18205
LT-2519 21343
INTRUSION • FIRE• ACCESS• NETWORKS
2500 North Partnership Boulevard
Springfield, Missouri 65803-8877
Domestic: 800.641.4282 | International: 417.831.9362
DMP.com
© 2021
LED Operation
LED COLOR LED BEHAVIOR MEANING
None None No power or LED not connected
Yellow Spinning Powering on
Yellow Steady Connected to power, ready for enrollment
White Steady Enrolled, waiting for credential
Blue Spinning Searching for credential
Green Flash Access Granted
SR3 Installation and Programming Guide | Digital Monitoring Products 15
Specifications
Operating Voltage 12VDC
Current Draw 100 mA typical at 12 VDC
135 to 155 mA max at 12VDC
Read Range Adjustable, range 3.0 in to 30 ft (7.62 cm to 9.14 m)
Operating Temperature -27 °F to 151 °F (-33 °C to 66 °C)
Recommended Humidity 85% RH or lower, non-condensing
IP Rating IP65
Dimensions 6.0” x 1.7” x 1.3” (15.24 cm x 4.32 cm x 3.30 cm)
Weight 0.5 lb (0.23 kg)
Compliance Requirements
Wiring and Power
▶Connections must be made in accordance with NFPA 70: Do not connect to a receptacle controlled by a switch
▶Shield must run continuously from the reader to the panel
▶The reader ground, shield line, and earth ground must be connected to a single point at the panel
▶To avoid creating a ground loop, do not ground the shield line at the reader
▶Minimum wire gauge is 24 AWG with a maximum single wire run length of 500 ft (150 m)
UL 294
For UL 294 Compliance, the readers shall be connected to a class two power limited power supply or control panel
output.
Certifications
▶FCC Part 15 RFID Reader FCC ID: 2ANJI-SR3
▶Industry Canada ID: 10727A-SR3
Underwriters Laboratory (UL) Listed
ANSI/UL 294 Access Control System Units
Level I Destructive Attack, Line Security, Standby Power
Level III Endurance
Mobile Device and Software Requirements
▶The SR3 uses BLE Version 4.2 or higher
▶Android devices with Version 8.0 (Oreo) or higher and Bluetooth enabled
▶iOS devices with Version 10.0 or higher and Bluetooth enabled
▶Tech APP (Version 2.15.0 or higher) and Virtual Keypad (Version 6.35.0or higher)
▶Compatible with Mobile Credentials and 125 kHz proximity credentials
SR3 Installation and Programming Guide | Digital Monitoring Products 6
STEP 2: ENROLL & ASSOCIATE THE READER
A technician on site must associate each reader with a system before mobile credentials can be purchased in Dealer
Admin by an Administrator.
Note: For XR Series panels with 734 Series Access Control Modules, ensure Program 734 Options is turned on and
Card Options is set to Custom in Device Setup before proceeding.
1. Stand at the reader and ensure your device has Bluetooth turned on.
2. Open Tech APP, then find and open the appropriate system.
3. Tap the Bluetooth Readers tile.
4. Tap Add. Name the reader, then tap Create.
5. When prompted, touch your device to the reader. When paired successfully, the reader beeps.
6. In Tech APP, open the reader you added. Use the slider to adjust the Reader Range closer or farther as needed.
Range is 3in to 30ft (7.62 cm to 9.14 m).
7. To update the reader’s firmware, go to Firmware and tap Update. If no new firmware is available, this button is not
displayed.
8. Tap Save.
After being enrolled and associated, the reader’s LED changes from steady yellow to steady white.
If you receive a message that states the 56-bit card format cannot be added, you must add the format manually in Full
Programming > Device Setup > Card Formats. For more information, refer to “56-Bit Card Format”.
56-Bit Card Format
NAME WIEGAND CODE
LENGTH
SITE CODE
POSITION
SITE CODE
LENGTH
USER CODE
POSITION
USER CODE
LENGTH
USER CODE
DIGITS
BLUETOOTHFORMAT 56 1 16 17 34 10
Configuring the Reader in Tech APP
Enroll & Associate the Reader in Tech APP