
3 Electrical connection
For installation of the electric cables,
you are required to observe the regula-
tions for electrical power systems ac-
cording to DIN VDE 0100 as well as
the regulations of your local power
supplier.
Use a suitable power supply which
guarantees that no dangerous voltages
from the system or parts of the system
reach the device in standard operation
or in the event of a fault.
Caution!
Only connect the device to the main
power network when the power is
switched off. Make sure the power
cannot be switched on unintentionally!
Particularly for 24 V, 50 Hz actuators,
use wires with a sufficiently large
cross-section to guarantee that the per-
missible voltage tolerances of
±
10 %
are not exceeded.
1. Establish electrical connection over the
cable entries (1.2 in Fig. 2) as illustrated
in Fig. 5 while observing the following
important instructions.
The control signals of the controller are con-
nected to the terminals eL and aL:
4If voltage is applied to eL, the actuator
motor retracts the actuator stem in oper-
ating direction "IN" (into the actuator).
4Voltage applied to aL causes the actua-
tor stem to extend in operating direction
"OUT" (out of the actuator).
Important instructions:
4The interference suppression capacitors
Ceinstalled in the output circuit of the
connected controllers may not exceed a
value of 2.5 nF, otherwise the proper
functioning of the actuator cannot be
guaranteed.
When actuators are to be connected to
controllers with larger interference sup-
pression capacitors, a special version is
available on request.
4Actuators operated in parallel must be
connected over separate contacts to pre-
vent the actuators hunting in the end po-
sitions due to a shared OPEN or
CLOSED contact.
4The 0 (2) to 10 V control signal must be
connected to the terminals 12 and 13,
whereas a 0 (4) to 20 mA control signal
must be connected to terminals 11 and
12 in versions with continuous-action
signal input.
4Do not connect more than two mA in-
puts in series.
4If more than two actuators are to be con-
nected to one controller, use 10 V inputs
and convert 20 mA signals into 10 V by
using resistors (RTotal = 500 Ω) connected
in parallel.
Use two-core cables for voltage supply,
signal input and output.
The “–“ inputs (terminals 12 and 32) can
be combined.
10 EB 5824 EN
Electrical connection