Elkay Ceilingmountpir Manual

IMPORTANT NOTICE
setup instructions for the ceilingmountpir
Product: 374B-1 Three wire
Rating at 220-240V AC 50Hz
• All load types 10A • Time Delay 2min - 1h • Sensitivity Adjustment
• Test Mode • Auto and Manual Lux Sensor for Daylight Control
Call +44 (0) 1675 468222 or visit www.elkay.co.uk
fitting and operating instructions
ceilingmountpir
fitting and operating instructions
ceilingmountpir
Removing the Sensor from
Surface Mount Box
Squeeze
the housing on
either side as shown here
diagram 1
The Ceiling Mount PIR comes with surface and flush mounted options. It also
has interchangeable white and chrome fascias.
Usage
The PIR sensor has been designed to switch lighting, heating and ventilation loads up
to 10A. The unit is switched on by the detection of moving infra red heat within
a specified range. When infra red heat, such as a moving body, is no longer detected,
the unit will switch off the load after the adjustable time period has elapsed.
If infra red heat is detected again during the timing period, the timing sequence will
restart. The unit has a lux level adjustment and Auto Lux function, which measures
the ambient light levels and prevents lighting being switched on, when there is sufficient lighting in the room. There is sensitivity adjustment
and test mode function added for your convenience.
A POWER FACTOR CORRECTION CAPACITOR OF 4 MICROFARADS WILL OFTEN BE REQUIRED WHEN SWITCHING LOW WATTAGE LOADS, e.g.
LED LOADS. THE CAPACITOR IS FITTED ACROSS SWITCH LIVE AND NEUTRAL SUPPLIES OF SUITABLE ELKAY CAPACITORS CAN BE FOUND AT YOUR
STOCKIST (REF PFCC-1). DO NOT INSULATION RESISTANCE TEST THIS PRODUCT. REMOVE BEFORE TESTING OR TEST CIRCUIT PRIOR TO FITTING.
Positioning
CAREFUL POSITIONING IS ESSENTIAL TO OBTAIN
OPTIMUM PERFORMANCE.
Use the detection range to determine a suitable location for
the sensor. When locating the position of the units, ensure
the sensor is not subjected to bright or direct sunlight or in
areas with high reflective surfaces. Do not site units on a
vibrating surface, or near forced air heating and ventilation.
They should not be placed within 1 metre of the load.
Sensors work when objects move across their field of view.
Position the sensor where people will be detected
walking across the zones rather than towards the zones
identified in Diagram 1. Adjust sensitivity to suit the area that
the sensor has been installed in.
IMPORTANT NOTICE
All wiring should be carried out by a competent person or a qualified electrician and should be fitted to IEE 17th Edition Wiring regulations BS7671:2008.
The circuit should be isolated before carrying out any work. Failure to adhere to the instructions will invalidate the warranty.
TECHNICAL HELPLINE
For further help or assistance or information on this or other products in the range please call the Elkay Technical team on 01675 468222.
Please call the Technical helpline before returning any products to your stockist.
Elkay Electrical, Coleshill, Birmingham, England.
Tel: +44 (0) 1675 468222 www.elkay.co.uk
RPM 305
IMPORTANT NOTICE
All wiring should be carried out by a competent person or a qualified electrician and should be fitted to IEE 17th Edition Wiring regulations BS7671:2008.
The circuit should be isolated before carrying out any work. Failure to adhere to the instructions will invalidate the warranty.
Surface
Mount
Box
Removable
Fascia
troubleshooting guide
Before calling Elkay Technical we recommend that you attempt to resolve the issue for yourself with this handy troubleshooting guide.
Issue Problem and Resolution
Load will not switch OFF • Check terminal connections.
• Check time settings (See Diagram 4).
• PIR is too close to load - Re-position away from lighting, heating and forced air ventilation.
• PIR is switching low wattage or LED loads - Fit Capacitor as stated in instructions PFCC-1.
• Windy weather conditions - Adjust Sensitivity down.
• PIR is re triggered - Check area is left unoccupied for longer that time setting using an
accurate time piece.
• Sensitivity set too high - Gradual incremental adjustments towards the low setting to
resolve the issue.
Load will not switch ON • Check terminal connections.
• Lux set too low - Turn off Auto Lux and turn UP lux level to the PLUS (+) setting and wait
for sensor to adjust.
• Sensitivity set too low- Gradual incremental increases towards the High setting to
resolve the issue.
Load switches OFF and • Check terminal connections.
then immediately comes • PIR is detecting normally- Find source that is triggering PIR.
back ON • PIR is seeing infra red heat from the load- Re-position away from heat source
(See Positioning).
• PIR is switching low wattage or LED loads- Fit Capacitor PFCC-1 across switch live and
neutral of load.
• PIR is switching a contactor and the contactor chatters or stays ON - Fit a PFCC-1
capacitor across the switch live and neutral of the contactor coil.
THIS IS AN ALL MASTER SYSTEM.
DO NOT USE SLAVES WITH THIS PRODUCT. THESE PIR’s CAN ONLY BE WIRED WITH EACH OTHER.
PLEASE BE AWARE OF THE CHANGES TO THE TERMINALS FROM PREVIOUS ELKAY CEILING MOUNT TIMERS.
L IN L OUT N OLD TERMINALS
L IN L OUT N N NEW TERMINALS
Do not wire neutrals unless the terminals are marked with an N.
RPM 305
7 metres approx.
2.4 metres
7 metres approx.
CEILING
FLOOR

IMPORTANT NOTICE
All wiring should be carried out by a competent person or a qualified electrician and should be fitted to IEE 17th Edition Wiring regulations BS7671:2008.
The circuit should be isolated before carrying out any work. Failure to adhere to the instructions will invalidate the warranty.
diagram 3
Please note that the black bar denotes the position of the dip switch.
Dip switch 4 is only used for Setting Automatic (150 Lux) or Manual Lux ONLY.
4.
3.
2.
1.
4.
3.
2.
1.
4.
3.
2.
1.
4.
3.
2.
1.
4.
3.
2.
1.
ON DIP
ON DIP
ON DIP
ON DIP
ON DIP
Manual Lux
2 mins 5 mins 10 mins 15 mins
4.
3.
2.
1.
4.
3.
2.
1.
4.
3.
2.
1.
ON DIP
ON DIP
ON DIP
20 mins
30 mins
60 mins
LIVE IN
LIVE OUT
NEUTRAL
LIVE IN
LIVE OUT
NEUTRAL
LUX LEVEL
ADJUSTMENT
SENSITIVITY
ADJUSTMENT
DIL
SWITCHES
Wiring diagram for a single unit. Wiring diagram for wiring multiple devices together.
LIVE IN
LIVE OUT
NEUTRAL
fitting and operating instructions
ceilingmountpir
IMPORTANT NOTICE
Call +44 (0) 1675 468222 or visit www.elkay.co.uk
IMPORTANT NOTICE
All wiring should be carried out by a competent person or a qualified electrician and should be fitted to IEE 17th Edition Wiring regulations BS7671:2008.
The circuit should be isolated before carrying out any work. Failure to adhere to the instructions will invalidate the warranty.
IT IS ESSENTIAL THAT YOU FOLLOW CLOSELY STEPS 1 TO 8 OF
THE MOUNTING AND INSTALLATION INSTRUCTIONS BELOW.
FAILURE TO DO SO WILL INVALIDATE THE WARRANTY.
Mounting and Installation
Step 1 - Please ensure that you position the PIR in the correct
place by reading the Positioning section of these instructions.
For flush mounting cut a clean hole measuring 64mm in
diameter in the chosen area for the sensor. For surface
mounting attach surface mount cup to ceiling with
connection cable hanging through the middle. Seal any large
holes on ceiling to prevent air current activation.
Step 2 - Ensure that the mains power to the circuit is
switched off. Ensure terminal cover and cable clamp are
correctly fitted with screws supplied. Place the Live In into the
Terminal marked Live In and the switched Live Out into the
Live Out terminal. Place the neutral into the connection
marked N for neutral. Please note that it is essential that the
Live In wire and the switch Live Out and Neutral are identified
prior to commencing installation. To connect multiple units
connect the live switch live and neutrals as shown in Diagram
2. Turn off mains supply for installation as live working is not
recommended and can damage the unit.
Step 3 - For flush mounting fold the two arms up into the
vertical position and insert unit into the hole. Release unit
ensuring arms are securely in place. For surface mounting fit
surface mount cup onto ceiling or conduit terminal box and
return connected PIR into surface mount cup.
Step 4 - Remove the fascia by turning anti-clockwise to show
the lux pot, sensitivity pot and the timing/lux Dip switches.
Please adjust the Lux Level and Sensitivity potentiometer
gently without force as this is a sensitive electronic part. After
adjustment please wait 30 seconds for changes to take
effect. It is recommend product is set up initially using the 10
secs walk test mode.
Step 5 - To set Auto Lux (150 Lux), switch Dip switch 4 to the
ON position. This will allow activation of the PIR from Dusk
until Dawn only. To set manually then put dip switch 4 off
and use the potentiometer to adjust to desired lux level
setting. All the way to the plus setting will allow the PIR to
switch day and night. All the way to the minus sets the timer
to ZERO lux and effeftively switches off the PIR. To set
manually you will need to be present at dusk (See Diagram 3).
Step 6 - To adjust sensitivity turn anti-clockwise to the High
(H) setting to increase sensitivity and clockwise to the Low (L)
to decrease sensitivity.
Step 7 - To set time please utilise the dip switch timing
diagram above. The black bar denotes dip switch position.
Replace fascia ring by turning anti clockwise (See Diagram 4).
Step 8 - The PIR will take approximately 2½ minutes to
initialise and will flash rapidly after the mains power is first
applied to allow the sensor to learn its environment. The load
will be ON after 7 seconds initially, then switch off after 2½
minutes if there is no detection in the zones.
Operation
In standard operation the PIR will now sense infra red heat
when a person or source of heat passes through the
detection zone. Each time the PIR is triggered it will reset the
timer back to the start of the timing period. The unit will then
wait 5 seconds before allowing the PIR to sense and re trigger
the timing period again.
If no one is present in the room or the detection zone is not
passed through, during its set time period, the timer will time
out, turning off the lights or appliance.
The PIR unit will only trigger the lights or appliance if the
ambient light level is below that set on the lux level
adjustment.
4.
3.
2.
1.
ON DIP
Test Mode
10 Secs
4.
3.
2.
1.
ON DIP
Auto Lux
diagram 2
diagram 4
Time Settings (Test Mode to 60 mins)
RPM 305
There are now 2 neutral terminals - one or both can be used.
Please note Elkay ceilingmount PIR’s have ONLY one neutral terminal.
This manual suits for next models
1
Popular Security Sensor manuals by other brands

RKI Instruments
RKI Instruments 35-3001A-13-XX Operator's manual

System Sensor
System Sensor WFDT Installation and maintenance instructions

Elcometer
Elcometer 270 user guide

Tractel
Tractel Tracpode Operating and maintenance instructions

Friendtrol Technologies
Friendtrol Technologies TMS PLUS Series manual

SubSurface Instruments
SubSurface Instruments AML Operator's manual