EarthLinked Prime Series Programming manual

PSC-QS (10/16) ©2016 EarthLinked Technologies, Inc.
PrimeSeries
PSCGeothermal HeatingandCoolingSystem
Quick-Start Instructions

PSC-QS (10/16) Page 2
Table of Contents
List of Figures...................................................................................................................................3
List of Revisions ...............................................................................................................................4
Model Nomenclature .......................................................................................................................5
Safety................................................................................................................................................6
Equipment Manuals.........................................................................................................................6
Installation ........................................................................................................................................7
1) Component Matching...............................................................................................................7
2) Compressor Unit Placement ....................................................................................................8
3) Refrigeration ............................................................................................................................9
4) System Applications and Electrical.........................................................................................13
5) EarthLinked® Diagnostic and Monitoring system (EDM)........................................................19
6) Air Zoning ..............................................................................................................................19
7) SureStart................................................................................................................................21
Earth Loop Protection System .......................................................................................................25
1) Anode Wire Installation..........................................................................................................25
2) EPS Operation and Service ...................................................................................................30
3) Current Verification ................................................................................................................31
Start-Up Process.............................................................................................................................32
1) System Leak Check...............................................................................................................32
2) Evacuation.............................................................................................................................35
3) Initial Charge..........................................................................................................................37
4) Final Charge ..........................................................................................................................39
Troubleshooting.............................................................................................................................44
1) Compressor ...........................................................................................................................44
2) System...................................................................................................................................48
Commissioning Document ............................................................................................................51
Tools and Equipment.....................................................................................................................58
Triple Evacuation............................................................................................................................59
Appendix: Functions of the Nano-PLC (for Air-only models) ......................................................60

PSC-QS (10/16) Page 3
List of Figures
Figure 1. Matching Component Model Numbers................................................................................... 7
Figure 2. General Layout of System Components ...............................................................................8
Figure 3. Compressor Unit Bracket Installation.....................................................................................9
Figure 4. Compressor Unit Clearance................................................................................................... 9
Figure 5. PSC Connections ................................................................................................................ 10
Figure 6. Line Set Sizes...................................................................................................................... 12
Figure 7. PSC Electric Box Components & Electrical Data ................................................................. 14
Figure 8a. PSC Compressor Electrical Schematic, 230-1-60.............................................................. 15
Figure 8b. PSC Compressor Unit Electrical Schematic, 230-3-60....................................................... 16
Figure 9. PSC Air Heating/Cooling System Application....................................................................... 17
Figure 10. PSC Air Heating/Cooling System Field Wiring Diagram..................................................... 18
Figure 11. Air Zoning Option Kit, Field Wiring Diagram....................................................................... 20
Figure 12. SureStart Mode of Operation............................................................................................. 22
Figure 13. Compressor Cabinet Socket/Cap...................................................................................... 25
Figure 14. Disassembled Plug Connector.......................................................................................... 26
Figure 15. Anode Wire Insertion ........................................................................................................ 27
Figure 16. Install the Plug Insert ........................................................................................................ 28
Figure 17. Engage the Gland Nut ...................................................................................................... 28
Figure 18. Secure the Anode Wire..................................................................................................... 29
Figure 19. The Plug and Socket Joint................................................................................................ 29
Figure 20. Electric Box with EPS Components .................................................................................. 30
Figure 21. EPS Curent Ratings.......................................................................................................... 31
Figure 22. Typical Test for DC Current .............................................................................................. 31
Figure 23. PSC Internal Flow Schematic ............................................................................................ 33
Figure 24. PSC Piping........................................................................................................................ 34
Figure 25. Evacuation of PSC System................................................................................................ 36
Figure 26. Initial Charge of PSC System............................................................................................. 38
Figure 27. Final Charge of PSC System............................................................................................ 40
Figure 28. Charging to the Middle Sight Glass (Heat only units)........................................................ 41
Figure 29. Final charging to the Top Sight Glass (Heat/Cool units).................................................... 41
Figure 30. Pressure-Temperature for R-410A..................................................................................... 42
Figure 31. Start-Up Process ............................................................................................................... 43
Figure 32. Compressor Unit Voltage Information............................................................................... 45
Figure 33. Compressor Motor Circuit Testing..................................................................................... 46
Figure 34. Compressor Motor Grounded Winding Test...................................................................... 47

PSC-QS (10/16) Page 4
Figure 35. System Troubleshooting Chart.......................................................................................... 48
List of Revisions
Corrected Piping and Internal Flow Schematic
Revised electrical drawings and electric box
Revised charging method due to elimination of TXV
Units now feature a nano Programmable Logic Controller (PLC) which allows
the following features:
True two-speed system
Automatically controls Heating and Cooling staging both of the
Geothermal system and the Auxiliary Heat
Comes with Dual fuel mode capability - Gas or Electric
Thermostat-agnostic: works with most thermostats on the market.
Minimum requirement: single stage Heat/Cool thermostat
Eliminates the need for external balance point control or for an outdoor
sensor
Zoning-friendly for air applications (relies on a damper zone)
See Appendix for more details

PSC-QS (10/16) Page 5
Model Nomenclature
Disclaimer
Proper installation and servicing of the EarthLinked®Heat Pump is essential to its reliable
performance. All EarthLinked®systems must be installed and serviced by an ETI trained and
authorized technician. Installation and service must be made in accordance with the instructions set
forth in this manual. Failure to provide installation and service by an ETI trained and authorized
installer in a manner consistent with this manual will void and nullify the limited warranty coverage for
the system.
EarthlinkedTechnologies shall not be liable for any defect, unsatisfactory performance, damage or
loss, whether direct or consequential, relative to the design, manufacture, construction, application or
installation of the field specified components.
Earthlinked Technologies, Inc.
4151 S. Pipkin Road
Lakeland, Florida 33811 USA
phone: 863-701-0096 | toll-free: 866-211-6102
General Info: info-question@earthlinked.com
www.earthlinked.com
CSI # 23 80 00

PSC-QS (10/16) Page 6
Safety
Warning, Caution and Important notices appear throughout the manual. Read these items carefully
before attempting installation, servicing or troubleshooting the equipment.
Equipment Manuals
The following is a listing of the equipment installation manuals that are provided with each component
specified for this EarthLinked®system.
Series AVS and AVV Air Handler
Series CCS Cased Coil
Series HCM Hybrid Cooling Module
Earth Loop Specification and Installation Manual
Earth Loop Protection Kit Installation Manual
EarthLinked Diagnostic and Monitoring system (EDM) Installation Manual
IMPORTANT!
Notification of installation, operation or maintenance information which
is important, but which is not hazardous.
WARNING!
Indicates a hazardous situation, which if not avoided will result in
serious injury or death, or equipment or property damage.
CAUTION!
Indicates a potentially hazardous situation or an unsafe practice, which
if not avoided, may result in injury, or equipment or property damage.
IMPORTANT!
Read and follow all installation instructions in these manuals,
appropriate for the EarthLinked®system being installed, BEFORE
initiating the Start-Up procedure.

PSC-QS (10/16) Page 7
Installation
1) Component Matching
Upon receipt of the equipment, carefully check the component model numbers by referencing
Figure 1, to ensure that all components of the system match.
Prime
Compress.
Unit1
Air Handler
Cased Coil
Hybrid
Cooling
Module
Earth
Loop2
ETI
Four Speed
Model
Arcoaire
Four Speed
Model
ETI
Variable
Speed Model
Arcoaire
Variable Speed
Model
ETI
Model
Arcoaire
Model
-025
AVS-0025-C*
FEM4P3000AL
AVV-0025-C*
FVM4X3600BL
CCS-0025-C*
EAM4X30L17A
HCM-1836C
-024-C
-030
AVS-0030-C*
FEM4P3600AL
AVV-0030-C*
FVM4X3600BL
CCS-0030-C*
EAM4X36L21A
-030-C
-036
AVS-0036-C*
FEM4P4200AL
AVV-0036-C*
FVM4X4800BL
CCS-0036-C*
EAM4X42L24A
-036-C
-040
AVS-0040-C*
FEM4P4800AL
AVV-0040-C*
FVM4X4800BL
CCS-0040-C*
EAM4X48L24A
HCM-4272C
-042-C
-050
AVS-0050-C*
FEM4X6000BL
AVV-0050-C*
FVM4X6000BL
CCS-0050-C*
EAM4X60L24A
-048-C
-060
AVS-0060-C*
FEM4X6000BL
AVV-0060-C*
FVM4X6000BL
CCS-0060-C*
EAM4X60L24A
-060-C
1. Contained in each compressor package:
compressor unit
four L-shaped hold down brackets
product literature
2. All series Earth Loops
Figure 1. Matching Component Model Numbers
Guidelines for the general layout of the system components are shown in Figure 2. Before placing the
compressor unit (outside or indoors), review the guidelines in Figure 2.
Warning!
WEAR ADEQUATE PROTECTIVE CLOTHING AND PRACTICE ALL
APPLICABLE SAFETEY PRECAUTIONS WHILE INSTALLING THIS
EQUIPMENT. FAILURE TO DO SO MAY RESULT IN EQUIPMENT
AND/OR PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

PSC-QS (10/16) Page 8
Figure 2. General Layout of System Components
2) Compressor Unit Placement
EarthLinked®compressor units may be located inside or outside. If outside, place
compressor unit on a standard HVAC outdoor unit pad. If inside, place it on a level, hard
surface. If the compressor unit is to be fastened down, see Figure 3 for bracket installation.
Avoid placing the compressor unit in or near sound sensitive areas of the residence.
Attic installations must include an auxiliary condensate pan with drain, and suspension from
rafters with suspension isolators.
Clearance around the unit for service is illustrated in Figure 4. However, local codes and
applicable regulations take precedence.
If the compressor unit or other refrigerant-containing system components are located
indoors, they shall be in a location which (1) is an unoccupied space, or (2) is served by the
circulating air system, or (3) provides 280 cu. ft. of open space per nominal ton of rated
system capacity. The 2012 International Mechanical Code defines residential occupancy
as including permanent provisions for living, sleeping, eating, cooking, and sanitation.
Consult local code authorities to define unoccupied space for the specific installation.

PSC-QS (10/16) Page 9
Figure 3. Compressor Unit Bracket Installation
Figure 4. Compressor Unit Clearance
Placement instructions for other pieces of equipment that make up the EarthLinked®System are
included with those pieces of equipment and are listed in this manual under Equipment Manuals.
3) Refrigeration
After the EarthLinked®compressor unit and other system components are placed, the refrigeration
system tubing is run from the compressor unit to the other components, as appropriate. Figure 5
illustrates the refrigeration and electrical connection points for the compressor unit.
IMPORTANT!
EarthLinked®compressor units that provide space cooling shall be
equipped with an EarthLinked® Hybrid Cooling Module (HCM) when:
(1) Required by the performance tables; OR
(2) System is in a Cooling dominant application where soil thermal
conductivity is unknown or known to be poor (less than 1
BTU/hr.ft.°F). Examples of such soils are light dry soil, dry sand, peat
and organic soils, dry clay and hardpan; OR
(3) In any system where soil thermal conductivity is unknown or known
to be poor (see (2) for definition) and ambient outdoor temperatures
have exceeded the outdoor summer design temperature conditions
for a continuous system run time of at least 7 hours.

PSC-QS (10/16) Page 10
PORT
FUNCTION
TYPE OF
CONNECTION
COMPRESSOR UNIT MODEL
CONNECTION SIZE, INCHES
-025
-030
-036
-040
-050
-060
A
Electrical, Power
1-1/4” Hole
1
1
1
1
1
1
B
Electrical, Control
7/8” Hole
3/4
3/4
3/4
3/4
3/4
3/4
1
AH/CC/HWM Liquid
Braze
1/2
1/2
1/2
1/2
1/2
1/2
3
EL Liquid*
Braze
3/8
3/8
1/2
1/2
1/2
1/2
4
Anode Socket
--
---
---
---
---
---
---
5
EL Vapor*
Braze
5/8
3/4
3/4
3/4
7/8
7/8
6
AH/CC/HWM Vapor
Braze
3/4
3/4
3/4
7/8
7/8
7/8
7
Plugged
----
----
----
----
----
----
----
8
Plugged
----
----
----
----
----
----
----
9
Electrical, control
----
----
----
----
----
----
----
10
Electrical, control
----
----
----
----
----
----
----
N = Nameplate and other information
*Line set sizes
LEGEND
AH –Air Handler
CC –Cased Coil
EL –Earth Loop
HWM –Hydronic Water Module
HWT –Hydronic Buffer Tank
DWT –Domestic Water Tank
Figure 5. PSC Connections
IMPORTANT!
EarthLinked®compressor units that provide space heating shall be
equipped with a Heating Performance Enhancement kit (HPE) when
required by the performance tables.

PSC-QS (10/16) Page 11
Caution!
REFRIGERANT PIPING CONNECTIONS
Refrigerant joints are to be brazed with 15% silver content brazing
alloy, utilizing the NITROGEN BRAZING PROCESS.
NITROGEN BRAZING PROCESS
PURPOSE:
Utilize the NITROGEN BRAZING PROCESS on all brazed refrigerant
piping connections. This process eliminates oxidation products from
inside joint surfaces.
TECHNIQUE:
“Trickle” nitrogen gas at 1-2 psi pressure through the joint area being
brazed, to displace the oxygen. When oxygen has been displaced,
turn off the nitrogen, and relieve the pressure at the joint to
atmospheric prior to brazing.
CONSEQUENCES:
Failure to displace oxygen with nitrogen at the brazed joint will result
in particulate matter being released into the system. The result is
discoloration of refrigerant oil, contamination of the system and
possible system failure.
Compressor units are shipped from the factory with a low pressure nitrogen holding charge. Carefully
relieve the holding charge when the compressor unit is being prepared to connect refrigerant system
piping.
Caution!
This compressor unit is equipped with Copeland Ultra 32-3MAF Polyol
Ester Oil (POE). This is the only brand and type of oil that is
recommended for use with ETI compressor units.
POE oil absorbs significant amounts of moisture from the air very
rapidly. Exposure of the POE oil to air must be minimized. Even a few
minutes of exposure to air can be harmful to the system.
After the initial nitrogen holding charge has been released from the
compressor unit, it is critical that air not be allowed to enter the
compressor unit during the process of preparing compressor unit
refrigerant connections (tube cutting, deburring, cleaning, brazing, etc).
To ensure air does not enter the compressor unit while preparing
refrigerant connections, “trickle” dry nitrogen through the compressor
unit, entering at the access port nearest the Active Charge Control
(ACC), to keep airborne moisture out of the compressor unit and the
POE oil.
Complete preparing and brazing all compressor unit refrigerant
connections at one setting to minimize exposure of open connections
to air. Failure to implement the above precautions will result in an
extended period of time to effectively evacuate the system, and may
adversely affect system performance and cause system failure.

PSC-QS (10/16) Page 12
The compressor unit has factory installed service valves on the earth loop vapor and liquid stubouts
outside the compressor cabinet.
For the installation of system components requiring refrigeration connections, refer to Figure 6 for line
set sizes and the appropriate installation manual(s) following Figure 6.
LINE SET ADAPTERS REQUIRED FOR THE AIR HANDLER OR CASED COIL ARE FIELD
SUPPLIED. CHECK ALL APPROPRIATE COMPRESSOR UNIT STUB-OUT TUBING SIZES FOR
REQUIRED FIELD SUPPLIED ADAPTERS!
EARTHLOOP, AIR HANDLER, CASED COIL LINE SETS
COMPRESSOR UNIT
SIZE
LINE SET O.D., INCHES
LIQUID
VAPOR
2.0 Tons (-025)
3/8
5/8
2.5 Tons (-030)
3/8
3/4
3.0 Tons (-036)
1/2
3/4
3.3 Tons (-040)
1/2
3/4
4.2 Tons (-050)
1/2
7/8
5.0 Tons (-060)
1/2
7/8
*Liquid and Vapor lines must BOTH be insulated with Armaflex®
or equivalent with at least 1/2” wall thickness for the full length of
the line set.
Figure 6. Line Set Sizes
Series AVS and AVV Air Handler
Series CCS Cased Coil
Series HCM Hybrid Cooling Module
Earth Loop Specification and Installation Manual
After installing and nitrogen brazing the HVAC system components, turn the Service Valves to Full
Open and pressurize the refrigeration system to 150 psig with dry nitrogen and a trace of refrigerant.
Valve off the nitrogen Tank from the HVAC system components and check joints with a sensitive
Electronic Leak Detector and bubble solution to ensure they are sealed. Repair any leaks and re-test
as appropriate.

PSC-QS (10/16) Page 13
4) System Applications and Electrical
The PSC compressor unit electrical box major components and electric data for all compressor sizes
are shown in Figure 7.
The PSC series compressor units are equipped with a Nano-PLC (Programmable Logic Controller) to
provide a range of functions that enhance the comfort and efficiency of system operation. See the
Appendix detailing the PLC Functions for Air Only Systems.
The SureStart Module is a factory installed component that (1) reduces compressor starting current;
(2) reduces compressor starting torque, thus reducing stress on the compressor at start-up; and (3)
monitors the run capacitor.
The Earth Loop Protection Control System, comprised of the EPS Power Supply, EPS Module and
EPS Fuse is contained within the electric box. This system is factory wired and ready to be connected
to the anode wire through an external electrical connection on the backside of the compressor cabinet.
The anode wire connection is detailed in a later section of this manual.
PSC Heating and Cooling System electrical and application illustrations are as follows.
Figure 8a. PSC Compressor Unit Electrical Schematic, 230-1-60
Figure 8b. PSC Compressor Unit Electrical Schematic, 230-3-60
Figure 9. PSC Air Heating/Cooling System Application
Figure 10. PSC Air Heating/Cooling System Field Wiring Diagram

PSC-QS (10/16) Page 14
Compressor
Unit Model
Compressor
Model
Voltage/Phase/
Hz
Voltage
LRA
RLA
MCA
MFS
Min.
Max.
-025-1C
ZPS26K5E-PFV
230-1-60
207
253
73.0
14.6
18.0
30
-025-2C
ZPS26K5E-TF5
230-3-60
207
253
58.0
9.6
12.0
20
-030-1C
ZPS30K5E-PFV
230-1-60
207
253
83.0
17.0
21.0
35
-030-2C
ZPS30K5E-TF5
230-3-60
207
253
73.0
12.9
16.0
25
-036-1C
ZPS35K5E-PFV
230-1-60
207
253
96.0
20.0
25.0
40
-036-2C
ZPS35K5E-TF5
230-3-60
207
253
88.0
15.8
19.0
30
-040-1C
ZPS40K5E-PFV
230-1-60
207
253
104.0
23.6
29.0
45
-040-2C
ZPS40K5E-TF5
230-3-60
207
253
83.1
15.6
19.2
30
-050-1C
ZPS51K5E-PFV
230-1-60
207
253
152.9
30.2
37.0
50
-050-2C
ZPS51K5E-TF5
230-3-60
207
253
110.0
18.4
23.0
35
-060-1C
ZPS60K5E-PFV
230-1-60
207
253
179.2
33.1
41.0
60
-060-2C
ZPS60K5E-TF5
230-3-60
207
253
136.0
19.6
24.0
35
LRA = Locked Rotor Amps
RLA = Rated Load Amps
MCA = Minimum Circuit Ampacity
MFS = Maximum Fuse or HACR Circuit Breaker Size
(External)
Average Wire Size = Consult NEC and Local Codes
Figure 7. PSC Electric Box Components & Electrical Data
Single Phase Electric Box

PSC-QS (10/16) Page 15
Figure 8a. PSC Compressor Electrical Schematic, 230-1-60

PSC-QS (10/16) Page 16
Figure 8b. PSC Compressor Unit Electrical Schematic, 230-3-60

PSC-QS (10/16) Page 17
Figure 9. PSC Air Heating/Cooling System Application

PSC-QS (10/16) Page 18
Figure 10. PSC Air Heating/Cooling System Field Wiring Diagram

PSC-QS (10/16) Page 19
5) EarthLinked® Diagnostic and Monitoring system (EDM)
The EarthLinked® Diagnostic and Monitoring system (EDM), as shown in Figure 7, provides real-time
remote monitoring and tracks pressures, temperatures, power consumption and thermostat signals. It
connects via Internet, Bluetooth, USB and SD card. The EDM system is factory-installed in all PRIME
series units. Sensors are already connected to respective components and the system will begin
collecting data at unit startup. The EDM system has the ability to send data remotely to the Earthlinked
online Dealer Dashboard when connected to the homeowner’s internet router with an Ethernet cable.
Technicians can also wireless access the EDM data onsite with a Bluetooth connection to a phone or
tablet. For homeowners without Internet access, or as a secondary data backup, the EDM system has
an onboard SD Memory Card Writer that records the time, date, and sensor/signal values that can be
personally graphed or uploaded to the Dealer Dashboard for review.
For more information on the EDM system, refer to the EDM-IOM manual.
6) Air Zoning
Prime series compressor units are compatible with Air Zoning thanks to the Nano-PLC (see Appendix
for more information).
When zoning a forced air system, it is recommended to design the smallest zone of the system so that
it has the air flow capacity to support the minimum airflow requirement of the system (400 CFM /
nominal) while the system is in a second stage without exceeding 1” WC total static pressure across
the Air Handler unit when only that zone calls.
AVV Series Variable Speed Air Handlers should be used in any zoning application.
Bypass dampers between the supply and return plenums should not be used.
In the event that a zone is too small to meet the requirements above, the Air Zoning Option kit (AZO-
KIT) must be purchased and installed. Such a designed zone may in fact never see a second stage
call, which will force the system into a 5 minute second stage maintenance cycle from time to time to
ensure oil return from the field back to the compressor unit.
IMPORTANT!
Failure to meet this requirement can result in shortened blower motor
life, noise issues and can cause performance, efficiency and reliability
issues with the compressor unit itself.

PSC-QS (10/16) Page 20
The Air Zoning Option kit is designed to use the Damper Override “D” terminal signal of the
compressor unit to force open the largest zone while the EarthLinked system is in maintenance mode.
The kit isolates the zone control and air handler power supplies and ensures system performance and
reliability by providing a means of making “R” and “Y” thermostat input of the zone board’s largest
zone. Forcing that zone open relieves excessive static pressure at the air handler.
See Figure 11 for the Field Wiring Diagram of the Air Zoning Option Kit.
Figure 11. Air Zoning Option Kit, Field Wiring Diagram
Table of contents
Other EarthLinked Air Conditioner manuals