Duelco DSC Series Quick start guide

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 2
SUMMARY
INTRODUCTION ...................................................................................................... 3
ELECTRICAL CONNECTIONS ..................................................................................... 3
SIGNALS AND PINOUT ............................................................................................. 4
Module MBC............................................................................................................ 4
Module MBD ........................................................................................................... 4
Module MBP ............................................................................................................ 5
Module MBEC.......................................................................................................... 5
Module MBEI ........................................................................................................... 6
Module MBEP .......................................................................................................... 6
Module MBEM ......................................................................................................... 7
Module MBCCL........................................................................................................ 7
Module MBMR ......................................................................................................... 8
Module MBU............................................................................................................ 8
DESCRIPTION.......................................................................................................................................................9
PROCESS IMAGE ...................................................................................................... 9
DIAGNOSTICS........................................................................................................ 10
The "I/O index" field .......................................................................................... 10
The "Diagnostic code" field ................................................................................ 11
EXAMPLES OF DIAGNOSTICS .................................................................................. 13
Example 1 ......................................................................................................... 13
Example 2 ......................................................................................................... 13
Example 3 ......................................................................................................... 14
Example 4 ......................................................................................................... 14
BUS CONFIGURATOR USER INTERFACE ............................................................................................. 15
Graphical User Interface ........................................................................................ 16
BACKWARD COMPATIBILITY (VERSION FOR M1 fw < 5.0.0) .................................................. 17
Process Image in backward compatibility (version for M1 fw < 5.0.0) ..................... 17
Graphical User Interface, backward compatibility (version for M1 fw< 5.0.0.) ..................... 19
Process image configuration in backward compatibility ......................................... 20
EXAMPLES OF DSD CONFIGURATION AS PRESENTED BY THE BUS CONFIGURATOR 21
MV MODULES INPUT STATUS .............................................................................. 22

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 3
INTRODUCTION
This technical sheet describes the operation of the fieldbus modules of the DSC series:
MBP (PROFIBUS DP-V1), MBD (DeviceNet), MBC (CANOpen), MBEC (ETHERCAT), MBEI (ETHERNET/IP),
MBEP (PROFINET), MBEM (Modbus TCP), MBMR (Modbus RTU), MBCCL (CC-Link), MBU (USB).
ELECTRICAL CONNECTIONS
Each module is provided with four connectors (Figure 1):
1) 5 way connector MSC --> to the system DSC
2) USB miniB connect --> to the PC
3) BUS connector --> to the fieldbus (not present on MBU)
4) Front terminal --> power supply
TERMINAL BLOCK (SIDE A - TOP)
TERMINAL BLOCK (SIDE B - BOTTOM)
TERMINAL
SIGNAL
TERMINAL
SIGNAL
1
+24VDC + 20%
5
-
2
-
6
Serial line RS-485 -(A)
3
-
7
GND
4
GND
8
Serial line RS-485 +(B)
Table 1
Install safety units in an enclosure with a protection class of at least IP54.
The supply voltage to the units must be 24Vdc ±20%
(PELV, in compliance with the standard EN 60204-1).
Do not use DSC to supply external devices.
The same ground connection (0VDC) must be used for all system components.
Figure 1

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 4
SIGNALS AND PINOUT
MEANING
LED
ON
RUN
IN FAIL
EXT FAIL
LED1
LED2
GREEN
GREEN
RED
RED
RED/GREEN
RED/GREEN
Startup - Initial test
ON
ON
ON
ON
ON
ON
Waiting for configuration from Master
ON
OFF
OFF
OFF
see the modules tables
Received configuration from Master
ON
ON
OFF
OFF
Table 2 – Initial/ dynamic view.
Module MBC
Module MBD
DB9 – male
(front view)
Pin
Signal
1
-
2
CAN_L
3
CAN_GND
4
-
5
CAN_SHIELD
6
-
7
CAN_H
8
-
9
-
Housing
CAN_SHIELD
LED OPR
STATUS
INDICATION
DESCRIPTION
GREEN
OPERATIONAL
OPERATIONAL status
GREEN blinking slow
PRE-OPERATIONAL
PRE-OPERATIONAL status
GREEN 1 flash
STOPPED
STOPPED status
GREEN blinking fast
Autobaud
Baud rate detection
RED
EXCEPTION
EXCEPTION status
LED ERR
STATUS
INDICATION
DESCRIPTION
OFF
-
Normal operation
RED 1 flash
Warning level
A bus error counter has reached the warning level
RED blinking fast
LSS
LSS service operative
RED 2 flashes
Event Control
Detected Node Guarding (NMT master or slave) or Heartbeat (Consumer)
RED
Lack of BUS
BUS not working
Pin Signal Description
1 V- Negative BUS power supply
2 CAN_L CAN low bus line
3 SHIELD Cable shield
4 CAN_H CAN high bus line
5 V+ Positive BUS power supply
LED NET
STATUS
INDICATION
DESCRIPTION
GREEN
On-line connected
1 or more connections established
GREEN blinking (1Hz)
On-line non connected
No connection established
RED
Critical connection error
MBD unable to communicate
RED blinking (1Hz)
Time-out of 1 or more connection
One or more I/O device in time-out
GREEN/RED alternate
TEST
MBD in Test
LED STS
STATUS
INDICATION
DESCRIPTION
GREEN
-
Normal operation
GREEN blinking (1Hz)
Pending
Configuration incomplete, MBD waiting for activation
RED
Fatal error
One or more unrecoverable errors detected
RED blinking (1Hz)
Error
One or more recoverable errors detected
GREEN/RED alternate
TEST
MBD in Test
The image does not
show the specific
model
The image does not
show the specific
model

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 5
Module MBP
Module MBEC
DB9 – female
(front view)
Pin
Signal
Description
1
-
-
2
-
-
3
B-line
Positive RxD/TxD, RS485 level
4
RTS
Request to send
5
GND Bus
0VDC (isolated)
6
5V
+5VDC (isolated/short circuit protected)
7
-
-
8
A-line
Negative RxD/TxD, RS485 level
9
-
-
Housing Cable shield
Internally connected to the Anybus protective earth via
cable shield filters according to the PROFIBUS standard.
LED MODE
STATUS
INDICATION
DESCRIPTION
GREEN
On-line
data exchange
GREEN blinking
On-line
CLEAR
RED blinking (1 flash)
Parameterization error
rif. IEC 61158-6
RED blinking (2 flashes)
PROFIBUS configuration error
configuration data MASTER or MBP wrong
LED STS
STATUS
INDICATION
DESCRIPTION
OFF
MBP not initialized
Status SETUP o NW_INIT
GREEN
Initialized
End of initialization NW_INIT
GREEN blinking
Initialized with diagnostic active
EXTENDED DIAGNOSTIC bit set
RED
Exception error
EXCEPTION status
LED STS
STATUS
INDICATES
DESCRIPTION
OFF
INIT
INIT or no power
Green
OPERATIONAL
OPERATIONAL state
Green blinking
PRE-OPERATIONAL
PRE-OPERATIONAL state
Green blinking (1 flash)
SAFE-OPERATIONAL
SAFE-OPERATIONAL state
Red
(Fatal Event)
System locked
LED ERR
STATUS
INDICATES
DESCRIPTION
OFF
No error
No error or no power
RED blinking (1 flash)
Configuration not valid
Status change requested by master not possible
RED blinking (2 flashes)
Watchdog timeout
Synch manager watchdog timeout
Red
Controller fault
Anybus module in EXCEPTION state
The image does not
show the specific
model
The image does not
show the specific
model

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 6
Module MBEI
Module MBEP
LED NET
STATE
INDICATES/DESCRIPTION
OFF
No power or no IP address
GREEN
On-line, connected
GREEN blinking
On-line, not connected
RED
Duplicate IP address
RED blinking
Connection timeout
LED STS
STATE
INDICATES
DESCRIPTION
OFF
No power
-
GREEN
RUN state
-
GREEN blinking
Not configured
-
RED
Fatal error
One or more non-recoverable errors detected
RED blinking
Error
One or more recoverable errors detected
LED NET
STATE
INDICATES
DESCRIPTION
OFF Offline
•No power
•Connection with IO controller not present
GREEN Online (RUN)
•Established connection with IO controller
•IO controller in RUN state
GREEN blinking (1 flash) Online (STOP)
•Established connection with IO Controller
•IO Controller in STOP state or IO data bad
•IRT synchronization not finished
GREEN blinking
Blink
Used to identify the network node
RED
Fatal event
Major internal error (combined with a red module STS led)
RED blinking (1 flash)
Station Name error
Station Name not set
RED blinking (2 flashes)
IP address error
IP address not set
RED blinking (3 flash)
Configuration error
Expected identification differs from real identification
LED STS
STATE
INDICATES
DESCRIPTION
OFF
Not initialized
No power or Module in SETUP or NW_INIT state
GREEN
Normal operation
Module has shifted from the NW_INIT state
GREEN blinking (1 flash)
Diagnostic event (s)
Diagnostic event (s) present
RED
Exception error
Device in state EXCEPTION
Fatal event
Major internal error (combined with a red NET led module)
Alternating RED/GREEN Firmware update
Do NOT power off the module.
It could cause a permanent damage.
The image does not
show the specific
model
The image does not
show the specific
model

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 7
Module MBEM
Module MBCCL
LED NET
STATE
INDICATES/DESCRIPTION
OFF
No power or no IP address
GREEN
Module is in Process Active or Idle state
GREEN blinking
Waiting for connections
RED
Duplicate IP address, or FATAL event
RED blinking
Process Active Timeout
LED STS
STATE
INDICATES
DESCRIPTION
OFF
No power
-
GREEN
RUN
Normal operation
RED Fatal error
•Major fault;
•module in state EXCEPTION (or fatal event)
RED blinking Error
•Minor fault in diagnostic object
•IP conflict
Pin
Signal
Description
1 DA Positive RS485 RxD/TxD
2 DB Negative RS485 RxD/TxD
3 DG Signal Ground
4 SLD Cable shield
5 FG Protective Earth
LED NET
STATUS
DESCRIPTION
OFF
No network participation, timeout status (no power)
GREEN
Participating, normal operation
RED
Major fault (FATAL error)
LED ERR
STATUS
INDICATION
DESCRIPTION
OFF
No error (no power)
Normal operation
RED
Major fault
Exception or FATAL event
RED flickering
(Temporary flickering)
CRC
CRC Error
RED flashing
(Continuous flashing)
PARAMETERS
Station Number or Baud Rate has changed since startup
The image does not
show the specific
model
The image does not
show the specific
model

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 8
Module MBMR
Module MBU
FAULT DIAGNOSIS
MEANING
LED
ON
RUN
IN FAIL
EXT FAIL
LED1
LED2
GREEN
GREEN
RED
RED
RED/GREEN
RED/GREEN
Internal fault microcontroller
ON
OFF
2 flashes*
OFF
see the modules tables
Internal board fault
ON
OFF
3 flashes*
OFF
Configuration Error
ON
OFF
5 flashes*
OFF
BUS communication Error
ON
OFF
5 flashes*
OFF
BUS communication interruption
ON
OFF
ON
OFF
Detected an identical module
ON
OFF
5 flashes*
5 flashes
Table 3
* The LED frequency of flashing is: ON for 300ms and OFF for 400ms, with an interval between two sequences of 1s.
DB9 – female
(front view)
Pin
Direction
Signal
Description
Housing
-
PE
Protective Earth
1
-
GND
Bus polarization 0VDC (isolated)
2
OUT
5V
Bus polarization +5VDC (isolated)
3
IN
PMC
Connect to pin 2 for RS-232 / Leave unconnected for RS-485
4
-
-
-
5
Bidirectional
B-line
RS-485 B-line
6
-
-
-
7
IN
Rx
RS-232 Data Receive
8
OUT
Tx
RS-232 Data Transmit
9
Bidirectional
A-line
RS-485 A-line
LED NET
STATE
INDICATES
DESCRIPTION
OFF
No power or no data exchange
-
YELLOW
Frame Reception or Transmission
Data exchange
RED
Fatal Error
One or more non-recoverable errors detected
LED STS
STATE
INDICATES
DESCRIPTION
OFF
Initializing or no power
-
GREEN
Module initialized
Module initialized – no error
RED
Fatal Error
One or more non-recoverable errors detected
RED blinking (1 flash) Communication fault or
configuration error
•Invalid setting in Network Configuration Object
•Setting in Network Configuration Object has been changed
during operation
RED blinking (2 flashes)
Application diagnostic available
-
LED CONNECT
STATE
INDICATES
DESCRIPTION
Green
USB connected
Module connected to Pc via USB
OFF
USB not connected
Module not connected
The image does not
show the specific
model
The image does not
show the specific
model

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 9
DESCRIPTION
The MBx communication module gives access to various information related to the DSC
system and allows to send commands from the PLC.
Each device connected to the DSC inputs is characterized by an ON/OFF status and a
possible diagnostic. The processing of the inputs according to the program loaded on
the DSC generates the ON/OFF status of the safety outputs which can also have
diagnostics.
PROCESS IMAGE
System status and I/O status are available on the cyclic process image, while I/O
diagnostics, system errors and the M1/M1S program CRC are accessible as acyclic data.
The process image has a fixed size with subsections for each information group: there
are sections showing the status of the DSC inputs, the status of the safety outputs, the
status of the probes and, if the dedicated module is present, the value of the analogue
measures.
The Fieldbus inputs allows the PLC to cyclically send up to 32 ON/OFF status and are
used as unsafe inputs in the DSC program.
The System status bits are described as follows:
1. Bit 0: present DSC presence
2. Bit 1: present diagnostic presence
3. Bit 2: error presence
The acyclic sections for diagnostics or errors report significant data if the relative bit is
present in the status byte.
The section dedicated to the input status has a size of 16 bytes and allows to know the
status of up to 128 inputs. The priority order of the modules is as follows:
•M1/M1S, MI8O2, MI16, MI8, MI12, MV2, MV1, MV0, MI8O4.
The section dedicated to the safety outputs status has a size of 4 bytes and allows to
know the status of up to 32 outputs. The priority order of the modules is as follows:
•M1/M1S, MI8O2, MO2, MO4, MOR4, MOR4S8, MO4LHCS8, MI8O4.
If two or more modules of the same type are installed the one with the lowest node
number is shown first.
Each module with inputs has a number of bits corresponding to the number of physical
inputs; thus modules M1/M1S, MI8, MI8O2, MI8O4 will use 1 byte and modules MI12T8
and MI16 2 bytes. Modules MV0, MV1 and MV2 uses 1 byte each.
The status of the probe is represented with 4 bytes.
In fieldbus where the allocation is important (e.g. PROFIBUS, PROFINET), the Fieldbus
input bytes must be mapped before the bytes in output.
If there is a fieldbus module in the DSC system, DSDESIGNER will include in the report a
table with the I/O index for all inputs, fieldbus inputs, probes and safety outputs in the
circuit diagram.
For the process data mapping description for your fieldbus please refer to the
Addendum1: “Process data mapping for MBx Fieldbus expansion modules” annex at
the bottom of the present manual.

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 10
DIAGNOSTICS
Each input and each safety output can generate a diagnostic code.
When the I/O is connected correctly, the diagnostic code is OK and is not exported to the
fieldbus; when a problem on the I/O is detected, the system exports 2 bytes to the fieldbus with:
- the index of the I/O in question
- the relative diagnostic code
The "I/O index" field
This field indicates the number used to identify the I/O with a diagnostic code other than OK.
The I/O index range depends from the system version used. Refer to the following tables to
know these data.
SYSTEM VERSION IN USE (version for M1 fw < 5.0.0)
TYPE OF SIGNAL
I/O INDEX
Input
1-128
Output
192-255
Table 4
SYSTEM VERSION IN USE (version for M1S fw > 5.0.0)
TYPE OF SIGNAL
I/O INDEX
Input
1-128
Output
1-32
Table 5
Figure 2 - Index of I/O
I/O index

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 11
The "Diagnostic code" field
The "Diagnostic code" field indicates the diagnostics for the I/O. Possible values for this field are
shown in the following tables.
Input diagnostics
CODE
NAME
MEANING
128
Input diagnostics OK
1
Not passed from zero
Both contacts have not returned to their rest position
2 Simultaneous control failed
The two contacts of a generic two-channel input do not close
simultaneously
3
Two hands Simultaneity failed hand 1
Incorrect connection of one side of a two-hand command
4
Two hands Simultaneity failed hand 2
Incorrect connection of one side of a two-hand command
7
Incoherent selector
The selector cannot have more than one active input
8
Disconnected selector
The selector cannot have any active input
10
OUT_TEST error
Presence of diagnostics on an OUT_TEST connected to the input
11
Second input KO
Redundancy check failed on entry
13
Output connected to other inputs
The test output is not connected to the configured input
14
Output OK but input connected to 24DC
Input blocked
15
Short circuit between photocell test and
photocell input
The response time of the photocell is too low
16
Photocell does not respond
Test signal on the emitter is not present on the photocell receiver
17
Short circuit between photocells
Test signal is present on two different photocells
18
Safety carpet not connected
One of the two carpet connections is not correct
19
Output not congruent to feedback
Test signal applied to the input is present on more than one OUT_TEST
20
Wrong connection
Test signal is present on more than one input
21
Stucked output
Test signal applied to the input is not present on the OUT_TEST
22
Second OUT_TEST KO
Redundancy check failed on OUT_TEST
23
MVx Proxy resource missing
24
MVx Encoder resource missing
25
MVx Resource proxy encoder missing
26
MVx Resource proxy1 proxy2 missing
27
MVx Resource encoder1 encoder2 missing
28
MVx Frequency congruence error
29
MVx Encoder supply missing
30
MVx Encoder fault
40
MA4 Reading out of lower threshold
41
MA4 Disconnected sensor
42
MA4 Reading out of upper threshold
43
MA4 Overload
44
MA4 Mismatch between channels
133
Simultaneity two failed hands
The two contacts of a two-handed control do not close at the same time
134
Never started
Input with failed test at startup
137
Waiting for restart
Reset to an input with manual reset has not been activated
133 (0x85)
1
TWO-HAND concurrent failed
Two-hands switch has to change state simultaneously
134 (0x86)
2
Not started
Start test failed
137 (0x89) 3
Waiting for restart
The input has manual reset and has not been restarted
Table 6
1 The diagnostic 133 does not provide visual error message on the LED DSC
2 The diagnostic 134 does not provide visual error message on the LED DSC
3 The diagnostic 137 does not provide visual error message on the LED DSC

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 12
Output diagnostics
CODE
NAME
MEANING
0
Output diagnostics OK
1
Enable missing
2
Waiting for OSSD to restart
3
Feedback K1 K2 missing
4
Waiting for other micro
Redundancy check failed on the OSSD
5
OSSD power supply missing
6
Exceeded maximum time restart
7
Feedback K1 K2 external not congruous
8
Waiting feedback K1 K2
9
OSSD output overload
10
OSSD with load set to 24V
Table 7

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 13
EXAMPLES OF DIAGNOSTICS
Example 1
In the example shown in Figure 3, Input 1 (connected to module M1/M1S) is tested with the M1-
T1 test signal. During wiring, the 24Vdc is connected to input 1 instead of the M1-T1 test signal.
-The I/O index and Diagnostic code fields assume the following values: 1 - 20 to
indicate the diagnostics on input 1 of module M1/M1S (Connection error).
Figure 3
Example 2
In this example, the I/O index corresponds to the logical block and not to the physical terminal
on module M1/M1S.
In Figure 4 for example, the two-hand element connected to the Input 1 and Input 2 physical
terminals corresponds to I/O index No. 1 and the emergency stop connected to the Input 3 and
Input 4 terminals corresponds to I/O index No. 2.
Figure 4
index I/O n°1
index I/O n°2

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 14
Example 3
The example in Figure 5 is similar to example 1, except in this case Input1 is connected to
module MI16 and is tested with the MI16-T1 test signal.
During wiring, the 24Vdc is connected to input 1 instead of the MI16-T1 test signal.
Input 1 has diagnostic code 10 (OUT_TEST error) and OUT_TEST MI16-T1 has diagnostic code 8
(Connection error).
-The I/O index and Diagnostic code fields assume the following values: 1 - 20 to indicate the
diagnostics on input 1 of module MI16.
Figure 5
In the example shown in Figure 5 the manual reset function is enabled on OSSD 1.
The pushbutton connected to input 1 is pressed without sending a reset command.
Example 4
-The I/O index and Diagnostics code fields assume the following values: 1 - 2
-to indicate the diagnostics on OSSD 1A/1B (Table 4: 1= first output).
-to indicate the diagnostic code (Table 7: 2 = Waiting for OSSD to restart).
Figure 6

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 15
BUS CONFIGURATOR USER INTERFACE
The bus module is configured using the USB miniB interface on the front panel and the
“Bus Configurator – User interface” software installed on the DSDESIGNER CD ROM disk.
This software can be used for configuration/communication of the DSC system with a PC (using
an MBU module) or to monitor the data transmitted on the fieldbus (via connection to the USB
port of a bus module).
The diagram below is helpful for understanding possible connections:
EXAMPLES OF CONNECTION
M1/M1S MBx (bus) M1/M1S MBU (USB)
Figure 7
It is important to note that the Bus Configurator behaves differently, depending on whether
communication is with an MBx module or an MBU module:
•MBx MODULE: THE SOFTWARE ONLY ALLOWS DATA TRANSMITTED VIA BUS TO BE
DISPLAYED.
•MBU MODULE: THE SOFTWARE ALLOWS TWO-WAY DATA TRANSMISSION MBU↔PC
(in this case the programmer can set the Fieldbus input directly via computer).
The configuration data depend on the type of the fieldbus module that is connected: the address
field range and the baudrate data will adapt to the fieldbus type.
Selecting the checkbox Analog data will enable the data to be present on the Process image,
changing its size.

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 16
Graphical User Interface
Module configuration must be performed with the system switched off (outputs OFF).
Operator can query module configuration at any time while the module is in use.
To configure the MBx module, proceed as follows:
1. connect the module to the 24VDC+20% power supply via the terminal block;
2. connect the USB cable to the PC and to the MBx module;
3. double click on the "
BUS CONFIGURATOR – USER INTERFACE"
desktop icon.
The configuration window is displayed:
(1) (2) (3) (4)
Figure 8
4. Press the “CONNECT” button.
The program recognizes that a MBx bus module is connected (Figure 8); the status bar shows the
the MBx fieldbus model (1), the MBx firmware version (2), the schematic CRC (3) and the Master
status and firmware version (4):
•gray: the MBx is not connected
•orange: the MBx is getting/sending the configuration from the Bus configurator
•green: the Master is active (RUN)
•red: the Master is not active (e.g. communication with Designer)
Once the module is connected it is recognized and the operator can configure the parameters by
selecting the different areas shown in Figure 8; press the
WRITE
button to send the configuration data to
the module.
As soon as the bus module receives the data, the configurator enters the monitor condition.
The input, output, analog data status and relative diagnostics are illustrated in Figure 8.
Only the first 16 input diagnostics and output diagnostics are shown, if there are more than 16
diagnostics the exceeding one are displayed after the previous one are solved.
The Fieldbus input logical status can be changed by the user only with the MBU module, they are in read
only mode for all the other fieldbuses and they’ll display the status written by the external PLC.

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 17
BACKWARD COMPATIBILITY (VERSION FOR M1 fw < 5.0.0)
Process Image in backward compatibility (version for M1 fw < 5.0.0)
The backward compatibility mode allows the Bus module to use the "old" process image
mapping, i.e.: it will adapt to the hardware installed on the system. This allows to replace
an existing Bus module without changing the PLC program.
The backward compatibility mode works only if the Bus module is connected to an
M1 master module. If a Bus device is set-up in backward compatibility mode and is
connected to an M1S the Bus module will go in fault.
System status, I/O status and I/O diagnostics are available on the cyclic process image.
The process image has a variable size depending on which modules are installed in the
DSC system.
In the process image there are subsections for each information group: there are sections
showing the status of the DSC inputs, the status of the safety outputs, the status of the
probes.
The Fieldbus inputs allows the PLC to cyclically send up to 8 ON/OFF status and are used
as unsafe inputs in the DSC program.
The System status bits are described as follows:
1. Bit 0: present DSC presence
2. Bit 1: present diagnostic presence
The section for diagnostics reports significant data if the relative bit is present in the
status byte.
The section dedicated to the input status has a size of 16 bytes and allows to know the
status of up to 128 inputs. The priority order of the modules is as follows:
•M1, MI8O2, MI16, MI8, MI12, MV2, MV1, MV0.
The section dedicated to the safety outputs status has a size of 1 or 2 bytes and allows
to know the status of up to 16 outputs. The priority order of the modules is as follows:
•M1, MI8O2, MO2, MO4, MOR4, MOR4S8, MO4LHCS8.
If two or more modules of the same type are installed the one with the lowest node
number is shown first.
Each module with inputs has a number of bits corresponding to the number of physical
inputs; thus modules M1, MI8, MI8O2, MI8O4 will use 1 byte and modules MI12T8 and
MI16 2 bytes. Modules MV0, MV1 and MV2 uses 1 byte each.
The status of the probe is represented with 2 bytes.
In fieldbus where the allocation is important (e.g. PROFIBUS, PROFINET), the Fieldbus input
bytes must be mapped before the bytes in output.
If there is a fieldbus module in the DSC system, DSDESIGNER will include in the report a
table with the I/O index for all inputs, fieldbus inputs, probes and safety outputs in the
circuit diagram.
The input and output memory maps are described in Figure 10.

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 18
Diagnostic elements will use 2 bytes which indicate the number of the I/O with the
problem and the value of the diagnostic element. If there is more than one diagnostic
element, the relative values alternate every 500ms.
Each set of information:
-input status,
-input diagnostics,
-fieldbus input status,
-probe status,
-safety output status,
-safety output diagnostics
can be enabled/disabled in order to control the information and thus the number of bytes
exported to the fieldbus.
The definition of the process image in the input and output is shown from the point of
view of the DSC.

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 19
Graphical User Interface, backward compatibility (version for M1 fw< 5.0.0.)
The backward compatibility mode allows the operator to use the DSD software by having an M1
master module with firmware version lower than 5.0.0.
This mode can be enabled from the menu: “settings -> enable backward compatibility”
This will bring up a pop-up window with the following message:
The user can choose which subsection must be exported in the fieldbus (refer to Figure 9).
Once the configuration data are selected the operator must press the “WRITE” key to send them
to the module.
Figure 9 - Backward Compatibility
If more than one I/O has some diagnostic the I/O index and diagnostic code data will cycle every
500ms between all the diagnostics present.

DSC fieldbus modules
8540467 • 28/03/2019 • Rev.2 20
Process image configuration in backward compatibility
The input process image and the output process image can be configured using the Bus Configurator User
Interface software.
With this software the user can choose which subsection must be exported in the fieldbus, changing the
size of each process image and then the size used in the PLC physical memory. Once the module is
connected all the data are showed in the main window of the software.
Figure 10 - Data Package Composition in backward compatibility
1
1
2
2
3
3
4
4
5
5
6
6
This manual suits for next models
10
Table of contents