Elentek DRYTEK 1 Mono User manual

DRYTEK 1 - User Manual
ELECTRICAL PANEL FOR 1 MOTOR WITH POWER FACTOR CONTROL


III
CONTENTS
1. INTRODUCTION......................................................................................................5
2. WARNINGS ............................................................................................................6
3. GENERAL DESCRIPTION..........................................................................................7
4. INSTALLATION........................................................................................................8
5. CONTROL PANEL ....................................................................................................9
5.1 Luminous indicators and control commands ...................................................................9
6. KEY TO FUNCTIONS AND SETTINGS ......................................................................10
6.1 Main display items.........................................................................................................10
6.2 Activation of load in manual mode................................................................................10
6.3 User programming in automatic mode .........................................................................11
7. ALARMS ...............................................................................................................15
8. ASSISTANCE MENU PARAMETERS........................................................................16
9. STANDARD CIRCUIT DIAGRAMS ...........................................................................17
9.1 DRYTEK 1 Single phase circuit diagram..........................................................................17
9.2 DRYTEK 1 Three phase circuit diagram ..........................................................................18
10. STANDARD WIRING DIAGRAMS.......................................................................19
10.1 DRYTEK 1 Single phase wiring diagram .........................................................................19
10.2 DRYTEK 1 Three phase wiring diagram..........................................................................19
11. STANDARD DIMENSIONAL DIAGRAM ..............................................................20
11.1 DRYTEK 1 Single phase dimensional ..............................................................................20
11.2 DRYTEK 1 Three phase dimensional...............................................................................20
12. TROUBLESHOOTING.........................................................................................21
13. GENERAL CONDITIONS.....................................................................................22
13.1 Warranty .......................................................................................................................22
13.2 Maintenance..................................................................................................................22
13.3 Disposal .........................................................................................................................22
14. DECLARATION OF CONFORMITY ......................................................................23

IV

5
1. INTRODUCTION
This manual must always accompany the relevant equipment and be conserved in an accessible
location for consultation by qualified technicians assigned for operation and maintenance of the
system.
The installer/user is strongly recommended to carefully read all instructions and information in this
manual before using the product, in order to avoid damage or improper use of the unit, which
would also render the warranty null and void.
Before operating the equipment, carefully read the manual and follow all instructions provided.
The information and instructions in this manual refer to the standard use of this product; in the
event of special circumstances, functions or applications not described in this document, contact our
service center for assistance.
If technical assistance or spare parts are required, when contacting the manufacturer always specify
the identification code of the model and construction number as stated on the data plate.
Our service center is available for any requirement or clarification.
On receipt of the goods, inspect immediately to ensure that the equipment has not been damaged
during transport. If defects are found, the client should promptly notify our retailer within 5 days of
receiving the goods, or in the event of direct purchases, the Elentek service center.
N.B. the information provided in this manual is subject to modifications without
notice. The manufacturer shall not be held liable for any damage caused in relation
to the use of these instructions, as they are to be considered guideline only. Note
that failure to observe the instructions provided in this manual may cause physical
injury or damage to objects.
In any event all local and/or current legislation must be observed at all times.

6
2. WARNINGS
The electrical panel must be used exclusively for the purpose and function as specified in design.
Any other application or use is to be considered improper and therefore hazardous.
In the event of a fire in the place of installation or the surrounding area, avoid the use of water jets
and use the appropriate extinguishing equipment and means (powder, foam, carbon dioxide).
Install the equipment far from heat sources and in a dry and sheltered location in observance of the
stated protection rating (IP).
The installation of a safety device is recommended to protect the panel power line in compliance
with current electrical standards.
The electrical panel must be connected by a qualified electrician in observance of the relevant
electrical standards.
No parts of the panel must be disassembled without the official authorization of Elentek: any
tampering with or modifications to the unit will render all terms of the warranty null and void.
All installation and/or maintenance operations must be performed by a specialized technician who is
fully aware of the relevant current safety standards.
Ensure the installation is connected to an efficient earthing system.
After making the electrical connection, check that all electrical panel settings are correct to avoid
automatic start-up of the electric pump.
Elentek declines all liability in the event of the following:
-Incorrect installation;
-Use by personnel not adequately trained in the correct use of the panel;
-Serious failure to perform scheduled maintenance;
-Use of non-original spare parts or parts not specific to the model;
-Unauthorized modifications or interventions;
-Partial or total failure to observe instructions.

7
3. GENERAL DESCRIPTION
Power supply 1 ~ 50/60Hz 230V±15% (DRYTEK 1-Single);
Power supply 3 ~ 50/60Hz 400V±15% (DRYTEK 1-Three);
C/I1 normally open input for start-up command;
Buttons for function selection and programming;
Buttons AUTOMATIC-0-MANUAL (spring return);
Display for values: Volts, Amperes, Cos ϕof motor and alarms;
Green led: motor active;
Adjustable electronic motor overload control;
Motor control on 2 phases;
Motor current overload protection (adjustable);
Protection of sequence/phase
Protection of minimum/maximum voltage (adjustable);
Protection against dry running (adjustable power factor);
Automatic reset from dry running status with 4 separate programmable times, from 0 to
240 minutes (also possible cyclical);
Protection of aux. circuits and motor with fuses;
Alarm output (NC-C-NO resistive load - 5A / 250V);
Door lock general disconnect switch;
Provision for start-up capacitor for single-phase (not included);
Box in ABS, IP55;
Ambient temperature: -5/+40 °C;
Relative humidity 50% at 40 °C (condensate free).

8
4. INSTALLATION
Ensure that the mains power supply specifications correspond to the voltage specified on the data
plate of the electrical panel and motor connected, then make the earthing connection before all
other connections.
DRYTEK 1 Mono ►1~230V ± 15% 50/60Hz
DRYTEK 1 Tri ►3~400V ± 15% 50/60Hz
The power line must be protected by a residual current circuit breaker.
Tighten the electrical cables on the relative terminals using a suitable tool correctly sized to avoid
the risk of damage to the fixing screws. Take care if using an electric screwdriver.
The electrical panel is designed for wall-mounting using screws and plugs in the pre-drilled holes at
the corners of the enclosure, or by means of brackets when present.
Install the equipment in areas compliant with the protection rating and ensure that the box is kept
intact when drilling the holes for fitting the cable clamps.
Avoid the use of multicore cables where there are wires connected to inductive loads and power
cables and signal cables such as sensors and digital inputs.
Keep connection cables as short as possible, preventing any twisting of cables which may be harmful
due to inductive effects on the electronic equipment.
All wires used in the cabling must be suitably sized to withstand the load to be powered.

9
5. CONTROL PANEL
5.1 Luminous indicators and control commands
The DRYTEK 1 electrical panel has been designed for the adjustable protection of 1 motor with dry
running safety control, obtained from the power factor (where “fi” is the timing angle between
current and voltage), without the need for external commands (float or pressure switch).
N.B. The load is activated or deactivated on closure or opening of the normally open
contact C/I1. If no float or pressure switch is used, a jumper must be wired in on
input C/I1.
KEY TO LUMINOUS INDICATORS AND COMMANDS
Display of values and programming
Green led: electric pump operating
SETUP (or multifunction) button
UP arrow button
DOWN arrow button
OK button
230V 0.0A 1.00ϕ
MAN ( ) AUT (*)

10
6. KEY TO FUNCTIONS AND SETTINGS
6.1 Main display items
On activation of the DRYTEK 1 panel, the display shows the following:
At the end of the start-up sequence, the main menu is displayed, as described below.
This screen enables display of the electrical data as read by the DRYTEK 1
panel in real time:
230 V = Power supply voltage reading;
0.0 A = Current absorbed by connected load;
1.00 ϕ= Power factor of connected load;
MAN () = Panel set to manual mode;
AUT () = Panel set to automatic mode;
6.2 Activation of load in manual mode
On activation the panel always starts up in Automatic mode, indicated by the asterisk () displayed
alongside the text AUT on display.
The operating mode can be changed by pressing the UP arrow to change to Manual mode, or the
DOWN arrow to change to Automatic mode.
Therefore, to enable operation in Manual mode, press the UP arrow (the asterisk () is displayed
alongside the text MAN) and then press and hold OK.
The display then displays current absorption of the motor and the power factor values in real time;
the green led also lights up to indicate the electric pump is running.
On release of the OK button, the motor is shut down.
N.B. in manual mode, the load is activated and bypasses all alarms, but in the event
of a fault the display flashes, and the user can press the DOWN arrow to view a
description of the alarm.
ELECTRIC PUMP
DRYTEK v 2.0
E L E N T E K
www.elentek.com
MODEL 50HZ
M/2.2
230V 0.0A 1.00ϕ
MAN ( ) AUT (*)

11
6.3 User programming in automatic mode
To access the user programming menu, press and hold the SETUP button until the first parameter
settings menu is displayed (minimum power factor).
Practical examples:
① Protection against dry run by motor cos φ.
② Pressure switch ON-OFF.
③ Float ON-OFF.

12
MINIMUM POWER FACTOR (COS-FI)6.3.1
On access to the menu, the first window enables modifications to the
minimum power factor value, below which the load is deactivated due to
dry running conditions (use the arrows to modify the value).
To go to the next window, press OK.
EXAMPLE:
To enable operation in manual mode, activate in no-load conditions (dry running), check the
power factor reading (e.g. 0.65) and enter the minimum power factor, increasing it by approx.
0.05.
MAXIMUM CURRENT6.3.2
The second screen enables modifications to the maximum motor current
value, above which it is shut off due to current overload (use the arrows to
change the value).
To go to the next window, press OK.
EXAMPLE:
To enable operation in manual mode, read the load current value displayed (e.g. 6.0 Ampere) and
check that this corresponds to the motor data plate specifications.
Enter the maximum current value, increasing it by 10-15% with respect to the previously checked
value.
MINIMUM COS-FI
0.70
ϕ
MAXIMUM CURRENT
5.7 A
MAXIMUM CURRENT
6.9 A
MINIMUM COS-FI
0.80
ϕ

13
RESET6.3.3
In the event of a dry running alarm (minimum power factor) the panel may attempt to reset
automatically, which can be programmable in minutes, with the option of setting this function as
sequential.
4 reset times can be set, in which the system automatically restarts after
being blocked;
By default these values are set as shown alongside:
The first reset attempt is performed 5 minutes after the dry running alarm.
The second reset attempt is performed 10 minutes after the alarm.
The third reset attempt is performed 20 minutes after the alarm.
The fourth reset attempt is performed 30 minutes after the alarm.
N.B. On each reset screen, use the arrows to modify any set times and press OK to
go to the next screen.
After setting all times, press OK to go to the screen for the reset cycle settings.
If the value 0(zero) is set, all automatic resets are blocked after the fourth
attempt; if the value is set to 1(one) at the end of the fourth attempt, the
reset cycle is repeated continuously;
The system protecting the panel against dry running conditions activates the reset cycle
according to the time intervals set, and resumes the same reset cycle each time water is
detected for more than 10 seconds.
To exit the menu, press SETUP.
RESET N.4
TIME 30 MIN
CYCLE RESET
( 0 ) NO ( 1 ) YES ?: 1
RESET N. 3
TIME 20 MIN
RESET N. 2
TIME 10 MIN
RESET N. 1
TIME 5 MIN

14
SUMMARY SETUP TABLE6.3.4
DESCRIZIONE PARAMETRO
VALORE
DEFAULT
MAXIMUM CURRENT
This parameter enables entry of the maximum current for each motor.
Enter the maximum current value, increasing it by 10-15% with respect to
the rated motor value.
Modifications to operating limits beyond the parameters stated on the
model data plate will immediately render the warranty null and void.
1 - … A
-
MINIMUM COS-PHI
This parameter establishes the minimum Cos-Phi power factor value for
each motor
Enable operation in manual mode, activate in no-load conditions (dry
running), check the power factor reading (e.g. 0.65) and enter the
minimum power factor, increasing it by approx. 0.05.
0.15 - 1.00
-
AUTOMATIC RESET ON DRY RUNNING ALARM
In the event of a dry running alarm (minimum power factor) the panel may
attempt to reset automatically, which can be programmable in minutes.
4 reset times can be set, in which the system automatically restarts after
being blocked; By default these values are set as shown below:
The first reset attempt is performed 5 minutes after the dry running alarm.
The second reset attempt is performed 10 minutes after the alarm.
The third reset attempt is performed 20 minutes after the alarm.
The fourth reset attempt is performed 30 minutes after the alarm.
1 - 240 Min
1° 5 Min
2° 10 Min
3° 20 Min
4° 30 Min
SEQUENTIAL RESET ON DRY RUNNING ALARM
If the value 0(zero) is set, all automatic resets are blocked after the
fourth attempt; if the value is set to 1(one) at the end of the fourth
attempt, the reset cycle is repeated continuously;
The system protecting the panel against dry running conditions activates the
reset cycle according to the time intervals set, and resumes the same reset
cycle each time water is detected for more than 10 seconds.
Y or N
Y
DISPLAY BRIGHTNESS ON STANDBY
This parameter enables entry of the brightness setting applied when the
display sets to standby (wait 9 seconds for a preview).
0 - 9
4
TIME FOR ENTRY TO SET-UP
This parameter enables entry of the time to keep the SETUP button pressed
for access to the set-up menu.
2 - 30 Sec
3 Sec

15
7. ALARMS
The measured power factor value is the set value and the panel shuts down
the relative pump. The display blink and the cumulative alarm output is
activated (voltage-free contacts NC-C-NO).
The system resets automatically on the basis of the times set during programming, or manually by
pressing the button SETUP until the screen is displayed without flashing, after which the button OK
can be pressed to reset.
The load current absorption is higher than the set value and the panel
shuts down the relative pump. The display blink and the cumulative alarm
output is activated (voltage-free contacts NC-C-NO).
The system is reset manually by pressing the button SETUP until the screen is displayed without
flashing, after which the button OK can be pressed to reset.
The measured mains voltage is too low (the pumps are shut down).
The display blink and the cumulative alarm output is activated (voltage-free
contacts NC-C-NO).
The system automatically resets every 60 seconds or manually by pressing the OK button.
The measured mains voltage is too high (the pumps are shut down).
The display blink and the cumulative alarm output is activated (voltage-free
contacts NC-C-NO).
The system automatically resets every 60 seconds or manually by pressing the OK button.
The phase sequence is incorrect or one or more phases is missing (the
pumps are shut down). The display blink and the cumulative alarm output
is activated (voltage-free contacts NC-C-NO).
The system is reset manually turning off and on the electrical panel after reconnecting the phases
correctly.
ALARM MOTOR
DRY RUNNING
ALARM MOTOR
IN PROTECTION
ALARM VOLTAGE
TOO LOW
ALARM VOLTAGE
TOO HIGH
ALARM SEQUENCE
OR LACK PHASES

16
8. ASSISTANCE MENU PARAMETERS
This menu is accessed by simultaneously pressing the buttons SETUP and OK during activation of the
panel.
This menu enables modifications to the language, minimum and maximum voltage, with the latter
programmed by default as shown in the table below (modify only if absolutely necessary).
IF YOU CHANGE THE OPERATING LIMITS, BEYOND THE DEFAULT PARAMETERS,
WILL RESULT IN IMMEDIATE FORFEITURE OF THE GUARANTEE.
Press OK to go to the next screen.
DESCRIPTION OF PARAMETER
VALUE
LANGUAGE
ITALIAN / ENGLISH / FRENCH / SPANISH / GERMAN
ENGLISH
MINIMUM VOLTAGE
Single-phase voltage rated 230 - 15%
Three-phase voltage rated 400 - 15%
195 V
340 V
MAXIMUM VOLTAGE
Single-phase voltage rated 230 - 15%
Three-phase voltage rated 400 - 15%
264 V
460 V
COS-PHI ALARM OUTPUT
This parameter enables removal of the dry running alarm.
Y or N
N.B. On each screen, use the arrows to modify any set values and press OK to go to
the next screen.
To exit the menu, press SETUP.

17
9. STANDARD CIRCUIT DIAGRAMS
9.1 DRYTEK 1 Single phase circuit diagram

18
9.2 DRYTEK 1 Three phase circuit diagram

19
10. STANDARD WIRING DIAGRAMS
10.1 DRYTEK 1 Single phase wiring diagram
10.2 DRYTEK 1 Three phase wiring diagram

20
11. STANDARD DIMENSIONAL DIAGRAM
11.1 DRYTEK 1 Single phase dimensional
11.2 DRYTEK 1 Three phase dimensional
This manual suits for next models
1
Table of contents
Other Elentek Control Panel manuals
Popular Control Panel manuals by other brands

Overland Storage
Overland Storage SnapServer XSR 120 instructions

RHINO
RHINO SMS8 instructions

Simrad
Simrad OPERATING PANEL OUTLINE - SCHEMA REV A manual

Extron electronics
Extron electronics RCP 101 D Setup guide

Bosch
Bosch D9412GV4 Installation and operation guide

CAME BPT
CAME BPT TH/PLUS Installation and commissioning manual