Under BS5839 part 1 a zone plan of the premises must be
created and should be positioned on, adjacent to or in close
proximity to the fire panel and repeater panels. The zone
plan should have North at the top of the plan and should
ideally be positioned on a North facing wall. This is to help
the fire brigade locate a fire quickly.
IT IS THE RESPONSIBILITY OF THE PREMISES
MANAGEMENT TO ENSURE THAT AN APPROPRIATE
ZONE PLAN IS ISSUED BY THE INSTALLER WHEN THE
SYSTEM IS HANDED OVER.
What are Sounder Circuits?
The sounder circuits allow for conventional only sounders,
beacons or sounder beacons to be installed on the system.
These will operate in a fire condition at the same time as
any BiWire sounders/beacons on BiWire configured zones.
What is FRE?
FRE is an abbreviation for Fire Routing Equipment.
Depending on the model of panel purchased, an optional
FRE output may be provided. This optional output is
generally used for connecting the fire alarm system to fire
routing equipment such as auto diallers that will contact the
fire brigade or an alarm receiving centre (ARC), etc. This type
of output is fully monitored by the fire system for any fault
condition.
What is FPE?
FPE is an abbreviation for Fire Protecting Equipment.
Depending on the model of panel purchased, an optional
FPE output may be provided. This optional output is
generally used for connecting the fire alarm system to
fire protection equipment such as sprinklers, door release
systems, etc. This type of output is fully monitored by the
fire system for any fault condition.
Important Instructions
3
1. Introduction
1.1 Purpose
This user manual is aimed at the Premises Management
responsible for the fire alarm system and provides guidance
on how to operate the system, undertake routine testing,
and filling in the log book as required by BS5839 part 1.
After the system has been installed and commissioned by
a Competent Person, the Premises Management for the
site must ensure that all users of the system have read this
manual and are trained on its use.
1.2 Definitions
Premises Management
Is a delegated person or persons with specialist knowledge
and day-to-day control of the premises, the Fire System, and
the implementation of the fire procedures.
Competent Person
Is a person with relevant current training and experience,
and with access to the requisite tools, equipment and
information, and capable of carrying out the defined task.
A competent person is generally an employee from the
manufacturer of the fire alarm system, an installer, or service
engineer who is contracted to maintain the system.
1.3 About the BiWire Flexi System
What is BiWire Flexi?
Standard conventional panels have the fire detection devices
and manual call points on zone circuits with separate
circuits for activating fire alarm devices. Standard 2-wire
panels (such as the BiWire Ultra) have the fire detection and
fire alarm devices combined onto the zone circuits.
BiWire Flexi is switchable between conventional and
BiWire zone circuits allowing a combination of zone type
configurations to suit every application, along with separate
conventional sounder circuits to provide a full conventional
solution.
What are Zones?
The premises that the fire alarm system is providing
coverage for is split into areas of fire detection called zones.
The size of each zone is governed by BS5839 part 1 and will
be calculated when the fire system is being specified prior
to installation.
The number of zones required to provide coverage of the
entire premises will govern the fire panel model required, 2,
4 or 8 zones are available in the BiWire Flexi range.
IMPORTANT
March 2016 www.eaton.com
EATON BiWire Flexi User Manual (PR215-216-519-03 15-03-16, PINSTFLEXIUSER)