Isimet DLA Series Style 2 Installation manual

Application:
The DLA Series Style 2 Controller is a single circuit controller used to operate remotely located 12-vdc latching solenoids
for domestic water services in a Drug Testing Laboratory.
This unit is provided with ISIMET latching circuit boards that permit a 24-vac signal to latch the solenoids ON and OFF,
controlling the water supply to the restroom facility.
ISIMET DLA Controller
Drug Testing Labs
Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s)
Installation, Operations, Start-up and
Maintenance Instructions
Table of Contents:
Page
Warranty………………………………………………….. 2
Enclosure Specifications and Dimensions………………… 3
Styles……………………………………………………… 3
Model Number……………………………………………. 3
Mounting Instructions (Flush)….…………………………. 4
Mounting Instructions (Casework)..………………………. 4
Mounting Instructions (Surface Mount)..…………………. 4
Mounting the Wall Panel..………………………………… 4
Circuit Output Configurations………………………….…. 5
Monitoring Configurations………………………….…….. 5
Installing the Electrical Conduit…………………………... 6
Wiring the Unit……………………………………………. 6
Wiring Configurations.. …………………………………… 6
Operation of Unit………………………………………….. 7
Equipment Maintenance…………………………………… 7
October 2013
Meets all Standards for Canadian Industrial Control Panels

2
ISIMET DLA Series Utility Controller
Installation, Maintenance, Operations, and Startup Instructions
Copyright © 2013 ISIMET, LLC.
All rights reserved.
Patent 6,757,589 B1
6,990,393 B2
This document is copyrighted. This document may not, in whole or part, be copied, duplicated, reproduced,
translated, electronically stored, or reduced to machine readable form without prior written consent from ISIMET,
LLC.
Although the material contained herein has been carefully reviewed, ISIMET, LLC does not warrant it to be free of
errors or omissions. ISIMET reserves the right to make corrections, updates, revisions, or changes to the
information contained herein.
Warranty:
ISIMET will repair or replace any defective parts or workmanship of this product for a period of one year
from date of installation. The P.C. Board has a two year limited warranty. Damage caused by incorrect
installation or improper usage is not warranted. Failure to follow recommended installation, operation,
and/or maintenance procedures listed in this manual may void product warranty. Recovery rights shall be
limited to the total sum of the amounts paid for the product by the purchaser.
EXTENDED WARRANTY:
ISIMET will extend the warranty of this product to a period of two years from date of installation when
installation complies with all start up and routine maintenance procedures and Start up has been performed
by an authorized factory representative. Refer to Extended Warranty Policy.
Limits of Liability:
ISIMET's liability shall be limited to costs of repair or replacement parts. The Laboratory Service Panel and
Utility Controller are not intended for usage other than those expressly described in this manual. ISIMET
shall not be liable for damage or injury caused by the improper use of the product.
ISIMET does not warrant against or assume liability for failure of operation or lack of notification to
secondary integrated monitoring systems. The system should be thoroughly tested and adjustments made at
time of initial operation. Periodic testing should be conducted by the user to assure that all components
function and operate according to specifications.
Care should be taken in the installation of this product. ISIMET shall not be liable for damage or injury
caused from the improper installation of the product.
Warranty is Subject to Compliance with Specific Installation Requirements.
DISCLAIMER OF IMPLIED WARRANTY:
THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE DESCRIPTION HEREIN. SELLER
DISCLAIMS ANY IMPLIED WARRANTY OF MERCHANTABILITY OF THE GOODS OR OF THE
FITNESS OF THE GOODS FOR ANY PURPOSE, AND BUYER AGREES THAT THE GOODS ARE
SOLD “AS IS.”

3
Warranty is Subject to Compliance with Specific Installation Requirements.
Specifications:
Control Panel - Stainless Steel 16 gauge
8.375 X 16.50
Wall Box – 16 gauge powder coated sheet metal
6.0 X 14.25 X 4.0
* all dimensions are in inches
.
Style
# Output
Circuits
Trans-
former
Switch\
Breaker
pcb
Fuse 1
Output Rating
(standard)
Pulse Output
DLA -2 1 @ 24 vac 2 amp 5 amp 2 amp 2 amp @ 24 vac 2 @ 12 vdc
DLA -2 1 @ 24 vac 3 amp 5 amp 3 amp 2 amp @ 24 vac 4 @ 12 vdc
Output fuse on PCB, FUSE 1 is Slow Blow. PCB circuit fuse, FUSE 3 is 500 mA Fast Acting

4
Wall Panel Terminal Mounting Brackets (2)
Mounting
Screws
(4)
Mounting Instructions: Flush Wall Mount
Two mounting flanges with screws are provided with the
unit. Attach flanges as shown. Flanges can be affixed to
any two corners of the unit. Then, fasten unit between two
(2) wall studs. The face of the box should be even with the
face of finished wall surface. After mounting unit, protect
interior of box from construction debris.
CAUTION: Provided mounting hardware must be used.
Mounting Instructions: Casework Mount
Two mounting flanges with screws are provided with unit.
Holes are slotted to permit adjustments for variations in
cabinet material thickness. Attach flanges as shown in
figure above. Make cutout in desired location in casework
to permit wall unit to pass easily into opening. From within
the cabinet fit into opening and fasten unit to back of
casework. Face of wall box should be even with face of
cabinet. After mounting unit, protect interior of box from
construction debris.
CAUTION: Provided mounting hardware must be used.
Mounting Instructions: Surface Mount
In order to surface mount the unit, it is necessary to attach
the provided brackets to the rear of the housing. Care should
be taken to verify that the mounting means securely fastens
the unit to the wall surface. A stainless skirt is provided in
order to conceal the wall box from view.
CAUTION: Provided mounting hardware must be used
Mounting the Wall Panel:
•Verify that Unit is wired with junction box cover in
place.
•With the Door open, position the Wall Panel over the
Wall Box as shown.
•Holding panel in front of box, affix panel to box using
four (4) 8-32 stainless screws
•Close the panel and lock.
CAUTION! Do not install the panel until all wall finishes
are complete.
Output
Terminal
Wall

5
WARNING!! Other pcb Jumper placements
Jumpers at JP 1, JP 4 and JP 5 are factory placed in order to configure the circuit board to specific functions for the
Controller. Removal and/or re-placement may cause the unit to malfunction.
Figure 1:
Utilized when two (2) supply solenoids
are provided without drain-down valves.
Connect both supply valves to pins 4 & 5.
or
Utilize when one (1) supply and one (1)
drain-down solenoid is provided.
Connect supply valve to pins 4 & 5.
Connect drain-down to pins 6 & 7.
Figure 2:
Utilized when two (2) supply solenoids are
provided with two (2) drain-down valves.
Connect both supply valves to pins 4 & 5.
And both drain-down valves to pins 6 & 7.
Monitoring Circuit- JP3
Output Configuration Jumpers
@ Panic Output
1 jumper across center two posts
= dry-contact.
2 jumpers across each pair of posts
= 24-vac output

6
Installing the Electrical Conduit:
Knockout holes for connecting the electrical conduits are located at the top left and right of the Wall Box.
•Connect rigid conduit for the required 120-vac electrical service.
•Connect conduit for the operating power to the upper left top of the enclosure at the junction box.
•Connect conduit for the operating power for the output to the upper right top of the enclosure.
Wiring the Unit:
Important!
Verify that the electrical supply is disconnected prior to connecting wiring to the DLA Controller.
To wire the Controller:
1. Remove the junction box cover.
2. Make final connections to the 120-vac electrical service to wiring within the junction box. Verify that line
wiring (Black), neutral (White), and ground wire (Green) are correctly connected.
Minimum recommended wire size is 14 AWG.
3. Replace the junction box cover before activating or testing the unit.
Optional Input Control circuit:
Alarm Input: 24-vac/vdc active OFF. Refer to jumper configuration chart above. Make connection of this optional
wiring at CON 4.
Optional Remote Panic Input Connection:
An optional input from an ISIMET Remote Panic Assembly can be connected to the PCB at CON 4-a.
Optional Panic Output Terminal:
A configurable Panic output is activated at CON 5. See configuration chart and location of this connector
on page 5.
Connection of the Wall Panel Plug:
The Unit is equipped with a 9 pin d-sub connector
•Turn counter-clockwise the two retaining clips at the top of the Panel, and open.
•Insert plug onto circuit header on PCB.
•Turn Power ON.
•Close the panel and lock.
CAUTION! Do not install the panel until all wall finishes are complete. Verify that the plug is configured
correctly. Incorrect insertion will prevent operation of unit.
Important!
All local electrical codes must be followed when connecting the conduit to the service panel and making
wiring connections. Do not install wiring or cable for integrated systems, remote panic assemblies or other
interface wiring within conduit for either 24-vac control or 120-vac line voltage. Each wiring system
including outputs should be housed in independent conduit and not bundled with wiring for other systems.
Failure to comply with these wiring specifics may create transient voltage at the pc board and cause system
malfunction and/or failure.
Output Circuit Terminal:
The solenoids provided are ISIMET S-200 or S-220 Series General Service Brass Valves with 12 vdc coils.
These coils are polarized and must be connected correctly to the Output Terminal in order to function as intended.
Connect Supply Solenoids to the ‘ON w/Latch Terminals.
Connect Drain-down Solenoids (where provided) to the ON w/Un-Latch Terminals.
Make connections to ‘BLK’ and ‘WHT’ pins to match instructions provided with the solenoids that are similarly color coded.
Piping and wiring for solenoids should follow details provided with the solenoids.
Pins 1, 2, and 3 are provided for connection to an optionally provided 24v beacon. This beacon indicates whether the facility is
occupied or non-occupied.

7
Operation of the Unit:
With the panel service switch ON, engage the Key-switch. The circuit will activate and the panel Green LED will
illuminate to indicate that the water services to the testing restroom are active. After turning a switch OFF, it will be
necessary to re-engage the Key-switch in order to reactivate the services. The Red LED will illuminate when the
circuit is OFF.
Pressing the panic button will deactivate the services. All Panel lights should illuminate with Panic.
Once in the Panic Mode the Key-switch must be engaged in order to reactivate service. The Alarm Signal must be
withdrawn prior to reactivation.
This unit utilizes latching solenoids that pulse ON with circuit active to open the water supply and pulse OFF with
circuit inactive to close it. Where provided, secondary solenoid(s) are provided that pulse ON when inactive in
order to provide drain-down of supply piping.
Equipment Maintenance:
The DLA Series Controller should have semi-annual inspections.
ISIMET recommends that you periodically conduct a brief test of the system to verify that the output circuit
performs as intended.
If examination of the unit indicates tampering, ISIMET recommends that you first review the installation and
wiring portions of this manual prior to placing the unit in service.
ISIMET recommends that piping systems be thoroughly flushed and cleaned and tested for leaks prior to
placing the system into use. Periodic testing of these solenoids will assure that the piping system continues to
function properly.
If you have any questions regarding the operation and maintenance of the DLA Controller, please contact an
ISIMET Service Representative.
The enclosure has a NEMA 1 rating. It is not intended for use in wet areas. Exercise caution to prevent exposure of
the interior compartment of the enclosure to moisture. If moisture is present within the enclosure, ISIMET
recommends that the control switch be turned OFF, power be disconnected from the unit until the source of the
moisture is determined, and all moisture is removed from the compartment.
The electronic controller (PCB) is sensitive to dust and other air-borne particles. Do not expose the interior
compartment of the enclosure to dust. During the semi-annual inspection, if dust or other material is present,
ISIMET recommends that you remove all foreign matter before operating the unit.
If the Unit fails to operate, ISIMET recommends that you check the power supply to the unit. With the control
switch in the ON position, LED Fuse 1 should illuminate. If not, check the service breaker and PCB fuses.
If the fuse is not damaged and the unit still does not function, contact ISIMET or your local Service Representative.
CAUTION:
ISIMET DOES NOT recommend that service to emergency and/or safety devices, such as emergency
showers and eyewashes, be controlled by the DLA Controller System or Solenoids. Such devices are
intended to operate independent of restrictive authority operation, as is the case with the design of this unit.
ISIMET makes available components for the monitoring of such safety devices. Please contact ISIMET
regarding any questions regarding this type of application.

8
PO Box 129 (Mailing)
103 W. CJ Wise Pkwy
Naples, Texas 75568-0129
Phone (866) 897-0737
Fax (903) 897-0740
www.ISIMET.com
Innovative Systems
Integrating
Mechanical and Electrical
Technology
ISIMET believes that sole and local authority means that the primary operator or the
instructors should have the sole authority to start and stop the utility services within the
immediate area of use during normal usage. This should distinguish this type of operating
environment from that where a single emergency shut-down device is located remotely from
the areas of use.
Table of contents
Other Isimet Controllers manuals
Popular Controllers manuals by other brands

Shell
Shell NewMotion DPM Quick installation guide

Gewiss
Gewiss Chorus GW 10 766 manual

American Lighting
American Lighting TRULUX DMX 3Z Touch Control Installation instructions manual

Andover Controls
Andover Controls SCX 920 installation guide

Samson
Samson 4765 Mounting and operating instructions

Skyworth
Skyworth FILTOUCH WI-FI Use and installation manual