BE - ER15012 1 / 5 IT2656
Technical Sales
Documentation Department
TI
Technical information
Heading No 1
Fuel oil fired boilers
EFU 22 / 29 (FF) - EFU C 19 / 24 / 32
EFU C 24 /32 PLUS
Diagnostic aid - Fault finding
Product evolution
P5253 JS F 67580 Mertzwiller N° IT2656-en 27/01/2017
EN
1. Blocking of the safety control box
After 5 safety shutdowns, the safety box remains blocked at fault.
To unlock the safety box: turn off the burner power supply with the ON/
OFF button or by pulling out the burner plug.
After switching on again, reset the safety box by pressing the reset button.
The fault counting of the safety box is reset to 0, after each safety
box switching off (switching off by ON/OFF button, by unplugging
the burner or by power failure).
Troubleshooting help - Signification of the safety control box reset
button flashing:
L000836-A
Normal operating Reset button colour
Colour code
OFF OFF
- -
Pre-heating time GREEN blinking
2,5
Pre-ventilation ORANGE blinking
0,5
Safety time GREEN blinking
0,5
Normal operating GREEN
*
-
Blinking
or steady ON
Fault description Reset button colour
Colour code
Extraneous light (false flame signal)
GREEN
, RED
blinking
alternatel
0,5
Frequency supply error ORANGE
- Steady ON
Voltage monitor error ORANGE,
GREEN
fast
blinkin
alternatel
0,2
Reset button fault
GREEN
, RED fast
blinking
alternatel
0,2
Lockout due to no flame after ts RED
-Steady ON
Lockout for false flame signal RED
blinking
0,5
Lockout for maximum number of recycles RED
fast blinking
0,2
Lockout for pre-heating not finished RED blinking
2,5
Lockout for fan motor error RED, ORANGE
inverted blinking
0,5
Lockout for oil valve error RED RED, GREEN
inverted blinking
0,5
Lockout for eeprom error ORANGE, GREEN
blinking alternately
0,5
Key :
ON OFF Colour code
RED
ORANGE
GREEN
* Blinking depending on the flame signal quality : correct (1-2 blinks),
good (3-4 blinks) or excellent (5 blinks or always ON).