Danfysik SYSTEM 8700 User manual

System 8700 User Manual
Page 1 of 32
Preparation/Review
Signature
Date
Author:
Per Mørkegaard Hansen
PMH
TSS
27-11-2017
Check:
Thomas Bay
Approved by:
TSS
23-11-2017
Tomas Bruunshuus Sørensen
SYSTEM8700
User’s Manual
Manual for setup and
use of SYSTEM8700
Control system

Page 2 of 32 Rev 0.95
Document change log:
Date:
Rev.:
Init:
Changes:
09-10-2017
0.9
PMH
Initial edition
23-10-2017
0.91
TSS
25-10-2017
0.92
PMH
Changed link to Cerhost software. Updated SCPI command description.
31-10-2017
0.93
PMH
Changes after Heine Dølrath Thomsens review. Removed a few SCPI commands
that are not fully implemented yet.
20-11-2017
0.94
PMH
Changed default names of interlocks..
Added status register from digi loop card.
27-11-2017
0.95
PMH
Added the SYSTem:LOCK:LREQuest? SCPI command.
Added the two warnings Pre trig fault and polarity signal missing.
Danfysik A/S
Gregersensvej 8 • DK-2630 Taastrup • Denmark
Tel. +45 7220 2400 • Fax +45 7220 2410 • sales@danfysik.dk • www.danfysik.com
VAT reg. No. DK 31 93 48 26 • Bankers: Jyske Bank, Denmark
Email sales: [email protected]
Email service: [email protected]k
IMPORTANT!
This documentation contains information which is the
property of DANFYSIK A/S, Denmark.
It is submitted to you in confidence that it will not be
disclosed or transmitted to others without
DANFYSIK’s authorization.

System 8700 User Manual
Rev 0.95 Page 3 of 32
1. INTRODUCTION ............................................................................................................................................ 5
IMPORTANT SAFETY INFORMATION ...................................................................................................................... 5
1.1.1. General warnings .................................................................................................................................... 5
ABOUT THIS DOCUMENT ....................................................................................................................................... 6
1.2.1. Intended use ............................................................................................................................................. 6
WARRANTY AND WARRANTY REPAIR .................................................................................................................... 7
2. UNPACKING AND INSTALLATION ........................................................................................................ 8
RECEIVING THE GOODS ........................................................................................................................................ 8
INSTRUCTIONS FOR UNPACKING .......................................................................................................................... 8
INSTALLATION REQUIREMENTS ............................................................................................................................ 8
ELECTRICAL INSTALLATION ................................................................................................................................. 9
2.4.1. Connection of Power .............................................................................................................................. 9
2.4.2. Connection of Remote Control Cable .............................................................................................. 9
2.4.3. Connection of External Interlocks..................................................................................................... 9
3. LOCAL CONTROL INTERFACE ................................................................................................................ 10
THE RIGHT-HAND MENU ..................................................................................................................................... 10
3.1.1. Changing the mode .............................................................................................................................. 10
3.1.2. Interlocks and warnings ..................................................................................................................... 10
3.1.3. Turning the power supply on ............................................................................................................ 11
3.1.4. Turn the Power Supply Off ................................................................................................................ 11
SETTING A CURRENT OR VOLTAGE .................................................................................................................... 12
SETTINGS ............................................................................................................................................................ 13
THE LOGIN SCREEN ............................................................................................................................................ 14
ADVANCED SETTINGS ........................................................................................................................................ 14
3.5.1. The interlock file .................................................................................................................................... 14
3.5.2. Editing the files ...................................................................................................................................... 15
4. REMOTE CONTROL INTERFACE ............................................................................................................ 15
ETHERNET INTERFACE ........................................................................................................................................ 15
SERIAL RS232 INTERFACE ............................................................................................................................... 16
REMOTE CONTROL COMMANDS .......................................................................................................................... 16
4.3.1. SCPI commands .................................................................................................................................... 16
4.3.1.1. Status reporting ................................................................................................................................................ 19
4.3.1.2. Status, bit 9 ........................................................................................................................................................ 19
4.3.1.3. Operation status , bit 7 .................................................................................................................................. 20
4.3.1.4. Register 1, bit 10 .............................................................................................................................................. 21
4.3.1.5. Register 2, bit 11 .............................................................................................................................................. 21
4.3.1.1. Register 3, bit 12 .............................................................................................................................................. 22
4.3.1.1. Register 4, bit 13 .............................................................................................................................................. 23
4.3.2. Legacy commands ................................................................................................................................ 24
4.3.2.1. S1H response ..................................................................................................................................................... 26
4.3.2.2. S3H response ..................................................................................................................................................... 27
ADDITIONAL REMOTE ACCESS ........................................................................................................................... 28
4.4.1. Remote Desktop .................................................................................................................................... 28
4.4.2. Setting IP ................................................................................................................................................. 29
4.4.3. Testing remote communication ....................................................................................................... 30
5. MAINTENANCE ............................................................................................................................................. 30
WARNING BEFORE SERVICING/WORKING ON THE POWER SUPPLY ..................................................... 30
INTRODUCTION ................................................................................................................................................... 31

Page 4 of 32 Rev 0.95
PREVENTIVE MAINTENANCE................................................................................................................................ 31
ADJUSTMENT AND CALIBRATION ....................................................................................................................... 31
6. SPARE PARTS, ORDERING OF .............................................................................................................. 32
HANDLING ESD-SENSITIVE COMPONENTS ...................................................................................................... 32

System 8700 User Manual
Rev 0.95 Page 5 of 32
1. Introduction
Important safety information
This document may contain warnings:
GENERAL HAZARD
Indicates a potentially hazardous general situation. The keyword (DANGER,
WARNING, and CAUTION) indicates the hazard level.
ELECTRICITY
Indicates a potentially hazardous electrical situation. The keyword (DANGER,
WARNING, and CAUTION) indicates the hazard level.
MAGNETIC FIELD
Indicates a potentially hazardous magnetic field situation. The keyword
(DANGER, WARNING, and CAUTION) indicates the hazard level.
1.1.1. General warnings
Please review the following safety precautions and all warning and caution information
throughout the manual.
WARNING!
This Magnet Power Supply (MPS) is intended for professional incorporation into
complete accelerator systems as a part of a fixed installation. If installed
incorrectly it may present a safety hazard. Close attention is required to system
design and electrical installation to avoid hazards in either normal operation or
in the event of equipment malfunction.
WARNING!
Do not perform any flash test or voltage withstand test on the Magnet Power
Supply. Any electrical measurements required must be carried out with power
supply disconnected.
CAUTION!
Only qualified electricians are allowed to install and maintain this equipment.

Page 6 of 32 Rev 0.95
DANGER! ELECTRIC SHOCK HAZARD!
Disconnect power at switch board before attempting to work on the Magnet
Power Supply. High voltages are present at the terminals and within the power
supply for up to 10 minutes after disconnection of the electrical supply. Always
ensure by using a suitable measuring device that no voltage is present prior to
commencing work.
CAUTION!
Ensure correct grounding connection. The grounding cable must be selected to
be able to carry the maximum supply fault current. This is normally limited by
fuses at the switch board. Fuses at the switch board must be selected according
to local legislation or code.
About this document
This document is intended for design and service engineers responsible for the installation,
maintenance and repair of the Power Supplies using SYSTEM8700 control system supplied by
Danfysik A/S. The power supply itself and its regulation system is not within the scope of this
document.
1.2.1. Intended use
The Magnet Power Supply (MPS) is intended for professional incorporation into complete
accelerator systems as a part of a fixed installation. It must be installed in an enclosed
operating area. The power supplies are built according to industrial standards.
The intended use is to control a magnet by supplying the current for the magnet. The MPS
includes an interlock system, which shuts down the power supply in case a number of
predefined errors occur.
Only qualified personnel are allowed to install the MPS, and only instructed personnel are
allowed to operate it.
In case of failure, the accelerator system must have the means to shut down in a safe manner.

System 8700 User Manual
Rev 0.95 Page 7 of 32
Warranty and warranty repair
Unless other specific warranty terms has been agreed upon following terms apply:
DANFYSIK A/S warrants that the products manufactured by us will be free from defects in
material and workmanship that adversely would affect the normal functioning of the unit, for a
period of 24 months from the date of shipment. The exceptions to this are:
a ) Parts not manufactured by DANFYSIK A/S which are covered by the original equipment
manufacturer's warranty.
b ) Repair work which is warranted for six (6) months from the date of shipment from
DANFYSIK.
DANFYSIK A/S will repair or replace either on site or at the factory, at option and without
charge, any equipment which proves to be defective within its warranty period.
In the case of warranty, DANFYSIK A/S will pay or reimburse lowest freight rate (two-way) of
any item returned to DANFYSIK or our designated agent/representative, provided that prior
written authorization for such return has been given by DANFYSIK A/S.
This warranty shall not apply to any equipment which has become defective or unworkable due
to mishandling, improper maintenance, incorrect use, radiation damage or any other
circumstance not generally acceptable for equipment of a similar type.
On standard products, DANFYSIK A/S reserves the right to make changes in design without
incurring any obligation to modify previously manufactured units.
The foregoing is the full extent of this warranty, and no other warranty is expressed or implied.
In no event shall DANFYSIK be liable for special damages arising from the delivery, late delivery
or use of the equipment.
If any fault develops, the following steps should be taken:
•All RMA-cases are handled via Danfysik’s web based RMA-system. It can be accessed from
the official Danfysik web page www.danfysik.com (via the Service & Test tab), where a
RMA Quick Guide also can be downloaded. Alternatively, the RMA-system can be accessed
directly via www.dfservice.dk/rma/
•Notify DANFYSIK A/S, giving full details of the problems, and include Model-Type and Serial
number.
On receipt of this information, DANFYSIK A/S will give you either service information or
instructions for shipping.
•All shipments of DANFYSIK equipment should be made according to our instructions and
shipped in the original or a similar container.
•Only suitable materials are to be used for shipment.

Page 8 of 32 Rev 0.95
2. Unpacking and installation
Receiving the goods
The Shipping container and the Magnet Power Supply should be thoroughly inspected for signs
of obvious physical damage immediately upon receipt.
All materials in the container should be checked against the enclosed packing list. DANFYSIK
A/S will not be responsible for shortages against the packing list unless notified immediately.
The following must be included in the delivery:
•To be defined
Instructions for unpacking
The Magnet Power Supply is shipped on a wooden pallet enclosed in either reinforced
cardboard or wood crate.
Remove the packing straps and nails. If packed in a wood crate, the top lid should be removed
first. If the equipment is damaged in any way, a claim should be filed with the shipping agent,
and a full report of the damage should be forwarded to DANFYSIK A/S or our local
agent/representative immediately.
Upon receipt of this report, you will be issued instructions for the repair, replacement or return
shipment.
Please include the Model no, Type no, Serial no and Order no for the Magnet Power Supply on
any communication with DANFYSIK A/S or our representatives.
Installation requirements
During installation of the Magnet Power Supply (MPS), local rules and regulations for electric
power and water supplies should be respected and the following conditions and installations
should be available.
•A normal, dust free room with humidity not above 80 % and a room temperature within 15
to 35 centigrade.
•The Control System is supplied from a 24Vdc. This is typically handled as an internal
voltage within the power supply. Please see Power Supply manual and drawing for details.
•Ground connection according to the local authority regulation and the requirements for the
equipment.

System 8700 User Manual
Rev 0.95 Page 9 of 32
Electrical Installation
2.4.1. Connection of Power
The PLC is powered by 24 V DC, please see Figure 1.
2.4.2. Connection of Remote Control Cable
The power supply can be remote controlled via an Ethernet connection. The connection is made
directly on the rear of the IPC. Seen from behind, open the right-hand door and make the
connection to the rightmost of the two RJ45 connectors.
Figure 1: Connections to the PLC
Instructions for remote line setup and use are given in chapter 4.
2.4.3. Connection of External Interlocks
Interlocks, externals as well as internals, are connected to the control system PLC through 24V
relays. Both PLC and the relays can shut down the power supply in case of an interlock. This
offers two undependable ways of shutting down.
Interlock inputs are designed for external potential free contacts. The open circuit
voltage is <30V and the closed-circuit current is <20mA. See power supply manual and
drawings for details.
Remote
Ethernet
connection
to IPC
EtherCAT
connection,
used by internal
I/O modules
Power

Page 10 of 32 Rev 0.95
3. Local control interface
The local interface is a Beckhoff CP6706 Industrial PC with a touch sensitive monitor on which
the HMI of the control system is displayed.
Figure 2: The main screen
When the power supply is turned on, the operating system will boot up and show the main
screen, please see Figure 2. The main screen consists of three main areas, the right-hand
menu, bottom menu and the set and display area. In the bottom of the screen the IP address
for remote connection can be seen as well as the version of the current software running on the
PLC and the time of date.
The right-hand menu
The right-hand menu consists of four buttons and they are from the bottom the mode button,
controlling the local/remote mode of the MPS, the interlock button, showing the interlock state,
the standby button and the on button.
3.1.1. Changing the mode
The control system can be in four command modes: Local, Local Locked, Remote and Remote
Locked. When the system is in Local mode, the MPS can be controlled only from the local
interface. It is possible to ask about status on the remote line but it is not possible to set values
on the remote line. It is possible to switch to Remote mode from the local interface and also set
it in Remote mode from the remote line. When the system is in Local Locked mode, the system
can only be set in a different mode from the local interface. When the system is in Remote
Locked mode, the system can only be set in a different mode from remote.
When the system is in Remote mode it is possible to set values over the remote line and the
values will be displayed on the local interface but it is not possible set values from the local
interface.
3.1.2. Interlocks and warnings
All interlocks and warnings are displayed in the interlock list, which can be accessed by pressing
the interlock button in the right-hand menu. When there is an interlock, the interlock button is
red, when there are only warnings the button is yellow. All interlocks are latched, meaning they
will only be reset and disappear from the list after a Reset command has been issued or the
reset button, depending on what mode the MPS is in. Warnings are not latched and are
Right
hand
menu
Bottom menu
Set and
display
area

System 8700 User Manual
Rev 0.95 Page 11 of 32
therefore only displayed while they are active. Interlocks are displayed in red text, and
warnings are displayed in red text with a star (*) in front.
Figure 3: The interlock list
The interlock list is collapsed again when the interlock button is pressed.
3.1.3. Turning the power supply on
The power supply has three states: Off, Standby and On. The power supply must first be in
Standby state before it can be turned On.
In order to turn the power supply On from the local panel, the following sequence must be
executed:
1. Set the system in Local mode by pressing the mode button in the right-hand panel and
pressing “L”.
2. Make sure that there are no faults. Faults are indicated with a red “FAULT” button in the right
panel. Press the red Faults button to view the faults in the Faults screen. Press the Reset
button to reset them.
3. Press the STANDBY button, the button will turn green when it is in standby mode
4. Press the ON button, the button will turn green when it is in On mode.
3.1.4. Turn the Power Supply Off
To turn the power supply Off, press the OFF button (it is not necessary to go through the
Standby state).
An overview if the Standby, On and Off state is shown in Figure 5. A diagram of how the states
relate to each other is indicated in Figure 4.

Page 12 of 32 Rev 0.95
On
Off
Standby Off & fault
On
Reset & fault
Figure 4 The state diagram.
Setting a current or voltage
From the main screen the current can be set by
selecting a digit and change its value using the + and
- buttons. If the MPS is in the On state, the set
current (or set voltage, see later) is changed as soon
as the digit is changed. The current is set and read in
amps by default but the software can be configured
to use PPM for the set current, in the setup screen.
When the digit is changed upward and it reaches “9”,
moving it up one more will change that digit to “0”
but the digit to the left will also increase by 1.
The set values are limited to the minimum and
maximum values indicated in the setup screen.
Off Standby On
Figure 5 How the Off, Standby
and On states are indicated

System 8700 User Manual
Rev 0.95 Page 13 of 32
Settings
In order to get access to the setup screen the Setup button in the bottom menu can be
pressed.
Figure 6: The Setup window
On the setup screen the Maximum
and minimum current can be set as
well as the maximum voltage. The
user will not be allowed to set
values on the main page outside
the ranges indicated here.
Also, the control mode can be set,
current or voltage controlled. If the
control mode is set to Voltage, an
extra input field appears on the
front page allowing to also set a
voltage. Note that this is only
possible for power supplies with
implemented voltage control loop
in the regulation system. For
power supplies without this feature; use of voltage control will have no effect
The units for the set current can be set to either Amps or PPM (parts per million). If PPM is
selected the current set digits changes to a 6 digit display where 999999 ppm is 100% output
current. The read back value of the current is always in Amps. Both set voltage and read back
voltage is always in volts, please see Figure 8.
Figure 7 Control mode set to Voltage

Page 14 of 32 Rev 0.95
Figure 8 Unit set to PPM
The login screen
Figure 9 The setup screens login window
The login screen is used by Danfysik staff for calibration and maintenance tasks.
Advanced Settings
Following settings are for advanced use only. Use of strict syntax is important for the stability of
the control system.
3.5.1. The interlock file
The interlock file controls the setup of interlocks: what text should be shown and if it is a
warning or a real interlock.
The format is as follows:
PersistentData.aInterlocks[3].sDisplayText:='Water flow too low'
PersistentData.aInterlocks[3].bIsLock:=TRUE
PersistentData.aInterlocks[3].bIsWarn:=FALSE

System 8700 User Manual
Rev 0.95 Page 15 of 32
and there is a section like above for each interlock. The number in the square brackets is the
index of the interlock, please use Table 4, Table 5 and Table 6 to find out what digital input is
connected to what interlock data variables.
The variables are used as follows:
•sDisplayText: This variable sets the display text that will be shown in the interlock list in
the HMI.
•bIsLock: True indicates that this is a true interlock.
•bIsWarn: True indicates that this a warning.
bIsLock and bIsWarn cannot be true at the same time.
It is very important that the format and the order of the file is maintained. The software that
reads the file on the PLC requires a specific syntax to read the file. It is not allowed to make
comments in the file. It is not allowed to add extra white spaces in the file.
3.5.2. Editing the files
Basically there are two ways to edit the file:
•FTP. Use a normal FTP client to connect to the PLCs IP address and use the user name
“Danfysik” and password “Danfysik”. Navigate to the directory /root-www/Recipes and
download the required file. Edit the file and upload the file again.
•Local editor. On the local monitor go to the Windows Start menu as described in section
4.4.1 and Click Run and type in “notepadce”. In the NotepadCE program click File/Open and
navigate to \Hard Disk\WWW\Recipes\ and load the required file.
4. Remote control interface
The MPS can be controlled remotely either via ethernet or via RS232.
Ethernet interface
The remote communication interface is TCP/IP, via the RJ45 connector marked LAN2 in the
bottom of the Beckhoff CP6706 IPC (Industrial PC), please see Figure 10. Please note that there
are two RJ45 connectors on the IPC, the one marked “LAN1” in Figure 1 is for the
communication to the I/O modules.
Figure 10: The connections on the Beckhoff CP6706 IPC

Page 16 of 32 Rev 0.95
Serial RS232 interface
To be described
Remote control commands
There are two sets of commands for controlling the MPS, SCPI commands and a subset of the
commands used for the older models of the Danfysik MPS.
4.3.1. SCPI commands
The SCPI communication protocol is based on the IEEE standard “Standard Commands for
Programmable Instruments” (SCPI) but only a subset of commands is implemented. The
definition of the standard can be found here:
http://www.ivifoundation.org/docs/scpi-99.pdf
However, this is rather lengthy and an easier to read example of how it can be implemented
can be found here:
http://www.us.tdk-lambda.com/hp/pdfs/product_manuals/83034100.pdf, please see
page 35-45.
In short, SCPI is a standard set of commands implemented by many of the major instrument
companies, making it much easier to implement different instruments in software.
Most SCPI commands, but not all, have “set” version and an “ask” version. Example:
•The command “OUTP:CURR 22.56” sets the current to 22.56 amps.
•The command “OUTP:CURR?” asks for the current set value and will return “22.56”.
The computer uses port 13000 for the SCPI communication.
The implemented commands are listed in Table 1.
Table 1: Implemented SCPI commands
Command
Description
*CLS
Clear status command, same as the reset
command *RST
*IDN?
Identification query. The response includes the
PLC version as well as the parser version.
*RST
Reset command, resets all interlocks.
*STB?
Returns the Status register. The command is
equivalent to STATus?
SYSTem:ERRor[:NEXT]?
Returns the top entry of the status queue for the
parsing of the commands in the format "error#,
error text". Error# 0 means no error. When the
command is issued the entry is removed from the
queue and next entry is brought to the top of the
queue.
SYSTem:VERSion?
Returns the software release number

System 8700 User Manual
Rev 0.95 Page 17 of 32
Command
Description
STATus?
Returns the Status register bits as a decimal
number. What the bits represents is listed in
Table 2.
STATus:OPERation?
Returns the Status:Operations register bits as a
decimal number. What the bits represents is listed
in Table 3.
STATus:OPERation:REG1?
Returns the Status:operations:REG1 register bits
as a decimal number. These are the
warning/interlock bit, but the exact mapping is
Listed in Table 4.
STATus:OPERation:REG2?
Returns the Status:operations:REG2 register bits
as a decimal number. These are the
warning/interlock bit, the exact mapping is listed
in Table 5.
STATus:OPERation:REG3?
Returns the Status:operations:REG3 register bits
as a decimal number. These are the
warning/interlock bit, the exact mapping is listed
in Table 6.
STATus:OPERation:REG4?
Returns the Status:operations:REG4 register bits
as a decimal number. These are the
warning/interlock bit from the digiloop card, the
exact mapping is listed in Table 7.
[:SOURce]:CURRent[:LEVel][:IMMediate][:AMPLitude]
{<level (A)>
Sets the current
[:SOURce]:CURRent[:LEVel][:IMMediate][:AMPLitude]
?
Returns the set current
[:SOURce]:VOLTage[:LEVel][:IMMediate][:AMPLitude]
{<level (V)>
Sets the voltage
[:SOURce]:VOLTage[:LEVel][:IMMediate][:AMPLitude]
?
Returns the set voltage
OUTPut:RELay[:STATe] {0|1|2|STB|ON|OFF}
Sets the state of the system, on/off/standby. 0 =
STB, 1 = ON, 2 = OFF. The system must be in
STB before it can be set in ON state.
OUTPut:RELay[:STATe]?
Returns the state of the system 0 = STB, 1 = ON,
2 = OFF, 3 = ERROR.
MEASure[:SCALar]:VOLTage[:DC]?
Returns the read voltage
MEASure[:SCALar]:CURRent[:DC]?
Returns the read current
SYSTem:DATE yyyy, mm, dd
Sets the date. Both e.g. “9” and “09” will work for
setting moth and day.

Page 18 of 32 Rev 0.95
Command
Description
SYSTem:DATE? <yyyy>-<mm>-<dd>-
<hh>:<mm>:<ss>
Returns the date and time in the format
DT#yyyy-mm-dd-hh:mm:ss
SYSTem:LOCK:OWNer?
This query returns what mode the system is
currently in. 0 = Local, 1 = Remote, 2 = Local
locked, 3 = Remote locked
SYSTem:LOCK:RELease
This event releases the system from the Remote
Locked Mode. If the system is not in the remote
locked mode, this command has no effect. This
command has no query form.
SYSTem:LOCK:REQuest?
The command attempts to set the system in
remote mode. This event is only implemented as
a query.
SYSTem:LOCK:LREQuest?
The command attempts to set the system in
remote locked mode. The system must be in
remote mode to allow this operation. This event
is only implemented as a query.
SYSTem:TIME hh, mm, ss
Sets the system time. All three parameters must
be given. Both 9 and 09 will work for e.g. setting
the hours. Hours are set as on a 24 hour clock.
SYSTem:TIME? <yyyy>-<mm>-<dd>-
<hh>:<mm>:<ss>
Returns the date and time in the format
DT#yyyy-mm-dd-hh:mm:ss
[SOURce:]FREQuency[:LEVel] {<level (Hz)>|
Sets the switching frequency. This command is
not implemented on all versions of the MPS.
[SOURce:]FREQuency[:LEVel]?
Returns the switching frequency. This command
is not implemented on all versions of the MPS.

System 8700 User Manual
Rev 0.95 Page 19 of 32
4.3.1.1. Status reporting
The status reporting is done via the OPERation status register with the command
STATus:OPERation. The different status, warnings and errors are split up in separate arrays,
see below. The array is summed up on the level above with an “or” so that if one or more bits
are set in an array, the bit on the level above will also be set. New sub commands have been
constructed to get the individual sub arrays e.g. to read the status bits in register 1, the
command STATus:QUEStionable:REG1 is used.
In the tables below the Bit indicates what bit the signal corresponds to after the decimal
number returned by the command has been converted to a binary digit, see also the example
after Table 6 for further explanation. The Input column indicates what digital input the signal is
connected to. If no input is indicated the signal is generated internally.
4.3.1.2. Status, bit 9
Command: STATus
Bit
Signal
Interpretation
0
Output On
1: Output is on
1
Ready
1: regulation reports output within defined limits
2
-
Not used
3
-
Not used
4
Sum interlock
1: one or more interlocks present
5
-
Not used
6
-
Not used
7
Operation Status
1: Further info in Operation Status registers available
Table 2 The status register

Page 20 of 32 Rev 0.95
4.3.1.3. Operation status , bit 7
Command: STATus:OPERation
Bit
Signal
Interpretation
0
-
Not used
1
-
Not used
2
-
Not used
3
-
Not used
4
-
Not used
5
-
Not used
6
-
Not used
7
-
Not used
8
-
Sum interlock
9
-
Not used
10
REG1
Sum bit for register 1, see below.
11
REG2
Sum bit for register 2, see below.
12
REG3
Sum bit for register 3, see below.
13
REG4
Sum bit for register 4, see below.
14
-
Not used
Table 3 Operation register
Table of contents
Other Danfysik Control System manuals