Duco DucoBox Focus User manual

1
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
Installation guide
ENGLISH
DucoBox Focus
Product version 17xxxx and above
L2000631 (Revision L | 06.09.2022)
Step by step
instructions
duco.tv
L2000631-installatiehandleiding-DucoBox-Focus-(en)-DRUK
installation-guide-DucoBox-Focus-(en)

2
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
Table of contents
01 Introduction............................................................................................................ 3
02 Installation ............................................................................................................. 4
02.A Positioning ..................................................................................................... 4
02.B Mounting......................................................................................................... 4
02.C Air duct connections................................................................................... 4
03 Wiring....................................................................................................................... 5
03.A Connections & buttons .............................................................................. 5
03.B Wiring diagram............................................................................................. 5
04 Control valves........................................................................................................ 6
04.A Mounting the control valves..................................................................... 6
04.B Pairing the control valves ......................................................................... 7
04.C Removing / replacing control valves..................................................... 7
04.D LED indications............................................................................................. 7
05 Additional control options................................................................................. 8
05.A Communication Print................................................................................. 8
06 Electronical installation .................................................................................... 9
06.A Installer / User mode ................................................................................. 9
06.B LED indications DucoBox Focus............................................................. 9
06.C Pairing components.................................................................................... 9
06.D Removing / replacing components......................................................11
06.E Tips .................................................................................................................11
07 Air calibration......................................................................................................12
07.A Air calibration procedure for DucoBox Focus..................................12
07.B Checking.......................................................................................................13
08 Maintenance & service.....................................................................................14
09 Warranty................................................................................................................14
10 Legislation............................................................................................................15
English
Vero Duco - Handelsstraat 19 - 8630 Veurne - Belgium
DUCO, HANDELSSTRAAT 19
VEURNE, B8630
09
See www.duco.eu for information regarding warranty, maintenance, technical data, etc.
Installation, connection, maintenance and repairs are to be carried out by an accredited installer. The electronic components of this product may be live. Avoid
contact with water.
Translation of the original instructions

2 3
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
CO2
HIGH
LOW
INST
RH
Master
Slave
01 Introduction
Congratulations on your DucoBox Focus, the smartest box in Europe! The DucoBox Focus performs two functions in a Duco
Demand-Controlled Natural Ventilation System:
On the one hand it is the extractor fan that exhausts contaminated air with excessive CO2content or relative humidity. Thanks to
integrated control valves, air is only exhausted in the zone that requires it.
On the other hand, it is the master or brain of the system. It receives and interprets signals from slave components (measurements
from sensors or manual input), on the basis of which it controls the ventilation system.
It is inadvisable to connect the DucoBox (via a duct or directly) to an extractor hood, regardless of type. This usually causes exces-
sive fouling in the DucoBox, which affects its operation or has a more direct effect on the flow rate.

4
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
≥ 200 kg / m²
02 Installation
02.A Positioning
Select a roof pass-through
with low resistance.
0,5 à 1 m
Duct leading to the roof pass-through: use a
reducer 125mm– 160mm. Never use flexible
connections. Avoid curves in this part of the
canalization. If the DucoBox is not mounted in a
protected (insulated) volume, this duct needs to be
thermally insulated.
Use an
acoustic
silencer of
minimum
0.5 to 1 m.
This in every
connection
which leads
to a different
room.
Keep the box airtight. Close
the cover tightly and place
a cap onto any unused
opening.
Avoid as much as
possible the use of
curves. Avoid sharp
angles.
Avoid bumps and dirt in the ducts.
> 90°
160
mm
125 mm → ≥ 30 m³/h
100 mm → < 30 m³/h
< 90°
Reduce the transmission of
vibrations:
• Use Silent Block elements when
fixing the DucoBox to the wall.
• Use duct suspension clamps with
rubber.
Do not place an
exhaust air valve
directly on the box.
Use a 90° bend
between the DucoBox
and the valve. Use
valves with an as low
as possible back-
pressure and follow
the instructions as
given in the manual
regarding the opening
of the valves.
Assure an airtight
connection by using
tape, clamping strips
or tie-wrap. Do not
use screws.
Diameter of the ducts:
125mm upward from 30m³/h
100mm less than 30m³/h
Or an equivalent based on a specific duct calculation
(p.e. for ducts placed in floor screed). Make sure that
the total counter pressure in the ducts is as low as
possible (preferably ≤150Pa) and that the airspeed in
every duct does not exceed 3m/s.
installation-tips-duct-system-DucoBox-Silent-Focus-(en)
1
7
8
9
10
2
3
4
5
6
DISCLAIMER: no rights can be derived from this document.
All tips are only advisory. All those carrying out
the work can, depending on the project at
hand, determine for themselves which
tips are feasible and/or useful.
The smooth running of your Duco ventilation system is totally dependent
on the choice and the quality of implementation of the duct system!
10 UNMISSABLE TIPS
Has the duct system been optimized? Ask
professional advice from your duct supplier. It
saves you time, ensures quality and provides
energetic advantage for the end user!
L1025000-B 01.06.2018
02.C Air duct
connections
Limit the resistance. A non-return flap is
required when discharging into a manifold.
Position it at least 30cm away from the
DucoBox.
Be sure to take note of the ‘10 unmissa-
ble tips’ as well when fitting the DucoBox.
Avoiding excessive use of bends, especially
angles sharper than 90° and adhering to the
diameter guidelines for the ductwork will
ensure that the ventilation box is able to do
its job satisfactorily. Failure to take account of
this recommendation may result in a highly
energy and maintenance intensive system
that gives rise to excessive noise nuisance
frequently.
02.B Mounting

5
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
03 Wiring
03.A Connections & buttons
Strain relief
It is mandatory to place the power supply cable in the slot provided, as shown in the drawing, before powering up the DucoBox.
03.B Wiring diagram
The DucoBox Focus is able to communicate with Duco slave components via a wireless (RF) or wired link. Both types of communi-
cation can be combined in one system. Communication with non-Duco components is possible via the Switch Sensor or one of the
connections on the optional Communication Print (see page 8).
* Use a screened solid-core cable not exceeding 300 m in length, with 5 cores 0.8 mm each.
RF RF
Wired
RF
24 VDC 24 VDC
24 VDC
230 VAC 230 VACA AB BGND GND
BA GND
POWER
SUPPLY
User controller User controller Max 99 Wired
+ 25 RF
Tronic vent Tronic vent
230 VAC
230 VAC
DucoBox
Focus
≥ 30 cm
A
B
The power supply is to be determined depending
on the technical data sheet for each component
(see www.duco.eu). The power rating of all
individual components needs to be checked.
The power supply needs to be capable of
coping with the sum of these requirements
with a cable length not exceeding 300m.*
RF obstacle-free zone
Do not place any obstacles causing RF interference
or other devices with an RF connection within
a radius of at least 30 cm around the RF
component. Understood are items such as washing
machines, tumble dryers, ironing boards, etc.
Valve 2 Valve 1 HIGHDOWN LOWENTER INSTUP
Power
230 VAC
Fan
Duco
Wired
Antenna
Duco
Network
Tool
Switch
Contact
(n132)
GND
B
A
Blue Yellow Red White
Connector for
Communication Print
Display
PE
N
L
Illustrations and connections may vary depending on product configuration.
Incorrect connection or failure to follow the instructions may result in
damage to the connected devices.

6
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
RF (wireless communication)
RF components have a maximum free-field range of 350 metres. This dis-
tance will be much less in a building because of obstacles. Therefore, you will
need to take objects such as walls, concrete and metal into account. All slave
components (except those which are battery powered) also act as repeaters.
Signals from components that are unable to make a (strong) connection with
the master component are forwarded automatically via no more than one other
non-battery-powered component (= hop). Please refer to information sheet
RFcommunication (L8000018) at www.duco.eu for further information.
DUCO RF
Power supply 230 VAC
Wiring 1,5 mm²
Frequency 868 Mhz
Maximum distance 350 m, free field (less
through obstacles)
Maximum number
of components
Up to 25 wireless
components in a
single system
Wired (cabled communication)
Wired components can be daisy-chained (= recommended). This means that a
separate cable will not be required for each component. A single central power
supply can be used.
The cable required is a 5x0.75 mm² data cable. We strongly advise using a
shielded cable. This is to prevent any interference that may affect the data com-
munication. Any Tronic window ventilators will be supplied with a 5x0.25 mm²
cable which can be connected via a splicing terminal block.
DUCO WIRED
Power supply 24 VDC
Wiring
5 x 0,75 mm²
(5 x 0.25mm² from Tronic
window ventilators)
Maximum distance up to 300 m
Maximum number
of components
Up to 99 wired
components in a
single system
04 Control valves
The control valves, whether or not they are fitted with a sensor for measuring CO or humidity, can be built into the DucoBox Focus.
Together with the fan, they ensure the correct exhaust air flow rate in the right room.
A control valve with combined CO2and RH measurement can only be used with a DucoBox Focus with a software
version of 11.2 or higher.
A DucoBox Focus can contain up to a maximum of 7 control valves (= one per intake duct). This can be expanded to a maximum of
11 control valves by using the ‘Control Valve Manifold’ (item 0000-4454).
A control valve must always be provided for each ventilation duct connected!
04.A Mounting the control valves
Slide the control valve into the locations
provided in the DucoBox Focus. Connect
the ‘VALVE’ connector on the DucoBox
to IN on the control valve. If applicable,
connect OUT on the valve to IN on another
control valve to be added. At least one
valve must be connected to the DucoBox at
any time. VALVE1 VALVE2
OUT
DucoBox
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
IN
OUT
OUT
TIP: Use the letter labels on the DucoBox
and the valves (A/B/C/D/E/F/G) to give
these the same letter, so that the valves
always remain in the same position.
IN
OUT
B
B
E
E
A
A
F
F
D
D
G
G
C
C
A
B
C
D
E
F
G

7
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
04.B Pairing the control valves
The control valves are paired automatically to the DucoBox whenever ‘installer mode’ is activated (see “Pairing components”
chapter).
04.C Removing / replacing control valves
Taking control valve out temporarily
Follow these steps to take a control valve out of the unit tem-
porarily, e.g. to clean it during maintenance. Make sure that it
is inserted back in the same location. Use the letter labels on
the DucoBox and the relevant valve for this. The DucoBox will
retain all its settings when the control valve is reconnected.
Temporarily removing control valve
1Briefly press the button on the valve to close it
for 15 minutes. The LED will go out.
2Disconnect the wiring.
3Slide the valve out of the DucoBox.
Permanently removing or replacing control valve
To remove a control valve permanently from the system or to replace it (e.g. in the event of a fault) it is important that it should be
deregistered correctly. The DucoBox will not be able to be calibrated correctly if this is not done.
Permanently removing control valve
1Briefly press the button on the valve to drive it shut.
2
Activate ‘Installer mode’ by pressing ‘INST’ on the
DucoBox. The LEDs on the DucoBox and control
valves will flash green rapidly.
3
Long-press the button once on the control valve to
be removed in order to remove it from the network.
ATTENTION: any underlying components will also
be removed from the network.
4Disconnect the wiring from the control valve to be
removed and slide it out of the DucoBox.
5Deactivate ‘Installer mode’ by pressing ‘INST’ on the
DucoBox. All LEDs will stop flashing.
Replacing a control valve
1Briefly press the button on the valve to drive it shut.
2
Activate ‘Installer mode’ by pressing ‘INST’ on the
DucoBox. The LEDs on the DucoBox and control
valves will flash green rapidly.
3Short-press the button twice on the control valve to
be replaced in order to remove it from the network.
4Disconnect the wiring from the control valve to be
replaced and slide it out of the DucoBox.
5Slide the new control valve into the DucoBox and
connect it.
6
Short-press the button on the new control valve
once. The latter will take on all settings / connec-
tions in the network.
7Deactivate ‘Installer mode’ by pressing ‘INST’ on the
DucoBox. All LEDs will stop flashing.
04.D LED indications
In normal operation, the LED on the control valves will be white
or off, depending on the control valve position. The brightness
of the LED indicates the flow rate through the valve.
Please refer to “06.B LED indications on page 9 for the
meaning of the remaining LED colours.
Valve open
= max air flow
LED
Valve shut
= lowest air flow
LED

8
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
05 Additional control options
05.A Communication Print
With the optional Communication Print you have the option
of allowing the Duco ventilation systems to communicate via
ModBus and/or ethernet. ModBus integration enables them to
be linked to a building management system.
Disconnect the DucoBox from the power supply before connect-
ing the Communication Print and follow the instructions in the
manual included with the Communication Print.
ModBus
Ethernet Micro SD-card
PWM-OUT
PWM-IN
Switch Contact 1 (n133)
Switch Contact 2 (n134)
Switch Contact 3 (n135)
GND
B
A
-
+
-
+
Connector for
DucoBox

9
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
06 Electronical installation
06.A Installer / User mode
To add, remove or replace components to the network, the system should be put in ‘Installer mode’. The LED on each component
indicates the active mode of the component (seetable in next section).
‘Installer mode’ can be activated by pressing the DucoBox Focus ‘INST’ button (see drawing in section "03.A Connections &
buttons" on page 5. Once the LED on the master unit starts flashing, it means that ‘Installer mode’ is active. Press ‘INST’ again
to return to ‘User mode’ (LED fully on or off). The system reverts automatically to ‘User mode’ after 15 minutes of inactivity.
06.B LED indications DucoBox Focus
RED (blinking slowly)
Not in network
RED (blinking rapidly)
Logging in
GREEN (blinking slowly)
In network
GREEN (blinking rapidly)
In network, waiting for associated components
YELLOW (blinking slowly)
Transitional phase (please wait)
YELLOW (on)
Initialising (system configuration in progress)
WHITE or OFF
Normal
BLUE
Component is displayed if changes are being put through via the master.
ORANGE
The system is not working correctly because the DucoBox has not been calibrated. Restart the
DucoBox. Follow the guidelines in ‘10 essential tips’ if the problem recurs continually.
06.C Pairing components
The DucoBox Focus is an extractor fan for a zonal ventilation system. This means that ventilation will only operate in the zones
where it is needed (e.g. only in the bathroom while showering) for the most energy-efficient operation. Thus, in the example below,
pressing the button in zone1 will change the ventilation setting only for this zone. Pressing the button on the master user control
will control all zones that are set to ‘AUTO’ at that point in time.
Master user control
This controls the
entire system
Zonal components
These components only control the zone with which they are paired.
ZONE 1
ZONE 2
ZONE 3 ZONE 4
A
B

10
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
It is important that components are paired with the correct zone for this zonal operation. Components can be paired with the
DucoBoxFocus itself (controlling all zones) or with a control valve (controlling a single zone). A component will be paired in every
case with the component (control valve or DucoBox) that is flashing rapidly. It is possible to pair several user controls in one zone,
but not to link one user control to multiple control valves or DucoBoxes.
Never pair more than one system with RF components at the same time. If you do so, a component could be paired
in the wrong network, (e.g. in the neighbours’ DucoBox) or the component may not pair.
With RF components it is recommended to start with the component closest to the DucoBox. This enables this
component to be used as a hop for components that are too distant from the DucoBox and unable to make a direct
RF connection with the DucoBox.
Pairing components
1Activate ‘Installer mode’ by tapping ‘INST’ on the DucoBox. The LED will flash green rapidly.
2Pairing components on the DucoBox:
Use this method for any components that are required to control the entire system (e.g. a master user control).
2a Tap on the button of the component to be paired once while the LED on the DucoBox is flashing rapidly. The LED on
this component will flash red briefly and then start to flash green rapidly.
3
Pairing components with a control valve:
Use this method for components that only control the zone connected to the control valve duct. Repeat these steps for
each zone.
3a Tap the control valve once so the LED starts to flash green rapidly. Underlying components can now be added in
this zone.
3b Add control components by tapping once on the component to be paired. The LED will flash red briefly and then
start to flash green rapidly.
3c Add any window ventilators by tapping once on the component to be paired. The LED will flash green slowly.
4Once all components have been paired, ‘Installer mode’ can be deactivated by tapping ‘INST’ on the DucoBox Focus. The
LEDs on all components will stop flashing.
Please refer to the manual with the components for more detailed information.

11
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
06.D Removing / replacing components
Removing paired components from the network or replacing is only possible within 30minutes after the component is paired in
or is restarted. Restarting can be done by disconnecting the power for a moment. After a time-span of 30 minutes, remove and
replace operations are ignored. This is valid for all components from date of manufacture 170323.
Removing a component
1
Activate ‘Installer mode’ by
long-pressing 2diagonal buttons
on a paired control. The LED will
flash green or yellow rapidly. 5 sec
2
Press once and hold a button on
the component to be removed
in order to remove it from the
network. ATTENTION: any under-
lying components will also be
removed from the network.
5 sec
3
Deactivate ‘Installer mode’ by
pressing the 4buttons on a paired
control simultaneously (or using
the palm of your hand on a control
featuring touch buttons). The LED
will turn white.
Replacing a component
1
Activate ‘Installer mode’ by
long-pressing 2diagonal buttons
on a paired control. The LED will
flash green or yellow rapidly. 5 sec
2Briefly press twice on the button
of the component to be replaced.
2x
OLD
3
Tap once on the button of the new
component. The latter will take on
all settings / connections in the
network. 1x
NEW
3
Deactivate ‘Installer mode’ by
pressing the 4buttons on a paired
control simultaneously (or using
the palm of your hand on a control
featuring touch buttons). The LED
will turn white.
06.E Tips
• Removing all components from the network (e.g. in the event of problems): Activate ‘Installer mode’ and long-press ‘INST’
until the LED starts flashing red. The DucoBox will reboot and the LED will stop flashing.
• Restoring factory settings for the DucoBox and all paired components (AS FROM DucoBox version 18xxxx): Long-press ‘INST’
and ‘ENTER’ if not in ‘Installer mode’. The network remains in place.
• Use the Duco Network Tool to read out information from components.

12
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
07 Air calibration
For the system to work correctly, it needs to be configured. This will ensure its operation is as quiet as possible and energy-ef-
ficient. For information on determining the ventilation flow rates, see Instruction Sheet Checking Product References and Flow
Rates at www.duco.eu.
07.A Air calibration procedure for DucoBox Focus
The air calibration procedure must be carried out on a calm day (no more than wind force 2: leaves rustling,
feeling the wind in one’s face).
DucoBox Focus air calibration
1The exhaust vents must be set depending on the situation. Proper pre-setting makes for rapid and correct configuration.
SITUATION 1:
one vent per valve
Set all vents to the fully open
position, regardless of the desired
flow rate.
SITUATION 2:
Multiple vents per valve
with equal flow rates
Set all vents to the fully open
position, regardless of the desired
flow rate. Set the valve to the
sum of the vent flow rates via the
display menu or the Duco Network
Tool. Example: 2 vents, 50 m³/h
each → set valve to 100 m³/h.
100
m3/h
+ =
SITUATION 3:
Multiple vents per valve
with different flow rates
Set the exhaust vents so they
match the desired flow rate in line
with the table below. Set the valve
to the sum of the vent flow rates
via the display menu or the Duco
Network Tool. Example: 25 m³/h
vent and 75 m³/h vent → set valve
to 100 m³/h.
100
m3/h
+ =
When using DucoVent Design exhaust vents always leave
the outer ring in place for acoustic effect.
Flow rate DucoVent
Design
DucoVent Basic
and other vents
75m³/h 100% open
50m³/h 50% open
25m³/h 25% open

13
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
2
Before activating air calibration mode:
• Close all windows and doors.
• Ensure that all duct openings in the DucoBox are fully closed and that the
DucoBox cover is closed!
• Avoid air leaks in the ventilation ducts.
• Set all window ventilators to the open position. Any Tronic ventilators will open
automatically.
open
3Pull the plug out of the socket and wait a few seconds.
Iteration Rev. Date Name Description
23-Nov-17
Status DateStatus
STEKKER_STOPCONTACT
mm³dm²/mkg/mmm
Handelsstraat 19 - 8630 VEURNE
tel. 0032-58/330033 - fax.0032-58/330044
email: info @ duco.eu www.duco.eu
This drawing is property of Vero Duco NV and can not be copied, neither shown to
third party/externally without written permission.
0.0000.000
Drawing NumberVolumeCoat. Surf.WeightOutline
STEKKER_STOPCONTACT
Format: A3
Production Number:Mat.:
Draftsman: -Tol.: -
Scale: 1.000
POWERCABLE Date: 23-Nov-17
4Put the plug back into the socket. The DucoBox will be configured automatically on
start-up. Calibration takes 30seconds + 1minute per connected control valve.
Iteration Rev. Date Name Description
23-Nov-17
Status DateStatus
STEKKER_STOPCONTACT
mm³dm²/mkg/mmm
Handelsstraat 19 - 8630 VEURNE
tel. 0032-58/330033 - fax.0032-58/330044
email: info @ duco.eu www.duco.eu
This drawing is property of Vero Duco NV and can not be copied, neither shown to
third party/externally without written permission.
0.0000.000
Drawing NumberVolumeCoat. Surf.WeightOutline
STEKKER_STOPCONTACT
Format: A3
Production Number:Mat.:
Draftsman: -Tol.: -
Scale: 1.000
POWERCABLE Date: 23-Nov-17
07.B Checking
The steps set out below can be used to check whether flow rates have been set correctly.
Checking configured flow rate
1Open the DucoBox cover.
2Press ‘HIGH’ briefly. The DucoBox will remain in configuration mode for 30
minutes (as standard).
3Close the cover.
4Wait at least one minute to allow the ventilation system to stabilise.
5Measure the vents. If a flow rate differs from the desired output, this can be
adjusted via the display menu or using the Duco Network Tool.
6If you finish before the standard setting of 30 minutes, re-open the DucoBox cover
and press ‘HIGH’ again. Then replace the cover on the DucoBox.

14
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
08 Maintenance & service
Please refer to the maintenance instructions at www.duco.eu and view the videos on duco.tv for more information.
For service problems as a user:
Please contact your installer. Keep the serial number of your product
to hand.
For service problems as an installer:
Please contact your Duco products seller. Keep the serial number of
your product to hand.
09 Warranty
All warranty conditions concerning the DucoBox and Duco's ventilation systems can be found on the DUCO website.
All complaints are to be reported to Duco by the Duco distributor with a clear description and the order/invoice number under
which the products were delivered. In order to register the complaint, please use the complaint registration form found on the Duco
website and the product's serial number in your message to serviceduco.eu.
Sticker inside the DucoBox

15
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
10 Legislation
Product card, EC declaration of conformity and energy labels can be viewed and downloaded at www.duco.eu.

16
ENGLISH
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
Installed by:
L2000631 Document last modified on 06.09.2022 (revision L)
Other manuals for DucoBox Focus
3
Table of contents
Other Duco Controllers manuals