Digiplex DGP-848 Operating instructions

Digiplex DGP-848 - 1 - Programming Guide
SECURITY AND ACCESS CONTROL (DGP-848)
PROGRAMMING GUIDE
Software Version 4.0
DEFAULT INSTALLER CODE
000000(see section [800] on page 39)
DEFAULT SYSTEM MASTER CODE
123456
HOW DO I ENTER PROGRAMMING MODE?
1) Press and hold the [0] key.
2) Enter your [INSTALLER CODE].
3) Enter 3-digit [SECTION].
4) Enter required [DATA].
DECIMAL AND HEXADECIMAL PROGRAMMING TABLE
Certain sections may require the entry of one or more Hexadecimal values from 0 to F.
For LCD keypads:
For Grafica keypads:
[0] to [9] = values 0 to 9 respectively [DISARM]= D
[STAY]= A [BYP]= E
[FORCE]= B [MEM]= F
[ARM]= C [CLEAR]= Exit section without saving
[ENTER]= Save current data and advance to next section
[0] to [9] = values 0 to 9 respectively Right Action Key (Exit) = Exit section without saving
[#]= A to F (press the [#] key until the desired letter
appears) Center Action Key (Save) =Save current data and advance to next
section
DGP-848

Digiplex DGP-848 - 2 - Programming Guide
Table of Contents
Serial Number List................................................................................................................................................................. 3
Zone Programming................................................................................................................................................................ 5
Keyswitch Programming........................................................................................................................................................ 8
Access Control .................................................................................................................................................................... 11
Programmable Outputs ....................................................................................................................................................... 14
Other Settings...................................................................................................................................................................... 17
Zone Labels......................................................................................................................................................................... 17
System Options................................................................................................................................................................... 18
Partition 1: Options.............................................................................................................................................................. 20
Partition 2: Options.............................................................................................................................................................. 21
Partition 3: Options.............................................................................................................................................................. 22
Partition 4: Options.............................................................................................................................................................. 23
Dialer Options...................................................................................................................................................................... 24
Partition 1: Event Call Direction........................................................................................................................................... 25
Partition 2: Event Call Direction........................................................................................................................................... 26
Partition 3: Event Call Direction........................................................................................................................................... 27
Partition 4: Event Call Direction........................................................................................................................................... 28
System Event Call Direction................................................................................................................................................ 29
Global Access Control Features.......................................................................................................................................... 29
Communication Settings...................................................................................................................................................... 30
Report Codes ...................................................................................................................................................................... 31
Other Settings and Modes................................................................................................................................................... 39
Power Unit Consumption..................................................................................................................................................... 42
Hardware Connections........................................................................................................................................................ 43
Trouble Display.................................................................................................................................................................... 48

Digiplex DGP-848 - 3 - Programming Guide
Serial Number List
All modules connected to the control panel’s combus have an 8-digit serial number. Remove the extra serial number sticker
from the modules’ PC board and affix in the appropriate spaces provided below (Max. 95 Modules).
Module Type & Details Serial # Module Type & Details Serial #
1:_________________________ ___________ 24:________________________ ___________
2:_________________________ ___________ 25:________________________ ___________
3:_________________________ ___________ 26:________________________ ___________
4:_________________________ ___________ 27:________________________ ___________
5:_________________________ ___________ 28:________________________ ___________
6:_________________________ ___________ 29:________________________ ___________
7:_________________________ ___________ 30:________________________ ___________
8:_________________________ ___________ 31:________________________ ___________
9:_________________________ ___________ 32:________________________ ___________
10:________________________ ___________ 33:________________________ ___________
11:________________________ ___________ 34:________________________ ___________
12:________________________ ___________ 35:________________________ ___________
13:________________________ ___________ 36:________________________ ___________
14:________________________ ___________ 37:________________________ ___________
15:________________________ ___________ 38:________________________ ___________
16:________________________ ___________ 39:________________________ ___________
17:________________________ ___________ 40:________________________ ___________
18:________________________ ___________ 41:________________________ ___________
19:________________________ ___________ 42:________________________ ___________
20:________________________ ___________ 43:________________________ ___________
21:________________________ ___________ 44:________________________ ___________
22:________________________ ___________ 45:________________________ ___________
23:________________________ ___________ 46:________________________ ___________

Digiplex DGP-848 - 4 - Programming Guide
47:________________________ ___________ 72:________________________ ___________
48:________________________ ___________ 73:________________________ ___________
49:________________________ ___________ 74:________________________ ___________
50:________________________ ___________ 75:________________________ ___________
51:________________________ ___________ 76:________________________ ___________
52:________________________ ___________ 77:________________________ ___________
53:________________________ ___________ 78:________________________ ___________
54:________________________ ___________ 79:________________________ ___________
55:________________________ ___________ 80:________________________ ___________
56:________________________ ___________ 81:________________________ ___________
57:________________________ ___________ 82:________________________ ___________
58:________________________ ___________ 83:________________________ ___________
59:________________________ ___________ 84:________________________ ___________
60:________________________ ___________ 85:________________________ ___________
61:________________________ ___________ 86:________________________ ___________
62:________________________ ___________ 87:________________________ ___________
63:________________________ ___________ 88:________________________ ___________
64:________________________ ___________ 89:________________________ ___________
65:________________________ ___________ 90:________________________ ___________
66:________________________ ___________ 91:________________________ ___________
67:________________________ ___________ 92:________________________ ___________
68:________________________ ___________ 93:________________________ ___________
69:________________________ ___________ 94:________________________ ___________
70:________________________ ___________ 95:________________________ ___________
71:________________________ ___________
Module Type & Details Serial # Module Type & Details Serial #

Digiplex DGP-848 - 5 - Programming Guide
Zone Programming
Zone Description Module Section 8-digit Serial Number Input# Section Define Assign Zone Options
1________________ __________ [001] __/__/__/__/__/__/__/__ __/__/__ [101] ___ ___ 1 2 3 4 5 6 7 8
2________________ __________ [002] __/__/__/__/__/__/__/__ __/__/__ [102] ___ ___ 1 2 3 4 5 6 7 8
3________________ __________ [003] __/__/__/__/__/__/__/__ __/__/__ [103] ___ ___ 1 2 3 4 5 6 7 8
4________________ __________ [004] __/__/__/__/__/__/__/__ __/__/__ [104] ___ ___ 1 2 3 4 5 6 7 8
5________________ __________ [005] __/__/__/__/__/__/__/__ __/__/__ [105] ___ ___ 1 2 3 4 5 6 7 8
6________________ __________ [006] __/__/__/__/__/__/__/__ __/__/__ [106] ___ ___ 1 2 3 4 5 6 7 8
7________________ __________ [007] __/__/__/__/__/__/__/__ __/__/__ [107] ___ ___ 1 2 3 4 5 6 7 8
8________________ __________ [008] __/__/__/__/__/__/__/__ __/__/__ [108] ___ ___ 1 2 3 4 5 6 7 8
9________________ __________ [009] __/__/__/__/__/__/__/__ __/__/__ [109] ___ ___ 1 2 3 4 5 6 7 8
10 ________________ __________ [010] __/__/__/__/__/__/__/__ __/__/__ [110] ___ ___ 1 2 3 4 5 6 7 8
11 ________________ __________ [011] __/__/__/__/__/__/__/__ __/__/__ [111] ___ ___ 1 2 3 4 5 6 7 8
12 ________________ __________ [012] __/__/__/__/__/__/__/__ __/__/__ [112] ___ ___ 1 2 3 4 5 6 7 8
When option [7] in section [502] is enabled for
PGM1 to act as a zone input for two-wire smoke
detectors, the control panel will recognize
PGM1 as input number 255.
Sections [001] to [048] represent zones 1 through
48. This feature tells the control panel where the
detection device is connected and which of the 48
zones is assigned to that device.
Enter 3-digit [INPUT NUMBER] of the
Module to which the hardwired
detection device is connected.
NOTE: No input number is required
for Addressable Motion Detectors,
Keypad Zones or the Access Control
Module (DGP2-ACM1P).
Enter a 8-digit [SERIAL NUMBER]of
the Addressable Detector or
Module to which the hardwired
detection device is connected.
0- Disabled (Default)
1- Entry Delay 1 8- 24Hr Burglary
2- Entry Delay 2 9- Delayed 24Hr Fire
3- Entry Delay 3 A- Standard 24Hr Fire
4- Entry Delay 4 B- Stay Delay 1
5- Follow C- Stay Delay 2
6- Instant D- Stay Delay 3
7- 24Hr Buzzer E- Stay Delay 4
1- Zone Assigned to Partition1 (Default)
2- Zone Assigned to Partition 2
3- Zone Assigned to Partition 3
4- Zone Assigned to Partition 4
[1] Auto Zone Shutdown Enabled
[2] Bypass Enabled (Default)
[3] Stay Zone
[4] Force Zone
[5] [6] Zone Alarm Type
off off Steady Alarm
off on Pulsed Alarm
on off Silent Alarm
on on Report Only
[7] Intellizone
[8] Delay before transmission
Sections [101] to [148] represent zones 1 through 48. This
feature defines the type of zone, its partition assignment and
the zone’s options.

Digiplex DGP-848 - 6 - Programming Guide
13 ________________ __________ [013] __/__/__/__/__/__/__/__ __/__/__ [113] ___ ___ 1 2 3 4 5 6 7 8
14 ________________ __________ [014] __/__/__/__/__/__/__/__ __/__/__ [114] ___ ___ 1 2 3 4 5 6 7 8
15 ________________ __________ [015] __/__/__/__/__/__/__/__ __/__/__ [115] ___ ___ 1 2 3 4 5 6 7 8
16 ________________ __________ [016] __/__/__/__/__/__/__/__ __/__/__ [116] ___ ___ 1 2 3 4 5 6 7 8
17 ________________ __________ [017] __/__/__/__/__/__/__/__ __/__/__ [117] ___ ___ 1 2 3 4 5 6 7 8
18 ________________ __________ [018] __/__/__/__/__/__/__/__ __/__/__ [118] ___ ___ 1 2 3 4 5 6 7 8
19 ________________ __________ [019] __/__/__/__/__/__/__/__ __/__/__ [119] ___ ___ 1 2 3 4 5 6 7 8
20 ________________ __________ [020] __/__/__/__/__/__/__/__ __/__/__ [120] ___ ___ 1 2 3 4 5 6 7 8
21 ________________ __________ [021] __/__/__/__/__/__/__/__ __/__/__ [121] ___ ___ 1 2 3 4 5 6 7 8
22 ________________ __________ [022] __/__/__/__/__/__/__/__ __/__/__ [122] ___ ___ 1 2 3 4 5 6 7 8
23 ________________ __________ [023] __/__/__/__/__/__/__/__ __/__/__ [123] ___ ___ 1 2 3 4 5 6 7 8
24 ________________ __________ [024] __/__/__/__/__/__/__/__ __/__/__ [124] ___ ___ 1 2 3 4 5 6 7 8
25 ________________ __________ [025] __/__/__/__/__/__/__/__ __/__/__ [125] ___ ___ 1 2 3 4 5 6 7 8
26 ________________ __________ [026] __/__/__/__/__/__/__/__ __/__/__ [126] ___ ___ 1 2 3 4 5 6 7 8
27 ________________ __________ [027] __/__/__/__/__/__/__/__ __/__/__ [127] ___ ___ 1 2 3 4 5 6 7 8
28 ________________ __________ [028] __/__/__/__/__/__/__/__ __/__/__ [128] ___ ___ 1 2 3 4 5 6 7 8
29 ________________ __________ [029] __/__/__/__/__/__/__/__ __/__/__ [129] ___ ___ 1 2 3 4 5 6 7 8
30 ________________ __________ [030] __/__/__/__/__/__/__/__ __/__/__ [130] ___ ___ 1 2 3 4 5 6 7 8
31 ________________ __________ [031] __/__/__/__/__/__/__/__ __/__/__ [131] ___ ___ 1 2 3 4 5 6 7 8
32 ________________ __________ [032] __/__/__/__/__/__/__/__ __/__/__ [132] ___ ___ 1 2 3 4 5 6 7 8
33 ________________ __________ [033] __/__/__/__/__/__/__/__ __/__/__ [133] ___ ___ 1 2 3 4 5 6 7 8
34 ________________ __________ [034] __/__/__/__/__/__/__/__ __/__/__ [134] ___ ___ 1 2 3 4 5 6 7 8
Zone Description Module Section 8-digit Serial Number Input# Section Define Assign Zone Options

Digiplex DGP-848 - 7 - Programming Guide
To clear a zone’s numbering (sections [001] to [048]):
For LCD keypads:
1)Enter a section number between [001] and [048].
2)Press [0] and then [ENTER]to save and exit.
For Grafica keypads:
1)Enter a section number between [001] and [048].
2)Press [0] to clear the serial number.
3)Using Grafica’s scroll keys, highlight the input number and then press [0] to clear the data.
4)Press Grafica’s center action key (Save) to save and exit.
35 ________________ __________ [035] __/__/__/__/__/__/__/__ __/__/__ [135] ___ ___ 1 2 3 4 5 6 7 8
36 ________________ __________ [036] __/__/__/__/__/__/__/__ __/__/__ [136] ___ ___ 1 2 3 4 5 6 7 8
37 ________________ __________ [037] __/__/__/__/__/__/__/__ __/__/__ [137] ___ ___ 1 2 3 4 5 6 7 8
38 ________________ __________ [038] __/__/__/__/__/__/__/__ __/__/__ [138] ___ ___ 1 2 3 4 5 6 7 8
39 ________________ __________ [039] __/__/__/__/__/__/__/__ __/__/__ [139] ___ ___ 1 2 3 4 5 6 7 8
40 ________________ __________ [040] __/__/__/__/__/__/__/__ __/__/__ [140] ___ ___ 1 2 3 4 5 6 7 8
41 ________________ __________ [041] __/__/__/__/__/__/__/__ __/__/__ [141] ___ ___ 1 2 3 4 5 6 7 8
42 ________________ __________ [042] __/__/__/__/__/__/__/__ __/__/__ [142] ___ ___ 1 2 3 4 5 6 7 8
43 ________________ __________ [043] __/__/__/__/__/__/__/__ __/__/__ [143] ___ ___ 1 2 3 4 5 6 7 8
44 ________________ __________ [044] __/__/__/__/__/__/__/__ __/__/__ [144] ___ ___ 1 2 3 4 5 6 7 8
45 ________________ __________ [045] __/__/__/__/__/__/__/__ __/__/__ [145] ___ ___ 1 2 3 4 5 6 7 8
46 ________________ __________ [046] __/__/__/__/__/__/__/__ __/__/__ [146] ___ ___ 1 2 3 4 5 6 7 8
47 ________________ __________ [047] __/__/__/__/__/__/__/__ __/__/__ [147] ___ ___ 1 2 3 4 5 6 7 8
48 ________________ __________ [048] __/__/__/__/__/__/__/__ __/__/__ [148] ___ ___ 1 2 3 4 5 6 7 8
Zone Description Module Section 8-digit Serial Number Input# Section Define Assign Zone Options

Digiplex DGP-848 - 8 - Programming Guide
Keyswitch Programming
Keyswitch Location Module Section 8-digit Serial Number Input# Section Define Assign Keyswitch
Options
1_______________ __________ [049] __/__/__/__/__/__/__/__ __/__/__ [149] ___ ___
14 5 6 7 8
2_______________ __________ [050] __/__/__/__/__/__/__/__ __/__/__ [150] ___ ___
14 5 6 7 8
3_______________ __________ [051] __/__/__/__/__/__/__/__ __/__/__ [151] ___ ___
14 5 6 7 8
4_______________ __________ [052] __/__/__/__/__/__/__/__ __/__/__ [152] ___ ___
14 5 6 7 8
5_______________ __________ [053] __/__/__/__/__/__/__/__ __/__/__ [153] ___ ___
14 5 6 7 8
6_______________ __________ [054] __/__/__/__/__/__/__/__ __/__/__ [154] ___ ___
14 5 6 7 8
7_______________ __________ [055] __/__/__/__/__/__/__/__ __/__/__ [155] ___ ___
14 5 6 7 8
8_______________ __________ [056] __/__/__/__/__/__/__/__ __/__/__ [156] ___ ___
14 5 6 7 8
Sections [049] to [056] represent keyswitches 1 to 8
respectively. This feature tells the control panel where
the keyswitch is connected and which of the 8
keyswitch locations is assigned to that device.
Enter 3-digit [INPUT NUMBER]of the
Module to which the keyswitch is
connected.
Enter 8-digit [SERIAL NUMBER]of the
Module to which the keyswitch is
connected.
Sections [149] to [156] represent keyswitches 1 to 8
respectively. This feature defines the keyswitch’s
partition assignment and arming method.
1- Keyswitch Assigned to Partition 1
2- Keyswitch Assigned to Partition 2
3- Keyswitch Assigned to Partition 3
4- Keyswitch Assigned to Partition 4
1- Momentary Keyswitch
2- Maintained Keyswitch
[4] Stay/Instant Disarm
[5] On = Arm Only
Off = Arm/Disarm
[6] *Stay Arming
[7] *Force Arming
[8] *Instant Arming
* Select only one. If all are off
keyswitch will regular arm

Digiplex DGP-848 - 9 - Programming Guide
SYSTEM TIMERS
Section # Decimal Value (000 to 255) Description Default
[200] ___/___/___ seconds (min. = 10sec.) INTELLIZONE DELAY 10sec.
[201]
___/___/___ x 20 msec. INPUT SPEED 001=PANEL TERMINAL 1 600 msec.
[202]
___/___/___ x 20 msec. INPUT SPEED 002=PANEL TERMINAL 2 600 msec.
[203]
___/___/___ x 20 msec. INPUT SPEED 003=PANEL TERMINAL 3 600 msec.
[204]
___/___/___ x 20 msec. INPUT SPEED 004=PANEL TERMINAL 4 600 msec.
[205]
___/___/___ x 20 msec. INPUT SPEED 005=PANEL TERMINAL 5 600 msec.
[206]
___/___/___ x 20 msec. INPUT SPEED 006=PANEL TERMINAL 6 600 msec.
[207]
___/___/___ x 20 msec. INPUT SPEED 007=PANEL TERMINAL 7 600 msec.
[208]
___/___/___ x 20 msec. INPUT SPEED 008=PANEL TERMINAL 8 600 msec.
[209]
___/___/___ x 20 msec. INPUT SPEED 009=PANEL DOUBLER 1 600 msec.
[210]
___/___/___ x 20 msec. INPUT SPEED 010=PANEL DOUBLER 2 600 msec.
[211]
___/___/___ x 20 msec. INPUT SPEED 011=PANEL DOUBLER 3 600 msec.
[212]
___/___/___ x 20 msec. INPUT SPEED 012=PANEL DOUBLER 4 600 msec.
[213]
___/___/___ x 20 msec. INPUT SPEED 013=PANEL DOUBLER 5 600 msec.
[214]
___/___/___ x 20 msec. INPUT SPEED 014=PANEL DOUBLER 6 600 msec.
[215]
___/___/___ x 20 msec. INPUT SPEED 015=PANEL DOUBLER 7 600 msec.
[216]
___/___/___ x 20 msec. INPUT SPEED 016=PANEL DOUBLER 8 600 msec.
[217]
___/___/___ (max.=15) AUTO ZONE SHUTDOWN Disabled
[218]
___/___/___ (max.=15) AUTO TROUBLE SHUTDOWN Disabled
[219]
___/___/___ seconds RECENT CLOSING DELAY Disabled
[220]
___/___/___ tries # OF INVALID CODE BEFORE LOCKOUT Disabled
[221]
___/___/___ minutes (000 = report only) KEYPAD LOCKOUT DURATION Report Only
[222]
___/___/___ x15 minutes NO MOVEMENT TIMER PARTITION 1 Disabled
[223]
___/___/___ x15 minutes NO MOVEMENT TIMER PARTITION 2 Disabled
[224]
___/___/___ x15 minutes NO MOVEMENT TIMER PARTITION 3 Disabled
[225]
___/___/___ x15 minutes NO MOVEMENT TIMER PARTITION 4 Disabled
[226]
___/___/___ seconds EXIT DELAY PARTITION 1 60 sec.
[227]
___/___/___ seconds EXIT DELAY PARTITION 2 60 sec.
[228]
___/___/___ seconds EXIT DELAY PARTITION 3 60 sec.
[229]
___/___/___ seconds EXIT DELAY PARTITION 4 60 sec.
[230]
___/___/___ seconds ENTRY/STAY DELAY 1 30 sec.
[231]
___/___/___ seconds ENTRY/STAY DELAY 2 60 sec.
[232]
___/___/___ seconds ENTRY/STAY DELAY 3 90 sec.
[233]
___/___/___ seconds ENTRY/STAY DELAY 4 120 sec.
[234]
___/___/___ minutes BELL CUT-OFF TIMER PARTITION 1 4 min.
[235]
___/___/___ minutes BELL CUT-OFF TIMER PARTITION 2 4 min.
[236]
___/___/___ minutes BELL CUT-OFF TIMER PARTITION 3 4 min.
[237]
___/___/___ minutes BELL CUT-OFF TIMER PARTITION 4 4 min.

Digiplex DGP-848 - 10 - Programming Guide
[238]
___/___/___ zone(s) MAX. BYPASS ENTRIES PARTITION 1 Unlimited
[239]
___/___/___ zone(s) MAX. BYPASS ENTRIES PARTITION 2 Unlimited
[240]
___/___/___ zone(s) MAX. BYPASS ENTRIES PARTITION 3 Unlimited
[241]
___/___/___ zone(s) MAX. BYPASS ENTRIES PARTITION 4 Unlimited
[242]
___/___/___ minutes RECYCLE DELAY PARTITION 1 Disabled
[243]
___/___/___ minutes RECYCLE DELAY PARTITION 2 Disabled
[244]
___/___/___ minutes RECYCLE DELAY PARTITION 3 Disabled
[245]
___/___/___ minutes RECYCLE DELAY PARTITION 4 Disabled
[246]
___/___/___ recycle(s) # OF RECYCLES PARTITION 1 Unlimited
[247]
___/___/___ recycle(s) # OF RECYCLES PARTITION 2 Unlimited
[248]
___/___/___ recycle(s) # OF RECYCLES PARTITION 3 Unlimited
[249]
___/___/___ recycle(s) # OF RECYCLES PARTITION 4 Unlimited
[250]
___/___/___ see section [503] PGM1 DELAY 5 sec.
[251]
___/___/___ see section [503] PGM2 DELAY 5 sec.
[252]
___/___/___ see section [503] PGM3 DELAY 5 sec.
[253]
___/___/___ see section [503] PGM4 DELAY 5 sec.
[254]
___/___/___ see section [503] PGM5 DELAY 5 sec.
[255]
___/___/___ x2 sec. (min. = 32sec.) TLM FAIL TIMER 32 sec.
[256]
___/___/___ seconds DELAY ALARM TRANSMISSION TIMER Instant
[257]
___/___/___ attempts MAXIMUM DIALING ATTEMPTS 8 attempts
[258]
___/___/___ seconds DELAY BETWEEN DIALING ATTEMPTS 20 sec.
[259]
___/___/___ seconds (max. 60 sec.) PAGER DELAY BEFORE DATA TRANSMISSION Disabled
[260]
___/___/___ minutes DELAY POWER FAILURE REPORT 30 min.
[261]
___/___/___ days AUTO TEST REPORT Disabled
Hours (00 to 23) & Minutes (00 to 59)
[270] ___/___:___/___ AUTO TEST REPORT TIME OF DAY
[271] ___/___:___/___ AUTO ARM TIME PARTITION 1
[272] ___/___:___/___ AUTO ARM TIME PARTITION 2
[273] ___/___:___/___ AUTO ARM TIME PARTITION 3
[274] ___/___:___/___ AUTO ARM TIME PARTITION 4
Section # Decimal Value (000 to 255) Description Default

Digiplex DGP-848 - 11 - Programming Guide
Access Control
ASSIGNING THE DOOR TO AN ACCESS CONTROL MODULE
These doors are used to program the Access Level in sections [341] to [355]. If you want an Access door to be linked to the
alarm system, install a door contact and assign it to a zone through Zone Programming.
Section Door Description Access Module Serial Number
[301] 01 ____________________________________________ __/__/__/__/__/__/__/__
[302] 02 ____________________________________________ __/__/__/__/__/__/__/__
[303] 03 ____________________________________________ __/__/__/__/__/__/__/__
[304] 04 ____________________________________________ __/__/__/__/__/__/__/__
[305] 05 ____________________________________________ __/__/__/__/__/__/__/__
[306] 06 ____________________________________________ __/__/__/__/__/__/__/__
[307] 07 ____________________________________________ __/__/__/__/__/__/__/__
[308] 08 ____________________________________________ __/__/__/__/__/__/__/__
[309] 09 ____________________________________________ __/__/__/__/__/__/__/__
[310] 10 ____________________________________________ __/__/__/__/__/__/__/__
[311] 11 ____________________________________________ __/__/__/__/__/__/__/__
[312] 12 ____________________________________________ __/__/__/__/__/__/__/__
[313] 13 ____________________________________________ __/__/__/__/__/__/__/__
[314] 14 ____________________________________________ __/__/__/__/__/__/__/__
[315] 15 ____________________________________________ __/__/__/__/__/__/__/__
[316] 16 ____________________________________________ __/__/__/__/__/__/__/__
[317] 17 ____________________________________________ __/__/__/__/__/__/__/__
[318] 18 ____________________________________________ __/__/__/__/__/__/__/__
[319] 19 ____________________________________________ __/__/__/__/__/__/__/__
[320] 20 ____________________________________________ __/__/__/__/__/__/__/__
[321] 21 ____________________________________________ __/__/__/__/__/__/__/__
[322] 22 ____________________________________________ __/__/__/__/__/__/__/__
[323] 23 ____________________________________________ __/__/__/__/__/__/__/__
[324] 24 ____________________________________________ __/__/__/__/__/__/__/__
[325] 25 ____________________________________________ __/__/__/__/__/__/__/__
[326] 26 ____________________________________________ __/__/__/__/__/__/__/__
[327] 27 ____________________________________________ __/__/__/__/__/__/__/__
[328] 28 ____________________________________________ __/__/__/__/__/__/__/__
[329] 29 ____________________________________________ __/__/__/__/__/__/__/__
[330] 30 ____________________________________________ __/__/__/__/__/__/__/__
[331] 31 ____________________________________________ __/__/__/__/__/__/__/__
[332] 32 ____________________________________________ __/__/__/__/__/__/__/__

Digiplex DGP-848 - 12 - Programming Guide
DOOR ACCESS MODE
Each door can be programmed to grant access only to cards assigned to all the door’s assigned partitions (“AND” Door
Access Mode) or to cards assigned to at least one of the door’s partitions (“OR” Door Access Mode). Enable the option
corresponding to the door to be set in “OR” Door Access Mode. Options that remain disabled represent doors set in the
“AND” Door Access Mode.
PROGRAMMING ACCESS LEVELS
Each Access Level is a combination of Access Control doors. Use Feature Select Programming to enable or disable options.
For example, if option [1] in the First Screen is enabled in section [341], Level 01 will allow access only to Door 01. Access
Level 00 = access to all doors.
SCHEDULE PROGRAMMING
Each Schedule determines when users are permitted access. Holidays are programmed in sections [381] to [392]. Schedule
00 = access granted at all times.
Section Door Access Mode (turn ON for “OR” Door Access Mode):
First Screen
Doors 01 to 08 Second Screen
Doors 09 to 16 Third Screen
Doors 17 to 24 Fourth Screen
Doors 25 to 32
[340] 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Section Level Access to Doors (turn ON or OFF access):
First Screen
Doors 01 to 08 Second Screen
Doors 09 to 16 Third Screen
Doors 17 to 24 Fourth Screen
Doors 25 to 32
[341] 01 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[342] 02 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[343] 03 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[344] 04 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[345] 05 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[346] 06 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[347] 07 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[348] 08 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[349] 09 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[350] 10 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[351] 11 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[352] 12 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[353] 13 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[354] 14 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
[355] 15 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Section Schedule Intervals Start Time (from) End Time (to) Days (turn ON or OFF)
S M T W T F S H
[361] 01 Interval A ___ ___: ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[362] 02 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[363] 03 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[364] 04 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[365] 05 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8

Digiplex DGP-848 - 13 - Programming Guide
The Start and End Time of an Interval cannot cross over into another day. For example, to program a shift
from 10PM one day to 6AM the next morning, you must program Interval 1A: Start Time 22:00 and End Time
23:59 then program Interval 1B Start Time 00:00 and End Time 06:00. The schedule will not be interrupted
between 23:59 and 00:00.
HOLIDAY PROGRAMMING
The holidays are determined in these sections. When [H] is enabled in sections [361] to [375], access is permitted to users
during the days programmed in sections [381] to [392].
*option not used in this screen
[366] 06 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[367] 07 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[368] 08 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[369] 09 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[370] 10 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[371] 11 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[372] 12 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[373] 13 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[374] 14 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[375] 15 Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Section Month Days Programmed (turn ON or OFF access):
First Screen
Days 01 to 08 Second Screen
Days 09 to 16 Third Screen
Days 17 to 24 Fourth Screen
Days 25 to 31
[381] January 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 *
[382] February 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 * * *
[383] March 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 *
[384] April 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 * *
[385] May 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 *
[386] June 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 * *
[387] July 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 *
[388] August 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 *
[389] September 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 * *
[390] October 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 *
[391] November 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 * *
[392] December 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 *
Section Schedule Intervals Start Time (from) End Time (to) Days (turn ON or OFF)
S M T W T F S H

Digiplex DGP-848 - 14 - Programming Guide
Programmable Outputs
The control panel deactivates an activated PGM one of two ways (also see sections [502] and [503]):
Section [502]: Option OFF = Follow Activation Event:
If the first digit of the PGM Activation Event is set at 1, 2, 3, 4, or 7, the PGM will remain activated until the PGM Activation
Event has ended. It will ignore the PGM Deactivation Event. If the first digit of the PGM Activation Event is set at 8, 9, A, B, C,
D, E, or F, the PGM will remain activated until the PGM Deactivation Event occurs.
Section [502]: Option ON = Follow PGM Delay Timer:
After activating the PGM, the control panel will start the PGM delay timer and the PGM will deactivate only when the PGM
delay timer has elapsed regardless of the PGM Deactivation Event.
NOTE1*:
0 = Occurs in all partitions enabled in the system (see section [500]).
1 = Partition 1 3 = Partition 3
2 = Partition 2 4 = Partition 4
8 = Occurs in at least one partition enabled in the system.
† : If you select a group and set all options to OFF, all users/zones/selections of that group will be enabled (result is “ANY” of
that group). For example, if you select A0 and set all 8 options to OFF, the PGM will activate/deactivate whenever a user
between 1 and 8 arms the system.
Section PGM Event Group
(First Digit) Event Group
(Second Digit) Event Selection
(on/off)†
[400] PGM1 Activation Event ___ ___ 1 2 3 4 5 6 7 8
[401] PGM1 Deactivation Event ___ ___ 1 2 3 4 5 6 7 8
[402] PGM2 Activation Event ___ ___ 1 2 3 4 5 6 7 8
[403] PGM2 Deactivation Event ___ ___ 1 2 3 4 5 6 7 8
[404] PGM3 Activation Event ___ ___ 1 2 3 4 5 6 7 8
[405] PGM3 Deactivation Event ___ ___ 1 2 3 4 5 6 7 8
[406] PGM4 Activation Event ___ ___ 1 2 3 4 5 6 7 8
[407] PGM4 Deactivation Event ___ ___ 1 2 3 4 5 6 7 8
[408] PGM5 Activation Event ___ ___ 1 2 3 4 5 6 7 8
[409] PGM5 Deactivation Event ___ ___ 1 2 3 4 5 6 7 8
First Digit Second
Digit Feature Select Programming †
12345678
0 = PGM Disabled N/A N/A N/A N/A N/A N/A N/A N/A N/A
1 = Status 1
Note 1* Any Arming
Method Force
Arm Stay
Arm Instant
Arm Strobe
(until alarm is
cancelled)
Silent
Alarm
(until alarm is
cancelled or
bell is cut off)
Audible
Alarm
(until alarm is
cancelled or
bell is cut off)
Fire Alarm
(until alarm is
cancelled or
bell is cut off)
2 = Status 2 Note 1* Ready
Status Exit Delay Entry Delay Trouble Alarm
Memory Zone
Bypassed
(armed or not)
Master or
Installer
Programming
Keypad
Lockout
3 = Status 3 Note 1* Intellizone Fire Delay Auto Arm
Delay N/A Any Tamper Zone Low
Battery Fire Loop Zone
Supervision

Digiplex DGP-848 - 15 - Programming Guide
First Digit Second
Digit Feature Select Programming
12345678
4 = Status 4
0Chime
Partition 1 Chime
Partition 2 Chime
Partition 3 Chime
Partition 4 Siren
Partition 1 Siren
Partition 2 Siren
Partition 3 Siren
Partition 4
1N/AN/AN/AN/ASmoke
Reset Ground
Start Kissoff N/A
2System
Trouble Dialer
Trouble Module
Trouble Combus
Trouble N/A N/A N/A Timer Loss
3 AC Fail Battery fail Aux. Limit Bell Limit No Bell ROM Error N/A N/A
4 TLM Fail to
Com1 Fail to
Com2 Fail to
Com3 Fail to
Com4 Fail to
Com PC N/A N/A
5 Module
Tamper Module
ROM Error Module
TLM Module Fail
to Com
Phone#
Printer Fault Module AC
Fail Module
Battery Fail ModuleAux.
fail
6 Missing
Keypad MissingAny
Module N/A N/A N/A Global Com-
bus Failure Combus
Overload Module Com-
bus Com Fail
7 = At the
Selected Time
0 00:00 00:15 00:30 00:45 01:00 01:15 01:30 01:45
1 02:00 02:15 02:30 02:45 03:00 03:15 03:30 03:45
2 04:00 04:15 04:30 04:45 05:00 05:15 05:30 05:45
3 06:00 06:15 06:30 06:45 07:00 07:15 07:30 07:45
4 08:00 08:15 08:30 08:45 09:00 09:15 09:30 09:45
5 10:00 10:15 10:30 10:45 11:00 11:15 11:30 11:45
6 12:00 12:15 12:30 12:45 13:00 13:15 13:30 13:45
7 14:00 14:15 14:30 14:45 15:00 15:15 15:30 15:45
8 16:00 16:15 16:30 16:45 17:00 17:15 17:30 17:45
9 18:00 18:15 18:30 18:45 19:00 19:15 19:30 19:45
A 20:00 20:15 20:30 20:45 21:00 21:15 21:30 21:45
B 22:00 22:15 22:30 22:45 23:00 23:15 23:30 23:45
8 = Utility Keys
0 Keys 1-2 Keys 4-5 Keys 7-8 LCD:
(CLEAR & 0)
Grafica:
(*& 0)
Keys 2-3 Keys 5-6 Keys 8-9 LCD:
(0 & ENTER)
Grafica:
(0 & #)
9 = Access
Granted
0 Door 01 Door 02 Door 03 Door 04 Door 05 Door 06 Door 07 Door 08
1 Door 09 Door 10 Door 11 Door 12 Door 13 Door 14 Door 15 Door 16
2 Door 17 Door 18 Door 19 Door 20 Door 21 Door 22 Door 23 Door 24
3 Door 25 Door 26 Door 27 Door 28 Door 29 Door 30 Door 31 Door 32
9 = User Code
Entered
8 Code # 01 Code # 02 Code # 03 Code # 04 Code # 05 Code # 06 Code # 07 Code # 08
9 Code # 09 Code # 10 Code # 11 Code # 12 Code # 13 Code # 14 Code # 15 Code # 16
A Code # 17 Code # 18 Code # 19 Code # 20 Code # 21 Code # 22 Code # 23 Code # 24
B Code # 25 Code # 26 Code # 27 Code # 28 Code # 29 Code # 30 Code # 31 Code # 32
C Code # 33 Code # 34 Code # 35 Code # 36 Code # 37 Code # 38 Code # 39 Code # 40
D Code # 41 Code # 42 Code # 43 Code # 44 Code # 45 Code # 46 Code # 47 Code # 48
E Code # 49 Code # 50 Code # 51 Code # 52 Code # 53 Code # 54 Code # 55 Code # 56
F Code # 57 Code # 58 Code # 59 Code # 60 Code # 61 Code # 62 Code # 63 Code # 64
A = Arming
0 Code # 01 Code # 02 Code # 03 Code # 04 Code # 05 Code # 06 Code # 07 Code # 08
1 Code # 09 Code # 10 Code # 11 Code # 12 Code # 13 Code # 14 Code # 15 Code # 16
2 Code # 17 Code # 18 Code # 19 Code # 20 Code # 21 Code # 22 Code # 23 Code # 24
3 Code # 25 Code # 26 Code # 27 Code # 28 Code # 29 Code # 30 Code # 31 Code # 32
4 Code # 33 Code # 34 Code # 35 Code # 36 Code # 37 Code # 38 Code # 39 Code # 40
5 Code # 41 Code # 42 Code # 43 Code # 44 Code # 45 Code # 46 Code # 47 Code # 48
6 Code # 49 Code # 50 Code # 51 Code # 52 Code # 53 Code # 54 Code # 55 Code # 56
7 Code # 57 Code # 58 Code # 59 Code # 60 Code # 61 Code # 62 Code # 63 Code # 64
A = Disarming
8 Code # 01 Code # 02 Code # 03 Code # 04 Code # 05 Code # 06 Code # 07 Code # 08
9 Code # 09 Code # 10 Code # 11 Code # 12 Code # 13 Code # 14 Code # 15 Code # 16
A Code # 17 Code # 18 Code # 19 Code # 20 Code # 21 Code # 22 Code # 23 Code # 24
B Code # 25 Code # 26 Code # 27 Code # 28 Code # 29 Code # 30 Code # 31 Code # 32
C Code # 33 Code # 34 Code # 35 Code # 36 Code # 37 Code # 38 Code # 39 Code # 40
D Code # 41 Code # 42 Code # 43 Code # 44 Code # 45 Code # 46 Code # 47 Code # 48
E Code # 49 Code # 50 Code # 51 Code # 52 Code # 53 Code # 54 Code # 55 Code # 56
F Code # 57 Code # 58 Code # 59 Code # 60 Code # 61 Code # 62 Code # 63 Code # 64

Digiplex DGP-848 - 16 - Programming Guide
First Digit Second
Digit Feature Select Programming
12345678
B = Zone is OK
0 Zone # 01 Zone # 02 Zone # 03 Zone # 04 Zone # 05 Zone # 06 Zone # 07 Zone # 08
1 Zone # 09 Zone # 10 Zone # 11 Zone # 12 Zone # 13 Zone # 14 Zone # 15 Zone # 16
2 Zone # 17 Zone # 18 Zone # 19 Zone # 20 Zone # 21 Zone # 22 Zone # 23 Zone # 24
3 Zone # 25 Zone # 26 Zone # 27 Zone # 28 Zone # 29 Zone # 30 Zone # 31 Zone # 32
4 Zone # 33 Zone # 34 Zone # 35 Zone # 36 Zone # 37 Zone # 38 Zone # 39 Zone # 40
5 Zone # 41 Zone # 42 Zone # 43 Zone # 44 Zone # 45 Zone # 46 Zone # 47 Zone # 48
B = Zone is Open
8 Zone # 01 Zone # 02 Zone # 03 Zone # 04 Zone # 05 Zone # 06 Zone # 07 Zone # 08
9 Zone # 09 Zone # 10 Zone # 11 Zone # 12 Zone # 13 Zone # 14 Zone # 15 Zone # 16
A Zone # 17 Zone # 18 Zone # 19 Zone # 20 Zone # 21 Zone # 22 Zone # 23 Zone # 24
B Zone # 25 Zone # 26 Zone # 27 Zone # 28 Zone # 29 Zone # 30 Zone # 31 Zone # 32
C Zone # 33 Zone # 34 Zone # 35 Zone # 36 Zone # 37 Zone # 38 Zone # 39 Zone # 40
D Zone # 41 Zone # 42 Zone # 43 Zone # 44 Zone # 45 Zone # 46 Zone # 47 Zone # 48
C = Auto Zone
Shutdown
0 Zone # 01 Zone # 02 Zone # 03 Zone # 04 Zone # 05 Zone # 06 Zone # 07 Zone # 08
1 Zone # 09 Zone # 10 Zone # 11 Zone # 12 Zone # 13 Zone # 14 Zone # 15 Zone # 16
2 Zone # 17 Zone # 18 Zone # 19 Zone # 20 Zone # 21 Zone # 22 Zone # 23 Zone # 24
3 Zone # 25 Zone # 26 Zone # 27 Zone # 28 Zone # 29 Zone # 30 Zone # 31 Zone # 32
4 Zone # 33 Zone # 34 Zone # 35 Zone # 36 Zone # 37 Zone # 38 Zone # 39 Zone # 40
5 Zone # 41 Zone # 42 Zone # 43 Zone # 44 Zone # 45 Zone # 46 Zone # 47 Zone # 48
C = Zone Bypass
(when system
is armed)
8 Zone # 01 Zone # 02 Zone # 03 Zone # 04 Zone # 05 Zone # 06 Zone # 07 Zone # 08
9 Zone # 09 Zone # 10 Zone # 11 Zone # 12 Zone # 13 Zone # 14 Zone # 15 Zone # 16
A Zone # 17 Zone # 18 Zone # 19 Zone # 20 Zone # 21 Zone # 22 Zone # 23 Zone # 24
B Zone # 25 Zone # 26 Zone # 27 Zone # 28 Zone # 29 Zone # 30 Zone # 31 Zone # 32
C Zone # 33 Zone # 34 Zone # 35 Zone # 36 Zone # 37 Zone # 38 Zone # 39 Zone # 40
D Zone # 41 Zone # 42 Zone # 43 Zone # 44 Zone # 45 Zone # 46 Zone # 47 Zone # 48
D = Zone Fault
(Tamper / Fire
Loop)
0 Zone # 01 Zone # 02 Zone # 03 Zone # 04 Zone # 05 Zone # 06 Zone # 07 Zone # 08
1 Zone # 09 Zone # 10 Zone # 11 Zone # 12 Zone # 13 Zone # 14 Zone # 15 Zone # 16
2 Zone # 17 Zone # 18 Zone # 19 Zone # 20 Zone # 21 Zone # 22 Zone # 23 Zone # 24
3 Zone # 25 Zone # 26 Zone # 27 Zone # 28 Zone # 29 Zone # 30 Zone # 31 Zone # 32
4 Zone # 33 Zone # 34 Zone # 35 Zone # 36 Zone # 37 Zone # 38 Zone # 39 Zone # 40
5 Zone # 41 Zone # 42 Zone # 43 Zone # 44 Zone # 45 Zone # 46 Zone # 47 Zone # 48
D = RF Zone Fault
(Low battery
Supervision)
8 Zone # 01 Zone # 02 Zone # 03 Zone # 04 Zone # 05 Zone # 06 Zone # 07 Zone # 08
9 Zone # 09 Zone # 10 Zone # 11 Zone # 12 Zone # 13 Zone # 14 Zone # 15 Zone # 16
A Zone # 17 Zone # 18 Zone # 19 Zone # 20 Zone # 21 Zone # 22 Zone # 23 Zone # 24
B Zone # 25 Zone # 26 Zone # 27 Zone # 28 Zone # 29 Zone # 30 Zone # 31 Zone # 32
C Zone # 33 Zone # 34 Zone # 35 Zone # 36 Zone # 37 Zone # 38 Zone # 39 Zone # 40
D Zone # 41 Zone # 42 Zone # 43 Zone # 44 Zone # 45 Zone # 46 Zone # 47 Zone # 48
E = Fire /Burglar
Alarms
0 Zone # 01 Zone # 02 Zone # 03 Zone # 04 Zone # 05 Zone # 06 Zone # 07 Zone # 08
1 Zone # 09 Zone # 10 Zone # 11 Zone # 12 Zone # 13 Zone # 14 Zone # 15 Zone # 16
2 Zone # 17 Zone # 18 Zone # 19 Zone # 20 Zone # 21 Zone # 22 Zone # 23 Zone # 24
3 Zone # 25 Zone # 26 Zone # 27 Zone # 28 Zone # 29 Zone # 30 Zone # 31 Zone # 32
4 Zone # 33 Zone # 34 Zone # 35 Zone # 36 Zone # 37 Zone # 38 Zone # 39 Zone # 40
5 Zone # 41 Zone # 42 Zone # 43 Zone # 44 Zone # 45 Zone # 46 Zone # 47 Zone # 48
E = Fire/Burglar
Restore
8 Zone # 01 Zone # 02 Zone # 03 Zone # 04 Zone # 05 Zone # 06 Zone # 07 Zone # 08
9 Zone # 09 Zone # 10 Zone # 11 Zone # 12 Zone # 13 Zone # 14 Zone # 15 Zone # 16
A Zone # 17 Zone # 18 Zone # 19 Zone # 20 Zone # 21 Zone # 22 Zone # 23 Zone # 24
B Zone # 25 Zone # 26 Zone # 27 Zone # 28 Zone # 29 Zone # 30 Zone # 31 Zone # 32
C Zone # 33 Zone # 34 Zone # 35 Zone # 36 Zone # 37 Zone # 38 Zone # 39 Zone # 40
D Zone # 41 Zone # 42 Zone # 43 Zone # 44 Zone # 45 Zone # 46 Zone # 47 Zone # 48
F = Module
Troubles
0 Combus
Fault Tamper ROM Error TLM Fail to
Comm. Printer Fault AC Fail Battery Fail
1 Auxiliary
Output Fail N/A N/A N/A N/A N/A N/A N/A
8 Combus
Fault
Restore
Tamper
Restore ROM Error
Restore TLM
Restore Fail to
Comm.
Restore
PrinterFault
Restore AC Fail
Restore Battery Fail
Restore
9 Auxiliary Fail N/A N/A N/A N/A N/A N/A N/A

Digiplex DGP-848 - 17 - Programming Guide
Other Settings
Zone Labels
For instructions on how to enter letters and special characters when using an LCD or Grafica keypad, refer to the LCD
keypad’s Installation Manual or Grafica’s User Manual. A complete Grafica user manual is available on our Web site at
www.paradox.ca.
Section # Decimal Value (00 to 15) Description Default
[440]
___/___ 00 to 04 (00 = all enabled partitions) CONTROL PANEL PARTITION ASSIGNMENT 00
[441]
___/___ x4 sec. ANSWERING MACHINE OVERRIDE DELAY 32 sec.
[442]
___/___ x1 Ring NUMBER OF RINGS 8 rings
Section Zone # Zone Label Section Zone # Zone Label
[451] Zone 1 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [475] Zone 25 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[452] Zone 2 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [476] Zone 26 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[453] Zone 3 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [477] Zone 27 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[454] Zone 4 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [478] Zone 28 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[455] Zone 5 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [479] Zone 29 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[456] Zone 6 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [480] Zone 30 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[457] Zone 7 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [481] Zone 31 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[458] Zone 8 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [482] Zone 32 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[459] Zone 9 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [483] Zone 33 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[460] Zone 10 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [484] Zone 34 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[461] Zone 11 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [485] Zone 35 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[462] Zone 12 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [486] Zone 36 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[463] Zone 13 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [487] Zone 37 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[464] Zone 14 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [488] Zone 38 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[465] Zone 15 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [489] Zone 39 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[466] Zone 16 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [490] Zone 40 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[467] Zone 17 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [491] Zone 41 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[468] Zone 18 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [492] Zone 42 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[469] Zone 19 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [493] Zone 43 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[470] Zone 20 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [494] Zone 44 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[471] Zone 21 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [495] Zone 45 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[472] Zone 22 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [496] Zone 46 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[473] Zone 23 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [497] Zone 47 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
[474] Zone 24 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [498] Zone 48 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__

Digiplex DGP-848 - 18 - Programming Guide
System Options
Bold = Default setting
Bold = Default setting
SECTION [500]: System Options
Option OFF ON
[1] Partition 1 NDisabled NEnabled
[2] Partition 2 NDisabled NEnabled
[3] Partition 3 NDisabled NEnabled
[4] Partition 4 NDisabled NEnabled
[5] Bell/Siren Output in Partition 1 NDisabled NEnabled
[6] Bell/Siren Output in Partition 2 NDisabled NEnabled
[7] Bell/Siren Output in Partition 3 NDisabled NEnabled
[8] Bell/Siren Output in Partition 4 NDisabled NEnabled
SECTION [501]: System Options
Option OFF ON
[1]&[2]
Nsee table
Nsee table Nsee table
Nsee table
[3] Generate Supervision Failure if detected on a
Bypassed Wireless Zone NYes NNo
[4] Restrict Arming on Wireless Transmitter
Supervision Failure NDisabled NEnabled
[5]&[6]
Nsee table
Nsee table Nsee table
Nsee table
[7] Generate Tamper if detected on Bypassed Zone NYes NNo
[8] Restrict Arming on Tamper Trouble NDisabled NEnabled
SECTION [502]: PGM & Other Options
Option OFF ON
[1] PGM 1 Deactivation Type NFollows Event NFollows Timer
[2] PGM 2 Deactivation Type NFollows Event NFollows Timer
[3] PGM 3 Deactivation Type N Follows Event NFollows Timer
[4] PGM 4 Deactivation Type NFollows Event NFollows Timer
[5] PGM 5 Deactivation Type NFollows Event NFollows Timer
[6] Auto adjust panel clock for Daylight Savings NDisabled NEnabled
[7] PGM 1 = 2-wire smoke detector input (255) NDisabled NEnabled
[8] No bell cut-off during fire alarm NDisabled NEnabled
Wireless Transmitter Supervision Options
[1] [2]
OFF OFF Disabled (default)
ON OFF When disarmed: GENERATES TROUBLE ONLY
When armed: Follows Zone Alarm Types (page 5)
OFF ON When disarmed: GENERATES SILENT ALARM
When armed: Follows Zone Alarm Types (page 5)
ON ON When disarmed: GENERATES AUDIBLE ALARM
When armed: Follows Zone Alarm Types (page 5)
Zone & Module Tamper Recognition Options
[5] [6]
OFF OFF Disabled (default)
ON OFF When disarmed: GENERATES TROUBLE ONLY
When armed: Follows Zone Alarm Types (page 5)
OFF ON When disarmed: GENERATES SILENT ALARM
When armed: Follows Zone Alarm Types (page 5)
ON ON When disarmed: GENERATES AUDIBLE ALARM
When armed: Follows Zone Alarm Types (page 5)

Digiplex DGP-848 - 19 - Programming Guide
SECTION [503]: PGM & Other Options
Option OFF ON
[1] PGM 1 Timer (see section [250]) NSeconds NMinutes
[2] PGM 2 Timer (see section [251]) NSeconds NMinutes
[3] PGM 3 Timer (see section [252]) NSeconds NMinutes
[4] PGM 4 Timer (see section [253]) NSeconds NMinutes
[5] PGM 5 Timer (see section [254]) NSeconds NMinutes
[6] Battery charge current N350mA N700mA
[7] AC failure does not appear in Trouble Display NDisabled NEnabled
[8] Restrict arming on battery/AC failure NDisabled NEnabled
SECTION [504]: Keypad & Other Options
Option OFF ON
[1] Multiple Actions in User Menu NDisabled NEnabled
[2] User Code length NFixed (see option [3] below) NFlexible (1 to 6 digits)
[3] User Code length N4-digits (if option [2] = off) N6-digits (if option [2] = off)
[4] Power Save Mode NDisabled NEnabled
[5] Bypass not displayed while system is armed NDisabled NEnabled
[6] Trouble Latch NDisabled NEnabled
[7] EOL resistor on hardwire inputs NDisabled NEnabled
[8] ATZ (Zone Doubling) NDisabled NEnabled

Digiplex DGP-848 - 20 - Programming Guide
Partition 1: Options
Bold = Default setting
* If the keypad is assigned to more than one partition, the feature must be enabled in all the keypad’s partitions.
SECTION [505]: Partition 1 Options
Option OFF ON
[1] Switch to Stay Arming (if no delay zone opened) NDisabled NEnabled
[2] Partition 1 arms & disarms with Partition 2 NDisabled NEnabled
[3] Partition 1 arms & disarms with Partition 3 NDisabled NEnabled
[4] Partition 1 arms & disarms with Partition 4 NDisabled NEnabled
[5] Timed Auto-Arming NDisabled NEnabled
[6] “No Movement” Auto-Arming NDisabled NEnabled
[7] Arming method for auto arming NForce Arming NStay Arming
[8] Exit Delay termination NDisabled NEnabled
SECTION [506]: Partition 1 Options
Option OFF ON
[1] Panic 1 (keys [1] and [3]) NDisabled NEnabled
[2] Panic 2 (keys [4] and [6]) NDisabled NEnabled
[3] Panic 3 (keys [7] and [9]) NDisabled NEnabled
[4] Panic 1 alarm type NReport Only NAudible Alarm
[5] Panic 2 alarm type NReport Only NAudible Alarm
[6] Panic 3 alarm type NReport Only NFire Alarm
[7] Report Disarming Options NAlways report disarming NReport disarming only after alarm
[8] Always Force Arm When Regular Arming NDisabled NEnabled
SECTION [507]: Partition 1 Options
Option OFF ON
[1] Bell Squawk upon Disarming NDisabled NEnabled
[2] Bell Squawk upon Arming NDisabled NEnabled
[3] Bell Squawk upon Auto-Arming NDisabled NEnabled
[4] Bell Squawk during Exit Delay NDisabled NEnabled
[5] Bell Squawk during Entry Delay NDisabled NEnabled
[6] Bell Squawk upon Remote Arming/Disarming NDisabled NEnabled
[7] Ring Back: bell squawk if disarmed after alarm NDisabled NEnabled
[8] Ring Back: keypad beepsif disarmed after alarm NDisabled NEnabled
SECTION [508]*: Partition 1 Options
Option OFF ON
[1] One-Touch Regular Arming NDisabled NEnabled
[2] One-Touch Stay Arming NDisabled NEnabled
[3] One-Touch Instant Arming NDisabled NEnabled
[4] One-Touch Force Arming NDisabled NEnabled
[5] One-Touch Stay or Instant Disarming NDisabled NEnabled
[6] One-Touch Bypass Programming NDisabled NEnabled
[7] One-Touch Event Display NDisabled NEnabled
[8] No Exit Delay when arming with remote control NDisabled NEnabled
Table of contents