DCI C1103 User manual

• C1103
• C1203
• C2106
• C2206
• C3210
Copyright © 2006 DCI. All Rights Reserved.
Compressor Installation Guide
C Series
COMPRESSOR
92094, Rev. D, 08/13

1 www.dcionline.com www.dcionline.com

Oil-Less
C Series Installation Guide
Compressor Model Specification
C - Series
Compressor
# Heads Tank Power
Model # # of Heads Tank Size Voltage Breaker Size Amps
C1103 1 Horizontal 20 gal. 115 20 Amps 13.4
C1203 1 Horizontal 20 gal. 230V 20 Amps 6.7
C2106 2 Horizontal 20 gal. 115V 30 Amps 26.8
C2206 2 Horizontal 20 gal. 230V 20 Amps 13.4
C3210 3 Horizontal 30 gal. 230V 30 Amps 20.1
NOTE: Installation of this product should be undertaken only
by qualified service technicians.
This product has been factory-tested prior to shipment.
If the product does not function as described in the start-up and
test procedures in this manual, call the number below for assistance.
Technical Support: 1-800-624-2793
NOTE: Air flow rates in excess of compressor ratings will result
in reduced performance and possible overheating.
All Voltage Ratings ± 5%.
Space Requirements
Power
NOTE: 1) All machines are of the 3 wire grounded system type.
2) Minimum Breaker size 30 amp & larger wire size #10 supply connection.
29.50"
23"
11.69"
16"
39"
33"
46" 26"
1.800.624.2793 1

Installation Kit
The C - Series is shipped with the following:
C Series Installation Guide
Compressor Installation Kit
•
•
Installation Kit
You must provide:
Fittings and bushings as required to connect the
flexible hose to the on-site piping (the hose-end
is 3/8 in. NPT “male”).
Earthquake restraints for securing the equipment
if required by local codes.
Antivibration Foot
Nut
Lock Washer
Flat Washer
Wire Nuts
Split Bushing
Conduit Connector 6 ft. Hose
www.dcionline.com
2

Site Requirements
Clearance Site Requirements
Adequate clearance as shown below for servicing and air circulation — room
temperature should be maintained between 40°F and 100°F when the motors
are running.
A flat, level floor that provides stable support.
Protection from the weather and direct sunlight.
A power source within 3 ft. of back-center that provides a dedicated,
breaker-protected circuit.
•
•
•
•
C Series Installation Guide
Compressor Site Requirements
WARNING! Fire Hazard! Running motors generate heat. Do not store flammable
liquids or objects such as clothing, mops, or brooms near or above the unit.
ELECTRICAL REQUIREMENTS
PLUMBING REQUIREMENTS
1. 1/2 in I.D. minimum pipe size.
2. Pipe connection is to be located within 3 ft of
center back of compressor.
3. Install per all Local and State plumbing codes.
1. 3 wire single phase 115 vac or 230 vac. All
voltage ratings ± 5%.
2. Green Wire is to be grounded to a suitable
system ground.
3. Power supply must be on a dedicated circuit.
4. See data tag for appropriate breaker size.
5. Power supply connection is to be located
within 3 ft of center back of compressor.
6. Install per all local and State electrical codes.
1.800.624.2793 3

U
n-
packing
1 www.dcionline.com
C Series Installation Guide
Unpacking
Unpacking
NOTE: Returns must be in the original packaging. Retain the packaging until
installation and test are complete.
Step One:
Unbolt the crate from the pallet
and remove crate intact.
Step Two:
Remove the four bolts that
secure the C - Series to the
pallet and put them with the
other packaging.
Step Three:
Mount the four rubber feet.
www.dcionline.com
4

C Series Installation Guide
Unpacking
Unpacking
Step Four:
Grasp the C - Series by the tank and
move it into position.
NOTE: Returns must be in the original packaging. Retain the packaging until
installation and test are complete.
1.800.624.2793 5

U
n-
packing
1 www.dcionline.com
C Series Installation Guide
Installation
Installation
WARNING! Do not connect rigid pipe directly to the compressor. Motor vibration
loosens fittings, causing leaks. Use the flexible pipe provided or a similar substitute.
Step One:
Make sure the power supply is turned off and matches the voltage rating of the motors.
Note: Appropriate Breaker size is listed on the machine data tag.
Step Two:
Connect the power, making sure to adhere to all local and state codes.
Connect the “Green” Ground wire to an earth ground.
Note: 3 wire system.
Step Three:
Attach the flexible piping and connect to on-site piping.
Note:
Install appropriate over current protection; i.e., circuit breaker.
Model # Breaker Size
C 1103 20 Amps
C 1203 20 Amps
C 2106 30 Amps
C 2206 20 Amps
C 3210 30 Amps
Electrical
www.dcionline.com
6

C Series Installation Guide
Start-Up & Test
Un
p
ackin
g
Start-Up & Test
Step One:
Turn off the switches on the front of the compressor.
Step Two:
Ensure that the dryer by-pass shut-off valve is open.
Step Three:
Ensure that strainer shut-off valve is open.
Step Four:
Close outlet valve on the compressor tank.
Step Five:
Apply power to system — the purge valve my emit a hissing sound as the purge timer resets.
Step Six:
Switch on the motors. If you hear the popping sound of air escaping the relief valve, the dryer by-pass valve is closed.
1.800.624.2793 7

Un
p
ackin
g
1 www.dcionline.com
C Series Installation Guide
Start-Up & Test
Start-Up & Test
Step Seven:
As the tank pressurizes, watch the
pressure gauge. If the pressure switch
is functioning normally, the motors will
shut off at approximately 100 PSI.
Wait five minutes and watch the gauge
to ensure there are no leaks in the
C Series. The system should lose
no more than one PSI per minute.
Step Eight:
Test the purge valve by pressing the
TEST button. If the valve is functioning
normally, you will hear the hiss of air
escaping for approximately ten seconds.
NOTE! Do not adjust the timer dials on the purge valve.
If the purge timing needs adjustment, call technical support.
3
0
27
0
9
0
6
0
21
12
9
6
3
0
BAR
100xkPa
psi
2
4
0
18
1
2
0
180
210
150
3
00
0
15
www.dcionline.com
8

C Series Installation Guide
Start-Up & Test
Un
p
ackin
g
Start-Up & Test
Step Nine:
Release air using the purge-valve
TEST button and watch the pressure
gauge to see when the motors start.
The motors should start when the
pressure drops to approximately 80 PSI.
You may have to push the TEST button
several times before enough air is
released to lower the pressure to 80 PSI.
Step Ten:
Open the outlet valve on the tank to
pressurize the piping and wait until the
tank is fully pressurized and the motors
stop running.
Step Eleven:
Ensure that no equipment is drawing
pressure from the tank. When no equip-
ment is drawing on the tank, pressure
should drop no more than 1 PSI per
minute.
Watch the pressure gauge. If pressure
drops faster than 1 PSI per minute, an
air leak is indicated somewhere in the
system. Repair as necessary.
160
60
40
20
11
8
6
4
2
0
BAR
100xkPa
psi
140
10
80
100
120
3
0
270
9
0
6
0
21
12
9
6
3
0
BAR
100xkPa
psi
2
4
0
18
1
2
0
180
210
150
3
00
0
15
Loses less than 1 psi per min?
NO LEAKS!
30
270
90
60
21
12
9
6
3
0
BAR
100xkPa
psi
240
18
120
180
210
150
300
0
15
1.800.624.2793 9

1 www.dcionline.com
Bypass Valve
2008 Indicator
2007 Float Drain
2003 Coalescing Filter
2006 Coalescing Element
2135
Check Valve
2135 Check Valve
2014
Drying Chamber
Assembly
Pressure Gauge
2011 Automatic Purge Valve (230 Volt)
OR 2848 Automatic Puge Valve (115 Volt)
2009
Strainer Shut O
2002
1 hp Head
Outlet Ball Valve
2859
Petcock Valve
Data Tag
2012
Intake Element
2013
2005
Pressure
Switch Relief Valve
2856
Pressure Gauge
2856
www.dcionline.com
10

C Series Installation Guide
Electrical Schematic
Un
p
ackin
g
Electrical Schematic
1.800.624.2793 11

Un
p
ackin
g
1 www.dcionline.com
C Series Installation Guide
Plumbing Schematic
Plumbing Schematic
Left
Motor Right
Motor
Check
Valve Check
Valve
Aftercooling
Tubing
Coalescing
Filter
Condensate
Drain
Drying Chamber
Flow/Check
Drying System
Pressure Gauge
Dryer Bypass
Ball Valve
To
Storage
Tank
Strainer
Shutoff
Valve
Time Purge
Valve
www.dcionline.com
12

1.800.624.2793

305 N. Springbrook Road
Newberg, Oregon 97132 USA
503.538.8343
800.624.2793
www.dcionline.com
Other manuals for C1103
1
This manual suits for next models
4
Table of contents
Other DCI Air Compressor manuals
Popular Air Compressor manuals by other brands

Panasonic
Panasonic DC51C72RCU6 Specification sheet

Bambi
Bambi VT75 operating manual

EINHELL
EINHELL LE-AK 12/250 operating instructions

Clarke
Clarke RANGER 6/500 Operation & maintenance instructions

Scheppach
Scheppach HC51V Translation of original instruction manual

BERG
BERG KOMPBERG ZX90 Operating and maintenance manual