Danfoss Termix One Solar User manual

Operatingguide
TermixOneSolar
1.0TableofContents
1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotes–general............................................4
4.0Mounting........................................................5
4.1Mounting...........................................................5
4.2Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
5.2Schematicdiagram................................................9
6.0Controls..........................................................10
6.1DHWtemperaturecontrol........................................10
6.2Maintenance........................................................11
7.0Troubleshooting..............................................12
7.1Troubleshootingingeneral......................................12
7.2TroubleshootingDHW............................................12
7.3Disposal.............................................................13
8.0Declaration......................................................15
8.1Declarationofconformity........................................15
DanfossDistrictEnergyVI.CW.K4.02/LUK38004DEN-GT1

OperatingguideTermixOneSolar
2DEN-GTVI.CW.K4.02/LUK38004DanfossDistrictEnergy

OperatingguideTermixOneSolar
2.0Functionaldescription
Domestichotwatermodulewithheatexchangerand
thermostaticcontrol.Designedforwall-mounting.
Application
TheTermixOneSolarisaninstantaneouswaterheater,featuring
superbheatextractionandhighperformance.TheTermixOne
Solarisapplicableforheatingsystemswithbufferaccumulators,
solarsystemsorforotherheatsources,whereaverylowreturn
temperatureispreferred.Thewaterheaterisavailableinthree
sizes,eitherfor1apartment,for1-4apartmentsorfor5upto10
apartments.Thelargeheatexchangercoolsoutthewaterinthe
primaryreturnlineveryefciently,therebycreatingaverygood
operationeconomy.Aowswitchincoldwatermainsiscontrolling
theprimaryheatingpump.Anoptionalcirculationpumptogether
withathermostatcanmaintainthecirculatingtemperatureata
desiredtemperature.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerand
thetemperatureisregulatedwithathermostaticcontrolvalve.
Thepatentedsensoracceleratoracceleratestheclosingofthe
thermostaticcontrolvalveandprotectstheheatexchangeragainst
overheatingandlimescaleformation.Thesensoracceleratorand
thethermostaticcontrolvalvealsoworksasabypasskeepingthe
heatexchangerandsupplylinewarm.Thisshortensthewaiting
periods.Thesensoracceleratorhelpstoensureastablehotwater
temperaturebyvaryingloads,owtemperaturesanddifferential
pressurewithouttheneedforreadjustingthevalve.Thereisno
additionalpressurelossonthesecondarysideoftheDHWheat
exchangerwithathermostaticcontrol.Thereforethistypeof
regulationcanbeusedbylowpressureinthecoldwatermains.
DanfossDistrictEnergyVI.CW.K4.02/LUK38004DEN-GT3

OperatingguideTermixOneSolar
3.0Safetynotes
3.1SafetyNotes–general
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallation’spermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
4DEN-GTVI.CW.K4.02/LUK38004DanfossDistrictEnergy

OperatingguideTermixOneSolar
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Domesticcoldwater(DCW)
2.Domestichotwater(DHW)
3.BufferTank(BT)supply
4.BufferTank(BT)return
5.Hotwatercirculation(HWC)-(Optional)
Connectionsizes:
BT:G¾”(int.thread)
DCW+DHW+HWC:G¾”(int.thread)
Dimensions(mm):
Withoutcirculationandcover:
H760xW312xD155
Withoutcirculationandwithcover:
H760xW315xD165
Withcirculationandwithoutcover:
H935xW410xD190
Weight(approx.):20kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
DanfossDistrictEnergyVI.CW.K4.02/LUK38004DEN-GT5

OperatingguideTermixOneSolar
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
6DEN-GTVI.CW.K4.02/LUK38004DanfossDistrictEnergy

OperatingguideTermixOneSolar
4.2Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording
to60364-4-41:2007andIEC60364-5-54:2011.
Bondingpointonthemountingplatebelowrightcornermarked
withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
DanfossDistrictEnergyVI.CW.K4.02/LUK38004DEN-GT7

OperatingguideTermixOneSolar
5.0Design
5.1Design
5.1.1DesignTermixOneSolar
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
BHeatexchanger,DHW35Ballvalve/non-returnvalve
MElectricalwiringbox45Flowswitch
OTermixsensoraccelerator48Airvent,manual
7Thermostaticcontroller,DHW63Sieve
13Chargingpump
8DEN-GTVI.CW.K4.02/LUK38004DanfossDistrictEnergy

OperatingguideTermixOneSolar
5.2Schematicdiagram
5.2.1SchematicdiagramTermixOneSolarwithcirculation
BT
SupplyDHW
HWC
BT
ReturnDCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescriptionwithcirculation
BHeatexchanger,DHW4Safetyvalve35Ballvalve/non-returnvalve
MElectricalwiringbox7Thermostaticvalve39Connectionclosed
OTermixsensoraccelerator11ADHWpump,withbuiltincheckvalve45Flowswitch
1Ballvalve13Chargingpump48Airvent,manual
2Singlecheckvalve21Tobeorderedseparately63Sieve
DHW:DomesticHotWater
DCW:DomesticColdWater
HWC:HotWaterCirculation
BTSupply:Buffertanksupply
BTReturn:Buffertankreturn
5.2.2Technicalparameters
Technicalparameters
Nominalpressure:PN16
Max.DHsupplytemperature:120°C
Min.DCWstaticpressure:0.5bar
Brazingmaterial(HEX):Copper
Heatexchangerstestpressure:30bar
Soundlevel:≤55dB
DanfossDistrictEnergyVI.CW.K4.02/LUK38004DEN-GT9

OperatingguideTermixOneSolar
6.0Controls
6.1DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin
Danfosssubstations.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilisationofDHwater.AtDHWtemperaturesabove55°C,
thepossibilityoflimescaledepositsincreasessignicantly.
6.1.1AVTBcontroller(20–60°)
Thetemperaturesettingisasfollows:
1=20°C
2=35°C
3=50°C
4=60°C
5=70°C
Thevaluesareintendedasaguide.
TheAVTBoperatesatitsbestatDHsupplytemperaturesofupto
90°C.
Thermostaticcontrol
DHWtemperatureisadjustedasfollows:
Toincreasetemperature,turnthehandleonthethermostatic
controllertoselectahighernumber.
Todecreasetemperature,turnthehandleonthethermostatic
controllertoselectalowernumber.
6.1.2CirculatorpumpUPM3
UPM3Pumpscanbecontrolledinconstantpressure,proportional
pressureorconstantspeedmodedenedbythemeansofasmart
userinterface.
Thevariablespeedmodulatingmodesallowthepumptomatchits
performancetothesystemrequirements,helpingtoreducenoise
whenthermostaticvalvesareclosingdown.
EnergylabellingclassA
10DEN-GTVI.CW.K4.02/LUK38004DanfossDistrictEnergy

OperatingguideTermixOneSolar
6.1.3Domestichotwaterpump
Thedomestichotwaterpumpcanbeprogrammedwiththe
desiredtimeprogramme.
6.2Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
DanfossDistrictEnergyVI.CW.K4.02/LUK38004DEN-GT11

OperatingguideTermixOneSolar
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
•thesubstationisconnectedtoelectricity,
•thestrainerontheDHsupplypipeisclean,
•thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
•thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetwork–ifindoubt,ask
theDHplantsupervisor,
•pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
7.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.Replace–clean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Scalingoftheplateheatexchanger.Replace–rinseout.
Defectivemotorizedvalve.Check(usemanualfunction)–replace.
Defectivetemperaturesensors.Check–replace.
ToolittleornoDHW.
Defectivecontroller.Check–replace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Check–replace. Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Replace–clean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.
Check–set.
Scalingoftheplateheatexchanger.Replace–rinseout. Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
ThermostaticcontrolvalvedoesnotcloseTemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor
increasetheDHsupplytemperature.
12DEN-GTVI.CW.K4.02/LUK38004DanfossDistrictEnergy

OperatingguideTermixOneSolar
7.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
DanfossDistrictEnergyVI.CW.K4.02/LUK38004DEN-GT13

OperatingguideTermixOneSolar
14DEN-GTVI.CW.K4.02/LUK38004DanfossDistrictEnergy

OperatingguideTermixOneSolar
8.0Declaration
8.1Declarationofconformity
Category0withelectricalequipment
DanfossDistrictEnergyVI.CW.K4.02/LUK38004DEN-GT15

OperatingguideTermixOneSolar
ProducedbyDanfossA/S©11/2016
Table of contents
Other Danfoss Water System manuals
Popular Water System manuals by other brands

ZURN
ZURN Z1325 Assembly manual

iDM
iDM HYGIENIK 2.0 Installation instruction

Everpure
Everpure Exubera Pro UC EV9333-50 Specification sheet

Viking Pure
Viking Pure Mini Pure VPM user manual

Grizzly
Grizzly HWW 3819 InoxInox Translation of the original instructions for use

Hoshizaki
Hoshizaki WOX-40WA-EW instruction manual

Everpure
Everpure 2JT Cartridge EV9608-10 Specification sheet

HeatLink
HeatLink PEX-a installation guide

Culligan
Culligan Mark 100 owner's guide

GF
GF JRG Hycleen Installation Instructions, Operating and Maintenance Instructions

Spectra Watermakers
Spectra Watermakers Newport 400 Installation and owner's manual

VWR
VWR Avantor G5 instruction manual