manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Zamel
  6. •
  7. Controllers
  8. •
  9. Zamel exta SRP-05 User manual

Zamel exta SRP-05 User manual

FLUSH-MOUNTED ROLLER BLIND CONTROLLER SRP-05
USER MANUAL
ZAMEL Sp. z o.o.
ul. Zielona 27, 43-200 Pszczyna, Poland
tel. +48 (32) 210 46 65, fax +48 (32) 210 80 04
www.zamel.com, e-mail: [email protected]
plik: srp-05_inst_ext_gb | modykacja: 10.05.2023
INSTALLATION EXAMPLESINSTALLATION
1. Disconnect the power supply circuit with
a fuse, circuit breaker or switch discon-
nector connected to an appropriate cir-
cuit.
2. Check the de-energized condition on
the power supply cables by means of
the appropriate instrument.
3. Connect the cables to the appropriate
controller terminals in line with the con-
nection scheme.
4. Place the SRP-05 device in the junction
box.
5. Connect the power supply circuit and
check for correct operation.
Roller blind group
Extended roller blind installation
WYGLĄD
FEATURES
TECHNICAL DATADESCRIPTION
• Intended for wire control of window
roller blind, canopy, gate drives,
• control of other devices powered by 12
V DC or 24 V DC electric motors,
• local and central control,
• standalone operation or united in larger
sections (grouping),
• local control performed from the level
or single or double roller blind switches,
• central control performed from double
roller blind switches only,
• the roller blind is lockable in the closed
or open position from the central input
level,
• cooperation with alarm systems and
auxiliary devices (e.g. a weather sta-
tion, an illuminance sensor, a precipita-
tion sensor, control timers),
• release from the “+” line only,
• the device is energy-saving, adapted to
continuous operation,
• comfort mode - upper and lower - sav-
ing the roller blind position,
• programmable maximum roller blind
movement time.
The SRP-05 ush-mounted roller blind
controller is designed to control window
roller blinds or other devices powered
by direct current motors at 12 V or 24 V.
Control can be local or central, using re-
turn roller blind switches. With local con-
trol, double and single switches must be
used. With central control, only double
switches can be used. In terms of func-
tionality, the controller can be used to pro-
gram two independent comfort settings
(lower and upper) and maximum roller
movement time. SRP-05 can operate as
a standalone controller or can be united
in larger sections. A special functionality
of central control inputs can lock the roller
blind in the closed or open position. The
controller can thus cooperate with alarm
systems and auxiliary devices, such as
a weather station, an illuminance sen-
sor, a precipitation sensor, control timers.
Pulses from the “+” line are the release
signals.
Power terminals: +, -
Rated supply voltage: 12 ÷ 24 VDC
Rated power consumption:
standby:
0,053 W (at UIN=12 V DC)
0,21 W (at UIN=24 V DC)
work mode:
0,33 W (at UIN=12 V DC)
0,51 W (at UIN=24 V DC)
Maximum load: 6A
Control signal: short pulses from the “+” line
Optic signaling of roller blind movement: red LED
Default roller blind movement time: 120 s
Roller blind movement time programming: yes - from 1 s to 10 min.
Comfort position: yes - upper and lower
Time range for comfort modes: from 1 s to 10 min.
Local control terminals: LOCAL ( ), ( )
Central control terminals: CENTRAL ( ), ( )
Local control: double or single roller blind switches
Central control: double roller blind switches
Motor power terminals: M1, M2
Relay terminal parameters: 2NO 8A / 30 VDC (voltage contacts)
Number of connection terminals: 8
Section of connection cables: 0.2 ÷ 2.50 mm²
Operating temperature: -10 ÷ +55 °C
Working position: any
Housing fastening: Ø60 mm junction box
Housing protection rating: IP20 (PN-EN 60529)
Protection class: III
Contamination level: 2
Dimensions: 47.5 x 47.5 x 20 mm
Weight: 0.044 kg
Compliance with the following standards: PN-EN 60669, PN-EN 61000
DIMENSIONS
WARRANTY CARD
24-month commercial warranty
granted by the manufacturer
Seller’s stamp and signature with date of sale
1.ZAMEL Sp. z o.o. grants a 24-month warranty for the goods it sells.
2.The warranty granted by ZAMEL Sp. z o.o. does not cover:
a)mechanical damage caused by transport, loading/unloading or other circumstances,
b)any damage resulting from improper installation or use of the goods sold by ZAMEL Sp. z o.o.,
c) any damage resulting from any modications made by the BUYER or any third party to the sold goods or to the equipment
required for the proper functioning of the sold goods,
d) damage caused by any force majeure event or another fortuitous event beyond any reasonable control of ZAMEL Sp. z o.o.
3. The BUYER shall report all warranty claims in writing at the point of sale or to ZAMEL Sp. z o.o.
4.ZAMEL Sp. z o.o. will examine each warranty claim as regulated by the applicable provisions of the Polish law.
5.The form of warranty claim resolution, i.e. replacement, repair or refund of the price of purchase, shall be decided upon by
ZAMEL Sp. z o.o.
6. This warranty does not exclude, limit or suspend any rights of the BUYER arising from the statutory or regulatory laws con-
cerning implied warranty for defects of sold goods.
Connect this product to a
single-phase power system ac-
cording to applicable electrical
and safety standards and regu-
lations. See this Manual for the
wiring instructions. Installation,
wiring and adjustment/setting shall only be
done by qualied electricians who have read
and understood this User Manual and the
functions of the product. Do not open or oth-
erwise disassemble the product housing; oth-
erwise the product warranty will be void and
an electrocution hazard may occur. Prior to
installing and wiring this product, make sure
that the wiring to be connected is not live. The
conditions and methods of transport, storage
and operation of this product may affect its
performance. Do not install the product if any
of its components are missing, the product
is damaged or deformed in any way. If any
malfunctions are found, consult the manufac-
turer.
CAUTION
Do not dispose of this device with
other waste! In order to avoid
harmful effects on the environment
and human health, the used device
should be stored in designated
areas. For this purpose, you can
dispose of household waste free
of charge and in any quantity to
a collection point set up, as well
as to the shop when you buy new
equipment. Terminals for connecting
a 12 V DC or 24 V DC
motor
Central control terminals
(up/down)
Roller blind status
and programming status
signaling
Programming button
Local control terminals
(up/down)
Input (supply) terminals
(+, -)
Power
Supply
12 V DC
or
24 V DC
Power
Supply
12 V DC
or
24 V DC
CENTRAL Roller blind123
CENTRAL
GROUP1
CENTRAL
GROUP123
CENTRAL
GROUP2
CENTRAL
GROUP3
LOCAL Roller blind1
LOCAL Roller blind1
LOCAL Roller blind3
LOCAL Roller blind5
LOCAL Roller blind2
LOCAL Roller blind2
LOCAL Roller blind4
LOCAL Roller blind6
LOCAL Roller blind3
GROUP1GROUP3 GROUP2
FUNCTION FUNCTION
TIMER PROGRAMMING
LOCAL CONTROL - DOUBLE ROLLER BLIND SWITCH
In this mode, short presses (<0.5s) on the corresponding local control switches will cause the SRP-05 controller to perform the following
operations: opening, closing or stopping a roller blind equipped with a 12 V DC or 24 V DC motor. Roller blind movement time is consistent
with the time programmed in the controller. The default timer setting is 120 s. After the rst press on the local control switch, the roller blind
moves in the selected direction. After consecutive pressing on any of the local control switches, the roller blind is stopped. Roller blind move-
ment is signaled by the STATUS LED. After a longer pressing on the corresponding local control switch (>2.5s), the controller executes the
congured comfort settings (lower / upper).
Execution of the upper comfort setting:
To execute the upper comfort setting, completely open the roller blind. Next, press and hold (>2.5s) the local control switch (LOCAL ). The
roller blind will start to close and will automatically stop in the programmed upper comfort position.
Execution of the lower comfort setting:
To execute the lower comfort setting, completely close the roller blind. Next, press and hold (>2.5s) the local control switch (LOCAL ). The
roller blind will start to open and will automatically stop in the programmed lower comfort position.
LOCAL CONTROL - SINGLE SWITCH
Local control using the single switch is enabled when LOCAL ( ) and LOCAL ( ) inputs are connected.
In this mode, short presses (<0.5s) on the corresponding local control switch will cause the SRP-05 controller to perform the following opera-
tions: opening, closing or stopping a roller blind equipped with a 12 V DC or 24 V DC motor. Roller blind movement time is consistent with the
time programmed in the controller. The default timer setting is 120 s. Roller blind movement is controlled according to the following sequence:
open - stop - close. Roller blind movement is signaled by the STATUS LED. After a longer pressing on the local control switch (>2.5s), the
controller executes the congured comfort settings.
Execution of the upper comfort setting:
To execute the upper comfort setting, completely open the roller blind. Next, press and hold (>2.5s) the local control switch. The roller blind
will start to close and will automatically stop in the programmed upper comfort position.
Execution of the lower comfort setting:
W celu wywołania ustawienia komfortowego dolnego należy całkowicie zamknąć roletę. Następnie należy dłużej (> 2,5 s) przytrzymać przy-
cisk sterowania lokalnego. Roleta zacznie się otwierać i automatycznie zatrzyma się w zaprogramowanym położeniu komfortowym dolnym.
NOTE:
The comfort setting timers (for both the upper and lower positions) are the same for the double and single switches. The pro-
grammed roller blind movement time must be longer than the programmed times for the comfort settings. After changing the local
control mode from the single switch to the double switch, make sure to restart the controller (disconnect from power supply and
reconnect).
CENTRAL CONTROL - DOUBLE ROLLER BLIND SWITCH ONLY
In this mode, short presses (<0.5s) on the corresponding local control switch will cause the SRP-05 controller to perform the following
operation: opening and closing a roller blind equipped with a 12 V DC or 24 V DC motor. The roller blind is stopped after the programmed
roller blind movement time or after pressing any local control switch. The default roller blind movement time is 120 s. if a central command
is send within this time, causing the roller blind to move in the opposite direction, the roller blind will be stopped and will start moving in the
opposite direction after about 0.5 s. Roller blind movement is signaled by the STATUS LED.
Central control input locking mode
Central control inputs can lock the roller blind in the closed or open position. For this purpose, signal from the “+” line should be this
sent to the corresponding CENTRAL ( ,) input. This can be performed, among others, by the alarm unit, the illuminance sensor, the
precipitation sensor or the control timer. In the locking mode, all other control inputs are disabled. Central control inputs are used for
long-term release.
Roller blind movement time programming
Roller blind movement time can be programmed from 1s to 10 minutes. This time is common for up and down movement. By default, the
roller blind movement time is 120 s. Due to mechanical issues, the opening of the roller blind lasts a bit longer than its closing. Therefore, the
roller blind movement time should be programmed from the lower position (with the roller blind completely closed). The time is saved up to
the power outage.
To program the roller blind movement time:
1. Close the roller blind completely.
2. Press the PRÓG button on the SRP-05 controller housing.
3. The roller blind will start to open and time will be measured, which will be signaled with the STATUS LED ashing.
4. When the roller blind reaches its upper position, press any local / central control switch. The roller blind will stop and the movement time
will be saved in the SRP-05 controller memory.
Programming comfort settings (times)
Comfort setting times can be programmed from 1s to 10 minutes. The upper and lower comfort settings are programmed separately.
UPPER COMFORT SETTING
To program the upper comfort setting (time):
1. Open the roller blind completely.
2. Press the PRÓG button on the SRP-05 controller housing.
3. The roller blind will start to close and time will be measured, which will be signaled with the STATUS LED ashing.
4. When the roller blind reaches the preset position (upper comfort position), press the PRÓG button on the SRP-05 controller housing again.
The roller blind will stop and the upper comfort time will be saved in the SRP-05 controller memory.
LOWER COMFORT SETTING
To program the lower comfort setting (time):
1. Close the roller blind completely.
2. Press the PRÓG button on the SRP-05 controller housing.
3. The roller blind will start to open and time will be measured, which will be signaled with the STATUS LED ashing.
4. When the roller blind reaches the preset position (lower comfort position), press the PRÓG button on the SRP-05 controller housing again.
The roller blind will stop and the lower comfort time will be saved in the SRP-05 controller memory.
To execute a required comfort setting, proceed according to the guidelines for the corresponding control method. Comfort setting times are
saved after a power outage.
Model application:
The ZCM-31 astro-
nomical clock centrally
closes the window roller
blind system at dusk.
Local / central control is
only enabled at dawn,
when the 11-14 contacts
of the clock are opened.
230 V AC
230 V AC
230 V AC
230 V AC
Power Supply
12 V DC
or
24 V DC
Power Supply
12 V DC
or
24 V DC
Power Supply
12 V DC
or
24 V DC
Power Supply
12 V DC
or
24 V DC
CENTRAL LOCAL

Other Zamel Controllers manuals

Zamel RTS-01A User manual

Zamel

Zamel RTS-01A User manual

Zamel RNK-02 User manual

Zamel

Zamel RNK-02 User manual

Zamel exta SRM-11 User manual

Zamel

Zamel exta SRM-11 User manual

Zamel ledix SLR-11 User manual

Zamel

Zamel ledix SLR-11 User manual

Zamel RTD-01 User manual

Zamel

Zamel RTD-01 User manual

Zamel Extra Free ROB-01/12-24V User manual

Zamel

Zamel Extra Free ROB-01/12-24V User manual

Zamel Extra Free ROB-01/12-24V User manual

Zamel

Zamel Extra Free ROB-01/12-24V User manual

Zamel Extra Free RZB-02 User manual

Zamel

Zamel Extra Free RZB-02 User manual

Zamel Wi-Fi supla SLW-01 User manual

Zamel

Zamel Wi-Fi supla SLW-01 User manual

Zamel RTM - 01 User manual

Zamel

Zamel RTM - 01 User manual

Zamel RZB-03 User manual

Zamel

Zamel RZB-03 User manual

Zamel RTD-02 User manual

Zamel

Zamel RTD-02 User manual

Zamel RZB-05 User manual

Zamel

Zamel RZB-05 User manual

Zamel supla SRW-01 User manual

Zamel

Zamel supla SRW-01 User manual

Zamel Supla SLW-02 User manual

Zamel

Zamel Supla SLW-02 User manual

Zamel exta RTM-20 User manual

Zamel

Zamel exta RTM-20 User manual

Zamel RTP-01 User manual

Zamel

Zamel RTP-01 User manual

Zamel RNK-02 User manual

Zamel

Zamel RNK-02 User manual

Zamel exta life ROB-21 User manual

Zamel

Zamel exta life ROB-21 User manual

Zamel Extra Free RZB-02 User manual

Zamel

Zamel Extra Free RZB-02 User manual

Zamel exta life SRM-22 User manual

Zamel

Zamel exta life SRM-22 User manual

Zamel exta ZCM-22 Series User manual

Zamel

Zamel exta ZCM-22 Series User manual

Zamel exta free RZB-01 User manual

Zamel

Zamel exta free RZB-01 User manual

Zamel SRP-22 User manual

Zamel

Zamel SRP-22 User manual

Popular Controllers manuals by other brands

JUMO DICON touch operating manual

JUMO

JUMO DICON touch operating manual

KIPI ecoMAX860P3-C Installation and operating manual

KIPI

KIPI ecoMAX860P3-C Installation and operating manual

ABB COMMANDER C355 user guide

ABB

ABB COMMANDER C355 user guide

TimeTec Security BLE-16 installation guide

TimeTec Security

TimeTec Security BLE-16 installation guide

Hunter ECO LOGIC instructions

Hunter

Hunter ECO LOGIC instructions

Exlar Tritex installation manual

Exlar

Exlar Tritex installation manual

Integra DHC-80.1 instruction manual

Integra

Integra DHC-80.1 instruction manual

Generac Power Systems Power Zone Pro owner's manual

Generac Power Systems

Generac Power Systems Power Zone Pro owner's manual

LOVATO ELECTRIC RGK600 installation manual

LOVATO ELECTRIC

LOVATO ELECTRIC RGK600 installation manual

Lexicon MC-8 user guide

Lexicon

Lexicon MC-8 user guide

SWASTIK LEMINAR CARD quick start guide

SWASTIK

SWASTIK LEMINAR CARD quick start guide

Andover Controls Infinity manual

Andover Controls

Andover Controls Infinity manual

Envirosight VISIONCONTROL VC500 user manual

Envirosight

Envirosight VISIONCONTROL VC500 user manual

PS Automation PSF operating instructions

PS Automation

PS Automation PSF operating instructions

Pilz PNOZ m3p (ETH) operating manual

Pilz

Pilz PNOZ m3p (ETH) operating manual

Star S430 manual

Star

Star S430 manual

Moore 500 Series Hardware Installation and Modification Manual

Moore

Moore 500 Series Hardware Installation and Modification Manual

NOVAK HAVOC 1S - ADDENDUM 11-2009 Using

NOVAK

NOVAK HAVOC 1S - ADDENDUM 11-2009 Using

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.