Data Aire DAP III Quick setup guide

Data Aire DAP III
SNMPv1/v2c
Protocol Integration Information
Data Aire, Inc.
230 West Blueridge Avenue
Orange, California 92865
Document Number 600-000-615
November 2010
Revision 3.0
Document 600-000-615 1

Table of Contents
1Overview.................................................................................................................................3
2Hardware Requirements and Installation........................................................................3
2.1 Required Network Card.....................................................................................................3
2.2 Network Card Installation..................................................................................................3
2.3 Network Wiring................................................................................................................. 4
3Communication Port Setting..............................................................................................5
4Community Data string .......................................................................................................5
5Sending Traps on Alarms....................................................................................................5
6MIB (Management Information Base) file.....................................................................5
7SNMP Object Definitions for DAP III............................................................................5
7.1 Control Module Status (Read Only).................................................................................. 5
7.2 Control Module Control (Read/Write)...............................................................................9
7.3 Control Module Configuration (Read/Write) ..................................................................10
7.4 Control Module Configuration (Read Only)....................................................................10
7.5 Control Expansion Module Status (Read Only-Optional)............................................... 13
7.6 Control Expansion Module Configuration (Read/Write-Optional).................................14
7.7 Control Expansion Module Configuration (Read Only-Optional) .................................. 14
7.8 Relay Module Status (Read Only-Optional)....................................................................15
7.9 Relay Module Configuration (Read/Write-Optional)......................................................15
7.10 Relay Module Configuration (Read Only-Optional).......................................................15
7.11 Analog Module Status (Read Only-Optional) ................................................................. 16
7.12 Analog Module control (Read/Write – Optional)............................................................ 16
7.13 Analog Module Configuration (Read Only-Optional).....................................................16
Document 600-000-615 2

1 Overview
The DAP III control panel supports SNMPv1and SNMPv2c protocol interface for a system
monitoring. This document describes all requirements in the DAP III to implement the
SNMPv1/v2c interface; it also provides all the DAP III SNMP objects definition that the DAP III
supports.
Note: Data Aire does not provide the SNMP tools or monitoring applications. The customer is
responsible for these tools or monitoring software.
2 Hardware Requirements and Installation
2.1 Required Network Card
2.1.1 The SNMP protocol interface requires a Data Aire Ethernet network card to be installed
into the DAP III Display board. The Ethernet card part number is 160-400-385. This card is
compliant with IEEE 802.3/802.3u 100BaseTX Ethernet standard and auto-negotiation at
10Mbps/ 100 Mbps.
RJ-45 CONNECTORBOARD CONNECTOR
Figure 1: Data Aire Ethernet Communications Network card
2.2 Network Card Installation
2.2.1 For SNMP interface, connect an Ethernet Communications network card to the
Communication Header J1 of the DAP III Display board. See figure 2 for the DAP III
Display board with an Ethernet card installed.
After installing the network card, go to menu 6-1 – Unit and Network ID in Group menu 6
to set the unit network ID and to menu 6-2 –Network protocol to configure the network
protocol. Menu 6-2 to 6-7 are locked menus, refer to the DAP III Operation Manual for the
procedure of how to unlock these menus before entering IP address. It is recommended to
reset the DAP III panel after changing the network protocol, IP adress or the unit ID
number.
Document 600-000-615 3

2.3 Network Wiring
2.3.1 For the Ethernet connection, Use the CAT-5 Ethernet cable. The DAP III panel should be
connected to the same network with the monitoring PC or BMS. See figure 3 for details.
Each unit requires having a dedicated IP address. Consult with the building IT personnel
or building network administrator on IP addressing.
Figure 2: DAP III Display Board With an Ethernet Communications Network Card
Communication Header J1
RJ-45 Connector with Link and Activity LED
N
etwork switch or hub
(Supplied by others)
Ethernet connection to BMS
Ethernet Communication Card
BMS computer
DAP III Display board of unit #1
with Ethernet card (Supplied by
Data Aire.)
DAP III Display board of unit #2
with Ethernet card (Supplied by
Data Aire.)
Figure 3: Network wiring
Document 600-000-615 4

3 Communication Port Setting
For SNMP communication UDP port setting is 161, refer to the DAP III Operation Manual for the
procedure to enter an IP address and port setting to the DAP III.
4 Community Data string
The Data Aire DAP III SNMP community data string is default to “public”.
See section 7.3 for community string override OID.
5 Sending Traps on Alarms
The DAP III with SNMP interface can be configured to send out traps on alarms to two
different IP addresses. These IP addresses are programmed on menu 6-12 SNMPv2
Manager 1 Address and menu 6-14 SNMPv2 Manager 2 Address of the DAP III using the
front panel keypad. These menus are locked menus; they must be unlocked before any
programming can be done. See DAP III IOM for the procedure of how to unlock these
menus.
The alarms’ selection for traps can be selected using menu 6-13 SNMPv2 Manager 1
Notifications and menu 6-15 SNMPv2 Manager 2 Notifications. When selected alarm
occurs, DAP III will send an alert trap to the assigned Manager IP address that is
programmed in menu 6-12 or 6-14.
6 MIB (Management Information Base) file
The MIB file of the DAP III control panel can be downloaded from Data Aire website at
http://www.dataaire.com in System Controls- Data Alarm Processor III (DAP III) page or contact
Data Aire technical support.
7 SNMP Object Definitions for DAP III
7.1 Control Module Status (Read Only)
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.1.1.0 INTEGER
off(0)
on(non-zero)
Dehumidifying
Unit is in the dehumidification cooling mode,
unit must have a reheat for this function to be
available
N/A
1.3.6.1.4.1.22731.1.2.1.2.0 INTEGER
off(0)
on(non-zero)
Humidifying
Unit is in the humidification mode, reheat will
be inhibited when humidifier is on
N/A
1.3.6.1.4.1.22731.1.2.1.3.0 INTEGER
off(0)
on(non-zero)
Energy Saver
Optional function. Unit must be an energy saver
model and a chilled water sensor must be
installed.
N/A
1.3.6.1.4.1.22731.1.2.1.4.0 INTEGER
off(0) Cooling Held
Cooling is in inhibited mode N/A
Document 600-000-615 5

Object Identifier Type Description Units
on(non-zero)
1.3.6.1.4.1.22731.1.2.1.5.0 INTEGER
off(0)
on(non-zero)
Heating Held
Heating is in inhibited mode N/A
1.3.6.1.4.1.22731.1.2.1.6.0 INTEGER
off(0)
on(non-zero)
Humidification Held
Humidification is in inhibited mode N/A
1.3.6.1.4.1.22731.1.2.1.7.0 INTEGER
off(0)
on(non-zero)
Dehumidification Held
Dehumidification is inhibted N/A
1.3.6.1.4.1.22731.1.2.1.8.0 INTEGER
off(0)
on(non-zero)
Reheating During Dehumidification
Heating is on during dehumidification mode N/A
1.3.6.1.4.1.22731.1.2.1.9.0 INTEGER Return Temperature
This represents the current return air
temperature
0.1°F
1.3.6.1.4.1.22731.1.2.1.10.0 INTEGER Current Humidity
This represents the current relative humidity 0.1%RH
1.3.6.1.4.1.22731.1.2.1.11.0 INTEGER (0..5) Cooling Stages On
Cooling stages are currently on – This point
applies to DX unit only
N/A
1.3.6.1.4.1.22731.1.2.1.12.0 INTEGER (0..4) Heating Stages On
Heating stages are currently on N/A
1.3.6.1.4.1.22731.1.2.1.13.0 INTEGER High Temperature Over Last 24 Hours
Maximum return air temperature in the last 24
hours of operation
0.1°F
1.3.6.1.4.1.22731.1.2.1.14.0 INTEGER Low Temperature Over Last 24 Hours
Minimum return air temperature in the last 24
hours of operation
0.1°F
1.3.6.1.4.1.22731.1.2.1.15.0 INTEGER High Humidity Over Last 24 Hours
Maximum return air humidity in the last 24
hours of operation
0.1°F
1.3.6.1.4.1.22731.1.2.1.16.0 INTEGER Low Humidity Over Last 24 Hours
Minimum return air humidity in the last 24
hours of operation
0.1°F
1.3.6.1.4.1.22731.1.2.1.17.0 INTEGER Cooling Utilization Over Last Hour
Percentage of cooling is used in the last hour of
operation; this point applies to DX unit.
%
1.3.6.1.4.1.22731.1.2.1.18.0 INTEGER Heating Utilization Over Last Hour
Percentage of heating is used in the last hour of
operation
%
1.3.6.1.4.1.22731.1.2.1.19.0 INTEGER Humidifier Utilization Over Last Hour
Percentage of humidifier is used in the last hour
of operation
%
1.3.6.1.4.1.22731.1.2.1.20.0 INTEGER Compressor 1 Runtime
This point applies to DX unit with one
compressor
Hours
1.3.6.1.4.1.22731.1.2.1.21.0 INTEGER Compressor 2 Runtime
This point applies to DX unit with dual
compressor
Hours
1.3.6.1.4.1.22731.1.2.1.22.0 INTEGER Heater 1 Runtime Hours
1.3.6.1.4.1.22731.1.2.1.23.0 INTEGER Humidifier Runtime Hours
Document 600-000-615 6

Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.1.24.0 INTEGER Blower Runtime Hours
1.3.6.1.4.1.22731.1.2.1.25.0 INTEGER Dehumidifier Runtime Hours
1.3.6.1.4.1.22731.1.2.1.26.0 INTEGER
off(0)
on(non-zero)
Water detected under floor: Check probe
Standard alarm on Data Aire series units N/A
1.3.6.1.4.1.22731.1.2.1.27.0 INTEGER
off(0)
on(non-zero)
No air flow: Check belt and motor
Standard alarm N/A
1.3.6.1.4.1.22731.1.2.1.28.0 INTEGER
off(0)
on(non-zero)
Dirty filter: Check filters
Standard alarm on Data Aire series, optional on
ceiling units
N/A
1.3.6.1.4.1.22731.1.2.1.29.0 INTEGER
off(0)
on(non-zero)
Humidifier problem: Check water pressure
Standard alarm on Data Aire series, optional on
ceiling units
N/A
1.3.6.1.4.1.22731.1.2.1.30.0 INTEGER
off(0)
on(non-zero)
Low voltage warning: Check unit
Standard alarm on unit with DAP III N/A
1.3.6.1.4.1.22731.1.2.1.31.0 INTEGER
off(0)
on(non-zero)
Fire stat alarm: Unit shutdown
Standard alarm, unit will temporary shutdown
when this alarm goes off
N/A
1.3.6.1.4.1.22731.1.2.1.32.0 INTEGER
off(0)
on(non-zero)
Compressor short cycle warning
Standard alarm on DX units. This does not apply
to chilled water units. Compressor starts and
stops10 times in one-hour period.
N/A
1.3.6.1.4.1.22731.1.2.1.33.0 INTEGER
off(0)
on(non-zero)
Power problem or unit restart
Standard programmable alarm. Power loses then
restores
N/A
1.3.6.1.4.1.22731.1.2.1.34.0 INTEGER
off(0)
on(non-zero)
Humidity sensor problem
Standard alarm. Humidity sensor reading is out
of range
N/A
1.3.6.1.4.1.22731.1.2.1.35.0 INTEGER
off(0)
on(non-zero)
Temperature sensor problem
Standard alarm. Temperature reading is out of
range
N/A
1.3.6.1.4.1.22731.1.2.1.36.0 INTEGER
off(0)
on(non-zero)
Scheduled maintenance due
Standard programmable alarm. N/A
1.3.6.1.4.1.22731.1.2.1.37.0 INTEGER
off(0)
on(non-zero)
High pressure/Internal overload: Comp 1
Standard alarm on DX unit with one
compressor. Compressor’s high pressure switch
is open
N/A
1.3.6.1.4.1.22731.1.2.1.38.0 INTEGER
off(0)
on(non-zero)
Low pressure C1: Automatic reset
Standard alarm on DX unit with one
compressor. Compressor’s low pressure switch
is open
N/A
1.3.6.1.4.1.22731.1.2.1.39.0 INTEGER
off(0)
on(non-zero)
High pressure/Internal overload: Comp 2
Standard alarm on DX unit with dual
compressor. Compressor’s high pressure switch
is open
N/A
1.3.6.1.4.1.22731.1.2.1.40.0 INTEGER
off(0)
on(non-zero)
Low pressure C2: Automatic reset
Standard alarm on DX unit with dual
compressor. Compressor’s low pressure switch
is open
N/A
Document 600-000-615 7

Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.1.41.0 INTEGER
off(0)
on(non-zero)
Smoke detector: Unit shutdown
Optional alarm. An optional smoke detector
required
N/A
1.3.6.1.4.1.22731.1.2.1.42.0 INTEGER
off(0)
on(non-zero)
No water flow: Check pump
Optional alarm. An optional flow switch
required
N/A
1.3.6.1.4.1.22731.1.2.1.43.0 INTEGER
off(0)
on(non-zero)
Discharge temperature sensor problem
Optional alarm. An optional discharge air
temperature sensor required
N/A
1.3.6.1.4.1.22731.1.2.1.44.0 INTEGER
off(0)
on(non-zero)
High temperature warning
Standard alarm. The return air temperature rises
above the high temperature limits
N/A
1.3.6.1.4.1.22731.1.2.1.45.0 INTEGER
off(0)
on(non-zero)
Low temperature warning
Standard alarm. The return air temperature drops
below the low temperature limits
N/A
1.3.6.1.4.1.22731.1.2.1.46.0 INTEGER
off(0)
on(non-zero)
High humidity warning
Standard alarm. The relative humidity rises
above the high humidity limits
N/A
1.3.6.1.4.1.22731.1.2.1.47.0 INTEGER
off(0)
on(non-zero)
Low humidity warning
Standard alarm. The relative humidity drops
below the low humidity limits
N/A
1.3.6.1.4.1.22731.1.2.1.48.0 INTEGER
off(0)
on(non-zero)
Fan motor overload: Check motor amperage
Optional alarm. Optional fan motor overload
required.
N/A
1.3.6.1.4.1.22731.1.2.1.49.0 INTEGER
off(0)
on(non-zero)
Local alarm #1: See tag inside door
Optional alarm. External alarm input required N/A
1.3.6.1.4.1.22731.1.2.1.50.0 INTEGER
off(0)
on(non-zero)
Local alarm #2: See tag inside door
Optional alarm. External alarm input required N/A
1.3.6.1.4.1.22731.1.2.1.51.0 INTEGER
off(0)
on(non-zero)
Local alarm #3: See tag inside door
Optional alarm. External alarm input required N/A
1.3.6.1.4.1.22731.1.2.1.52.0 INTEGER
off(0)
on(non-zero)
Local alarm #4: See tag inside door
Optional alarm. External alarm input required N/A
1.3.6.1.4.1.22731.1.2.1.53.0 INTEGER
off(0)
on(non-zero)
Standby pump on: Check primary pump
Optional alarm. Pump failure input signal
required
N/A
1.3.6.1.4.1.22731.1.2.1.54.0 INTEGER
off(0)
on(non-zero)
Alarm: UPS power on: Check main power
Optional alarm. External alarm input required
N/A
1.3.6.1.4.1.22731.1.2.1.55.0 INTEGER
off(0)
on(non-zero)
Custom alarm #1
Optional alarm. External alarm input required.
Factory programmed custom message required
N/A
1.3.6.1.4.1.22731.1.2.1.56.0 INTEGER
off(0)
on(non-zero)
Custom alarm #2
Optional alarm. External alarm input required
Factory programmed custom message required
N/A
1.3.6.1.4.1.22731.1.2.1.57.0 INTEGER
off(0)
on(non-zero)
Custom alarm #3
Optional alarm. External alarm input required
Factory programmed custom message required
N/A
Document 600-000-615 8

Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.1.58.0 INTEGER
off(0)
on(non-zero)
Custom alarm #4
Optional alarm. External alarm input required
Factory programmed custom message required
N/A
1.3.6.1.4.1.22731.1.2.1.59.0 INTEGER
off(0)
on(non-zero)
Humidification inhibited
Optional alarm. External alarm input required.
Humidification is inhibited when alarm goes off.
N/A
1.3.6.1.4.1.22731.1.2.1.60.0 INTEGER
off(0)
on(non-zero)
Reheat inhibited
Optional alarm. External alarm input required.
Reheat is inhibited when alarm goes off.
N/A
1.3.6.1.4.1.22731.1.2.1.61.0 INTEGER
off(0)
on(non-zero)
Reheat and humidification inhibited
Optional alarm. External alarm input required.
Reheat and humidification are inhibited when
alarm goes off.
N/A
1.3.6.1.4.1.22731.1.2.1.62.0 INTEGER
off(0)
on(non-zero)
Low discharge air temperature
Optional alarm. Optional discharge air
temperature sensor required.
N/A
1.3.6.1.4.1.22731.1.2.1.63.0 INTEGER
off(0)
on(non-zero)
Manual override: Check bypass switches
Standard alarm. Manual override switch is on N/A
1.3.6.1.4.1.22731.1.2.1.64.0 INTEGER
off(0)
on(non-zero)
High condensate water level
Standard alarm on Ceiling unit, optional alarm
on Floor mounts units.
N/A
1.3.6.1.4.1.22731.1.2.1.65.0 INTEGER
off(0)
on(non-zero)
Unit in standby, all functions held off
Optional alarm. Control input signal required
Factory setting required
N/A
1.3.6.1.4.1.22731.1.2.1.117 INTEGER
off(0)
on(non-zero)
Alarm: Chilled water temperature sensor
problem
This alarm requires optional chilled water sensor
N/A
1.3.6.1.4.1.22731.1.2.1.122 INTEGER
off(0)
on(non-zero)
Alarm: Check Humidifier Cylinder
This alarm requires optional humidifier cylinder
alarm contact from humidifier controller
N/A
7.2 Control Module Control (Read/Write)
Network Variable Network Variable Type Description Units
1.3.6.1.4.1.22731.1.2.1.66.0 INTEGER
off(0)
on(non-zero)
Cooling Inhibited
Cooling is inhibited by BMS or
BAS
N/A
1.3.6.1.4.1.22731.1.2.1.67.0 INTEGER
off(0)
on(non-zero)
Heating Inhibited
Heating is inhibited by BMS or
BAS
N/A
1.3.6.1.4.1.22731.1.2.1.68.0 INTEGER
off(0)
on(non-zero)
Humidification Inhibited
Humidifier is inhibited by BMS
or BAS
N/A
1.3.6.1.4.1.22731.1.2.1.69.0 INTEGER
off(0)
on(non-zero)
Dehumidification Inhibited
Dehumidification is inhibited by
BMS or BAS
N/A
1.3.6.1.4.1.22731.1.2.1.70.0 INTEGER
off(0)
on(non-zero)
Fan Inhibited
Fan is inhibited by BMS or BAS N/A
1.3.6.1.4.1.22731.1.2.1.71.0 INTEGER
Unit on(0) Standby Mode
Unit on/off control
p
oint b
y
N/A
Document 600-000-615 9

Network Variable Network Variable Type Description Units
Unit off (1)
Unit standby(2)
BMS or BAS
7.3 Control Module Configuration (Read/Write)
Network Variable Network Variable Type Description Units
1.3.6.1.4.1.22731.1.2.1.72.0 INTEGER (0..59) Time of Day: Seconds N/A
1.3.6.1.4.1.22731.1.2.1.73.0 INTEGER (0..59) Time of day: Minutes N/A
1.3.6.1.4.1.22731.1.2.1.74.0 INTEGER (0..23) Time of day: Hours N/A
1.3.6.1.4.1.22731.1.2.1.75.0 INTEGER (1..31) Time of day: Day N/A
1.3.6.1.4.1.22731.1.2.1.76.0 INTEGER (1..12) Time of day: Month N/A
1.3.6.1.4.1.22731.1.2.1.77.0 INTEGER Time of day: Year N/A
1.3.6.1.4.1.22731.1.2.1.78.0 INTEGER (100..150) Fire Temperature Limit °F
1.3.6.1.4.1.22731.1.2.1.79.0 INTEGER (10..90) High Humidity Limit %RH
1.3.6.1.4.1.22731.1.2.1.80.0 INTEGER (50..90) High Temperature Limit °F
1.3.6.1.4.1.22731.1.2.1.81.0 INTEGER (10..90) Low Humidity Limit %RH
1.3.6.1.4.1.22731.1.2.1.82.0 INTEGER (50..90) Low Temperature Limit °F
1.3.6.1.4.1.22731.1.2.1.83.0 INTEGER (1..15) Humidity Deadband %RH
1.3.6.1.4.1.22731.1.2.1.84.0 INTEGER (25..70) Humidity Setpoint %RH
1.3.6.1.4.1.22731.1.2.1.85.0 INTEGER (1..5) Temperature Deadband °F
1.3.6.1.4.1.22731.1.2.1.86.0 INTEGER (65..85) Temperature Setpoint °F
1.3.6.1.4.1.22731.1.2.1.87.0 INTEGER (5..600) Start Delay Seconds
1.3.6.1.4.1.22731.1.2.1.118 DisplayString
(SIZE (0..20)) Read Community String N/A
1.3.6.1.4.1.22731.1.2.1.119 DisplayString
(SIZE (0..20)) Write Community String N/A
1.3.6.1.4.1.22731.1.2.1.120 IPAddress Trap Destination Address 1 N/A
1.3.6.1.4.1.22731.1.2.1.121 IPAddress Trap Destination Address 2 N/A
7.4 Control Module Configuration (Read Only)
Network Variable Network Variable Type Description Units
1.3.6.1.4.1.22731.1.2.1.88.0 INTEGER
off(1)
on(2)
Humidity Anticipation Enable N/A
1.3.6.1.4.1.22731.1.2.1.89.0 INTEGER
off(1)
on(2)
Self-Test Auto Acknowledge N/A
1.3.6.1.4.1.22731.1.2.1.90.0 INTEGER
Fahrenheit(1)
Centigrade(2)
Temperature Mode N/A
1.3.6.1.4.1.22731.1.2.1.91.0 INTEGER
off(1)
on(2)
Short Cycle Alarm Enabled N/A
1.3.6.1.4.1.22731.1.2.1.92.0 DisplayString
(SIZE (0..40)) Custom Alarm Message 1
Optional factory programmed
alarm message.
N/A
1.3.6.1.4.1.22731.1.2.1.93.0 DisplayString
(SIZE (0..40)) Custom Alarm Message 2
Optional factory programmed
alarm message.
N/A
Document 600-000-615 10

Network Variable Network Variable Type Description Units
1.3.6.1.4.1.22731.1.2.1.94.0 DisplayString
(SIZE (0..40)) Custom Alarm Message 3
Optional factory programmed
alarm message.
N/A
1.3.6.1.4.1.22731.1.2.1.95.0 DisplayString
(SIZE (0..25)) Custom Contact
Optional factory programmed
contact information.
N/A
1.3.6.1.4.1.22731.1.2.1.96.0 INTEGER (0..5) Adjustment rate Minutes
1.3.6.1.4.1.22731.1.2.1.97.0 INTEGER (0..900) Optional Alarm 1 Delay Seconds
1.3.6.1.4.1.22731.1.2.1.98.0 INTEGER (0..900) Optional Alarm 2 Delay Seconds
1.3.6.1.4.1.22731.1.2.1.99.0 INTEGER (0..900) Optional Alarm 3 Delay Seconds
1.3.6.1.4.1.22731.1.2.1.100.0 INTEGER
checkHumidCylinder(1)
customAlarm1(2)
fanMotorOverload(3)
humidLockout(4)
localAlarm(5)
heatAndHumidLockout(6)
heatLockout(7)
standbyPumpOn(8)
upsOn(9)
unitInStandby(10)
Optional Alarm 1
Configuration N/A
1.3.6.1.4.1.22731.1.2.1.101.0 INTEGER
checkHumidCylinder(1)
customAlarm2(2)
fanMotorOverload(3)
humidLockout(4)
localAlarm(5)
heatAndHumidLockout(6)
heatLockout(7)
standbyPumpOn(8)
upsOn(9)
Optional Alarm 2
Configuration N/A
1.3.6.1.4.1.22731.1.2.1.102.0 INTEGER
checkHumidCylinder(1)
customAlarm3(2)
fanMotorOverload(3)
humidLockout(4)
localAlarm(5)
heatAndHumidLockout(6)
heatLockout(7)
standbyPumpOn(8)
upsOn(9)
Optional Alarm 3
Configuration N/A
1.3.6.1.4.1.22731.1.2.1.103.0 INTEGER Humidity Sensor Calibration 0.1%RH
1.3.6.1.4.1.22731.1.2.1.104.0 INTEGER Return Temperature Sensor
Calibration 0.1°F
1.3.6.1.4.1.22731.1.2.1.105.0 INTEGER
none(1)
pri(2)
pri-sec(3)
pri-pri(4)
pri-sec-pri-sec(5)
pri-pri-pri-pri(6)
Compressor Configuration
Factory setting N/A
1.3.6.1.4.1.22731.1.2.1.106.0 INTEGER
off(1)
one-with-limits(2)
Dehumidifier Configuration N/A
Document 600-000-615 11

Network Variable Network Variable Type Description Units
two-with-limits(3)
one-no-limits(4)
two-no-limits(5)
1.3.6.1.4.1.22731.1.2.1.107.0 INTEGER
none(1)
one-heat-strip(2)
two-heat-strips(3)
three-heat-strips(4)
hot-water(5)
Heater Configuration
Factory setting N/A
1.3.6.1.4.1.22731.1.2.1.108.0 INTEGER
none(1)
computer-non-modutating(2)
computer-modulating(3)
comfort-non-modulating(4)
comfort-modulating(5)
Humidifier Configuration
Factory setting N/A
1.3.6.1.4.1.22731.1.2.1.110.0 INTEGER
auto(1)
one-leads(2)
two-leads(3)
three-leads(4)
four-leads(5)
Lead-Lag Configuration N/A
1.3.6.1.4.1.22731.1.2.1.111.0 INTEGER (0..1000) Maintenance Interval Hours
1.3.6.1.4.1.22731.1.2.1.112.0 INTEGER (0..99) Front Panel Password N/A
1.3.6.1.4.1.22731.1.2.1.113.0 INTEGER
not-used(1)
data-processing-manager(2)
maintenance-engineer(3)
service-company(4)
custom-contact-message(5)
Person To Contact N/A
1.3.6.1.4.1.22731.1.2.1.114.0 INTEGER
auto-no-message-or-alarm(1)
auto-message-and-alarm(2)
manual-msg-alarm-relay(3)
Reset Mode N/A
1.3.6.1.4.1.22731.1.2.1.115.0 INTEGER
off(1),
short(2)
long(3)
full(4)
Buzzer Configuration N/A
1.3.6.1.4.1.22731.1.2.1.116.0 OCTET STRING
Each octet represents the index of
one current alarm from the
following table.
waterDetected(1)
noAirFlow(2)
dirtyFilter(3)
humidifierProblem(4)
lowVoltage(5)
fireAlarm(6)
shortCycle(7)
powerProblem(8)
humiditySensor(9)
temperatureSensor(10)
maintenanceRequired(11)
Alarm Relay 1 Settings N/A
Document 600-000-615 12

Network Variable Network Variable Type Description Units
highPressureC1(12)
lowPressureC1(13)
highPressureC2(14)
lowPressureC2(15)
smokeDetect(16)
noWaterFlow(17)
dischargeSensor(18)
chilledWaterSensor(19)
highTemperature(20)
lowTemperature(21)
highHumidity(22)
lowHumidity(23)
fanOverload(24)
localAlarm1(25)
localAlarm2(26)
localAlarm3(27)
localAlarm4(28)
standbyPumpOn(29)
upsOn(30)
customAlarm1(31)
customAlarm2(32)
customAlarm3(33)
customAlarm4(34)
humidInhibited(35)
reheatInhibited(36)
reheatAndHumidInhibited(37)
lowDischargeAlarm(38)
manualOverride(39)
highCondensate(40)
unitInStandbyHeldOff(41)
checkHumidCylinder(42)
7.5 Control Expansion Module Status (Read Only-Optional)
Note: these points do not apply to Mini-DAP III panel
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.2.1.0 INTEGER
not installed(0)
installed(non-zero)
Control Expansion Module Installed N/A
1.3.6.1.4.1.22731.1.2.2.2.0 INTEGER Chilled Water Temperature
Optional chilled water sensor required 0.1°F
1.3.6.1.4.1.22731.1.2.2.3.0 INTEGER Discharge Air Temperature
Optional Discharge Air temperature sensor required 0.1°F
1.3.6.1.4.1.22731.1.2.2.4.0 INTEGER Chilled Water Valve Open
This applies to Chilled water or Energy saver unit
only.
%
1.3.6.1.4.1.22731.1.2.2.5.0 INTEGER Chilled Water Utilization Over Last Hour
This applies to Chilled water or Energy saver units. %
1.3.6.1.4.1.22731.1.2.2.6.0 INTEGER Heater 2 Runtime Hours
1.3.6.1.4.1.22731.1.2.2.7.0 INTEGER Heater 3 Runtime Hours
1.3.6.1.4.1.22731.1.2.2.8.0 INTEGER Energy Saver Runtime
This optional point applies to energy saver units
only
Hours
Document 600-000-615 13

Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.2.9.0 INTEGER Chilled Water Runtime
This applies to chilled water units only Hours
1.3.6.1.4.1.22731.1.2.2.10.0 INTEGER Discharge Temperature Sensor Calibration
Optional discharge air temperature sensor required 0.1°F
1.3.6.1.4.1.22731.1.2.2.11.0 INTEGER Chilled Water Temperature Sensor Calibration
Optional chilled water temperature sensor required
0.1°F
7.6 Control Expansion Module Configuration (Read/Write-Optional)
Note: these points do not apply to Mini-DAP III panel
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.2.12.0 INTEGER (45..61) Low Discharge Temp Limit
This optional setting requires an
optional discharge air temperature
sensor
°F
1.3.6.1.4.1.22731.1.2.2.13.0 INTEGER (40..60) Chilled Water Available Limit
Optional chilled water temperature
sensor required. This applies to
energy saver units.
°F
7.7 Control Expansion Module Configuration (Read Only-Optional)
Note: these points do not apply to Mini-DAP III panel
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.2.14.0 DisplayString
(SIZE (0..40)) Custom Alarm Message 4
Optional factory programmed alarm
message.
N/A
1.3.6.1.4.1.22731.1.2.2.15.0 INTEGER (0..900) Optional Alarm 4 Delay Seconds
1.3.6.1.4.1.22731.1.2.2.16.0 INTEGER
checkHumidCylinder(1)
customAlarm4(2)
fanMotorOverload(3)
humidLockout(4)
localAlarm(5)
heatAndHumidLockout(6)
heatLockout(7)
standbyPumpOn(8)
upsOn(9)
highCondensateLevel(10)
Optional Alarm 4 Configuration N/A
1.3.6.1.4.1.22731.1.2.2.17.0 INTEGER
none(1)
one-compressor(2)
two-compressors(3)
Energy Saver Configuration
Factory setting N/A
1.3.6.1.4.1.22731.1.2.2.18.0 INTEGER
none(1)
chilled-water(2)
energy-saver(3)
aux-chilled-water(4)
Chilled Water Configuration
Factory setting N/A
1.3.6.1.4.1.22731.1.2.2.19.0 INTEGER
0-10 VDC(1) Water Valve Configuration
Factory setting N/A
Document 600-000-615 14

Object Identifier Type Description Units
4-7 VDC(2)
6-9 VDC(3)
7-10 VDC(4)
2-10 VDC(5)
1.3.6.1.4.1.22731.1.2.2.20.0 INTEGER
normal(1)
reverse(2)
Reverse Water Valve Configuration
Factory setting N/A
7.8 Relay Module Status (Read Only-Optional)
Note: these points do not apply to Mini-DAP III panel
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.3.1.0 INTEGER
not installed(0)
installed(non-zero)
Relay Module Installed
This applies when unit has an optional Relay
module installed
N/A
1.3.6.1.4.1.22731.1.2.3.2.0 INTEGER Humidifier Valve Open
This applies when unit has an optional
modulating humidifier
%
1.3.6.1.4.1.22731.1.2.3.3.0 INTEGER Compressor 3 Runtime
This applies when unit has four stages tandem
compressors
Hours
1.3.6.1.4.1.22731.1.2.3.4.0 INTEGER Compressor 4 Runtime
This applies when unit has four stages tandem
compressors.
Hours
1.3.6.1.4.1.22731.1.2.3.5.0 INTEGER Condenser Runtime Hours
7.9 Relay Module Configuration (Read/Write-Optional)
Note: these points do not apply to Mini-DAP III panel
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.3.6.0 INTEGER
none(1)
every6hours(2)
every12hours(3)
every24hours(4)
every36hours(5)
every48hours(6)
every60hours(7)
every72hours(8)
every84hours(9)
every96hours(10)
Autoflush Time
Use on unit with
an optional Infra-
red humidifier
only.
N/A
7.10 Relay Module Configuration (Read Only-Optional)
Note: these points do not apply to Mini-DAP III panel
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.3.7.0 OCTET STRING
Each octet re
p
resents one alarm Alarm Relay 2 Settings N/A
Document 600-000-615 15

Object Identifier Type Description Units
selection. See Section 2.5 for
specific alarm codes.
1.3.6.1.4.1.22731.1.2.3.8.0 OCTET STRING
Each octet represents one alarm
selection. See Section 2.5 for
specific alarm codes.
Alarm Relay 3 Settings N/A
1.3.6.1.4.1.22731.1.2.3.9.0 OCTET STRING
Each octet represents one alarm
selection. See Section 2.5 for
specific alarm codes.
Alarm Relay 4 Settings N/A
7.11 Analog Module Status (Read Only-Optional)
Note: all the objects in this section are optional. They require an Analog module to be installed
onto the DAP III panel and optional analog transducers or transmitters required.
Refer to the DAP III O&M manual for Analog Module configuration and programming.
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.4.1.0 INTEGER
not installed(0)
installed(non-zero)
Analog Module Installed N/A
1.3.6.1.4.1.22731.1.2.4.2.0 INTEGER Analog Sensor 1 Value N/A
1.3.6.1.4.1.22731.1.2.4.3.0 INTEGER Analog Sensor 2 Value N/A
1.3.6.1.4.1.22731.1.2.4.4.0 INTEGER Analog Sensor 3 Value N/A
1.3.6.1.4.1.22731.1.2.4.5.0 INTEGER Analog Sensor 4 Value N/A
1.3.6.1.4.1.22731.1.2.4.6.0 INTEGER Analog Output 1 Value N/A
1.3.6.1.4.1.22731.1.2.4.7.0 INTEGER Analog Output 2 Value N/A
1.3.6.1.4.1.22731.1.2.4.51 INTEGER Current Fan Airflow CFM
7.12 Analog Module control (Read/Write – Optional)
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.4.34 INTEGER Fan Speed Override %
1.3.6.1.4.1.22731.1.2.4.50 INTEGER Fan Airflow Override CFM
1.3.6.1.4.1.22731.1.2.4.52 INTEGER Zone Airflow Override CFM
7.13 Analog Module Configuration (Read Only-Optional)
Note: all the objects in this section are optional. They require an Analog module to be installed
onto the DAP III panel and optional analog transducers or transmitters required.
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.4.8.0 INTEGER
not-installed(1)
input-voltage-a-b(2)
input-voltage-a-c(3)
input-voltage-b-c(4)
output-voltage-a-b(5)
output-voltage-a-c(6)
output-voltage-b-c(7)
input-current-a(8)
input-current-b(9)
Analog Sensor 1 Name N/A
Document 600-000-615 16

Object Identifier Type Description Units
input-current-c(10)
output-current-a(11)
output-current-b(12)
output-current-c(13)
neutral-current(14)
ground-current(15)
frequency(16)
power(17)
cond-water-supply-temp(18)
cond-water-return-temp(19)
chill-water-supply-temp(20)
chill-water-return-temp(21)
supply-air-temp(22)
return-air-temp(23)
cond-water-flow(24)
chill-water-flow(25)
zone-air-temp(26)
zone-air-humidity(27)
outside-air-temp(28)
outside-air-humidity(29)
discharge-pressure(30)
suction-pressure(31)
diff-pressure(32)
pressure(33)
flow(34)
1.3.6.1.4.1.22731.1.2.4.9.0 INTEGER
VAC(1)
amps(2)
Hz(3)
kW(4)
degrees F(5)
degrees C(6)
gpm(7)
percent-RH(8)
psig(9)
inches-water(10)
psi(11)
Analog Sensor 1 Units N/A
1.3.6.1.4.1.22731.1.2.4.10.0 INTEGER
0-10 VDC(1)
0-5 VDC(2)
4-20 mA(3)
Analog Sensor 1 Type N/A
1.3.6.1.4.1.22731.1.2.4.11.0 INTEGER
Analog Sensor 1 Minimum Value N/A
1.3.6.1.4.1.22731.1.2.4.12.0 INTEGER Analog Sensor 1 Maximum
Value N/A
1.3.6.1.4.1.22731.1.2.4.13.0 INTEGER Analog Sensor 1 Calibration N/A
1.3.6.1.4.1.22731.1.2.4.14.0 INTEGER
not-installed(1)
input-voltage-a-b(2)
input-voltage-a-c(3)
input-voltage-b-c(4)
output-voltage-a-b(5)
output-voltage-a-c(6)
output-voltage-b-c(7)
input-current-a(8)
Analog Sensor 2 Name N/A
Document 600-000-615 17

Object Identifier Type Description Units
input-current-b(9)
input-current-c(10)
output-current-a(11)
output-current-b(12)
output-current-c(13)
neutral-current(14)
ground-current(15)
frequency(16)
power(17)
cond-water-supply-temp(18)
cond-water-return-temp(19)
chill-water-supply-temp(20)
chill-water-return-temp(21)
supply-air-temp(22)
return-air-temp(23)
cond-water-flow(24)
chill-water-flow(25)
zone-air-temp(26)
zone-air-humidity(27)
outside-air-temp(28)
outside-air-humidity(29)
discharge-pressure(30)
suction-pressure(31)
diff-pressure(32)
pressure(33)
flow(34)
1.3.6.1.4.1.22731.1.2.4.15.0 INTEGER
VAC(1)
amps(2)
Hz(3)
kW(4)
degrees F(5)
degrees C(6)
gpm(7)
percent-RH(8)
psig(9)
inches-water(10)
psi(11)
Analog Sensor 2 Units N/A
1.3.6.1.4.1.22731.1.2.4.16.0 INTEGER
0-10 VDC(1)
0-5 VDC(2)
4-20 mA(3)
Analog Sensor 2 Type N/A
1.3.6.1.4.1.22731.1.2.4.17.0 INTEGER
Analog Sensor 2 Minimum Value N/A
1.3.6.1.4.1.22731.1.2.4.18.0 INTEGER Analog Sensor 2 Maximum
Value N/A
1.3.6.1.4.1.22731.1.2.4.19.0 INTEGER Analog Sensor 2 Calibration N/A
1.3.6.1.4.1.22731.1.2.4.20.0 INTEGER
not-installed(1)
input-voltage-a-b(2)
input-voltage-a-c(3)
input-voltage-b-c(4)
output-voltage-a-b(5)
output-voltage-a-c(6)
output-voltage-b-c(7)
Analog Sensor 3 Name N/A
Document 600-000-615 18

Object Identifier Type Description Units
input-current-a(8)
input-current-b(9)
input-current-c(10)
output-current-a(11)
output-current-b(12)
output-current-c(13)
neutral-current(14)
ground-current(15)
frequency(16)
power(17)
cond-water-supply-temp(18)
cond-water-return-temp(19)
chill-water-supply-temp(20)
chill-water-return-temp(21)
supply-air-temp(22)
return-air-temp(23)
cond-water-flow(24)
chill-water-flow(25)
zone-air-temp(26)
zone-air-humidity(27)
outside-air-temp(28)
outside-air-humidity(29)
discharge-pressure(30)
suction-pressure(31)
diff-pressure(32)
pressure(33)
flow(34)
1.3.6.1.4.1.22731.1.2.4.21.0 INTEGER
VAC(1)
amps(2)
Hz(3)
kW(4)
degrees F(5)
degrees C(6)
gpm(7)
percent-RH(8)
psig(9)
inches-water(10)
psi(11)
Analog Sensor 3 Units N/A
1.3.6.1.4.1.22731.1.2.4.22.0 INTEGER
0-10 VDC(1)
0-5 VDC(2)
4-20 mA(3)
Analog Sensor 3 Type N/A
1.3.6.1.4.1.22731.1.2.4.23.0 INTEGER Analog Sensor 3 Minimum
Value N/A
1.3.6.1.4.1.22731.1.2.4.24.0 INTEGER Analog Sensor 3 Maximum
Value N/A
1.3.6.1.4.1.22731.1.2.4.25.0 INTEGER Analog Sensor 3 Calibration N/A
1.3.6.1.4.1.22731.1.2.4.26.0 INTEGER
not-installed(1)
input-voltage-a-b(2)
input-voltage-a-c(3)
input-voltage-b-c(4)
output-voltage-a-b(5)
Analog Sensor 4 Name N/A
Document 600-000-615 19

Object Identifier Type Description Units
output-voltage-a-c(6)
output-voltage-b-c(7)
input-current-a(8)
input-current-b(9)
input-current-c(10)
output-current-a(11)
output-current-b(12)
output-current-c(13)
neutral-current(14)
ground-current(15)
frequency(16)
power(17)
cond-water-supply-temp(18)
cond-water-return-temp(19)
chill-water-supply-temp(20)
chill-water-return-temp(21)
supply-air-temp(22)
return-air-temp(23)
cond-water-flow(24)
chill-water-flow(25)
zone-air-temp(26)
zone-air-humidity(27)
outside-air-temp(28)
outside-air-humidity(29)
discharge-pressure(30)
suction-pressure(31)
diff-pressure(32)
pressure(33)
flow(34)
1.3.6.1.4.1.22731.1.2.4.27.0 INTEGER
VAC(1)
amps(2)
Hz(3)
kW(4)
degrees F(5)
degrees C(6)
gpm(7)
percent-RH(8)
psig(9)
inches-water(10)
psi(11)
Analog Sensor 4 Units N/A
1.3.6.1.4.1.22731.1.2.4.28.0 INTEGER
0-10 VDC(1)
0-5 VDC(2)
4-20 mA(3)
Analog Sensor 4 Type N/A
1.3.6.1.4.1.22731.1.2.4.29.0 INTEGER
Analog Sensor 4 Minimum Value N/A
1.3.6.1.4.1.22731.1.2.4.30.0 INTEGER Analog Sensor 4 Maximum
Value N/A
1.3.6.1.4.1.22731.1.2.4.31.0 INTEGER Analog Sensor 4 Calibration N/A
1.3.6.1.4.1.22731.1.2.4.32.0 INTEGER
not-installed(1)
plug-fan(2)
Analog Output 1 Configuration N/A
1.3.6.1.4.1.22731.1.2.4.33.0 INTEGER
not-installed(1)plug-fan(2) Analog Output 2 Configuration N/A
Document 600-000-615 20
Other manuals for DAP III
2
Table of contents
Popular Computer Hardware manuals by other brands

WINTERMODULAR
WINTERMODULAR EME manual

LSI
LSI MegaRAID SATA 300-4XLP Quick installation guide

ATI Technologies
ATI Technologies P Class 450/500/550/600/650/700/750 user guide

Lumens
Lumens LC200 user manual

Intel
Intel BX80571E5300 - Pentium 2.6 GHz Processor datasheet

Keysight
Keysight E5867A installation guide