Ekinex EK-GD2-DL-1-LV User manual

1
DALI 2 standard dimmers at 12 / 48 Vdc
with 1 / 2 - channels
Codes: EK-GD2-DL-1-LV, EK-GD2-DL-2-LV
Main functional characteristics
• Memory function congurable via DALI bus: it stores
the last brightness level, in case of power failure
• Soft switching on and o
• Brightness adjustment to full power o (dim-to-dark)
• Min. brightness level: 0.1% (1% with push for 1 CH)
• DALI-settable dimming curve: linear/logarithmic for
1CH, 2 CH, linear/quadratic/exponential for 4 CH
• On and o times settable via DALI
• Control inputs: N.O. push button (for EK-GD2-DL-1-LV
only), DALI
• Optimized output curve
• Button for mode change and / or DT6 / DT8 selection
(depending on the device version)
• Status LED (switch to stand-by after 1 min.)
DALI 2 bus dimmer with 12/48 Vdc voltage supply and 1
or 2 channels, with brightness of LED sources control and
dimmable in PWM modulation.
Datasheet STEKGD2DL12LV_EN
Note: the 1-CH device factory default values are:
automatic detection of the local command set to
N.O. pushbutton and minimum dimming value set
to 1%.
i
Description
The ekinex dimmers DALI 2 standard with 1 / 2-channels
EK-GD2-DL-1-LV and EK-GD2-DL-2-LV allow brightness
control of LED loads from 12 to 48 Vdc in constant volta-
ge, dimmable in PWM modulation.
• The 1 CH model is DALI DT6 only and equipped with a
local control device (N.O. button), connected directly to
the dedicated input, with stand-alone or status update
function on the DALI bus.
• the 2 CH model can be congured with a single DT6
output channel, 2 single DT6 channels or a single chan-
nel in TW DALI DT8 mode.
DT6 / DT8 setting for EK-GD2-DL-2-LV model is done via
local selector switch. The devices have an integrated bus
communication module DALI 2 certied.
Technical data
Inputs
• Input (constant voltage): 12 / 48 Vdc
• Supply voltage: min: 10.8 Vdc .. max: 52.8 Vdc
• Power absorbed while awaiting command: <500 mW
(for EK-GD2-DL-1-LV only)
• DALI 2 bus input compliant with IEC 62386
Outputs
• Output voltage PWM 12 / 48 Vdc
• Output current: from 0 A to 10 A for EK-GD2-DL-1-LV,
5A on each channel for EK-GD2-DL-2-LV
• Rated power @12V: 120 W
• Rated power @24V: 240 W
• Rated power @48V: 480 W
• Command supply current (EK-GD2-DL-1-LV only): 0.5
mA (for 1-10V)
• Command required max. current (EK-GD2-DL-1-LV
only): 0.1 mA (for 0-10V)
Warning! Dimmers require the use of a power
supply in accordance with EN 61347-2-13, such
as the Mean Well mod. HLG-480H-24A.
!
Note: values for output current and nominal power
have to be intended as maximum values, depen-
ding on the ventilation conditions. The reported
values are measured with a room temperature of
40 °C
i
Dimming
• “Flicker-free” PWM modulation: 2000Hz f
• PWM resolution: 16 bit
• PWM dimming range: 0.1-100% for EK-GD2-DL-1-LV,
1-100% for EK-GD2-DL-2-LV
Environmental conditions and other characteristics
• Operating temperature: -20 ° C ... + 40 ° C
• Storage temperature: - 40 ° C ... + 60 ° C
• Transport temperature: - 40 ° C ... + 60 ° C
• Maximum case temperature (tc): 80 °C
• Relative humidity: 93% non-condensing
• Protection degree IP10 (device installed)
• Wiring: 1.5 mm2 solid – 1.0 mm2 stranded, 16-17 AWG
• Stripping: 5.0 - 6.0 mm
• Housing in plastic material
• Device suitable for installation in ush-mounting wall
boxes

2
Mounting
The devices have degree of protection IP10, and are the-
refore suitable for use in dry interior rooms. The 1 CH and
2 CH models are suitable for installation in wall-mounting
boxes. The plastic support allows mounting on a prole
rail according to EN 60715 inside electrical distribution
panels and cabinets.
Before removing the device, be sure that inputs, outputs,
and the DC power supply have been disconnected.
• Safety class II
• Weight 37 g
• Dimensions (LxHxP): 53 x 61 x 29 mm
1) Control logic protection only
Protections
The device is equipped with the following protections:
• OVP Over voltage protection1
• RVP Reverse polarity protection1
• OCP Open circuit protection
1
2
3
4a
EK-GD2-DL-1-LV
5
4b
2
1
3
EK-GD2-DL-2-LV
4a
4b
Nr. Label Connection
1DC IN (+) DC (+) input
DC IN (-) DC (-) input
2DA DALI pole 1
DA DALI pole 2
3 LED OUT x (+) Output x (+)
LED OUT x (-) Output x (-)
4a -Status internal LED
4b -Feedback or DT6 / DT8 selector (**)
5 (*) PUSH N.O. pushbutton, pole 1
PUSH N.O. pushbutton, pole 2
(*) EK-GD2-DL-1-LV only
(**) EK-GD2-DL-2-LV only
Accessory for 1 CH and 2 CH models
Rail-mounting support
The devices EK-GD2-DL-1-LV and EK-GD2-DL-2-LV
can be mounted on 35 mm rail (according to EN 60715)
with the plastic support included in the delivery.
Control, signaling and connection elements
The devices are equipped with screw terminals for con-
necting the 12 / 48 Vdc input power supply (1), the output
loads (3) and the DALI bus (2). The EK-GD2-DL-1-LV
model is equipped with 2 poles for local control (5).
Both models have internal status LEDs (4a) and a
feedback button (4b) which, in the EK-GD2-DL-2-LV mo-
del, also allows the selection of DALI DT6 / DT8 mode.
The meaning of the status LED for EK-GD2-DL-1-LV and
EK-GD2-DL-2-LV devices is as follows:
• Green steady on: normal operation and DALI line pre-
sent;
• Green ashing: no DALI line;
• Flashing red: generic output error.
The button (4b) for EK-GD2-DL-1-LV activates the
feedback function, while for EK-GD2-DL-2-LV it allows
the selection of DT6 (1 or 2 channels) or DT8 Tunable
White.

3
Note. When mounting the device in boards and ca-
binets it shall be provided the necessary ventilation
so that the temperature can be kept within the ope-
rating range of the device.
i
INSTALLATION TECHNICAL NOTES
• Installation and maintenance must be
performed only if the power supply has
been turned o.
• Installation and maintenance must only
be performed by qualied personnel in
compliance with current regulations.
• The product must be installed insi-
de an electrical panel protected against
overvoltages.
• The product must be installed in a verti-
cal position with the front / label facing
the front or in a horizontal position with
the front / label facing upwards. Other
product installation positions are not al-
lowed. The bottom position with the front
panel / label facing down is not allowed.
• Keep separated the circuits at 230V and
the circuits not SELV from circuits to low
voltage (SELV) and from any connection
with this product. It is absolutely forbid-
den to connect, for any reason whatsoe-
ver, directly or indirectly, the 230V mains
voltage to the bus or to other parts of the
circuit.
!
All the devices and the control signal connected to the
DALI bus and to the local command (where available)
must be SELV (the devices connected must be SELV or
supply a SELV signal).
Characteristics of the DALI terminal block
• Screw tightening of the conductors
• Command and bus wiring: 1.5 mm2 solid – 1.0 mm2
stranded – 16 - 17 AWG
• Conductor stripping recommended: 5.0 - 6.0 mm
• Maximum length of the connection between dimmer-
driver and control device < 10 m
• Length of bus connection cables < 10 m
Connection of power supply and LEDs
For the power supply use SELV power suppliers with li-
mited current, short circuit protection only and the power
must be correctly dimensioned. In case of usage of a po-
wer supplier with ground terminals, all points of the pro-
tective earth (PE = Protection Earth) must be connected
to a valid and certied protection earth.
Insert the mounting support in the appropriate shaped
prole of the back side of the device, then hook the teeth
to the prole guide starting from the bottom. Finally, push
the upper part towards the guide for nal coupling.
DALI bus line and command connection
The connection to the DALI bus network and the local
commands is done via the screw terminal, located on the
front of the device in the upper part.
For the EK-GD2-DL-1-LV device, the length of the con-
nection cables between the local commands (if available)
and the product must be less than 10m; the cables must
be correctly dimensioned and they should be isolated
from every wiring or parts at voltage not SELV. Use dou-
ble insulated shielded and twisted cables.
The length and type of the connection cables to the DALI
bus must be compliant with the protocol specication and
the present regulations and they should be isolated from
every wiring or parts at voltage not SELV. Use double in-
sulated shielded and twisted cables.
Installation scheme for EK-GD2-DL-1-LV
Installation scheme for EK-GD2-DL-2-LV
Setup and installation
The steps for installing the device are as follows:
• connect the loads to the “LED OUT” output terminals
of the device;
• for the EK-GD2-DL-1-LV model, connect the local com-
mand to the “PUSH” input if you want to use the “stand-
alone” mode;
• connect the DALI bus to the related DA terminal blocks;
• connect the 12/48 Vdc power supply to the terminal
blocks “DC IN” of the device.
All the devices and the control signal connected to the
DALI bus and to the local command (where available)
must be SELV (the devices connected must be SELV or
supply a SELV signal).

4
signal on the DALI bus and immediately use the fade,
otherwise the switching on and o would be immediate.
• Advanced function (blue status LED): using a DALI pro-
grammer such as USB DALI interface Tridonic, Lunato-
ne DALI Cockpit or similar, it is possible to program the
parameters System Fail Level = 100% and Fade Time
= 0, according to the DALI specications.
The connection cables between the power source “low
voltage” and the product must be correctly dimensioned
and they should be isolated from every wiring or parts at
not-SELV voltage. Use double insulated cables.
The power supply must be dimensioned according to
the load connected to the device. If the power supply is
oversized with respect to the maximum absorbed current,
then insert a protection against over-current between the
power supply and the device.
Characteristics of the supply and LEDs terminal block
• Screw tightening of the conductors
• Power and LEDs wiring: 1.5 mm2 solid – 1.0 mm2 stran-
ded – 16 - 17 AWG
• Power and LEDs stripping recommended approx.: 5.0
- 6.0 mm
• Max torque 0.5 Nm
Outputs
The length of the connection cables between the product
and the LED modules must be less than 10 m; the cables
must be dimensioned correctly and must be isolated from
any wiring or parts with non-SELV voltage. Use double
insulated shielded and twisted cables.
If you want to use connection cables between the product
and the LED modules over 10m, the installer must ensure
the proper functioning of the system. In any case, the con-
nection between the product and the LED modules must
not exceed 30 m.
A further long press of the programming button for at least
5 seconds conrms the setting of the selected function.
The device will always work in both modes: the default or
advanced programming only sets the DALI System Fail
Level and Fade Time parameters without the need for a
DALI programmer.
EK-GD2-DL-2-LV programming
The device is equipped with a programming button on the
front, near the DA terminals, to select the DALI DT6 / DT8
conguration of the channels.
While the status LED is on, a long press of the program-
ming button for at least 5 s allows you to enter program-
ming mode and the LED ashes.
At this point:
• by pressing the button once, the LED lights up purple,
to indicate the programming of both outputs as a single
DALI DT6 channel;
• by pressing the button again, the LED lights up blue,
to indicate the programming of the outputs as 2 single
channels DALI DT6;
• pressing the button again will cause the yellow LED to
light up, indicating that the programming of the outputs
is in Tunable White (dynamic white) with 1 DALI DT8
channel;
• with a long press of at least 5 s the conguration is
saved and the menu is exited;
• after 60 s without further pressing the programming key,
the device exits the menu without saving the setting.
Courtesy light function (EK-GD2-DL-1-LV) only)
When the output is o, a long press of the local control
button for at least 0.7 s turns on the load at minimum
intensity for 2 s, then starts dimming towards maximum
intensity. If the button is released at this stage, the bright-
ness level stops.
Conguration and commissioning
Conguration and commissioning activities of the device
must be carried out according to the design of the building
automation system done by qualied planners.
For commissioning the device the following activities are
required:
• make the electrical connections as indicated above;
• power up the bus;
• for EK-GD2-DL-1-LV device, it is possible to select the
“stand-alone” mode through the local command (con-
nection to the DALI bus is not necessary);
• carry out the device programming, as described below.
EK-GD2-DL-1-LV programming
At the rst start-up, in case of lack of the DALI bus, the
local control is active and the LED placed under the front
programming key is orange. When the presence of the
DALI bus is detected, control passes to it. In the absence
of the DALI bus, control passes to local control by pres-
sing the button.
Button behavior:
• Short press: on / o function;
• Long press: reverses the direction of dimming.
The device is equipped with a programming button on the
front, near the DA terminal: by pressing the programming
button for 5 seconds, the status LED starts ashing. Pres-
sing the button again allows you to select the function of
the device:
• Default function (orange status LED): sets the System
Fail Level parameter = 100% and the Fade Time = 0.7
s), to make the device work even in the absence of a
Note. If the dimmer is used together with a bro-
adcast DALI device, depending on the implemen-
tation of the rmware, the broadcast function may
prevail over the local command.
i
Note. The programming of the parameters men-
tioned above must be carried out only during the
programming phase. If the customer has a DALI
programmer / master, he can reprogram them as
he wishes.
i
The setting of the output channels can also be done using
DALI programmers. An example is shown in the next -
gures.

5
Status LED
The meaning of the status LED under the programming
button is as follows:
• Green steady on: normal operation and DALI line pre-
sent
• Flashing green: no DALI line
• Flashing red: generic error on the output
If the programming button is not pressed within 1 minute,
the status LED goes into standby. A short press of the
programming button turns the LED back on and shows
the status.
Conguration change
Subsequently, it is possible to change the device con-
guration and addressing using an application for para-
meterization, for example by downloading the ekinex
CGEKBG1TP software to the PC which allows you to:
• congure the DALI system and dene its parameters;
• set the DALI devices (groups, scenarios, IDs, etc.);
• test the communication on the DALI bus;
• update the device.
The software can be downloaded from the website www.
ekinex.com and its use is described in the application ma-
nual of the ekinex EK-BG1-TP DALI Gateway. The sof-
tware works with Microsoft Windows (7 and later).
DT6 with single output channel
DT6 with 2 independent output channels
DT8 with single Tunable White output channel
DALI System fail function
For each device it is possible to set the “system failure”
parameter, that is the brightness level at which the LED
load is set, in case of DALI bus outage.
This setting can be done using a DALI programmer such
as USB DALI interface Tridonic, Lunatone DALI Cockpit
or similar.
The range of brightness values is from 0 to 254 (100%).
If the value 255 (MASK) is set, the last brightness value
is restored.
Note. For the CGEKBG1TP conguration software
to work, it may be necessary to install .NET Fra-
mework 4, which can be downloaded freely from the
Microsoft website.
i

6
Marks
• CE: the device complies with the Electromagnetic
Compatibility Directive (2014/30/EU), the Low Volta-
ge Directive (2014/35/EU) and the RoHS III Directive
(2011/65/EU).
• Reference Standards: EN 61347-1:2015, EN 61347-
2-13, EN 55015:2013+A1:2015, EN 61547:2009, EN
50581:2012, IEC/EN 62386-101/102/207, IEC/EN
60929-E.2.1.
• IEC/EN 62386-207 Digital addressable lighting interfa-
ce, Particular requirements for control gear – LED mo-
dules (device type 6).
• IEC 60929-E.2.1 Control interface for controllable bal-
lasts - control by DC voltage - functional specication
Dimensions
25
29
61
53
25
29
61
53
Disposal
At the end of its useful life the product
described in this datasheet is classied
as waste from electronic equipment in
accordance with the European Direc-
tive 2012/19/EU (WEEE recast), and
cannot be disposed together with the
municipal undierentiated solid waste.
Maintenance
The device is maintenance-free. To clean use a dry cloth.
It must be avoided the use of solvents or other aggressive
substances.
Warnings
• Installation, electrical connection, conguration and
commissioning of the device can only be carried out by
qualied personnel in compliance with the applicable
technical standards and laws of the respective countri-
es
• Opening the housing of the device causes the imme-
diate end of the warranty period
• In case of tampering, the compliance with the essential
requirements of the applicable directives, for which the
device has been certied, is no longer guaranteed
• ekinex® defective devices must be returned to the ma-
nufacturer at the following address: Ekinex S.p.A. Via
Novara 35, I-28010 Vaprio d’Agogna (NO) Italy
Other information
• The instruction sheet must be delivered to the end cu-
stomer with the project documentation
• For further information on the product, please contact
the ekinex® technical support at the e-mail address:
[email protected] or visit the website www.ekinex.
com
• Each ekinex® device has a unique serial number on
the label. The serial number can be used by installers
or system integrators for documentation purposes and
has to be added in each communication addressed to
the EKINEX technical support in case of malfunctioning
of the device
• DALI, DALI2 and their logos are registered trademarks
of the Digital Illumination Interface Alliance (DiiA).
© EKINEX S.p.A. The company reserves the right to make changes to this
documentation without notice.
References
• IEC/EN 62386-101 - Digital addressable lighting inter-
face, General requirements - System
• IEC/EN 62386-102 Digital addressable lighting interfa-
ce, General requirements - Control gear
Warning! Incorrect disposal of this product may
cause serious damage to the environment and hu-
man health. Please be informed about the correct
disposal procedures for waste collecting and pro-
cessing provided by local authorities.
!
This manual suits for next models
1
Table of contents
Other Ekinex Home Automation manuals
Popular Home Automation manuals by other brands

Sengled
Sengled E1C-NB6 user guide

Forest
Forest SHUTTLE S installation manual

HeatTrak
HeatTrak WI-FI SMART OUTLET instructions

Leviton
Leviton TWR20-W installation instructions

Hearth and Home Technologies
Hearth and Home Technologies IntelliFire IFT-RC150 user guide

SmartDHOME
SmartDHOME 01335-1900-00 user manual