DIGIPRESSURE
DPC-HL SETTING METHOD
HPS
HPS
설
설정
정
HPS Input the setting value of high pressure
by pressing the button, to operate
alarm (26.0Kgf/cm2)
URL http:// www.digipressure.com
E-Mail :sales@digipressure .com FAX : 82-31-601-8600
TEL : 82-31-432-8843
Address: 414. KoFoMotechno center 1289-5.Jeongwang-dong, Siheung, Kyeonggi-Do Korea 429-450
Press 2buttons for 2 seconds simultaneously, and then the settin
Press 2buttons for 2 seconds simultaneously, and then the setting mode fixed.
g mode fixed.
LPS
LPS
설
설정
정
LPS Input the setting value of low pressure
by pressing the button, to operate
alarm (3.5Kgf/cm2)
LIF
LIF
설
설정
정
LIF Input the differential value of LPS
by pressing the button
(2.5Kgf/cm2)
Ldt
Ldt
설
설정
정
Ldt Input a delay time against output on the
status of low pressure by pressing
the button (0 ~100 sec)
H
H-
-A
A
설
설정
정
H-A Select the return mode with buttons
H: Hold (Manual) operation
A: Automatic operation
Add
Add
설
설정
정
Add Select the address by pressing the
button (0~255) for communication
by RS-485
End
End
설
설정
정
Press any button, and then the operation ends with
beep sound. If not, it returns to
the reset mode automatically
after 20 seconds.
SET L
SET L
설
설정
정
Press buttons for 3seconds at the same time
for correcting value of pressure to
fit ZERO“Never use while operating”
dPS
dPS
설
설정
정
DPS Input the differential value of dual
compressors by pressing button
to operate alarm (5.0 Kgf/cm2)
ddt
ddt
설
설정
정
ddt Input a delay time to operate alarm
for differential value by pressing
button(0 ~ 100 sec)
ddc
ddc
설
설정
정
ddc Input the type of differential pressure
“0”+ dp “1”-dp“2”±dp
(“0”, ”1”, ”2”)