Develco KEYZB-110 User manual

Keypad - KEYZB-110
Technical manual
Revised 06.05.2020

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
2
Content
1Cautionary notes ......................................................................................................................................................................................................................5
2Features ........................................................................................................................................................................................................................................ 6
2.1 Keypad - KEYZB-110........................................................................................................................................................................................................ 6
2.2 IAS ACE ..................................................................................................................................................................................................................................... 6
2.3 Key features .......................................................................................................................................................................................................................... 6
3Endpoints.......................................................................................................................................................................................................................................7
3.1 ZigBee Device Object (ZDO)........................................................................................................................................................................................7
3.2 IAS ACE ......................................................................................................................................................................................................................................7
3.3 Develco Utility.......................................................................................................................................................................................................................7
4Supported Clusters................................................................................................................................................................................................................ 8
4.1 Common clusters for each end point .................................................................................................................................................................. 8
4.1.1 Basic –Cluster id 0x0000................................................................................................................................................................................... 8
4.1.1.1 Attribute................................................................................................................................................................................................................... 8
4.1.2 Identify –Cluster id 0x0003.............................................................................................................................................................................. 8
4.1.2.1 Attribute................................................................................................................................................................................................................... 8
4.1.2.2 Commands............................................................................................................................................................................................................. 8
4.2 IAS ACE Device –EP 0x2C ............................................................................................................................................................................................9
4.2.1 IAS Zone - Cluster id 0x0500............................................................................................................................................................................9
4.2.1.1 Attribute....................................................................................................................................................................................................................9
4.2.1.2 Commands........................................................................................................................................................................................................... 10
4.2.1.3 Commands............................................................................................................................................................................................................11
4.2.2 Power Configuration - Cluster id 0x0001................................................................................................................................................12
4.2.2.1 Attribute..................................................................................................................................................................................................................12
4.2.3 Poll Control - Cluster id 0x0020....................................................................................................................................................................12
4.2.3.1 Attribute..................................................................................................................................................................................................................12
4.2.4 OTA Upgrade –Cluster id 0x0019...............................................................................................................................................................13
4.2.4.1 Attributes ...............................................................................................................................................................................................................13
4.2.4.2 Commands............................................................................................................................................................................................................13
4.2.4.3 OTA Upgrade Messages Diagram ....................................................................................................................................................... 14

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
3
4.2.5 Time –Cluster id 0x000A................................................................................................................................................................................. 15
4.2.5.1 Attribute................................................................................................................................................................................................................. 15
5MMI user guide....................................................................................................................................................................................................................... 16
5.1 Panel description ............................................................................................................................................................................................................. 16
5.2 Menu button.........................................................................................................................................................................................................................17
5.2.1 EZ mode - Initiator................................................................................................................................................................................................. 18
5.2.2 EZ mode - Target................................................................................................................................................................................................... 18
5.2.3 Factory reset............................................................................................................................................................................................................. 18
5.3 Action on Power On........................................................................................................................................................................................................ 18
6General network behaviour ........................................................................................................................................................................................... 19
6.1 Installation ............................................................................................................................................................................................................................ 19
6.2 Normal –Keep alive....................................................................................................................................................................................................... 19
6.2.1 Network lost.............................................................................................................................................................................................................. 19
6.3 Low battery..........................................................................................................................................................................................................................20
7Specifications ...........................................................................................................................................................................................................................21
8Contact Information ............................................................................................................................................................................................................22

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
4
Copyright © Develco Products A/S
All rights reserved.
Develco Products assumes no responsibility for any errors, which may appear in this manual. Furthermore,
Develco Products reserves the right to alter the hardware, software, and/or specifications detailed herein at any
time without notice, and Develco Products does not make any commitment to update the information contained
herein.
All the trademarks listed herein are owned by their respective owners.
RoHS

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
5
1Cautionary notes
Develco Products A/S reserves the right to make changes to any product to improve reliability without further
notice. Develco Products A/S does not assume any liability arising out of the application or use of any product or
circuit described herein; neither does it convey any license under patent rights or the rights of third parties.

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
6
2Features
2.1 Keypad - KEYZB-110
Enables secure access control
The Zigbee-based Keypad includes a tag reader and allows for users to enable and disable an alarm system using
a pin code and/or an RFID tag. In addition, access data can be updated remotely via a gateway to facilitate access
control.
Saves battery when not in use
The RFID only consumes energy when it is needed. The Keypad includes a sensor that detects when a person is
within operating distance, which will enable the RFID and make the Keypad light up in the dark. This saves energy
and allows for a longer battery lifetime.
Numerous features and design options
The Keypad includes a tamper switch that detects opening of the unit, which makes it suitable for alarm systems.
Also, the Keypad includes a programmable buzzer for indication of entry, exit, alarms, or any other indication
needed in your solution. Red, Green, and Yellow LEDs are available for indications of alarms, etc. The Keypad can
be delivered in white for indoor use or in black for outdoor use. The device has 16 buttons that you can design to
fit your solution. The Keypad can be mounted on the wall using screws or double-sided tape
2.2 IAS ACE
The Keypad is implemented as a IAS ACE ZigBee end point according to ZigBee Home Automation profile. The IAS
ACE cluster defines an interface to the functionality of any Ancillary Control Equipment of the IAS system. Using
this cluster, an ACE device can access a IAS CIE devices and manipulate the IAS system
2.3 Key features
•RFID tag reader
•Tamper-protected
•Buzzer and LED
•Intelligent backlight
•Battery-powered
•Alarm sensor –IAS Zone
•ZigBee OTA cluster for firmware upgrades
•ZigBee 3.0 stack supported
•Water repellent

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
7
3Endpoints
The device implements the following standard HA devices on different end points.
3.1 ZigBee Device Object (ZDO)
•End point number 0x00
•Application profile Id 0x0000
•Application device Id 0x0000
•Supports all mandatory clusters
3.2 IAS ACE
•End point number 0x2C
•Application profile Id 0x0104 (Home Automation)
•Application device Id 0x0401 (IAS Ancillary Control Equipment)
3.3 Develco Utility
•Application profile Id 0xC0C9 (Develco Products private profile)
•Application device Id 0x0001
•Manufactor code for Develco Products is 0x1015
•Private profile for internal Develco Products use only.
Reference documents:
053474r18ZB_CSG-ZigBee-Specification.pdf
075123r03ZB_AFG-ZigBee_Cluster_Library_Specification.pdf
053520r27ZB_HA_PTG-Home-Automation-Profile.pdf
075356r15ZB_ZSE-ZSE-AMI_Profile_Specification.pdf
They can all be downloaded from :
http://www.zigbee.org/Products/DownloadZigBeeTechnicalDocuments.aspx

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
8
4Supported Clusters
4.1 Common clusters for each end point
The ZCL “General Function Domain” clusters in this section are implemented as server clusters. Refer to ZigBee
Cluster Library Specification. http://www.zigbee.org/Specifications.aspx
4.1.1 Basic –Cluster id 0x0000
Only the first set has mandatory attributes, also the optional attributes that can be relevant to a Develco device
are all in set 0x000.
4.1.1.1 Attribute
Id#
Name
Type
Range
Man/Opt
Relevance and ref.
0x0
ZCLVersion
Uint8
Type range
M
0x4
ManufacturerName
String
0-32 byte
O
4.1.1.1.1
0x5
ModelIdentifier
String
0-32 byte
O
4.1.1.1.2
0x6
DateCode
String
0-32 byte
O
0x7
PowerSource
8 bit enum
Type range
M
4.1.1.1.1 ManufacturerName
“Develco Products A/S”
4.1.1.1.2 ModelIdentifier
“KEYZB-110”
4.1.2 Identify –Cluster id 0x0003
4.1.2.1 Attribute
Id#
Name
Type
Range
Man/Opt
Relevance and ref.
0x0000
IdentifyTime
Uint16
Type range
M
4.1.2.2 Commands
The identify cluster has 2 commands as server.
Id#
Name
Payload
Man/Opt
Relevance and ref.
0x00
Identify
Uint16 - Identify Time (seconds)
M
0x00

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
9
0x01
Identify Query
none
M
0x01
The identify cluster has 1 command as client.
Id#
Name
Payload
Man/Opt
Relevance and ref.
0x00
Identify Query Response
Uint16 - Identify Time (seconds)
M
0x00
4.2 IAS ACE Device –EP 0x2C
4.2.1 IAS Zone - Cluster id 0x0500
The IAS Zone cluster is described in ZigBee Cluster Library Specification.
4.2.1.1 Attribute
Id#
Name
Type
Man/Opt
Relevance and ref.
0x0000
Zone State
8-bit
Enumeration
M
0x0001
Zone Type
16-bit
Enumeration
M
Hard coded to
Keypad
0x0002
Zone Status
Uint16
M
The following bits are
supported:
Bit2: Tamper
Bit3: Battery
Bit4: Supervision reports
Bit5: Restore reports
0x0010
IAS CIE Address
Valid 64-bit
IEEE address
M
0x0011
ZoneID
Uint8
M
0x8000
Zone Status Interval
Uint16
O
Default 300 sec
4.2.1.1.1 Zone State
The device will automatically start to scan the network for an IAS Zone client in a predefine interval. When the
client is found it will automatically attempt to enrol. When it has successfully enrolled the Zone Status command
is send to the IAS Zone client.
The attribute value will change from not enrolled (0x00) to Enrolled (0x01).
4.2.1.1.2 IAS CIE Address
Attribute specifies the address that commands generated by the server shall be sent to.

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
10
To un-enrol the device the back end system has to write a new address into this attribute. Any value is valid. If the
back end system writes an IEEE address then it will try to enrol to this devices represented by the IEEE address.
4.2.1.1.3 ZoneID
A unique reference number allocated by the CIE at zone enrolment time.
Used by IAS devices to reference specific zones when communicating with the CIE. The ZoneID of each zone stays
fixed until that zone is un-enrolled.
4.2.1.2 Commands
The IAS Zone cluster has 2 commands as server.
Id#
Name
Payload
Man/Opt
Relevance and ref.
0x00
Zone Status Change
Notification
Uint16 –bit mask
M
The status is report
to the coordinator
every 5 min
0x01
Zone Enroll Request
Bits
16
16
M
Data type
16 bit enum
UINT16
Field
name
Zone
type
Manufacturer
code
Init sequence –when the device has join the network it start to scan for an IAS zone client cluster. If a client is
found a Zone enroll request command is send and a Zone Enroll response is expected. If it doesn’t receive a
response it will wait for 15 minutes and try again.
The following bits are supported in Zone status:
Bit2: Tamper
Bit3: Battery
Bit4: Supervision reports
Bit5: Restore reports
Bit3: When the battery is below 4.0 VDC. Battery bit is set high and “Zone Status” is transmitted to the coordinator.

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
11
4.2.1.3 Commands
The IAS ACE cluster has 3 commands as client server.
Id#
Name
Payload
0x00
Arm
Bits
8
Varies
8
Data
type
Enum8
string
Uint8
Field
name
Arm Mode
Arm/Disarm code
Zone ID
0x02
Emergency
No payload,
Commands indicate an emergency situation
0x07
GetPanelStatus
No payload,
Commands This command is used by ACE clients to request
an update to the status of the ACE
server (i.e., the IAS CIE).
Keypad button functionality
Symbol
Function
Arm All Zones
Disarm
Arm Day/Home Zones Only
Arm Night/Sleep Zones Only
Emergency –Press button for 3 sec
Delete last symbol input from keypress
“0”to “9”
Input to Arm/Disarm code

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
12
4.2.2 Power Configuration - Cluster id 0x0001
The power configuration cluster is described in ZigBee Cluster Library Specification
4.2.2.1 Attribute
Id#
Name
Type
Range
Man/Opt
Relevance and ref.
0x0020
BatteryVoltage
Uint8
0x00 - 0xFF
O
ZCL configure reporting is
supported
Note: The attribute “BatteryVoltage” is measuring the battery voltage, in units of 100mV.
4.2.3 Poll Control - Cluster id 0x0020
The poll control cluster is described in ZigBee Cluster Library Specification
This cluster provides a mechanism for the management of an end device’s MAC Data Request rate. For the
purposes of this cluster, the term “poll” always refers to the sending of a MAC Data Request from the end device
to the end device’s parent.
This cluster can be used for instance by a configuration device to make an end device responsive for a certain
period of time so that the device can be managed by the controller.
4.2.3.1 Attribute
Id#
Name
Type
Range
Man/Opt
Relevance and ref.
0x0000
Check-inInterval
Uint32
0x00 - 0xFF
M
Default value is 1 hour
0x0001
LongPoll Interval
Uint32
M
Default value is 7.5 sec
0x0002
ShortPollInterval
Uint16
M
Default value is 0.25
seconds
0x0003
FastPollTimeout
Uint16
M
Default value is 10
seconds
Start up, auto scan for client poll control cluster on the coordinator. If it is support on the coordinator an auto bind
is created and the smoke sensor will send a check-in command in the interval specified in attribute “Check-in
Interval. The coordinator has to reply with a check-in response. The sensor supports the following commands
send from the client (Typically the coordinator).
•0x00 Check-in Response,
•0x01 Fast Poll Stop,
•0x02 Set Long Poll Interval,
•0x03 Set Short Poll Interval,

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
13
If it doesn’t find a poll client it will search again periodically.
4.2.4 OTA Upgrade –Cluster id 0x0019
The cluster provides a ZigBee standard way to upgrade devices in the network via OTA messages. The devices
support the client side of the cluster.
When the devices has joined a network it will automatically auto scan for a OTA upgrade server in the network. If it
finds a server an auto bind is created and ones every 24 hour it will automatically send its “current file version” to
the OTA upgrade server. It is the server that initiate the firmware upgrade process.
4.2.4.1 Attributes
Id#
Name
Type
Range
Man/Opt
Relevance and ref.
0x0000
UpgradeServerID
IEEE
Address
-
M
0x0001
FileOffset
Uint32
Type range
O
0x0002
CurrentFileVersion
Uint32
Type range
O
0x0003
CurrentZigBeeStackVersion
Uint16
Type range
O
0x0004
DownloadedFileVersion
Uint32
Type range
O
0x0005
DownloadedZigBeeStackVersion
Uint16
Type range
M
0x0006
ImageUpgradeStatus
8 bit
enum
0x00 to 0xFF
O
0x0007
Manufacturer ID
Uint16
Type range
O
0x0008
Image Type ID
Uint16
Type range
O
0x0009
MinimumBlockRequestDelay
Uint16
Type range
O
Above attribute description is to be found in section 6.7 “OTA Cluster Attributes” in ZigBee document – “zigbee-
ota-upgrade-cluster-specification” provided by the ZigBee alliance.
4.2.4.2 Commands
The OTA Client cluster can send the following commands
Id#
Name
Man/Op
t
Relevance and ref.
0x01
Query Next Image request
M
6.10.1 OTA Cluster Command
Identifiers
0x03
Image Block Request
M
6.10.1 OTA Cluster Command
Identifiers
0x06
Upgrade End Request
M
6.10.1 OTA Cluster Command

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
14
Identifiers
4.2.4.3 OTA Upgrade Messages Diagram

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
15
4.2.5 Time –Cluster id 0x000A
The Time cluster is a general cluster for time it is based on a UTC time in seconds since 0 hrs 0 mins 0 sec on 1st
January 2000. Refer to [Z2] for ZigBee specification of the time cluster.
The device will use this clusters as a client –provided that a suitable Time Server is available on the network
(most likely on the Gateway).
4.2.5.1 Attribute
Id#
Name
type
Range
Man/Opt
Relevance and ref.
0x0000
Time
UTCTime
(Uint32)
Type range
M
The module will
periodically update its
clock by synchronizing
through this cluster
0x0001
TimeStatus
8 bit bitmap
00000xxx
M

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
16
5MMI user guide
5.1 Panel description
Symbol
Function
Arm All Zones
Disarm
Arm Day/Home Zones Only
Arm Night/Sleep Zones Only
Emergency –Press button for 3 sec
Delete last symbol input from keypress
“0”to “9”
Input to Arm/Disarm code
LED 1
Arm All Zones: RED LED solid on for 30 sec
Arm Day/Home Zones Only: RED LED solid on for 30 sec
Arm Night/Sleep Zones Only: RED LED solid on for 30 sec
Exit delay: Red LED flash slow along with beep
In alarm: Red LED flash fast
LED 2
Network connection lost: Yellow LED flash when it scans for
network to re-join

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
17
Low battery: Yellow LED will blink 2x every 60 second
Timeout since last input (5 sec): Yellow LED blink 3x
Wrong PIN code: Yellow LED blink 3x
LED 3
Disarm: Green LED solid on for 3 sec
Not ready to arm: Green LED solid on for 3 sec
Entry delay: Green LED flash along with beep
Sensor
Presence Sensor + Light Sensor + RFID tag reader
5.2 Menu button
How to get access to the menu button on the keypad:
Open the casing of the device by removing the screw at the bottom of the device. The menu button is placed
between the batteries and a thin pin (eg. a paper clip) can be used to activate the button.
Pushing the button on a device provides the user with several possibilities.
Pushing the button for longer (push, hold for a few seconds, and release) allows the user to set the device into a
desired mode. A mode change happens at 5 second interval. Below, these modes are illustrated in a state chart
Idle
EZ mode
Initiator
EZ mode
Target
Factory reset
Push + Hold button
untill led blinks once
Push + Hold button
untill led blinks
continously
Push + Hold button
untill led blinks
twice
Push + Hold button
untill led is off
When cycling through the menu modes, the state is indicated by a number of blinks on the LED. The device is
supporting the ZigBee standardized EZ- mode Commissioning.

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
18
5.2.1 EZ mode - Initiator
If the devices is not on the network EZ-Mode Network Steering is invoked when the user enter this menu. The led
blinks once every 1 sec until the devices has joined the network. If the device was already on the network it will
broadcast the PermitJoin messages. It is the trust center policy that decides if the device is allowed to join the
network.
When the device has joined the network EZ-Mode Finding and Binding is invoked and the device start to blink
every 3 sec until a cluster match is found. When a match is found or the cluster examine is finished the blinking
stops and the device sends a messages to the target device to stop the identify time.
The following clusters are support in EZ-mode finding and binding:
•Power configuration cluster
The EZ-mode time is hard coded to 3 minutes. This is the Minimum and recommended PermitJoin time broadcast
for EZ-Mode Network Steering and minimum IdentifyTime set for EZ-Mode Finding and Binding. If the user enters
the menu again another 3 minutes is started.
5.2.2 EZ mode - Target
If the devices is not on the network EZ-Mode Network Steering is invoked when the user enter this menu. The led
blinks twice every 1 sec until the devices has joined the network. If the device was already on the network it will
broadcast the PermitJoin messages. It is the trust center policy that decides if the device is allowed to join the
network.
When the device has joined the network identify mode is invoke and the device start to blink twice every 3 sec
until identify mode is stopped or after the EZ-mode time has expired. If the user enters the menu again another 3
minutes is started.
5.2.3 Factory reset
To allow a device to join a network, one either has to power up a device that has not previously joined a network
or push the button until the Reset To Factory default mode is indicated –and subsequently release the button.
This will cause the device to reset to its factory default state and scan for a suitable coordinator.
5.3 Action on Power On
As a general rule, all end devices and routers that have not previously joined a network (or have been reset to
factory default) will start up and search for a network with join permit open. In this mode, the Yellow LED will flash
while searching for a network to join
Once the device has joined the network, is will start scanning for an OTA server, Time server, Poll control client
and an IAS Zone client.
If a device has joined a network and is powered down, it will attempt to rejoin this network upon power up. For the
first 30 seconds hereafter, the device will be available for communication. This time can be expanded using the
poll control cluster functionality.

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
19
6General network behaviour
6.1 Installation
When the device is virgin and powered for the first time it will start looking for a ZigBee PAN Coordinator or router
to join. The device will scan each ZigBee channel starting from 11 to 24. The LED will flash once every second until
it joins a device.
#Scan mode - 1
Scan all 16 ZigBee
channel until join
network or 15
minutes
#Sleep mode
MCU is in sleep
mode (Radio off)
15 minutes
#Scan mode - 2
Scan all 16 ZigBee
ch x 1 or until join
network
~ 30 seconds
#Sleep mode
MCU is in sleep
mode (Radio off)
15 minutes
#Scan mode - 2
Scan all 16 ZigBee
ch x 1 or until join
network
~ 30 seconds
The device will start up using scan mode 1. To increase battery lifetime when the device is joining a network for
the first time a scan mode 2 will be used after scan mode 1 has expired. Scan mode 1 it will only be executed one
time when the device is powered. If the user invokes EZ-mode it will start scanning the next 3 minutes
In section 5 “MMI” it is explained how to put the device into a join or leave network mode.
Network settings are stored in NV-memory are after a power cycle the device re-join the same network.
If the device has to join a new PAN coordinator the MMI menu supports a “Reset To Factory Fresh Settings”
mode. This will erase all current network information.
6.2 Normal –Keep alive
The device is sending a “keep alive” message to the PAN coordinator every 15 minute to verify that the device is
still connected to the network.
6.2.1 Network lost
If no “keep alive” responses are received 5 times in a row (Worst case 1h15m), the devices will start scanning as
specified in the table below.
When the device is in scan mode the YELLOW LED will flash once every second until it re-joins the network.
According to the ZigBee specification TX is NOT allowed to be enabled all the time and a TX silent period has to
be defined.

Keypad - KEYZB-110 –Technical manual
Develco Products A/S
Tangen 6
http://develcoproducts.com
DK-8200 Aarhus N
info@develcoproducts.com
20
#Scan mode - 1
Scan current
channel 3 times
Scan remaining 15
channel 1 time
Scan all 16 ch 3
times
#Sleep mode
MCU is in sleep
mode (Radio off)
15 minutes
#Scan mode - 2
Scan current ch 3
times
Scan remaining 15
channel 1 time
#Sleep mode
MCU is in sleep
mode (Radio off)
15 minutes
#Scan mode - 2
Scan current
channel 3 times
Scan remaining 15
channel 1 time
6.3 Low battery
The current battery voltage can be read from the power configuration cluster described in section 4.3.1. The
attribute “BatteryVoltage”is measuring the battery voltage, in units of 100mV.
Low batt LED indication –YELLOW LED will blink twice every 60 second
Table of contents