3
!
i
i
Restore factory conguration
If the conguration made makes it impossible to access
the server delégo or its correct use, it is possible to re-
store the factory conditions, resetting the IP address and
emptying the supervision project using the “RESET” but-
ton available. In this case, compared to what was pre-
viously seen to restore the IP address, the procedure to
follow is the following:
• open the front panel of the device using a small slotted
screwdriver, and exerting a slight leverage eect in one
of the side slots
• locate the RESET button on the back of the vertical
card
• Press the RESET button for at least 10 seconds un-
til the SERVICE LED on the front of the device starts
ashing, then release the button.
• within the next 5 seconds, press and hold the button for
at least 10 seconds
• When the LED is solidly lit, release the button and wait
for it to go out.
• when the LED goes o, remove and restore the power
supply
• Wait about one minute and log in to the server with the
factory IP address (192.168.0.110).
Network connection
The conguration and use of the voice control interface
requires a connection to the home or company network.
The default IP address of the interface is: 192.168.0.110.
For the initial conguration of the interface, as well as in
case of absence of a network during the installation pha-
se, it is necessary to proceed as follows:
1. connect the interface to your PC via a “cross over” (or
“crossover”) network cable
2. access your PC’s network settings, as illustrated in
your operating system documentation
3. Change the TCP/IP communication protocol settings
(version 4) for the LAN port of your PC, and set the
following parameters manually:
• IP address: 192.16 8.0.100
• Network mask: 255.255.255.0
• Default gateway: 192.168.0.110
• Save and wait for the new settings to take eect. If
prompted, reboot the system.
After these operations, open an Internet browser and
type in the address bar:
http://192.168.0.110
Note! For an optimal browsing experience, we recommend using
one of the following browsers:
• Google Chrome
• Apple Safari
First access
When you open the browser at the default address, the
login screen is displayed:
the voice control interface has the following preset user
at the factory:
Warning! To avoid losing all the congurations made for the au-
tomation project during a factory reset operation, it is recommen-
ded to make periodic backups of the supervision project.
User Password
admin admin
Enter the credentials of the user “admin” and conrm to
access the main screen of the voice interface administra-
tion environment.
Restore factory IP address
If necessary, you can restore the factory IP address of the
voice interface using the RESET button available. Follow
the procedure below:
• open the front panel of the device using a small slotted
screwdriver, and exerting a slight leverage eect in one
of the side slots
• locate the RESET button on the back of the vertical
card
• Press the button for at least 10 seconds until the SER-
VICE LED on the front of the device starts ashing,
then release the button.
• within the next 5 seconds, press and release the button
for 1 second; within a couple of seconds the front LED
will light up solidly for a couple of seconds
• When the LED goes out, the device can be reached at
the factory IP address (192.168.0.110).
If the LED goes out after long press (10 seconds) before
short press, repeat the whole procedure. This procedure
resets the IP address and retains all data relating to the
conguration previously carried out on the automation sy-
stem.
The conguration and commissioning activities of the KNX voice
control interface require specialized skills on the KNX network
and knowledge of the specic automation project carried out with
ETS. To acquire these skills, it is essential to participate in the
courses organized at KNX certied training centers. For further
information: www.knx.it
Dimensions [mm]
36
90,5
Approvals
• CE the products complie with the Low Voltage Directive
(2014/35 / EU) and the Electromagnetic Compatibility
Directive (2014/30 / EU). Tests carried out in accordan-
ce with EN 50491-5-1: 2010, EN 50491-5-2: 2010.
Maintenance
The devices are maintenance-free. To clean them, use
a dry cloth. The use of solvents or other aggressive sub-
stances is absolutely to be avoided.