Deep Sea Electronics Plc 5220 Quick guide

Config’ Section Parameter Type Icons displayed
Analogue senders Low Pressure Trip
Low Pressure Pre Alarm
High Temperature Pre Alarm
High Temperature Trip
Fuel Level % Pre Alarm
Calendar Date/time Date/time
Timers Mains transient delay Timer (secs) 1
Start delay Timer (secs) 2
Preheat Timer (secs)
3
Crank attempt Timer (secs) 4
Crank rest Timer (secs) 5
Safety delay Timer (secs) 6
Overspeed overshoot Timer (secs) 7
Warming up Timer (secs) 8
Transfer delay Timer (secs) 9
Return delay Timer (secs) 10
Cooling run Timer (secs) 11
E.T.S.(Energise to stop) solenoid hold Timer (secs) 12
Mains (utility) supply Mains Low Voltage Trip V
Mains High Voltage Trip V
Mains Low Frequency Trip
Mains High Frequency Trip
Generator output Generator Under Voltage L1-N Trip V
Generator Under Voltage L1-N Pre Alarm V
Generator Over Voltage Pre Alarm
V
Generator Over Voltage Trip V
Generator Under Frequency Trip
Generator Under Frequency Pre Alarm
Generator Over Frequency Pre Alarm
Generator Over Frequency Trip
Delayed Overcurrent % Trip
A
Engine speed Under Speed (RPM) Trip
Under Speed (RPM) Pre Alarm
Over Speed (RPM) Pre Alarm
Over Speed (RPM) Trip
DC Voltages Low DC Voltage Warning V
High DC Voltage Warning
V
Charge Alternator Failure Warning
DEEP SEA ELECTRONICS
Model 5220 Installation and Configuration Instructions
Accessing the front panel config’ editor
Press the configure/log and Stop/Reset buttons simultaneously.
The LCD configure indicator#will flash to indicate that the module is in ‘configuration mode’. Release the
Stop/Reset button and the configure/log button.
If a PIN number has been set, press + / - to set the first digit, then press 9to adjust the next
digit.
Repeat this until all four digits have been entered.
The first configurable parameter is now displayed. Pressing the + or - buttons will cycle through the
parameters.
NOTE:- To exit the front panel configuration editor at any time, press the Stop/Reset
button. Ensure you have saved any changes you have made by pressing the 9button first.
Editing an analogue value
Access the front panel config editor as detailed above. Press the +/- buttons to view the parameter you
wish to change (see parameter table overleaf). Press the 9button to enter adjust mode. The value to be
adjusted will flash. Press the +/- buttons to adjust the parameter to the desired value. Press the 9button
to ‘save’ the value. The value will stop flashing to confirm that it has been saved. To select another value to
edit, press the + button. Continuing to press the +/- buttons will cycle through the available parameters.
Editing the time
The date/time should initially be set using the 5200 series configuration software. However there may be
certain circumstances where a minor change to the module’s time is required. One such instance is
correction for daylight saving. Access the front panel config editor as detailed above. Press the + button
until the calendar is shown :
To edit the time, press the 9button. The minutes, ‘30’ in this
example, will begin flashing. Press the +or - buttons to adjust
the minutes. Press the button to select hours, day, month
and year. The selected parameter will flash.
Press the 9button to save the change. The time stops flashing
to confirm that it has been successfully stored.
Example : This display is showing a time of 4:30 on 21st
October 2002.
NOTE:- Full configuration of the 5220 module is possible using the 5200 series configuration
software for PC in conjunction with the P810 interface.
Deep Sea Electronics Plc.
Highfield House, Hunmanby Industrial Estate,
North Yorkshire. YO14 0PH. ENGLAND.
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303.
Web: www.deepseaplc.com
LO CALL (from UK BT landlines) : Telephone
0845 260 8900.
Deep Sea Electronics Inc.
3230 Williams Avenue, Rockford,
IL 61101-2668, USA
Phone: +1 (815) 316-8706
Fax: +1 (815) 316-8708
Web: www.deepseausa.com
TOLL FREE (USA only) Tel: 1 866 636 9703
053-020 ISSUE 4
http://bestgenerator.spb.ru/?page_id=6765

Toplant supply +ve
Crank
Starter
motor
Battery Charge
alt. WL
F F
Fuel
Emergency
stop
internal emergency stop
Configurable auxiliary input 1
Configurable auxiliary input 2
Configurable auxiliary input 3
Configurable auxiliary input 4
Configurable auxiliary input 5
L1
L2
L3
NF2A F2A F2A
+
Supply for
controller
These ground connections must be
on the engine block and must be
a sound electrical connection
to the sender bodies.
The ground wire to terminal 47 must
not be used to provide a ground
connection to any other device.
Coolant temp. sender
Fuel level sender
RS485
Optional
9 way D
Optional
RS232
5220 controller
Optional
CanBus
Not connected
Output expansion
157 relay board
or
548 annunciator
5200 series
configuration software
810 interface
810
157/548 Ground screen
at one end only
Functional
Earth
MPU
17
18
16
6 7 8
1413
12
1110
474645
Oil pressure sender
449
4
531 2
39 40 41 42 43
CT
common
CT
Earth
35 36 37 38
20 21 22
23 24 25
26
Configurable auxiliary input 6
15
Configurable auxiliary output 1
Configurable auxiliary output 2
Configurable auxiliary output 3
SCR AB
COM HL
Not connected
F2A F2A F2A
31 32 33 34
G M
LOAD
Mechanical interlock
Electrical interlock
Generator Mains (utility)
19
Not connected
28273029
Generator
loading
relay
Mains
loading
relay
L1
L2
L3
N
Dimensions
Module Dimensions - 240mm x 172mm x 57mm (9.45” x 6.77” x 2¼”)
Panel cutout - 220mm x 160mm ( 8.7” x 6.3”)
Alternative AC wiring
2 phase, 3 wire ( 2 phase centre tap neutral)
L1
L2
NF2A F2A
39 40 41 42 43
CT
common
CT
Earth
35 36 37 38
Not connected
F2A F2A
31 32 33 34
G M
LOAD
Mechanical interlock
Electrical interlock
Generator Mains (utility)
28273029
Generator
loading
relay
Mains
loading
relay
L1
L2
N
3 phase, 3 wire
L1
L2
L3
F2A F2A F2A
39 40 41 42 43
CT
common
CT
Earth
35 36 37 38
Not connected
F2A F2A F2A
31 32 33
34
G M
LOAD
Mechanical interlock
Electrical interlock
Generator Mains (utility)
28273029
Generator
loading
relay
Mains
loading
relay
L1
L2
L3
Not connected
Not connected
T
yp
ical Wirin
g
Dia
g
ram
http://bestgenerator.spb.ru/?page_id=6765
Table of contents
Popular Control Panel manuals by other brands

Siemens
Siemens Series 2300 installation instructions

AEG
AEG S 64 D operating instructions

SALUPO
SALUPO RAIN PLUS 1 Instruction and installation manual

jablotron
jablotron JA-82KRC-US instruction manual

HEIDENHAIN
HEIDENHAIN POSITIP 8000 operating instructions

DMP Electronics
DMP Electronics XR200 installation guide