
1-11
1-111-11
1-11
stalled, the technician is committed to re-
placement of the drier and a sealed system
repair. Once again, this valve must be re-
moved upon completion of repair. Make
sure the gauges which are used to check the
operating pressures are accurately cali-
brated. When not connected to a system,
the gauge pointer should indicate zero pres-
sure. If necessary, turn the calibrating screw
until the pointer is at "0."
NOTE:NOTE:
NOTE:NOTE:
NOTE: The following situations are typi-The following situations are typi-
The following situations are typi-The following situations are typi-
The following situations are typi-
cal, however other factors such as gaugecal, however other factors such as gauge
cal, however other factors such as gaugecal, however other factors such as gauge
cal, however other factors such as gauge
placement, line voltage and ambient tem-placement, line voltage and ambient tem-
placement, line voltage and ambient tem-placement, line voltage and ambient tem-
placement, line voltage and ambient tem-
perature must also be considered.perature must also be considered.
perature must also be considered.perature must also be considered.
perature must also be considered.
The following symptoms use high and low
side pressures plus wattage measurements
to diagnose sealed system problems. Nor-
mal low side pressure will range from be-
low zero to about six pounds of pressure,
depending on several factors such as refrig-
erator model, ambient temperature, load
and customer usage. Normal high side
pressure is also dependent on external fac-
tors but will range in the 100 to 125 p.s.i.g.
range. Wattage and pressure figures will
vary based on the model and age of the re-
frigerator. Refer to the performance data
table(s) at the end of the manual.
SymptomsSymptoms
SymptomsSymptoms
Symptoms::
::
:
High Side -High Side -
High Side -High Side -
High Side - Near normal pressureNear normal pressure
Near normal pressureNear normal pressure
Near normal pressure
Low Side -Low Side -
Low Side -Low Side -
Low Side - Slightly lower pressureSlightly lower pressure
Slightly lower pressureSlightly lower pressure
Slightly lower pressure
WW
WW
Wattage -attage -
attage -attage -
attage - Lower than normalLower than normal
Lower than normalLower than normal
Lower than normal
DiagnosisDiagnosis
DiagnosisDiagnosis
Diagnosis - Low side restriction. The
evaporator, suction line or other low side
tubing is probably restricted (kinked or
blocked with a foreign article such as mois-
ture or contaminant). This condition is usu-
ally accompanied with a frost build up on
the low side of the restriction. High side
pressure will take longer to balance with the
low side pressure when the compressor is
stopped.
SymptomsSymptoms
SymptomsSymptoms
Symptoms::
::
:
High Side -High Side -
High Side -High Side -
High Side - Lower than normalLower than normal
Lower than normalLower than normal
Lower than normal
Low Side -Low Side -
Low Side -Low Side -
Low Side - Slightly lower than normalSlightly lower than normal
Slightly lower than normalSlightly lower than normal
Slightly lower than normal
WW
WW
Wattage -attage -
attage -attage -
attage - Lower than normalLower than normal
Lower than normalLower than normal
Lower than normal
DiagnosisDiagnosis
DiagnosisDiagnosis
Diagnosis - High side leak. Both high and
low side pressures will drop as more refrig-
erant escapes.
SymptomsSymptoms
SymptomsSymptoms
Symptoms::
::
:
High SideHigh Side
High SideHigh Side
High Side - Higher than normalHigher than normal
Higher than normalHigher than normal
Higher than normal
Low Side -Low Side -
Low Side -Low Side -
Low Side - Slightly lower thanSlightly lower than
Slightly lower thanSlightly lower than
Slightly lower than normalnormal
normalnormal
normal
WW
WW
W
attage -attage -
attage -attage -
attage - Higher than normalHigher than normal
Higher than normalHigher than normal
Higher than normal
DiagnosisDiagnosis
DiagnosisDiagnosis
Diagnosis - Low side leak. High side pres-
sure will continually increase since air is
being drawn into the system through the
leak and becomes trapped in the high side
tubing. The low side may show a slight in-
crease in pressure because of the air being
drawn in through the leak.
SymptomsSymptoms
SymptomsSymptoms
Symptoms::
::
:
High Side -High Side -
High Side -High Side -
High Side - Lower than normalLower than normal
Lower than normalLower than normal
Lower than normal
Low Side -Low Side -
Low Side -Low Side -
Low Side - In a vacuumIn a vacuum
In a vacuumIn a vacuum
In a vacuum
WW
WW
Wattage -attage -
attage -attage -
attage - Lower than normalLower than normal
Lower than normalLower than normal
Lower than normal
DiagnosisDiagnosis
DiagnosisDiagnosis
Diagnosis - Capillary tube restriction. High
side pressure will take much longer (or not
at all) to equalize with the low side pressure
when the compressor is stopped.
SymptomsSymptoms
SymptomsSymptoms
Symptoms::
::
:
High Side -High Side -
High Side -High Side -
High Side - Higher than normalHigher than normal
Higher than normalHigher than normal
Higher than normal
Low Side -Low Side -
Low Side -Low Side -
Low Side - Higher than normalHigher than normal
Higher than normalHigher than normal
Higher than normal
WW
WW
Wattage -attage -
attage -attage -
attage - Higher than normalHigher than normal
Higher than normalHigher than normal
Higher than normal
DiagnosisDiagnosis
DiagnosisDiagnosis
Diagnosis - Overcharged system. The
extent of the pressure increase depends on
the amount of overcharge and ambient tem-
perature. An overcharge may also cause the
suction line to be frosted during the run
cycle, resulting in water on the floor after
cycling off.