Eaton 9PHD Manual

User's and installation
guide
Eaton 9PHD Accessory Cabinets
TFC-A, EBC-F and EBC-G
P-164000538

Copyright © 2022 Eaton Corporation plc. All rights reserved.
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the
equipment and save this manual for future reference.
This is a product for commercial and industrial application in the second environment.
Installation restrictions or additional measures may be needed to prevent disturbances.
The contents of this manual are the copyright of the publisher and may not be reproduced
(even extracts) without the written approval of Eaton Corporation. Every care has been
taken to ensure the accuracy of the information contained in this manual, but no liability
can be accepted for any errors or omission. The right to make design modifications is
reserved.
Unauthorized copying and lending are prohibited.
Eaton Power Quality Oy
Address: Koskelontie 13
FI-02920 Espoo
FINLAND
Internet: www.eaton.eu
Approvals and version history
Revision Date Description of change Approved by
1 28.01.2016 First issue Otto Asunmaa
2 24.03.2017 Second issue, layout and other
changes
Otto Asunmaa
3 23.08.2022 Third issue, information on EBC-G bat-
tery cable connections updated
Juha Manninen
Original instructions _X_ / Translation of the original instructions __
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 2 (63)

Contents
1 How to read this manual.......................................................................... 5
1.1 Safety-related signs.................................................................... 5
1.2 Safety symbols............................................................................5
1.2.1 Hazard symbols............................................................. 5
1.2.2 Prohibited action symbols..............................................5
1.2.3 Mandatory action symbols............................................. 6
1.3 Conventions used in this document............................................ 6
1.4 Glossary......................................................................................6
2 Safety instructions....................................................................................8
2.1 Audience................................................................................... 10
2.2 CE marking............................................................................... 10
2.3 User precautions.......................................................................10
2.4 Environment..............................................................................11
2.5 Symbols on the UPS and accessories......................................12
2.6 Warning labels and notices in rooms........................................ 12
2.7 For more information.................................................................12
3 Installation and operation....................................................................... 14
3.1 Introduction to EBC-F and EBC-G............................................ 14
3.2 Site preparations.......................................................................17
3.3 Introduction to 9PHD transformer cabinet.................................20
3.4 Options......................................................................................21
3.4.1 IP classifications.......................................................... 21
3.4.2 Lifting eyes...................................................................21
3.4.3 Vibration dampers........................................................21
3.4.4 Other options............................................................... 22
3.5 How to unpack and unload the accessory cabinets..................22
3.5.1 How to unpack and unload the EBC-F and TFC-A
with casters.........................................................................22
3.5.2 How to unpack and unload the EBC-G with casters....25
3.5.3 How to unpack and unload all accessory cabinets
with vibration dampers........................................................30
3.6 How to install the EBC-F and EBC-G....................................... 32
3.7 How to install the transformer cabinet.......................................42
3.7.1 How to install transformer cabinet power wiring.......... 48
3.7.2 How to install transformer cabinet signal wiring...........51
3.8 Installation compatibility of the EBC-F, EBC-G and TFC-A...... 52
3.9 Installation checklist.................................................................. 53
3.10 Operation.................................................................................. 53
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 3 (63)

4 Maintenance...........................................................................................55
4.1 Important safety instructions..................................................... 55
4.2 Performing preventive maintenance......................................... 56
4.2.1 Periodic maintenance.................................................. 56
4.2.2 Annual maintenance.................................................... 56
4.2.3 Battery maintenance....................................................56
4.3 Recycling the used UPS or batteries........................................ 56
4.4 Maintenance training.................................................................57
5 Technical data........................................................................................58
5.1 Directives and standards.......................................................... 58
5.2 Battery specification..................................................................58
5.3 Environmental specifications.................................................... 59
5.4 Cabinet specifications............................................................... 60
6 Warranty.................................................................................................61
6.1 General..................................................................................... 61
6.2 Whom to contact in case of Warranty....................................... 62
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 4 (63)

1 How to read this manual
1.1 Safety-related signs
The following table explains the safety-related signs used in this document.
DANGER DANGER indicates a hazard with a high level of risk which, if
not avoided, will result in serious injury or death.
WARNING
WARNING indicates a hazard with a medium level of risk which,
if not avoided, could result in serious injury or death, or damage
to your machine.
CAUTION
CAUTION indicates a hazard with a low level of risk which, if not
avoided, could result in minor or moderate injury, or damage to
your machine.
Note: Notes are used to indicate important information and useful tips.
1.2 Safety symbols
1.2.1 Hazard symbols
These symbols indicate a hazardous situation or action. Symbols are used to
warn of situations, which may cause environmental damage and personal injury.
General warning sign Explosion and fire hazard
Electrical hazard Corrosive hazard
Battery hazard
1.2.2 Prohibited action symbols
These symbols are used to indicate an action that should not be taken.
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 5 (63)

General symbol for pro-
hibited action
No smoking
Limited or restricted ac-
cess
1.2.3 Mandatory action symbols
These symbols are used to indicate an action that must be taken.
General symbol for man-
datory action
Disconnect from power
source
Read the manual or in-
structions
1.3 Conventions used in this document
This document uses the following type conventions:
•Bold type highlights important concepts in discussions, key terms in
procedures and menu options, or represents a command or option that you
type or enter at a prompt.
•
Italic type
highlights notes and new terms when they are defined.
•Screen type represents information that appears on the screen or LCD.
1.4 Glossary
Eaton manuals use the following acronyms to refer to Eaton UPS products or
their parts.
Table 1: Glossary of acronyms
ABM Advanced Battery Management
BIB Bybass Input Breaker
EBC External battery cabinet
EMBS External Maintenance Bypass Switch
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 6 (63)

EPO Emergency Power-off
ESS Energy Saver System
FI-UPM Field Installed UPM
IPM Intelligent Power Manager
IPP Intelligent Power Protector
MBP Maintenance Bypass Switch (component)
MBS Maintenance Bypass Switch (system)
MCB Miniature Circuit Breaker
MCCB Molded Case Circuit Breaker
MIS Maintenance Isolation Switch
MOB Module Output Breaker
REPO Remote Emergency Power-off
RIB Rectifier Input Breaker
SCR Silicon-controlled Rectifier / thyristor
STSW Static Switch
TFC Transformer cabinet
UPM Uninterruptible Power Module
UPS Uninterruptible Power Supply
VMMS Variable Module Management System
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 7 (63)

2 Safety instructions
DANGER
Important safety instructions!
Save these instructions!
CAUTION
Read this document before you start to operate or perform work on the UPS
system.
This document contains important instructions that must be followed during the
installation, operation and maintenance of the accessory cabinets. Read all of
the instructions before operating the equipment. Keep this manual for future
reference.
In this manual, the term UPS refers only to the UPS cabinet and its internal
elements. The term UPS system refers to the entire power protection system –
the UPS cabinet, the battery cabinet, and options or accessories installed.
The accessory cabinets contain components that carry high currents and
voltage. A properly installed enclosure is earthed and IP23 rated against
electrical shock, foreign objects and water. The accessory cabinets are parts of
sophisticated power systems and only qualified personnel are allowed to install
and service them.
DANGER
The accessory cabinets carry lethal voltages. All repairs and service must be
performed by authorized personnel only. There are no user-serviceable parts
inside the cabinets.
DANGER
Operations inside the cabinets must be performed by an authorized Eaton
Customer Service Engineer or by a qualified service officer authorized by
Eaton.
WARNING
To reduce the risk of fire or electric shock, install the battery cabinet in a
temperature and humidity controlled, indoor environment that is free of
conductive contaminants.
The ambient temperature must not exceed 40 °C (104 °F). Do not operate the
UPS near water or excessive humidity (95% maximum). The system is not
intended for outdoor use.
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 8 (63)

Do not move the battery cabinets with batteries inside if the sheet plates are
not installed.
Before you start any installation or service work, make sure that all AC and
DC power sources are disconnected. Power may come from multiple sources.
Also ensure system grounding / protective bonding continuity.
In a parallel system, the output terminals may be energized even when the
UPS is turned off.
Batteries can present a risk of electrical shock or burn from high short-circuit
current.
Electric energy hazard. Do not attempt to alter any battery wiring or
connectors. Attempting to alter wiring can cause injury.
Do not open or mutilate batteries. Released electrolyte may be toxic and is
harmful to the skin and eyes.
IMPORTANT: The battery may consist of multiple parallel strings. Make sure
that you disconnect all strings before installation.
CAUTION
Only qualified service personnel knowledgeable of batteries and the required
precautions are allowed to perform installation or service work on batteries.
Keep unauthorized personnel away from the batteries. Before you install or
replace batteries, consider all the warnings, cautions, and notes concerning
appropriate handling. Do not disconnect the batteries when the UPS is in the
Battery mode.
Make sure that your replacement batteries are of the same number and type
as the battery that was originally installed.
Before you connect or disconnect battery terminals, disconnect the charging
source by opening the corresponding battery circuit breaker.
Check if the battery is inadvertently grounded. If it is, remove the source of
the ground. Contacting any part of a grounded battery can cause a risk of
electric shock. If you disconnect the grounding connection before you work on
the batteries, the risk of an electric shock is less likely.
Dispose of batteries according to your local disposal requirements.
Do not dispose of batteries in a fire. When exposed to flame, batteries may
explode.
To ensure proper cooling airflow and to protect personnel from dangerous
voltages inside the unit, keep the UPS door closed and the front panels
installed.
Do not install or operate the UPS system close to gas or electric heat
sources.
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 9 (63)

Keep the operating environment within the parameters stated in this
document.
Keep the surroundings of the UPS uncluttered, clean, and free from excess
moisture.
Observe all DANGER, CAUTION, and WARNING notices affixed to the inside
and outside of the equipment.
2.1 Audience
The intended audience of this document is as follows:
• People who plan and perform the installation of the UPS system
• People who use the UPS system
This document provides guidelines for how to check the external battery cabinet
delivery and how to install and operate the cabinet.
The reader is expected to know the fundamentals of electricity, wiring, electrical
components and electrical schematic symbols. This document is written for a
global reader.
2.2 CE marking
The product has a CE marking in compliance with the following European
directives:
• LV Directive (Safety) 2014/35/EU
Declarations of conformity with UPS harmonized standards and directives IEC
62040-1 (Safety) is available at www.eaton.eu or by contacting your nearest
Eaton office or authorized partner.
2.3 User precautions
For the external battery cabinet, the only permitted user operation is to turn the
battery circuit breaker on or off. There are no permitted user operations for the
transformer cabinet.
Follow the precautions and only perform the described operations. Any deviation
from the instructions can be dangerous to the user or cause accidental load
loss.
DANGER
Do not open any screws in the unit. Failure to follow the electrical precautions
can be fatal.
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 10 (63)

2.4 Environment
The accessory cabinets must be installed and operated according to the
recommendations in this document. Never install the accessory cabinets in an
airtight room, in the presence of flammable gases, or in an environment
exceeding the specifications.
Make sure that the battery cabinet room has a sufficient amount of ventilation air
flow. If possible, use natural ventilation. Otherwise, use forced (artificial)
ventilation. If you use forced ventilation, release the air extracted from the
battery room into the atmosphere outside the building.
EBC-F EBC-G
Minimum ventilation air flow
per battery cabinet
5.4 m3/hour 14.5 m3/hour
Minimum free area of open-
ing for inlet and outlet with
natural ventilation
152 cm2406 cm2
The air inlet and outlet must be located at the best possible location to create
ideal conditions for the exchange of air. The following conditions are
recommended:
• Openings on opposite walls
• A minimum separation distance of 2 meters when openings are on the same
wall
• If possible, locate the air inlet at the floor level and the air outlet close to the
ceiling level
Excessive amount of dust in the operating environment of the battery cabinet
may cause damage or lead to malfunction. Always protect the battery cabinet
from the outside weather and sunshine. In order to maximize battery service life
time, the recommended operating temperature range is from +20 ºC to +25 ºC.
A temperature increase of 10 degrees reduces the life approximately by 50%.
WARNING
During charge, float charge, heavy discharge, and overcharge, hydrogen and
oxygen gases are emitted from lead-acid and NiCd batteries into the
surrounding atmosphere. Explosive gas mixture may be created if the
hydrogen concentration exceeds 4% by volume in air. Ensure the necessary
air flow rate for the ventilation of the battery cabinet location.
Note: For more information about the battery room ventilation requirements,
including the calculation of the necessary air flow, see: IEC 62485-2: Safety
requirements for secondary batteries and battery installations.
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 11 (63)

2.5 Symbols on the UPS and accessories
The following are examples of symbols used on the UPS or its accessories. The
symbols are used to alert you of important information.
RISK OF ELECTRIC SHOCK
Indicates that a risk of electric shock is present and the associated
warning should be observed.
CAUTION: REFER TO OPERATOR'S MANUAL
Refer to your operator's manual for additional information, such as
important operating and maintenance instructions.
This symbol indicates that you may not discard the UPS or the UPS
batteries in the trash. This product involves sealed, lead-acid batter-
ies and they must be disposed of properly. For more information,
contact your local recycling / reuse or hazardous waste center.
This symbol indicates that you may not discard waste electrical or
electronic equipment (WEEE) in the trash. For proper disposal, con-
tact your local recycling / reuse or hazardous waste center.
2.6 Warning labels and notices in rooms
Doors to battery rooms and cabinets must be marked with warning labels as
follows:
• "Dangerous voltage", if the battery voltage is more than 60 V.
• Barring sign for "Fire, naked flames, smoking prohibited".
• Warning sign "Accumulator, Battery Room" to indicate corrosive electrolyte,
explosive gases, dangerous voltages and currents.
2.7 For more information
Address any inquiries about the UPS and the battery cabinet to the local office
or an agent authorized by the manufacturer. Quote the type code and the serial
number of the equipment.
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 12 (63)

Contact your local service representative if you need help with any of the
following.
• scheduling initial startup
• regional locations and telephone numbers
• a question about any of the information in this manual
• a question that this manual does not answer
Note: For more information about the installation space, safe operation and
working, see IEC 62485-2: Safety requirements for secondary batteries and
battery installations.
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 13 (63)

3 Installation and operation
Figure 1. 9PHD transformer cabinet TFC-A and external battery cabinets EBC-F and EBC-
G
3.1 Introduction to EBC-F and EBC-G
The Eaton external battery cabinets provide emergency short-term backup
power to safeguard operation during brownouts, blackouts, and other power
interruptions. The battery cabinets line-up and match with the Eaton UPS
product line, and should only be used in an Eaton UPS system. This manual
gives instructions on the use and installation of two battery cabinets: EBC-F and
EBC-G.
The EBC-F is designed to be used with an uninterruptible power supply (UPS)
that is rated up to 100 kW output power. The EBC-F has one battery string that
has 36 or 40 battery blocks.
The EBC-G is designed to be used with an uninterruptible power supply (UPS)
that is rated up to 200 kW output power. The EBC-G has one battery string that
has 36 or 40 battery blocks.
Control wiring for both EBC-F and EBC-G is supplied with the cabinet. The
battery cabinet can be located anywhere near the UPS cabinet, if you run the
Battery-to-UPS power wiring outside the cabinets. However, the recommended
way to install the cables is through the left side panel of the battery cabinet, with
the battery cabinet located next to the 9PHD UPS on its right side.
There are several cable entries in the battery cabinets. The cabinets can be
wired in the following ways.
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 14 (63)

• through the left side panel
• through the right side panel
• through the back panel
• through the bottom panel
By default, Eaton UPSs and battery cabinets should only be used with valve-
regulated lead-acid (VRLA) batteries. For the battery specification of your UPS,
see the User’s and Installation Guide of your UPS. Only use batteries that have
been approved by Eaton. If you have to connect other type of batteries or other
energy storage means, consult an authorized Eaton Customer Service Engineer
before you proceed with the installation.
The battery block configuration in the chosen battery cabinet must always match
the UPS requirement. The used battery configuration must be entered into the
UPS settings during commissioning or start-up. Refer to the UPS User’s and
Installation Guide for the UPS configuration.
Both battery cabinets have a temperature sensor (Harness 9PHD EBC
temperature sensor, P-152001325).
If you must use wiring other than that supplied with the cabinet, the following or
similar wiring is recommended.
Table 2: Wiring recommendations and cable connectors
EBC model F G
Breaker rating (A) 200 400
DC connector size (max. mm2)1) 2 x 150 2 x 150
DC connector torque (Nm) 30 30
DC power cable cross area (min. mm2) 2) vs.
UPS rating
(For a maximum of two cabinets in daisy chain)
30...50 kW 50 70
60...80 kW 70 70
90...100 kW 95 95
110...150 kW 2 x 70
160...200 kW 2 x 95
210...250 kW 2 x 120
260...300 kW 2 x 150
Protective bonding connector size (max. mm2)1) 150 M10
Protective bonding connector torque (Nm) 30 41
Protective bonding cable cross area (min.
mm2)2) vs. UPS rating
30...50 kW 25 35
60...80 kW 35 35
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 15 (63)

EBC model F G
90...100 kW 50 50
110...150 kW 70
160...200 kW 95
210...250 kW 120
260...300 kW 150
Cable harness strain relief, power inlets To be defined and drilled at the site
Cable harness strain relief, signal inlets Recommended: M16, Ø 5...10 mm 3)
DC power and protective bonding cable type Rubber insulated copper, 450/750 V,
style: H07
Signal wire connector size and torque 6 mm2, 0.8 Nm
Signal wire size and type 4 x 0.75 mm2, 300/500 V
1) Connectors for daisy chain are equal in number and size.
2) Cable (between the equipment cabinets, two insulating layers) manufacturer
types as an example:
BETAflam 145 flex 600/1000 V / Toxfree ZH RZ1-K HF / Helkama H-Flex PWR PUR
0,6/1 kV / Helkama LKM-HF 0,6/1 kV
50 mm2 15 mm
2 x 50 mm2 28-29 mm
70 mm2 16.4-17 mm
2 x 70 mm2 31.5-33 mm
95 mm 17.6-19.5 mm
2 x 95 mm2 36.7 mm
120 mm2 19.4-21.5 mm
150 mm2 21.5-24.5 mm
Conductor (for internal cabling in the equipment cabinet, one insulating layer)
H07V2-K 450/750 V PVC / BETAtherm 145, HF / NSGAFÖU 1,8/3 kV HF very flexible
25 mm2 o.d 9.2-13 mm
50 mm2 o.d 13-15.5 mm
70 mm2 14-17 mm
95 mm2 16-17 mm -19.5 mm
120 mm2 18-19.5 mm - 21.5 mm
150 mm2 20-21 mm - 23 mm
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 16 (63)

3) Strain reliefs, metal, manufacturer types as an example:
M50
- Wiska 21-35 mm 10065006, EMSKV 50
- Jacob 21-35 mm 50.650 M/R
- Hummel 22-29 mm 1.618.5000.51
- Hummel 27-35 mm 1.618.5000.50
- Hummel 25-31 mm 1.609.5000.51
- Hummel 32-38 mm 1.609.5000.50
- Jacob 24-35 mm 50.650 M
- Pflitsch 31-42 mm bg 250 ms
M40
- Wiska 16-28 mm 10065005, EMSKV 40
- Jacob 16-27 mm 50.640 M/R
M32
- Wiska 13-21 mm 10065004, EMSKV 32
- Jacob 12-21 mm 50.632 M/R
For more information on how to connect external battery cabinets to a UPS,
refer to the User’s and Installation Guide of the UPS in question.
3.2 Site preparations
The accessory cabinet installation site must meet the following guidelines.
• Install the system indoors on a level floor suitable for computer or electronic
equipment.
• Install the system in a temperature and humidity controlled indoor area.
• Install the system in an area that is free of conductive contaminants and has
sufficient air exchange.
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 17 (63)

Figure 2. Accessory cabinet dimensions for IP23/33 models (height with casters / with
vibration dampers)
ATFC-A CEBC-G
BEBC-F
Table 3: The dimensions of the IP54 cabinet
Dimensions (WxDxH)
mm TFC-A and EBC-F EBC-G
IP54 cabinet
dimensions 625 x 987 x 1,958/1,9781) 1,118 x 1,145 x 1,958/1,9781)
1) Height for models with casters: 1,958. Height for models with vibration dampers:
1,978.
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 18 (63)

Figure 3. EBC-F and EBC-G casters
Figure 4. TFC-A casters
Table 4: The maximum weights of the accessory cabinets
Without bat-
teries
With batter-
ies
Shipping
weight with-
out batteries
Shipping
weight with
batteries
Floor load-
ing [kg/m2]
EBC-F 266 kg 970 kg 315 kg 1,030 kg 1,885
EBC-G 750 kg 2,560 kg 820 kg 2,700 kg 2,100
TFC-A 720 kg - 780 kg - 1,400
The battery cabinets use convection cooling to regulate internal component
temperature. Optional ventilation tubes and other adapters for cabinet ventilation
systems are also available. For more information, contact your Eaton sales
representative.
EBC-F:
• Air inlets are at the bottom in front and rear of the cabinet
• Air outlets are at the top in front and rear of the cabinet
EBC-G:
• Air inlet is at the bottom in front of the cabinet
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 19 (63)

• Air outlet is at the top in the rear of the cabinet
Allow clearance in front and rear of each cabinet for proper air circulation. The
clearance required around the accessory cabinets is shown in the following
table.
Table 5: Accessory cabinet minimum clearances
EBC-F [mm] EBC-G [mm] TFC-A [mm]
From the top of the cabinet 500 2) 500 2) 500
From the front of the cabinet 900 900 900
From the rear of the cabinet 100 1) 2) 100 1) 2) 300 1)
From the side of the cabinet 0 3) 0 3) 0 3)
1) Cabling may require more space. 2) With an optional ventilation tube: 0 mm. 3) With
optional vibration dampers: 30 mm.
A DC-rated circuit breaker within each battery cabinet provides protection and
service isolation.
Table 6: Molded case circuit breakers (MCCB) for EBC-F and EBC-G
Rating
(A)
Type Article No
EBC-F 200A Eaton NZMN2-A200-S07-DC 191233
(P-122000239)
EBC-G 400A Eaton NZMN3-A400-S07-DC 189599
(P-122000240)
Use the following 24V shunt-release with early-make auxiliary contact with the
above circuit breakers.
Rating (A) Type Article No
200, 400 Eaton NZM2/3-XAHIV24AC/DC 259810
(P-122000148)
3.3 Introduction to 9PHD transformer cabinet
The 9PHD external transformer cabinet (TFC-A) can house one or two
transformers for the UPS system. You can use either isolation transformers or
autotransformers.
You can use the transformers for the UPS input line (a single feed that supplies
both rectifier and bypass inputs), rectifier input line, bypass input line or output
lines. Typically the transformer cabinet is used for input and output, or input and
bypass lines.
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G User's and installation guide
© Eaton Corporation plc 2022. All rights reserved. Document ID: P-164000538 20 (63)
Other manuals for 9PHD
1
This manual suits for next models
3
Table of contents
Other Eaton Transformer manuals
Popular Transformer manuals by other brands

DX Engineering
DX Engineering Antenna Auto/Transformer DXE-MM-1 manual

Jobsite
Jobsite BT-RF Installation and user guide

Superior Electric
Superior Electric POWERSTAT 136B Series instructions

Pulsar
Pulsar AWT268 quick start guide

F&F
F&F TR-24 quick start guide

Grandstream Networks
Grandstream Networks HT801 quick start guide