Universal Display TAA 1x43/ST
Page 2
Parameter und deren Bedeutung
P01 .......Istwert Temperaturfühler 1 in °C /°F .. (nur Anzeige, Bereich -100...+300)
P02 .......Istwert Temperaturfühler 2 in °C /°F... (nur Anzeige, Bereich -100...+300)
P03 .......4-20mA Stromeingang.......................(nur Anzeige, Bereich -150...+999)
P04 .......0..10V Spannungseingang................(nur Anzeige, Bereich -150...+999)
P10 .......Temperaturfühler 1 ...................ON = eingeschaltet, Off = ausgeschaltet
P11 .......Temperaturfühler 1, Korrektur...................................-10,0...+10,0K [0.0]
P12 .......Temperaturfühler 1 und 2, Fühlertyp
501 = TF 501 (Pt1000)
[201] = TF 201
202 = TF 202
120 = TF 120
So1 = kundenspezifisch
So2 = kundenspezifisch
P13 .......Temperaturfühler 1 und 2, Anzeige in C° oder °F
[01] = in °C 02 = in °F
P15 .......Temperaturfühler 1, Kommastelle ................................[on] = 0.1, off = 1
P16 .......Temperaturfühler 1, Untere Alarmgrenze....................-120...P17 [-120]
P17 .......Temperaturfühler 1, Obere Alarmgrenze ....................... P16...310 [310]
P18 .......Temperaturfühler 1, Alarmverzögerung........................0...120 min. [05]
P20 .......Temperaturfühler 2 .................ON = eingeschaltet, [Off] = ausgeschaltet
Wenn eingeschaltet, gleicher Temperaturfühlertyp
wie bei P12 festgelegt!
P21 .......Temperaturfühler 2, Korrektur...................................-10,0...+10,0K [0.0]
P25 .......Temperaturfühler 2, Kommastelle ...............................[on] = 0.1, off = 1
P26 .......Temperaturfühler 2, Untere Alarmgrenze ...................-120...P27 [-120]
P27 .......Temperaturfühler 2, Obere Alarmgrenze ....................... P26...310 [310]
P28 .......Temperaturfühler 2, Alarmverzögerung........................0...120 min. [05]
P30 .......4-20mA Stromeingang..........[Off] = ausgeschaltet , ON = eingeschaltet
P31 .......4-20mA Stromeingang, unterer Eckwert ..........................0...20mA [4.0]
P32 .......4-20mA Stromeingang, oberer Eckwert..........................0...20mA [20.0]
P33 .......4-20mA Stromeingang, Anzeige
Anzeigewert bei Strom festgelegt mit P31 .........................-150...P34 [0.0]
P34 .......4-20mA Stromeingang Anzeige
Anzeigewert bei Strom festgelegt mit P32 ........................ P33...999 [20.0]
P35 .......4-20mA Stromeingang, Kommastelle .........................[on] = 0.1, off = 1
P36 .......4-20mA Stromeing., Untere Alarmgrenze ...................-150...P37 [-150]
P37 .......4-20mA Stromeing., Obere Alarmgrenze....................... P36...999 [999]
P38 .......4-20mA Stromeing., Alarmverzögerung .......................0...120 min. [05]
P40 .......0-10V, Spannungseingang (U-Eingang)................ [Off] = aus, ON = ein
P41 .......0-10V U-Eingang, unterer Eckwert........................................0...10V [0.0]
P42 .......0-10V U-Eingang, oberer Eckwert.......................................0...10V [10.0]
P43 .......0-10V U-Eingang, Anzeige
Anzeigewert bei Spannung festgelegt mit P41.................. -151...P44 [0.0]
P44 .......0-10V U-Eingang, Anzeige
Anzeigewert bei Spannung festgelegt mit P42................... P43...999 [3.0]
P45 .......0-10V U-Eingang, Kommastelle ....................................[on] = 0.1, off = 1
P46 .......0-10V U-Eingang, Untere Alarmgrenze .......................-150...P47 [-150]
P47 .......0-10V U-Eingang, Obere Alarmgrenze ........................... P46...999 [999]
P48 .......0-10V U-Eingang, Alarmverzögerung............................0...120 min. [05]
P50 .......Standardanzeige
[01] = P01 wird dauerhaft angezeigt
02 = P02 wird dauerhaft angezeigt
03 = P03 wird dauerhaft angezeigt
04 = P04 wird dauerhaft angezeigt
05 = zwischen P01 / P02 wird automatisch gewechselt
06 = zwischen P03 / P04 wird automatisch gewechselt
07 = zwischen P01 bis P04 wird automatisch gewechselt
P51 .......Messintervalle .............01= 0,25sec, 02= 0,5s, [03]= 1s, 04= 2s, 05= 4s
Dient zur Dämpfung der Anzeige bei Störungen
P52 .......Buzzer-Alarm-Wiederholungszeit............................off, 1...240 min. [60]
P99 .......Code für Zugangsschutz, ............................................Codenummer ist 88
[..]-Werte sind Werkseinstellungen.
Parameter description
P01 .......Actual Value Probe 1 (°C or °F) ........... (display only, range -100...+300)
P02 .......Actual Value Probe 2 (°C or °F)............(display only, range -100...+300)
P03 .......4-20mA Current Input............................ (display only, range -150...+999)
P04 .......0..10V Voltage Input............................... (display only, range -150...+999)
P10 .......Temperature Probe 1......................ON = switched on, Off = switched off
P11 .......Temperature Probe 1, Correction .............................-10,0...+10,0K [0.0]
P12 .......Temperature Probe 1 and 2, probe type
501 = TF 501 (Pt1000)
[201] = TF 201
202 = TF 202
120 = TF 120
So1 = customer specific
So2 = customer specific
P13 .......Temperature Probe 1, display in °C or °F
[01] = in °C 02 = in °F
P15 .......Temperature Probe 1, Decimal place ...........................[on] = 0.1, off = 1
P16 .......Temperature Probe 1, Alarm low limit .........................-120...P17 [-120]
P17 .......Temperature Probe 1, Alarm high limit ......................... P16...310 [310]
P18 .......Temperature Probe 1, Alarm Delay................................0...120 min. [05]
P20 .......Temperature Probe 2....................ON = switched on, [Off] = switched off
If switched on, the same probe type as selected at P12
must be used !
P21 .......Temperature Probe 2, Correction .............................-10,0...+10,0K [0.0]
P25 .......Temperature Probe 2, Decimal place ...........................[on] = 0.1, off = 1
P26 .......Temperature Probe 2 , Alarm low limit ........................-120...P27 [-120]
P27 .......Temperature Probe 2, Alarm high limit.......................... P26...310 [310]
P28 .......Temperature Probe 2, Alarm Delay................................0...120 min. [05]
P30 .......4-20mA Current Input...................[Off] = switched off, ON = switched on
P31 .......4-20mA Current Input, low Current Value.........................0...20mA [4.0]
P32 .......4-20mA Current Input, upper Current Value ................. 0...20mA [20.0]
P33 .......4-20mA Current Input, display
Display value assigned to the electric current P31 ............-150...P34 [0.0]
P34 .......4-20mA Current Input, display
Display value assigned to the electric current P32 ........... P33...999 [20.0]
P35 .......4-20mA Current Input, Decimal place .................... 00 = 0.1, 01 = 1 [01]
P36 .......4-20mA Current Input, Alarm low limit ........................-150...P37 [-150]
P37 .......4-20mA Current Input, Alarm high limit ......................... P36...999 [999]
P38 .......4-20mA Current Input, Alarm Delay...............................0...120 min. [05]
P40 .......0-10V, Voltage Input..................................................... [Off] = off, ON = on
P41 .......0-10V Voltage Input, low Current Value ...............................0...10V [0.0]
P42 .......0-10V Voltage Input, upper Current Value.........................0...10V [10.0]
P43 .......0-10V Voltage Input, display
Display value assigned to the voltage P41 ................... -151...P44 [0.0]
P44 .......0-10V Voltage Input, display
Display value assigned to the voltage P42 .................... P43...999 [3.0]
P45 .......0-10V Voltage Input, Decimal place..............................[on] = 0.1, off = 1
P46 .......0-10V Voltage Input, Alarm low limit ............................-150...P47 [-150]
P47 .......0-10V Voltage Input, Alarm high limit............................. P46...999 [999]
P48 .......0-10V Voltage Input, Alarm Delay...................................0...120 min. [05]
P50 .......Standard Display
[01] = P01 will permanently displayed
02 = P02 will permanently displayed
03 = P03 will permanently displayed
04 = P04 will permanently displayed
05 = Display will change automatically within P01 and P02
06 = Display will change automatically within P03 and P04
07 = Display will change automatically within P01 up to P04
P51 .......Measuring Intervals.....01= 0,25sec, 02= 0,5s, [03]= 1s, 04= 2s, 05= 4s
Serves to dampen the display in case of disturbances
P52 .......Buzzer-Alarm Repetition Time........................................1...240 min. [60]
P99 .......Access Code ...............................................................Code number is 88
[..]-values are factory set.
Installation / Inbetriebnahme
Für die Inbetriebnahme benötigen Sie die Information über die Art des Fühlers
bzw. des elektrischen Signals und welchen Messwerten die von der Quelle
gelieferten elektrischen Signale entsprechen.
Beispiel1
TAA als Temperaturanzeige mit einem TF 201-Fühler auf Eingang 1, Anzeige
in °C mit Kommastelle. P10 = on, P12 = 201, P15 = on
Beispiel 2:
TAAals Feuchteanzeige an einem Transmitter der 4-20 mAliefert, entsprechend
einem Messbereich von 0 - 100% r.F, Auflösung 1% :
• Sie benutzen den 4-20mA-Eingang (Kl.9)
• P30 = on (eingeschaltet), P31 = 4.0, P32 = 20.0, P33 = 0, P34 = 100,
P35 = off
Installation / Start-up
Forstart-upyouneedinformationaboutthekindofproberesp.theelectricalsignal
provided by transmitter/controller and which values should correspond to this.
Example 1:
Youwanttouse theTAAasa temperaturedisplay withaTF201 probeconnected
to input 1, display should be °C with 0.1 resolution. P10 = 3, P12 = 0
Example 2
You want to constitute the TAAas a humidity display for a Humidity Sensor which
delivers 4-20 mA corresponding to a 0...100% range, resolution 1%.
• You have to use the 4...20mA input (terminal 9)
• P30 = on (activated), P31 = 4.0, P32 = 20.0, P33 = 0, P34 = 100, P35 = off