORMATION ON THE CLOSURE OF THE PLASTIC BOX TO ENSURE
THE DEGREE OF PROTECTION OF THE CASING.
→Cover fixing: Apply light pressure on the cover towards the
base of the plastic box, then proceed to close the 4 screws of
the cover. The screws will close very easily. Do not force the
closure;
→Cable gland: Use cables with a diameter between 5 and 10mm;
→Fasten the Compression nut of the cable gland in such a way
that the sealing gasket of the cable gland does not deform.
Overtightening would risk damaging the seal.
➢INSTALLATION
Install the product following the below scheme
DMX BUS CONNECTION
DALI BUS CONNECTION
REPEATER CONNECTION
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.4/ 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
➢CBU-REPEATER-IP SETUP
CASAMBI SIGNAL REPEATER
Characteristics:
The CBU-REPEATER-IP is a Casambi Repeater.
The device receives a Casambi Bluetooth signal and repeats it.
Status Led:
The status of LED is fixed on to indicate the correct power connection to the device.
TYPE OF PROFILE
Type
# Profile
Name of Profile
Description
REPEATER
9948
REPEATER
It works as a repeater, forwarding the Casambi signal.
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.5/ 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
➢CBU-MASTER-DALI-IP SETUP
CASAMBI SIGNAL CONVERSION INTO DALI PROTOCOL
CHARACTERISTICS:
The CBU-MASTER-DALI-IP is a Casambi to DALI Converter.
The device receives a command signal from Casambi APP and converts the signal into a DALI command. Send DT6 and DT8 command.
See the following table “ADDRESS MAP – DALI” for reference of Casambi-DALI conversion addresses.
STATUS LED:
oWhen the status of the LED is steady on, the Casambi module is configuring and addressing the SLAVE DALI devices connected to the
bus.
oWhen the LED status flashes quickly, the Casambi module is sending the command set via the Casambi APP to the SLAVE DALI devices
connected to the bus.
oWhen the LED status flashes slowly, it means the DALI bus is shorted.
oWhen the LED status is off there is no communication in the DALI bus.
AUTOMATIC DETECTION OF SHORT CIRCUITS IN THE DALI BUS:
When the device detects a short circuit on the DALI bus, it automatically switches off the power of bus and the LED signal flashes slowly.
At 15 seconds after the detection of the short circuit, CBU-MASTER-DALI tries to reactivate the power supply of the bus. If the short circuit has
been solved, the system returns to work correctly, otherwise the bus remains unpowered and cyclically, every 15 seconds, the device tries again
to reactivate the power supply of bus.
NOTE: CBU-MASTER-DALI-IP do not need a DALI Bus power Supply.
At switching on, all channels are set at same value 254.
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.6/ 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
TYPE OF PROFILE
Type
# Profile
Name of Profile
Description
DALI
9942 (*)
DALI BROADCAST
Basic DALI broadcast dimmer.
DALI Dimming Curve: Logarithmic.
Set power on level at maximum level (100% - 254).
No short addressing required.
13820
W AUTOMATIC
One channel dimmer:
- Dimmer 1: address A0
DALI Dimming Curve: Logarithmic.
Set power on level at off (0% - 0).
The short address is automatically assigned to the driver, if needed.
13818
WW AUTOMATIC
Two channel dimmers:
- Dimmer 1: address A0
- Dimmer 2: address A1
DALI Dimming Curve: Logarithmic.
Set power on level at off (0% - 0).
The short address is automatically assigned to the driver, if needed.
13816
WWW AUTOMATIC
Three channel dimmers.
- Dimmer 1: address A0
- Dimmer 2: address A1
- Dimmer 3: address A2
DALI Dimming Curve: Logarithmic.
Set power on level at off (0% - 0).
The short address is automatically assigned to the driver, if needed.
12992
WWWW AUTOMATIC
Four channel dimmers.
- Dimmer 1: address A0
- Dimmer 2: address A1
- Dimmer 3: address A2
- Dimmer 4: address A3
DALI Dimming Curve: Logarithmic.
Set power on level at off (0% - 0).
The short address is automatically assigned to the driver, if needed.
12993
TW AUTOMATIC
2700-6000K
Two channel dimmers.
- Dimmer 1: address A0-Warm White
- Dimmer 2: address A1-Cool White
DALI Dimming Curve: Logarithmic.
Set power on level at off (0% - 0).
The short address is automatically assigned to the driver, if needed.
19060
TW AUTOMATIC
2700-6000K [NEW]
Two channel dimmers.
- Dimmer 1: address A0-Warm White
- Dimmer 2: address A1-Cool White
DALI Dimming Curve: Quadratic.
Set power on level at off (0% - 0).
The short address is automatically assigned to the driver, if needed.
12994
RGB AUTOMATIC
Three channel dimmers.
- Dimmer 1: address A0-Red
- Dimmer 2: address A1-Green
- Dimmer 3: address A2-Blue
DALI Dimming Curve: Logarithmic.
Set power on level at off (0% - 0).
The short address is automatically assigned to the driver, if needed.
(*) Default Profile
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.7/ 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
DALI
12995
RGB+W AUTOMATIC
Four channel dimmers.
- Dimmer 1: address A0-Red
- Dimmer 2: address A1-Green
- Dimmer 3: address A2-Blue
- Dimmer 4: address A3-White
DALI Dimming Curve: Logarithmic.
Set power on level at off (0% - 0).
The short address is automatically assigned to the driver, if needed.
12996
WWWW GROUP
Four group luminaires.
- Dimmer 1: group G0
- Dimmer 2: group G1
- Dimmer 3: group G2
- Dimmer 4: group G3
DALI Dimming Curve: Logarithmic.
Set power on level at off (0% - 0).
The short address needs to be assigned to the control gear using a DALI Master device.
12998
TW GROUP
2700-6000K
Two group luminaires.
- Dimmer 1: group G0-Warm White
- Dimmer 2: group G1-Cool White
DALI Dimming Curve: Logarithmic.
Set power on level at off (0% - 0).
The short address needs to be assigned to the control gear using a DALI Master device.
12999
RGB GROUP
Three group luminaires.
- Dimmer 1: group G0-Red
- Dimmer 2: group G1-Green
- Dimmer 3: group G2-Blue.
DALI Dimming Curve: Logarithmic.
Set power on level at off (0% - 0).
The short address needs to be assigned to the control gear using a DALI Master device.
13000
RGB+W GROUP
Four group luminaires.
- Dimmer 1: group G0-Red
- Dimmer 2: group G1-Green
- Dimmer 3: group G2-Blue
- Dimmer 4: group G3-White
DALI Dimming Curve: Logarithmic.
Set power on level at off (0% - 0).
The short address needs to be assigned to the control gear using a DALI Master device.
15539
8xW GROUP SPECIAL
Eight group luminaires.
- Dimmer 1: group G0
- Dimmer 2: group G1
- Dimmer 3: group G2
- Dimmer 4: group G3
- Dimmer 5: group G4
- Dimmer 6: group G5
- Dimmer 7: group G6
- Dimmer 8: group G7
DALI Dimming Curve: Logarithmic.
Set Power on Level at 255 (Mask) –Memory Function at Power On.
Set System Failure at 255 (Mask) –In case of bus loss, there isn’t change of LED output.
The short address needs to be assigned to the control gear using a DALI Master device.
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.8/ 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
DALI
24688
8xW GROUP
Eight group luminaires.
- Dimmer 1: group G0
- Dimmer 2: group G1
- Dimmer 3: group G2
- Dimmer 4: group G3
- Dimmer 5: group G4
- Dimmer 6: group G5
- Dimmer 7: group G6
- Dimmer 8: group G7
DALI Dimming Curve: Logarithmic.
Set power on level at maximum level (100% - 254).
The short address needs to be assigned to the control gear using a DALI Master device.
DALI
DT8
18823
DALI BC DT8 TW
1 Address to control 2-channel TW.
Send DALI DT8 BROADCAST commands for device that supporting “Colour Temperature Tc”: Dim Level
and Colour Temperature channels.
DALI Dimming Curve: Logarithmic.
Set power on level at maximum level (100% - 254).
No short addressing required.
21458
DALI DT8 RGB LINEAR
1 Address to control 3-channel RGB.
Send DALI DT8 commands for device that supporting “RGBWAF colour-type”: Dim and RGBWAF channels.
DALI Dimming Curve: Linear.
Set power on level at maximum level (100% - 254).
The short address is automatically assigned to the driver, if needed.
21459
DALI DT8 RGBW
LINEAR
1 Address to control 4-channel RGBW.
Send DALI DT8 commands for device that supporting “RGBWAF colour-type”: Dim and RGBWAF channels.
DALI Dimming Curve: Linear.
Set power on level at maximum level (100% - 254).
The short address is automatically assigned to the driver, if needed.
24058
DALI DT8 BC RGB
LINEAR
1 Address to control 3-channel RGB.
Send DALI DT8 BROADCAST commands for device that supporting “RGBWAF colour-type”: Dim and
RGBWAF channels.
DALI Dimming Curve: Linear.
Set power on level at maximum level (100% - 254).
No short addressing required.
24008
DALI DT8 BC RGB+W
LINEAR
1 Address to control 4-channel RGBW.
Send DALI DT8 BROADCAST commands for device that supporting “RGBWAF colour-type”: Dim and
RGBWAF channels.
DALI Dimming Curve: Linear.
Set power on level at maximum level (100% - 254).
No short addressing required.
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.9/ 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
ADDRESSES MAP –DALI
FIXTURE AUTOMATIC
The Fixture “AUTOMATIC” of the CBU-MASTER-DALI-IP addressing automatically the devices connected to the DALI BUS.
Profile Type: BROADCAST
Addr
Function
Broadcast
+ALL
Broadcast
Dimmer (Brightness Value)
0 .. 254
Profile Type: W AUTOMATIC –Fixture for only 1 DALI address
Addr
Function
Dimmer
A0
Dimmer 1
Dimmer (Brightness Value)
0 .. 254
Profile Type: WW AUTOMATIC –Fixture for 2 DALI address
Addr
Function
Dimmer
A0
Dimmer 1
Dimmer (Brightness Value)
0 .. 254
A1
Dimmer 2
Dimmer (Brightness Value)
0 .. 254
Profile Type: WWW AUTOMATIC –Fixture for 3 DALI address
Addr
Function
Dimmer
A0
Dimmer 1
Dimmer (Brightness Value)
0 .. 254
A1
Dimmer 2
Dimmer (Brightness Value)
0 .. 254
A2
Dimmer 3
Dimmer (Brightness Value)
0 .. 254
Profile Type: WWWW AUTOMATIC –Fixture for 4 DALI address
Addr
Function
Dimmer
A0
Dimmer 1
Dimmer (Brightness Value)
0 .. 254
A1
Dimmer 2
Dimmer (Brightness Value)
0 .. 254
A2
Dimmer 3
Dimmer (Brightness Value)
0 .. 254
A3
Dimmer 4
Dimmer (Brightness Value)
0 .. 254
Profile Type: TW AUTOMATIC 2700-6000K –TW AUTOMATIC 2700-6000K NEW
Addr
Function
Tunable White
A0
Warm White
Dimmer (Brightness Value)
0 .. 254
A1
Cool White
Dimmer (Brightness Value)
0 .. 254
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.10 / 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
Profile Type: RGB AUTOMATIC
Addr
Function
RGBW
A0
Red
R
0 .. 254
A1
Green
G
0 .. 254
A2
Blue
B
0 .. 254
Profile Type: RGB+W AUTOMATIC
Addr
Function
RGBW
A0
Red
R
0 .. 254
A1
Green
G
0 .. 254
A2
Blue
B
0 .. 254
A3
White
W
0 .. 254
FIXTURE GROUP
With “Group” Fixture the CBU-MASTER-DALI-IP sends group commands. The SLAVE devices to be controlled correctly by these Fixture must be
previously addressed and assigned to the desired group through a Master DALI.
Profile Type: WWWW GROUP
Group
Function
Dimmer
G0
Dimmer 1
Dimmer (Brightness Value)
0 .. 254
G1
Dimmer 2
Dimmer (Brightness Value)
0 .. 254
G2
Dimmer 3
Dimmer (Brightness Value)
0 .. 254
G3
Dimmer 4
Dimmer (Brightness Value)
0 .. 254
Profile Type: TW GROUP 2700-6000K
Group
Function
Tunable white
G0
Warm White
Dimmer (Brightness Value)
0 .. 254
G1
Cool White
Dimmer (Brightness Value)
0 .. 254
Profile Type: RGB GROUP
Group
Function
RGB
G0
Red
R
0 .. 254
G1
Green
G
0 .. 254
G2
Blue
B
0 .. 254
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.11 / 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
Profile Type: RGB+W GROUP
Group
Function
RGBW
G0
Red
R
0 .. 254
G1
Green
G
0 .. 254
G2
Blue
B
0 .. 254
G3
White
W
0 .. 254
Profile Type: 8xW GROUP –8xW GROUP SPECIAL
Group
Function
Dimmer
G0
Dimmer 1
Dimmer (Brightness Value)
0 .. 254
G1
Dimmer 2
Dimmer (Brightness Value)
0 .. 254
G2
Dimmer 3
Dimmer (Brightness Value)
0 .. 254
G3
Dimmer 4
Dimmer (Brightness Value)
0 .. 254
G4
Dimmer 5
Dimmer (Brightness Value)
0 .. 254
G5
Dimmer 6
Dimmer (Brightness Value)
0 .. 254
G6
Dimmer 7
Dimmer (Brightness Value)
0 .. 254
G7
Dimmer 8
Dimmer (Brightness Value)
0 .. 254
The 8xW GROUP SPECIAL profile send SET POWER ON LEVEL and SET SYSTEM FAILURE LEVEL command at 255 (MASK). These commands are
sent at the DALI bus when you change the profile, by Casambi APP. For Control Gear to receive these commands correctly, they must be
connected to the DALI bus before changing profile.
Profile Type: DALI BROADCAST DT8 TW
Addr
Function
Broadcast –Colour Temperature Tc –DT8
+ALL
Broadcast TW
Colour Temperature Tc
Dimmer (Brightness Value)
0 .. 254
Profile Type: DALI DT8 RGB LINEAR
Addr
Function
RGB –DT8
A0
RGB
Colour Type
Dimmer (Brightness Value)
0 .. 254
Profile Type: DALI DT8 RGBW LINEAR
Addr
Function
RGBW –DT8
A0
RGBW
Colour Type
Dimmer (Brightness Value)
0 .. 254
Profile Type: DALI DT8 BC RGB LINEAR
Addr
Function
Broadcast RGB –DT8
+ALL
Broadcast RGB
Colour Type
Dimmer (Brightness Value)
0 .. 254
Profile Type: DALI DT8 BC RGB+W LINEAR
Addr
Function
Broadcast RGB+W –DT8
+ALL
Broadcast RGB+W
Colour Type
Dimmer (Brightness Value)
0 .. 254
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.12 / 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
➢CBU-MASTER-DMX-IP SETUP
CASAMBI SIGNAL CONVERSION INTO DMX PROTOCOL
Characteristics:
The CBU-MASTER-DMX-IP is a Casambi to DMX Converter.
The device receives the command signal from Casambi APP and convert it into a DMX command.
See the following “CHANNELS MAP – DMX”table for the reference of the Casambi-DMX conversion addresses.
Status Led:
Status LED is fixed on when the Casambi command is right transmitted.
Status LED slowly flashes (1 flash per second), when the device is powered.
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.13 / 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
TYPE OF PROFILE
Type
# Profile
Name of Profile
Description
DMX
13808
W
One channel dimmer:
- Dimmer 1: channel 1
13807
WWWW
Four channel dimmers.
- Dimmer 1: channel 1
- Dimmer 2: channel 2
- Dimmer 3: channel 3
- Dimmer 4: channel 4
13809
TW
Two channel dimmers.
- Warm White Dimmer: channel 1
- Cool White Dimmer: channel 2
13810
RGB
Three channel dimmers.
- Red Dimmer: channel 1
- Green Dimmer: channel 2
- Blue Dimmer: channel 3
13811
RGB+W
Four channel dimmers.
- Red Dimmer: channel 1
- Green Dimmer: channel 2
- Blue Dimmer: channel 3
- White Dimmer: channel 4
13812
MRGB+S
Five channel dimmers.
- Master Dimmer: channel 1
- Red Dimmer: channel 2
- Green Dimmer: channel 3
- Blue Dimmer: channel 4
- Strobe Rate Channel: channel 5
13813
MRGBW+S
Six channel dimmers.
- Master Dimmer: channel 1
- Red Dimmer: channel 2
- Green Dimmer: channel 3
- Blue Dimmer: channel 4
- White Dimmer: channel 5
-Strobe Rate Channel: channel 6
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.14 / 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
CHANNEL MAP –DMX
Profile Type: W–1 DMX channel
Ch.
Function
Dimmer
1
Dimmer 1
Dimmer (Brightness Value)
0 .. 255
Profile Type: WWWW –4 DMX channel
Ch.
Function
Dimmer
1
Dimmer 1
Dimmer (Brightness Value)
0 .. 255
2
Dimmer 2
Dimmer (Brightness Value)
0 .. 255
3
Dimmer 3
Dimmer (Brightness Value)
0 .. 255
4
Dimmer 4
Dimmer (Brightness Value)
0 .. 255
Profile Type: TW
Ch.
Function
Tunable White
1
Warm White
Dimmer (Brightness Value)
0 .. 255
2
Cool White
Dimmer (Brightness Value)
0 .. 255
Profile Type: RGB
Ch.
Function
RGB
1
Red
R 0 .. 255
2
Green
G 0 .. 255
3
Blue
B0 .. 255
Profile Type: MRGBS
Ch.
Function
Master+RGB+Strobe
1
Master Dimmer
Master Dimmer (Brightness Value)
0 .. 255
2
Red
R 0 .. 255
3
Green
G 0 .. 255
4
Blue
B0 .. 255
5
Strobe Rate (*)
STROBO 0 .. 255
Profile Type: RGBW
Ch.
Function
RGBW
1
Red
R 0 .. 255
2
Green
G 0 .. 255
3
Blue
B0 .. 255
4
White
W 0 .. 255
CBU MASTER BUS & CBU REPEATER
Device Manual
Made in Italy
Rev.10/01/2024
Pag.15 / 15
DALCNET S.r.l, Registered office: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
Headquarters: Via Lago di Garda, 22 –36077 Altavilla Vicentina (VI) –Italy
VAT: IT04023100235 –Tel. +39 0444 1836680 - www.dalcnet.com –inf[email protected]
 
             
            


Profile Type: MRGBWS
Ch.
Function
Master+RGBW+Strobe
1
Master Dimmer
Master Dimmer (Brightness Value)
0 .. 255
2
Red
R 0 .. 255
3
Green
G 0 .. 255
4
Blue
B0 .. 255
5
White
W 0 .. 255
6
Strobe Rate (*)
STROBO 0 .. 255
(*) Strobe Rate execute the functions of the strobe address of the control unit connected to the CBU-MASTER-DMX-IP. For example, if you
connect the CBU-MASTER-DMX-IP to the DLD1248-4CV-DMX control unit, which is also set with the MRGB+ or MRGBW+ map, the Strobe Rate
address has the following characteristics:
6
Strobe Rate
For other devices check the behaviour of the device at the respective channel 6 of the DMX.
➢BLUETOOTH RANGE
The range depends a lot on the surroundings and materials or building obstacles, see the technical notes on page 3.

This manual suits for next models

3

Other DALCNET Repeater manuals

DALCNET CASAMBI CBU-REPEATER-USB Application guide

DALCNET

DALCNET CASAMBI CBU-REPEATER-USB Application guide

Popular Repeater manuals by other brands

Teltonika WRP100 user manual

Teltonika

Teltonika WRP100 user manual

Motorola VRS750 Service manual

Motorola

Motorola VRS750 Service manual

KanexPro SDI-HDRPTPRO user manual

KanexPro

KanexPro SDI-HDRPTPRO user manual

Techly IDATA HDMI2-RIP4KT manual

Techly

Techly IDATA HDMI2-RIP4KT manual

Tait TB7304 user guide

Tait

Tait TB7304 user guide

Aztech WL580E Easy start guide

Aztech

Aztech WL580E Easy start guide

Fritz! 450E installation instructions

Fritz!

Fritz! 450E installation instructions

AV Outlet IR-EXT-RF user guide

AV Outlet

AV Outlet IR-EXT-RF user guide

Futurecom PDR8000 Programming guide

Futurecom

Futurecom PDR8000 Programming guide

Compaq Netelligent 1124 user guide

Compaq

Compaq Netelligent 1124 user guide

HongYu Technology KN300 user guide

HongYu Technology

HongYu Technology KN300 user guide

Danfoss 088U0230 instructions

Danfoss

Danfoss 088U0230 instructions

Futurecom DVRS user guide

Futurecom

Futurecom DVRS user guide

InterEpoch IWE1100-T user manual

InterEpoch

InterEpoch IWE1100-T user manual

GMI D5038DA instruction manual

GMI

GMI D5038DA instruction manual

Compaq Netelligent 2524 user guide

Compaq

Compaq Netelligent 2524 user guide

Vivid CLR-102 user manual

Vivid

Vivid CLR-102 user manual

Vigitron MaxiiNet Vi3002WP instruction manual

Vigitron

Vigitron MaxiiNet Vi3002WP instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.