Domus Bluebrain User manual

VENTILATION
LAB1306R, Issue 1, March 2018 Page 1
SPR418
Bluebrain Controller
Installation and
Operating Instructions
It is important to follow the advice in this manual and
correctly maintain the system to ensure a healthy
indoor environment.

VENTILATION
LAB1306R, Issue 1, March 2018 Page 2
Warnings & Safety Information
IMPORTANT! PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE
COMMENCING INSTALLATION
1. Do not install this appliance in areas where the following may be present or occur:
•Pollution degree 3 or 4 (as defined in EN 60335-1)
•Excessive oil or a grease laden atmosphere
•Corrosive or flammable gases, liquids or vapours
•Be subject to direct water spray
•Ambient temperatures higher than 50ºC and lower than -25ºC
•Possible obstructions that may hinder access or removal of the unit
2. This fan can be used by children aged from 8 years and above and persons with reduced
physical, sensory or mental capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning use of the appliance in a safe way and understand
the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision.
3. All wiring must be in accordance with the current IEE Wiring Regulations BS7671. The
electrical installation should be inspected and tested by a suitably qualified person after
completion.
4. The appliance should be provided with a local double pole fused spur fitted with a 3Amp fuse
and a minimum contact separation of at least 3mm.
5. Ensure that the mains supply (Voltage and Frequency) complies with the rating label.
6. This appliance must be earthed.
7. When installing the appliance, care should be taken not to damage any hidden utilities.
8. The installer is responsible for the installation and electrical connection of the Bluebrain
Controller on site. It is the responsibility of the installer to ensure that the equipment is safely and
securely installed and left only when electrically and mechanically safe.
9. All regulations and requirements must be strictly followed to prevent hazards to life and
property, both during and after installation and any subsequent servicing or maintenance.

VENTILATION
LAB1306R, Issue 1, March 2018 Page 3
Page 16
1.0 User control interface operation
User control interface
front view
User control interface
back view
Page 17
Thermal bypass active
Half hour time switch segments
Date
Programme number
Frost protection active
Intake temperature
Exhaust temperature
Humidity level
Speed
Time
Day
Filter check
reminder
Day
1.1 Time and date setting (this action is required when power is first applied to the system):
From the home screen, Press “DAY”. The hour text will flash
Use the “+” and “-“ buttons to set the hour
Press “DAY”. The minute text will flash
Use the “+” and “-“ buttons to set the minute
Press “DAY”. The day will flash
Use the “+” and “-“ buttons to set the day
Press “DAY”. The month will flash
Use the “+” and “-“ buttons to set the month
Press “DAY”. The year will flash
Use the “+” and “-“ buttons to set the year
Press “DAY”. 12/24 will flash
Use the “+” and “-“ buttons to set 12 or 24 hour clock format
Press “DAY” to confirm and return to home screen
12:00
1234567
60%
Low
Boost
Max
Frost
Filter
p9
28-01-2016
00
06
12
18
24
Bypass
21
.0
8
.0
°C °C

VENTILATION
LAB1306R, Issue 1, March 2018 Page 4
Page 16
1.0 User control interface operation
User control interface
front view
User control interface
back view
Page 17
Thermal bypass active
Half hour time switch segments
Date
Programme number
Frost protection active
Intake temperature
Exhaust temperature
Humidity level
Speed
Time
Day
Filter check
reminder
Day
1.1 Time and date setting (this action is required when power is first applied to the system):
From the home screen, Press “DAY”. The hour text will flash
Use the “+” and “-“ buttons to set the hour
Press “DAY”. The minute text will flash
Use the “+” and “-“ buttons to set the minute
Press “DAY”. The day will flash
Use the “+” and “-“ buttons to set the day
Press “DAY”. The month will flash
Use the “+” and “-“ buttons to set the month
Press “DAY”. The year will flash
Use the “+” and “-“ buttons to set the year
Press “DAY”. 12/24 will flash
Use the “+” and “-“ buttons to set 12 or 24 hour clock format
Press “DAY” to confirm and return to home screen
12:00
1234567
60%
Low
Boost
Max
Frost
Filter
p9
28-01-2016
00
06
12
18
24
Bypass
21
.0
8
.0
°C °C

VENTILATION
LAB1306R, Issue 1, March 2018 Page 5
Page 18
1.2 Pre-commissioning
The following steps inhibit automatic functions that could affect the commissioning
process and need to be carried out prior to commissioning:
Set the time and date – see 1
From the home screen, press “PROG”
Use the “+” and “-“ buttons to set the programme number to ‘P9’ (Factory default is P9)
Press “SET”
From the home screen, press and hold “SET” and “COPY” simultaneously for 3 seconds
This action allows access to the ‘Installer’ programming level (opens at menu 1)
Press “COPY” twice to move to ‘Menu 3’ ‘Bypass tEnp’
Use the “+” or “-“ button to set to ‘off’ (OF)
This action inhibits the automatic bypass operation
Press “COPY” four times to move to ‘Menu 7’ ‘IhuN’
Use the “+” or “-“ button to set to ‘off’ (OF)
This action inhibits the automatic humidity controlled boost operation
Press “SET” to return to the home menu
1.3 Commissioning (see also section 4.0 Ventilation Commissioning)
Use the “+” or “-“ button to set speed function to ‘Boost’
From the home screen, press and hold “SET” and “COPY” simultaneously for 3 seconds
to open the installer level
Press “COPY” once to move to ‘Menu 2’ ‘Fan 1 Low’
Press “PROG” once to ‘Fan 1 Boost’ (Extract/Exhaust fan)
Use the “+” or “-“ button to set the desired speed (Factory default speed is 50%)
Note: The installer level access will time out after 1 minute of inactivity but will record any
changes made to the settings
Press “SET” to record the settings and return to the home screen
Press “ESC” to discard the settings and return to the home screen

VENTILATION
LAB1306R, Issue 1, March 2018 Page 6
Page 19
Repeat the steps above for:
Fan 2 Boost (Supply/Intake fan) (Factory default speed is 50%)
Fan 1 Low (Extract/Exhaust fan) (Factory default speed is 20%)
Fan 2 Low (Supply/Intake fan) (Factory default speed is 20%)
‘Max’ speed can be set to a maximum of 99% (Factory default 80%)
Note: Low speed cannot be set higher than Boost speed and Boost speed cannot be set
higher than Max speed
Press “SET” to record or “ESC” to discard the settings and return to the home screen
1.4 Automatic heat exchanger bypass activation/inactivation (for adjustment see 5.10)
From the home screen, press and hold “SET” and “COPY” simultaneously for 3 seconds
Press “COPY” as required to move to ‘Menu 3’ ‘Bypass tEnp’
Use the “+” or “-“ button to set to ‘on’ or ‘off’ (OF) as required
Press “SET” to record or “ESC” to discard the settings and return to the home screen

VENTILATION
LAB1306R, Issue 1, March 2018 Page 7
Page 20
1.5 Automatic humidity controlled boost activation/inactivation (for adjustment see 5.12)
From the home screen, press and hold “SET” and “COPY” simultaneously for 3 seconds
Press “COPY” as required to move to ‘Menu 7’ ‘IhuN’
Use the “+” or “-“ button to set to ‘on’ or ‘off’ (OF) as required
Press “SET” to record or “ESC” to discard the settings and return to the home screen
1.6 Filter reminder adjustment/inactivation
From the home screen, press and hold “SET” and “COPY” simultaneously for 3 seconds
Press “COPY” as required to move to ‘Menu 1’ ‘Filter’
Use the “+” or “-“ buttons to change the time delay in steps of 50 hours as required or ‘off’.
Note: The filter check reminder is factory set at the maximum of 3000 hours (approx.
4months - recommended). During adjustment, when this maximum has been reached, the
‘off’ option can be accessed.
Press “SET” to record or “ESC” to discard the settings and return to the home screen
1.7 Frost protection trigger temperature adjustment
From the home screen, press and hold “SET” and “COPY” simultaneously for 3 seconds
Press “COPY” as required to move to ‘Menu 4’ ‘T5’
Menu T5 sets the frost protection trigger temperature between -15°C and +5°C (Factory
default +1°C)
Use the “+” or “-“ buttons to set the trigger temperature in steps of 1°C

VENTILATION
LAB1306R, Issue 1, March 2018 Page 8
Page 21
Press “SET” to record or “ESC” to discard the settings and return to the home screen
1.8 Delay-on timer activation/deactivation
From the home screen, press and hold “SET” and “COPY” simultaneously for 3 seconds
Press “COPY” once to move to ‘Menu 5’ ‘Delay-on setting’
The Delay-on setting provides a 3 minute delay before Boost speed is engaged
Use the “+” or “-“ button to set to ‘on’ or ‘off’
Note: The Delay-on function will always be overridden by automatic humidity sensing
Press “SET” to record or “ESC” to discard the settings and return to the home screen
1.9 Delay-off timer activation/deactivation
From the home screen, press and hold “SET” and “COPY” simultaneously for 3 seconds
Press “COPY” once to move to ‘Menu 6’ ‘Delay-off setting’
The Delay-off setting provides an adjustable run-on timer when Boost speed is engaged –
adjustable between 5 and 30 minutes or ‘off’
Use the “+” or “-“ button to set the desired run-on time in 1 minute steps (Factory default is
off)

VENTILATION
LAB1306R, Issue 1, March 2018 Page 9
Page 22
Press “SET” to record or “ESC” to discard the settings and return to the home screen
1.10 Setting the automatic heat exchanger bypass operating temperature (for activation see
1)
From the home screen, press “TEMP” as required to move to menu ‘T3’
T3 is the target indoor temperature setting at which the heat exchanger bypass
mechanism operates to allow the extract air to bypass the heat exchanger and is
adjustable between +15°C and +25°C (Factory default 20°C)
Use the “+” or “-“ buttons to set the operating temperature in steps of 1°C
Press “SET” to record or “ESC” to discard the settings and return to the home screen
1.11 Setting the optional duct-heater operating temperature (°C)
From the home screen, press “TEMP” as required to move to menu ‘T4’
T4 is the outdoor temperature setting at which an optional intake air duct-heater switch
can be activated and is adjustable between +5°C and +12°C (Factory default 10°C)
Use the “+” or “-“ buttons to set the activation temperature in steps of 1°C
Press “SET” to record or “ESC” to discard the settings and return to the home screen

VENTILATION
LAB1306R, Issue 1, March 2018 Page 10
Page 23
1.12 Setting the humidity activated boost switching level (%RH) (for activation see 5.5)
From the home screen, press “HUM” to move to the humidity (% RH) activated boost
setting (Factory default 60% RH – recommended)
Use the “+” or “-“ buttons to set the humidity switching level in steps of 1% RH (range 30-
85%RH)
Press “SET” to record or “ESC” to discard the settings and return to the home screen
1.13 Programming
From the home screen, press “PROG” (The programme number will flash in the bottom
left hand corner; P1 to P9
Use the “+” and “-“ buttons to view the selected programme number (Factory default is P9)
The pre-programmed Thermal bypass programmes are shown in the diagram on page 18
Note: Each square has a time value of 30 minutes. Black squares indicate a time period
where the unit is in automatic bypass mode i.e. the unit will monitor the temperatures and
open or close the bypass accordingly. White squares (blank spaces) indicate a time block
where the heat exchanger bypass will be permanently set to operate and divert air around
the heat exchanger regardless of the measured and set temperatures.
Each of the programmes can be edited to create bespoke programmes as follows:
From the home screen, press “PROG”
Use the “+” and “-“ buttons to select the programme number (Factory default is P9)
Press “PROG”. The programme number will stop flashing and the first block on the
timeline at the bottom of the screen will begin to flash.
Select the day to be edited by pressing “DAY” until the correct day is displayed along the
top of the screen (1 – Monday, 2 – Tuesday etc.)
To add a 30 minute temperature controlled bypass block (a black square) to the timeline,
ensure that the word “BYPASS” is displayed on the screen by pressing “BYPASS”.

VENTILATION
LAB1306R, Issue 1, March 2018 Page 11
Page 24
Press the “+” and “-“ buttons to move along the timeline at the bottom of the screen; a
block will be added to each position.
To remove a block, remove the word “BYPASS” from the screen by pressing “BYPASS”
and press the “+” and “-“ buttons to move along the timeline at the bottom of the screen; a
block will be removed from each position.
Daily ‘timeline patterns’ can be copied to another day or multiple days to avoid
programming each day individually.
From the home screen, press “COPY”
Select the day to copy by pressing “PROG” (the day number will be displayed) and then
the day to copy-to by pressing the “+” and “-“ buttons (the day number will flash). When
the two correct days have been selected, press “COPY” and the timeline pattern will copy
across.
Press “SET” to record
Filter reminder
The word ‘Filter’ will appear on the home screen after the set time has elapsed. When this
occurs, clean the filters (see section 6)
Note: The figure at the bottom of the screen indicates elapsed operating time in hours.
When the numbers are not flashing, they indicate the elapsed time since the last filter
reset. If “DAY” is pressed, the numbers will flash and indicate the total elapsed operating
time in hours.
To reset the filter elapsed time reminder following cleaning, press and hold “SET” for 5
seconds.

LAB1199R, Issue 4, Apr 2017 Page 24
5.15 Default interface factory settings
P1
t3 - 20°C
t4 - 10°C
Humidity – 60%
Filter – 3000 hours
Fan 1 – Low 20%
Fan 1 – Boost 50%
Fan 1 – Max 80%
Fan 2 – Low 20%
Fan 2 – Boost 50%
Fan 2 – Max 80%
Bypass temp – off
T5
Delay-on – off
Delay-off – off
Hum - on
LAB1199R, Issue 4, Apr 2017 Page 9
Filter access
2.0 Installation
2.1 Overview
2.1.1 The following instructions are intended to help prevent hazards. Installation should only be
carried out by a qualified electrician and competent persons in clean, dry conditions where
dust and humidity are at minimum levels
Note: we advise installers to fix all mains, switch and sensor wiring (in accordance with the
latest edition of the Wiring Regulations) prior to fixing the HRX-aQ unit in position
2.2 Preparation
2.2.1 When accepting delivery of the appliance, inspect for transit damage. If in doubt, call our
Customer Service Team on 03443 715523
2.2.2 The HRX-aQ appliance can be fitted directly to a concrete ceiling or suitable horizontal
timber support
2.2.3 Appropriate screw fixings to suit the support medium will need to be supplied by the
installer. The built-in mounts suit 4 x 4mm (No.8) pan head screws
2.2.4 Important: Ensure that there is sufficient space for access to the wiring centre (cover
removal), the condensation fittings and ductwork
2.2.5 Ensure that there is sufficient space below the appliance to access the filters and for
carrying out any future maintenance on the appliance
2.2.6 When viewed from below, the filter access and duct configuration is as shown on the
diagram below:
V E N T I L A T I O N
V E N T I L A T I O N
LAB1306R, Issue 1, March 2018 Page 12

LAB1199R, Issue 4, Apr 2017 Page 8
1.2 Physical specification
‘200’ models – net weight 7.9kg Rating: ‘-S’ 230V 50Hz 55W (0.54A) ‘-B’ 230V 50Hz
59W (0.54A)
‘240’ models – net weight 8.4kgRating: ‘-S’ 230V 50Hz 55W (0.54A) ‘-B’ 230V 50Hz 59W
(0.54A)
1.3 Main features
1.3.1 Thermal bypass
1.3.1.1 The AQH200-B and AQH240-B models are fitted with a fully automatic 100% heat
exchanger bypass mechanism. Time clock control and manual override are also
available
1.3.1.2 In automatic mode, the bypass will open when the indoor target temperature reaches a
pre-set value. Using the interface, the trigger temperature can be set between +15°C and
25°C
1.3.1.3 The interface contains an optional frost protection system. During periods of very cold
weather, the fresh air supply fan will automatically reduce in speed to approximately 20%
of its commissioned setting to reduce the load on your heating system and avoid
possible freezing of the heat exchanger. During these periods, the extract fan will
increase in speed to its commissioned boost speed to maintain an even air pressure.
Using the interface, the trigger temperature can be set between -15°C and +5°C
LAB1199R, Issue 4, Apr 2017 Page 25
V E N T I L A T I O N
V E N T I L A T I O N
LAB1306R, Issue 1, March 2018 Page 13

LAB1199R, Issue 4, Apr 2017 Page 26
6.0 Maintenance
6.1 Routine maintenance
6.1.1 The two appliance G3 filters should be cleaned on a regular basis, the exact frequency will
be determined by individual living conditions.
6.1.2 The word ‘FILTER’ will appear on the home screen of the digital user-interface after the
set time has elapsed – when this occurs, clean the filters – see 5.1.4 for resetting details.
6.1.3 Before cleaning the filters, turn off the appliance at the isolator switch.
6.1.4 To remove the two filters, pull out the two caps from the front of the appliance and gently
slide out the filters in their carrier frames.
6.1.5 Lightly vacuum the filters to remove surface debris and then gently wash through in warm
soapy water. Ensure that the filters are completely dry before refitting. Important: do not
dry on a radiator or use excessive heat as this may distort the carrier frames.
7.0 Faults
7.1 Fault finding
Caution - the electrical supply to the unit and from any external triggers into the unit must
be isolated before removing covers to electrical connections.
Fault
Checks and possible solutions
Nothing displayed on the
controller LCD screen
•
Check there is power connected to the unit.
Presence of an orange light visible from
outside the white wiring centre box will
indicate this.
•Check the electrical connections between
VCC (on controller) and 5V (on PCB)
•Check the electrical connections between
GND (on controller) and GND (on PCB)
‘Unconnect’ displayed on the
controller LCD screen
•
Check the electrical connections between TD
(on controller) and RXD (on PCB)
•Check the electrical connections between RX
(on controller) and TXD (on PCB)
‘Fail’ displayed on the
controller LCD screen
•
If relevant, check with the building
management services team if the external
inhibit function has been activated
•If connected, check the smoke detector isn’t
activating the external inhibit function
•If no external inhibit control is connected,
check there is a link wire present between the
two terminals of the external inhibit connection
on the main PCB
•Check the electrical connections of the
aforementioned link wire between the two
terminals of the external inhibit on the main
PCB
LAB1199R, Issue 4, Apr 2017 Page 7
•297 dry-trap and condensate drainage kit
V E N T I L A T I O N
V E N T I L A T I O N
LAB1306R, Issue 1, March 2018 Page 14

LAB1199R, Issue 4, Apr 2017 Page 27
‘Fail (fan 1)’ displayed on the
controller LCD screen
•
Check the electrical connections for fan 1 on
the main PCB. There are four connections at
the top of the board for control and three at
the bottom of the board for power
•By removing the exhaust duct connection,
check there is nothing obstructing fan 1
‘Fail (fan 2)’ displayed on the
controller LCD screen
•
Check the electrical connections for fan 2 on
the main PCB. There are four connections at
the top of the board for control and three at
the bottom of the board for power
•By removing the supply duct connection,
check there is nothing obstructing fan 2
Little or no air is extracting or
supplying through the room
valves
•
Check that the filters have been removed from
the pre-commissioning protective covers
•Check that the filters are not blocked
•Check that the system has been
commissioned correctly
•By removing the exhaust and supply duct
connections check there is nothing obstructing
the fans
The unit is excessively noisy
•
Check that the system has been
commissioned correctly
•By removing the exhaust and supply duct
connections check there is nothing obstructing
the fans
7.2 If the fault/faults cannot be resolved using the table in section 7.1, contact the Domus
Ventilation Customer Service Team on 03443 715523.
LAB1199R, Issue 4, Apr 2017 Page 6
1.1 Overview
1.1.1 The HRX-aQ appliance is a key part of a whole house ventilation system
specifically designed to improve indoor air quality in dwellings. The system is designed to
provide measured amounts of filtered, fresh air to living areas while constantly removing
polluted, stale air from bathing, cooking and washing areas at the same gentle rate. Any
available heat in the outgoing stale air is recovered by a built-in heat exchanger and used
to pre-warm the fresh supply air
1.1.2 A programmable user interface is provided to thereby maintaining a comfortable indoor
environment and includes the following features:
•Time and date functions
•Independent fan control adjustable at three levels; Low, Boost, Max
•Programmable filter check reminder
•Programmable 100% Thermal bypass
•Optional 3 minute delay-on boost switching
•Optional 5 to 30 minute delay-off boost switching
•Optional programmable frost protection
•Programmable humidity level boost switching
•Temperature controlled switching available for optional duct heater (supplied
by others)
•Elapsed runtime meter
1.1.3 The boost facility can also be triggered from a lighting circuit; contacts to accommodate
external sensors or switches are also available (see page 10)
1.1.4 The G3 filters in the appliance ensure that the fresh supply air is clean as it enters the
home. Additionally, the stale extract air is filtered to protect the heat exchanger from
unwanted contamination. These filters have to be cleaned regularly, depending on the
levels of pollution. The filters should be replaced when they start to show visible signs of
wear
1.1.5 This product is listed in the NCM PCDB, (was SAP Appendix Q) therefore, part of the
installation process requires that an installation checklist is completed and submitted to
the Building Control Body (BCB). Blank checklists are available at http://www.ncm-
pcdb.org.uk/sap/filelibrary/pdf/Check_Lists/Domestic_Ventilation_Compliance_Guide_201
0_-_Checklist_(extract).pdf
1.1.6 Pack includes:
•Domus HRX-aQ appliance
•Ventilation user-control centre
•4m length of 4 core signal cable (to connect AQH wiring centre and user-control)
•Installation and operating instructions manual
•Householders operating manual
•ErP label and data fiche
1.1.7 Ancillary items as required:
•204x60mm rectangular rigid duct system or,
•Ø125mm rigid duct system or,
•Radial duct system
•Thermal duct insulation
V E N T I L A T I O N
V E N T I L A T I O N
LAB1306R, Issue 1, March 2018 Page 15

LAB1280R, Issue 2, Apr 2017 Page 30
Installer contact details:
Company name:
Contact name:
Tel:
Email:
Notes :
Tel: +44 (0)3443 715523
Web: www.domusventilation.co.uk E&OE
LAB1280R, Issue 2, Apr 2017 Page 1
HRXD
With Bluebrain controller
Mechanical Ventilation with Heat Recovery appliance
Installation and Operating Instructions
Model: HRXD
DO NOT SWITCH OFF THE UNIT – it is designed to run continuously. If the
unit is switched off, indoor pollutants and moisture levels may increase
which could endanger your health or damage your home.
It is important to follow the advice in this manual and correctly maintain the
system to ensure a healthy indoor environment.
VENTILATION
VENTILAT IO
N
Domus Ventilation
Cambria House
Caerphilly Business Park
Van Road
Caerphilly
CF83 3ED
Tel: +44 (0)3443 715523
Fax: +44 (0)3443 715524
Email: [email protected]
www.domusventilation.co.uk
LAB1306R, Issue 1, March 2018 Page 16
This manual suits for next models
1
Other Domus Controllers manuals
Popular Controllers manuals by other brands

Spirax Sarco
Spirax Sarco MPC1 Installation and maintenance instructions

FAAC
FAAC E124S Translation of the original instructions

Vega
Vega VEGATOR 132 operating instructions

Microchip Technology
Microchip Technology USB2422 General description

Panasonic
Panasonic FP0R Series user manual

Weathermatic
Weathermatic smartline SL800 owner's manual