manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Ditel
  6. •
  7. Transmitter
  8. •
  9. Ditel KOS1015 User manual

Ditel KOS1015 User manual

1.0 DESCRIPTION
This 4-20mA isolator can be configured to accept most of the common
voltage found in both commercial and industrial applications. The input is
fully isolated from the output circuit. The isolator range can be specified at
the time of order, but if required the user may re-range the transmitter to
ta new range. The isolator is housed inside a plastic enclosure, suitable
for DIN rail mounting. Screw terminals are providedfor wire connections.
The enclosure provides side entry access to coarse offset and span
adjusters and a range selector switch.
2.0 SPECIFICATIONS @ 20ºC
2.1 OUTPUT
TYPE Passive 2wire current output
RANGE 4 to 20mA (30mA MAX.)
PROTECTION Reverse connection plus overvoltage
VOLTAGE 10-30V DC
STABILITY Typical 100ppm/ºC
RIPPLE Lessthan40µA/V (Measured at 1V ripple 50Hz)
RESPONSE 200mS to reach 70% of final value
2.2 INPUT
TYPE Isolated DC voltage covered by six ranges;
Range Span Offset
020 to 200mV -20 to 80mV
10.2 to 1.0V -0.1 to 0.4V
21.0 to 5.0V -0.5 to 2.0V
45.0 to 25V -2.5 to 10V
825 to 48V -5 to 25V
F20 to 100V -10 to 40V
The above settings are capable of covering most
standard industrial ranges. Range F is provided to
allow for –10 to +10V inputs. Note VMAX IN is limited
to 48V DC for BSEN 61010-1 compliance.
ISOLATION 500V AC (Flash tested to 1kV DC)
IMPEDANCE >1MΩ
ACCURACY Typical linearity ±0.01%(0.05%maximum)
RANGE SELECTCoarse Settings, by side entry 16 setting position
rotary screw adjustement switches. Fine by front
access potentiometers. Range setting by side entry
rotary switch.
2.3 GENERAL
AMBIENT 0-50ºC ; 10-95% RH non-condensing
CONNECTION Captiveclampscrews
CABLE SIZE 4mm2solid / 2.5mm2stranded
3.0 INSTALLATION
IMPORTANT NOTE ¡
This isolator is not suitable for providing isolation from hazardous
voltages, such as mains supplies. It is intended for use in with low
voltage signals only.
3.1 MECHANICAL
This unit must be housed within a suitable enclosure that will provide
protection from the external environment, ensuring that the stated
temperature and humidity operating ranges are not exceeded. It is good
practice to mount the unit away from sources of electrical noise, such as
swichgear and transformers. The unit enclosure is designed to snap fit
onto a standard “TOP HAT” DIN rail. To remove from rail, apply pressure
at the bottom face at the back upwards the rail to release the spring clip
and tip away from the top. The unit may be mounted in any orientation
and stacked side by side along the rail. Span and offset fine adjustements
can be made from the front panel, whilst re-ranging the transmitter,
access to adjusters in the case side is requiered.
3.2 ELECTRICAL
Connections to the isolator are made via screw terminals. Wire protector
plates are provided inside each terminal. To maintain CE compliance
twisted pair (screened) cables are recommended. The correct type of wire
must be used for thermocouple inputs, mV inputs must use screened
copper wires, Incorrect sensor connection or sensor wire burnout will
result in the output current saturating up scale on standard units(optionally
downscale if requested at the time of the order).
It is good practice to ensure all 4-20mA signal loops are grounded at one
point. Care must be taken when designing a 4-20mA circuit to ensure that
the total burden of the loop, (that is the total voltage requirements of all
the equipment connected in the loop at 20mA) does not exceed the loop
powersupplyvoltage.
To operate correctly the isolator requires a minimum of 10V across its
output terminals.
The isolator is protected agains reverse connection and over voltage
Figure shows a typical 4-20mA circuit, the load resistor represents
equipment such as indicators, loggers, PLC etc.
KOS1015
DIN RAIL
ISOLATED
TRANSMITTER
kos1015manualB.doc
30727040
Sep.99
KOSMOS SERIES
WARRANTY
The instruments are warranted against defective materials and
workmanship for a period of three years from date of delivery.
If a product appears to have a defect or fails during the normal use
within the warranty period, please contact the distributor from which
you purchased the product.
This warranty does not apply to defects resulting from action of the
buyer such as mishandling or improper interfacing.
The liability under this warranty shall extend only to the repair of the
instrument. No responsability is assumed by the manufacturer for
any damage which may result from its use.
1. Connect the calibrator to input terminals, ensure polarity is
correct.Connect as above with mA meter in place of, or in series
with load Turn on and wait a few minutes before calibration, to
allow the transmitter to stabilise.
Let Va= input voltage for 4mA output
Vb= input voltage for 20mA output
2. Set calibrator to simulate Va, first rotate coarse offset to obtain a
output reading close to 4mA. Use fine adjuster to trim reading to
4mA±0.005mA. (if the trim hits end of travel re-adjust coarse
adjuster one step , re-adjust fine offset).
3. Set calibrator to simulate Vb, first rotate coarse span to obtain a
output reading close to 20mA. Use fine adjuster to trim reading to
20mA±
0.005mA. (if the trim hits end of travel re-adjust coarse
adjuster one step , re-adjust fine offset. Note clockwise rotation of
the coarse adjuster reduces output current)
4. Set calibrator to Va, adjust fine offset for 4.00mA ±0.005mA
5. Set calibrator to Vb, adjust fine span for 20.00mA±0.005mA
6. Repeat steps 4 and 5 until both points are in calibration.
7. Turn off power and remove wires. Mark isolator with the new
range
5.0 MECHANICALS DETAILS
DISEÑOS Y TECNOLOGÍA
Travessera de Les Corts, 180
08028 BARCELONA, Spain
Tel: +34 - 93 339 47 58
Fax: +34 - 93 490 31 45
e-mail: [email protected]
DITEL FRANCE, s.a.r.l.
Les Costes,D18
30360 CRUVIERS-LASCOURS,France
Tel: +33 -(0)4 66 542 770
Fax: + 33 -(0)4 66 542 771
e-mail: [email protected]
DITEL CORP.
379 Rye Beach Avenue
Rye, NY 10580, USA
Tel: +1 914-967 2957
Fax: +1 914-967 0658
e-mail: [email protected]
2.2 ENTRADA
4.0 RANGES
The isolator is normally suplied factory ranged but if required the range
can be changed by means of the range selection switch plus a sixteen
step coarse, and multi turn fine, offset and span adjusters, accessible
from the side of the housing.
The following equipment is required;
•PrecisionmV/V calibrator to simulateinput
•DC miliamp meter(digital); accuracy 0.05% on 0 to 20mA range
•Power Supply, 24V DC 30mA max.
•Trim tools
Decide on the range required and ensure the transmitter is capable of the
range. If a range has not been specified at time of order, the transmitter
will leave the factory set as 0-1V. Refer to the table below and set the
range selection switch to the correct position.
Switch Span Offset
020 to 200mV -20 to 80mV
10.2 to 1.0V -0.1 to 0.4V
21.0 to 5.0V -0.5 to 2.0V
45.0 to 25V -2.5 to 10V
825 to 48V -5 to 25V
F20 to 100V -10 to 40V

Other Ditel Transmitter manuals

Ditel KOS1605P User manual

Ditel

Ditel KOS1605P User manual

Ditel Kosmos series User manual

Ditel

Ditel Kosmos series User manual

Ditel Kosmos series User manual

Ditel

Ditel Kosmos series User manual

Ditel Kosmos series User manual

Ditel

Ditel Kosmos series User manual

Ditel Kosmos series User manual

Ditel

Ditel Kosmos series User manual

Ditel KOS206TC User manual

Ditel

Ditel KOS206TC User manual

Popular Transmitter manuals by other brands

Warner RF FMT5.0-2U Series manual

Warner RF

Warner RF FMT5.0-2U Series manual

Siemens SITRANS P DS III manual

Siemens

Siemens SITRANS P DS III manual

Festo SDAT-MHS operating instructions

Festo

Festo SDAT-MHS operating instructions

ProComSol HM-APL-PCB user manual

ProComSol

ProComSol HM-APL-PCB user manual

Electia CS185 user guide

Electia

Electia CS185 user guide

Salcom 20-62 product manual

Salcom

Salcom 20-62 product manual

Emergency Caller Products LT-900 user manual

Emergency Caller Products

Emergency Caller Products LT-900 user manual

Varec 7532 Installation and operation manual

Varec

Varec 7532 Installation and operation manual

Endress+Hauser Proline 300 Brief operating instructions

Endress+Hauser

Endress+Hauser Proline 300 Brief operating instructions

FISCHER DE38D410 instruction manual

FISCHER

FISCHER DE38D410 instruction manual

Cooper Security Scantronic 735r manual

Cooper Security

Cooper Security Scantronic 735r manual

PR electrinics 2271V101-IN manual

PR electrinics

PR electrinics 2271V101-IN manual

GF Signet 9950 operating instructions

GF

GF Signet 9950 operating instructions

Marshall Amplification RT user guide

Marshall Amplification

Marshall Amplification RT user guide

BAPI H200 Installation and operating instructions

BAPI

BAPI H200 Installation and operating instructions

Emerson Rosemount 1208C quick start guide

Emerson

Emerson Rosemount 1208C quick start guide

Fox Micron TXR Plus operating instructions

Fox

Fox Micron TXR Plus operating instructions

United Electric Controls TX200 Installation & maintenance instructions

United Electric Controls

United Electric Controls TX200 Installation & maintenance instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.