Rev. 01 ©2020 Darfon Electronics Corp. 4| Page
INSTALLATION MANUAL DL-300 DATA LOGGER
Connections
Port Description
ANT Attach the antenna for WiFi connection.
WAN Connect the RJ-45 cable for a LAN connection.
3G/4G Connect a 3G/4G dongle for a cellular connection.
DATA USB flash drive.
(T0) RS485 Connects to the hybrid inverter for two-way communication.
(T1) RS485 External RS485 sensor device reserved.
RESET Factory default reset button. Insert a pin and hold for 30 seconds.
LED Definitions
LED Activity Description
WAN ●●Solid
●●Flashing
●●Off
The LAN is connected.
Data is being transmitted or received.
No connection established.
WIFI ●●Solid
●●Flashing
●●Off
The WIFI is enabled.
Data is being transmitted or received.
WIFI is disabled.
DL PWR ●●Solid
●●Solid
●●Off
Power is on.
System initialization.
There is no Power.
(T0) RS485 ●●Solid
●●Solid
●●Off
A command is transmitted to the inverter(s).
A command is received from the inverter(s).
No commands are being transmitted or received.
(T1) RS485 ●●Solid
●●Solid
●●Off
A command is transmitted to the device(s).
A command is received from the device(s).
No commands are being transmitted or received.
MOUNTING THE DATA LOGGER
Location Requirements
■ The DL-300 has an IP20 rated enclosure, which means it must be installed indoors.
■ The RS485 cable is about 4’ long, so the data logger should be mounted no more than 3 feet away from the inverter.
■ The data logger requires an internet connection, be it wired, WiFi or cellular.
■ The data logger can be mounted to the wall, or elsewhere with the use of the din rail and din rail mounts.
Step 1. If the data logger cannot be secured to a stud in the wall, insert drywall anchors prior to installation.
Step 2. Place the data logger against the wall and secure with two screws.