manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. DSE
  6. •
  7. Switch
  8. •
  9. DSE 7560 User manual

DSE 7560 User manual

Other DSE Switch manuals

DSE DSE103 MKII User manual

DSE

DSE DSE103 MKII User manual

DSE 335 User manual

DSE

DSE 335 User manual

Popular Switch manuals by other brands

SMC Networks SMC6224M Technical specifications

SMC Networks

SMC Networks SMC6224M Technical specifications

Aeotec ZWA003-S operating manual

Aeotec

Aeotec ZWA003-S operating manual

TRENDnet TK-209i Quick installation guide

TRENDnet

TRENDnet TK-209i Quick installation guide

Planet FGSW-2022VHP user manual

Planet

Planet FGSW-2022VHP user manual

Avocent AutoView 2000  AV2000BC AV2000BC Installer/user guide

Avocent

Avocent AutoView 2000 AV2000BC AV2000BC Installer/user guide

Moxa Technologies PT-7728 Series user manual

Moxa Technologies

Moxa Technologies PT-7728 Series user manual

Intos Electronic inLine 35392I operating instructions

Intos Electronic

Intos Electronic inLine 35392I operating instructions

Cisco Catalyst 3560-X-24T Technical specifications

Cisco

Cisco Catalyst 3560-X-24T Technical specifications

Asante IntraCore IC3648 Specifications

Asante

Asante IntraCore IC3648 Specifications

Siemens SIRIUS 3SE7310-1AE Series Original operating instructions

Siemens

Siemens SIRIUS 3SE7310-1AE Series Original operating instructions

Edge-Core DCS520 quick start guide

Edge-Core

Edge-Core DCS520 quick start guide

RGBLE S00203 user manual

RGBLE

RGBLE S00203 user manual

Thrustmaster FLIGHT SIMULATOR X quick guide

Thrustmaster

Thrustmaster FLIGHT SIMULATOR X quick guide

Southwire SURGE GUARD 41390 RVC troubleshooting guide

Southwire

Southwire SURGE GUARD 41390 RVC troubleshooting guide

Buhler Nivotemp NT 61 Brief instructions

Buhler

Buhler Nivotemp NT 61 Brief instructions

Kramer VS-41HDCP user manual

Kramer

Kramer VS-41HDCP user manual

Techly IDATA AU-270 user manual

Techly

Techly IDATA AU-270 user manual

Belkin F1U109 user manual

Belkin

Belkin F1U109 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

DEEP SEA ELECTRONICS
7560 INSTALLATIO N INSTRUCTIONS 053-054
ISSUE 4
ACCESSING THE FRONT PANEL CONFIGURATION EDITOR
.
•Press the Stop/Reset and Info buttons simultaneously.
•If a module security PIN has been set, the PIN number request is then
shown :
•Press
(up) or
(down) to adjust it to the correct value.
•Press (right) when the first digit is correctly entered. The digit you have just entered will now
show ‘#’ for security.
•
Repeat this process for the other digits of the PIN number. You can press
(left) if you need to
move back to adjust one of the previous digits.
•
When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is
not correct, you must re-enter the PIN.
•
If the PIN has been successfully entered (or the module PIN has not been
enabled), the editor is displayed :
EDITING A PARAMETER
•Enter the editor as described above.
•Press the left or right buttons to cycle to the section you wish to view/change.
•To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that
you are editing the value.
•Press the up
or down
buttons to change the parameter to the required value.
•Press to save the value. The parameter ceases flashing to indicate that it has been saved.
•To exit the editor at any time, press the button.
Deep Sea Electronics Plc.
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303
LO CALL (from UK BT landlines) :
Telephone 0845 260 8933
Email: [email protected]
Web:
www.deepseaplc.com
Deep Sea Electronics inc.
Phone: +1 (815) 316-8706
Fax: +1 (815) 316- 8708
TOLL FREE (USA only) : Tel: 1 866 636 9703
Email: [email protected]
Web: www.deepseausa.com
Deep Sea Electronics Plc.
(Far East)
Tel:+66 (0) 2191 8052
Fax: +66 (0) 81805 5625
Email: [email protected]
Web: www.deepseaplc.com
NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to
ensure security.
NOTE: The PIN number is automatically reset when the editor is exited (manually or
automatically) to ensure security.
NOTE: More comprehensive module configuration is possible using the 75xx series PC
configuration software. Please contact us for further details
NOTE: The contents of the tables overleaf may differ depending on the actual module
configuration.
TYPICAL WIRING DIAGRAM
ADJUSTABLE PARAMETERS.
Front Panel Configuration Editor
(Factory default settings are shown in bold italicised text)
Section
Parameter
as shown on
Values
Timers
Mains Transient Delay 0 -10s (2s)
Start Delay 0– 60m (5s)
Transfer Delay 0– 10s (0.7s)
Return Delay 0– 60m (30sa0
Low battery Delay 0– 10m (1m)
High battery Delay 0– 10m (1m)`
Mains
Mains Under Voltage Alarm 50V 360V ph N (184V)
(184V)(184V)
(184V)
Mains Over Voltage Alarm 50V 360V ph N (276V)
(276V)(276V)
(276V)
Mains Under Frequency 0Hz 75Hz (45Hz)
(45Hz)(45Hz)
(45Hz)
Mains Over Frequency 0Hz 75Hz (55Hz)
(55Hz)(55Hz)
(55Hz)
System
Plant Battery Under Volt Alarm 0 40V (10V)
(10V)(10V)
(10V)
Plant Battery Over Alarm 0 40V (30V)
(30V)(30V)
(30V)
Misc
Language English, Other
Alternative Frequency Enable Disable
DisableDisable
Disable
Alternative Voltage Enable Disable
DisableDisable
Disable
AC System
3 phase 4 wire
3 phase 4 wire3 phase 4 wire
3 phase 4 wire
Single phase 2 Wire
3 phase 3 wire
2 phase 3 wire L1 & L2
3 phase 4 wire ED
2 phase 3 wire L1 & L3
Contrast
 l 
Date and Time dd mmm yyyy hh:mm
Auto Scroll Time 0 10s (2s)
(2s)(2s)
(2s)
Mains CT Primary Rating 5A 6000A (600A)
(600A)(600A)
(600A)
Mains CT Secondary Rating 1A, 5A (5A)
(5A)(5A)
(5A)
Load Ramp Rate
0.1%
100% (
2.0%)
2.0%)2.0%)
2.0%)
(% per sec)
ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
•The ‘running’ editor can be entered while the engine is running. All protections remain active if the
engine is running while the running editor is entered.
•Press and hold the button to enter the running editor.
EDITING A PARAMETER
•Enter the editor as described above.
•Press the left or right buttons to cycle to the section you wish to view/change.
•Press the up
or down
buttons to change the parameter to the required value.
•To save paremeters scroll to `save changes and exit followed by the down buttton
•To cancel changes scroll to `Abandon changes and exit followed by the down
button
ADJUSTABLE PARAMETERS (Running editor)
Running Editor
Section
Parameter as shown on display
Factory Settings
DISPLAY Contrast
 l 
Language English
Load power factor %
Load parallel power %
Enable commissioning screens No
Voltage adjust
(manual mode only engine running bus breaker open)
Raise Steady Lower
Fr
eq
uency adjust
(manual mode only engine running bus breaker open)
Raise Steady Lower
Enable mains decoupling No
Abandon changes and exit
Save changes and exit
DIMENSIONS
240.0mm x 181.1mm x 41.7mm (9.4” x 7.1” x 1.6”)
PANEL CUTOUT
:
220mm x 160mm (8.7” x 6.3”)