Eltek Valere ACR INV222-6.75 LV User manual

AC Rack
ACR INV222-6.75 LV
USER MANUAL
UM_ACR_INV222_6.75_LV_E_R1.0

AC Rack
ACR INV222-6.75 LV
User Manual
Page 2 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
Notes to this manual
ATTENTION! Read this manual very carefully before installing and commissioning the AC rack.
This manual is a part of the delivered AC rack. Familiarity with the contents of this manual is required
for installing and operating the AC rack.
The rules for prevention of accidents for the specific country and the general safety rules in accor-
dance with IEC 364 must be observed.
The function description in this manual corresponds to the date of publishing.
Technical changes and changes in form and content can be made at any time by the manufacturer
without notice. There are no obligations to update the manual continually.
The AC rack is manufactured in accordance with applicable DIN and VDE standards such as VDE 0106
(part 100) and VDE 0100 (part 410). The CE marking on the module confirms compliance with EU stan-
dards 2006-95-EG (low voltage) and 2004-108-EG (electromagnetic compatibility) if the installation and
operation instructions are followed.
Supplier:
ELTEK VALERE INDUSTRIAL GmbH
Schillerstraße 16
D-32052 Herford
+ 49 (0) 5221 1708-210
FAX + 49 (0) 5221 1708-222
Email [email protected]
Internet http://www.eltekvalere-industrial.com
Copyright ELTEK VALERE INDUSTRIAL 2008. All rights reserved.

AC Rack
ACR INV222-6.75 LV
User Manual
Page 3 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
The current revision status of this user manual:
Revision: 1.0
Date: 2008-12-08
Revision Description of change Writer Date
00 First edition RTH 2008-03-18
01 Block diagrams reworked, index of figures
inserted, minor text modifications RTH 2008-05-08
02 Connection tables reworked according to the labelling on the (as
from now) serial plexiglass cover RTH 2008-06-05
1.0 Minor text modifications, new revision status numbering (X.X)
introduced, pinning of X23 (connector alarm relay) corrected. RTH 2008-12-08

AC Rack
ACR INV222-6.75 LV
User Manual
Page 4 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
Table of Contents
1. SAFETY INSTRUCTIONS ................................................................................................................6
2. WASTE DISPOSAL RULES..............................................................................................................6
3. GENERAL INFORMATION ...............................................................................................................7
3.1 Block Diagram ...........................................................................................................................................................7
3.2 Possible Configurations..........................................................................................................................................8
3.3 Perspective View .....................................................................................................................................................9
3.4 Optional Equipment: ................................................................................................................................................9
3.5 Cooling/Air Flow Direction .................................................................................................................................. 10
4. HANDLING ..................................................................................................................................... 11
4.1 Storage .................................................................................................................................................................... 11
4.2 Commissioning...................................................................................................................................................... 11
4.2.1 Assembling........................................................................................................................................................................... 11
4.2.2 Communication Interface/Termination ........................................................................................................................ 12
4.2.3 CAN-BUS Addresses .......................................................................................................................................................... 12
4.2.4 Termination.......................................................................................................................................................................... 12
4.2.5 Rear View/Electrical Connectors.................................................................................................................................... 13
4.2.6 Connection Tables.............................................................................................................................................................. 13
4.2.7 Schematic Diagram (Example of use)............................................................................................................................ 15
5. MAINTENANCE............................................................................................................................. 16
6. TECHNICAL SPECIFICATIONS .................................................................................................... 17
6.1 Dimensional Drawings:......................................................................................................................................... 18
7. NOTES............................................................................................................................................ 19

AC Rack
ACR INV222-6.75 LV
User Manual
Page 5 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
Index of Figures
Figure 1) - Block diagram..................................................................................................................................7
Figure 2) - AC rack fully equipped......................................................................................................................9
Figure 3) - Sub rack airflow..............................................................................................................................10
Figure 4) - Front view of the empty rack .........................................................................................................11
Figure 5) - Rear view of the rack......................................................................................................................12
Figure 6) - Detail: Jumper.................................................................................................................................12
Figure 7) - Rear side connectors......................................................................................................................13
Figure 8) - Schematic diagram (example of use).............................................................................................15
Figure 9) - Rack dimensions ............................................................................................................................18

AC Rack
ACR INV222-6.75 LV
User Manual
Page 6 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
1. Safety Instructions
Warning!
Because several components of operating electrical devices are charged by dangerous voltage, the
improper handling of electrical devices may be the cause of accidents involving electrocution, injury,
or material damages.
Operation and maintenance of electrical devices must be performed by qualified skilled
personnel such as electricians in accordance with EN 50110-1 or IEC 60950.
Install the module only in areas with limited access to unskilled personnel.
Before starting work, the electrical device must be disconnected from mains. Make sure that
the module is earthed.
Do not touch connector pins as they can be charged with dangerous voltage up to 30 seconds
after disconnection.
Only spare parts approved by the manufacturer must be used.
2. Waste Disposal Rules
All electric devices must be disposed of separate from domestic waste at collecting points that have
been set up by the government or municipal authority.
“Separate collection is the precondition to ensure specific treatment and recycling of WEEE and is
necessary to achieve the chosen level of protection of human health and the environment in the
Community.”
The above statement from EU directive 2002/96/EC applies to all electric devices installed within
EU countries.
In countries outside the EU, different rules may apply regarding waste disposal of electric devices.
For more information about waste disposal of your discarded equipment, contact your
ELTEK VALERE INDUSTRIAL partner.

AC Rack
ACR INV222-6.75 LV
User Manual
Page 7 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
3. General Information
The AC rack is a unit ready for integration in system cabinets with a standard 19’’ frame. It is designed
as a stand-alone rack (not cascadable). The unit can be equipped with a maximum of 3 inverters of type
INV222 (INV215) plus 1 static transfer switch STS207 and delivers an output power to a maximum of
6.75kVA. After safe mechanical and electrical connection, the unit is ready for operation.
3.1 Block Diagram
ACR INV222-6.75 LV
Figure 1) - Block diagram

AC Rack
ACR INV222-6.75 LV
User Manual
Page 8 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
3.2
Possible Configurations
Up to 3 INV222 (INV215) with DC input voltages according to the table below plus 1static transfer
switch STS207 (obligatory) can be integrated into one rack.
Rack designation Material code
For inverter/
input voltage
Necessary type of
static transfer switch
STS207/material code
INV215/24VDC STS207-24V/601-070-
415.00
INV222/48VDC
ACR INV222-6.75 LV 502-222-315.LV
Output
voltage=
230VAC
INV222/60VDC
STS207-LV/601-070-
515.00
Output power of the rack, equipped with INV215:
Number of installed
inverters (INV215)
Output power (without
redundancy) Output power (n + 1) Output power (n + 2)
1 1500VA --- ---
2 3000VA 1500VA ---
3 4500VA 3000VA 1500VA
Output power of the rack, equipped with INV222:
Number of installed
inverters (INV222)
Output power (without
redundancy) Output power (n + 1) Output power (n + 2)
1 2250VA --- ---
2 4500VA 2250VA ---
3 6750VA 4500VA 2250VA

AC Rack
ACR INV222-6.75 LV
User Manual
Page 9 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
3.3 Perspective View
Figure 2) - AC rack fully equipped with 3 inverters INV222
and 1 static transfer switch STS207.
1 Four screws M6 to fix the sub rack to the frame of the system cabinet Component parts of the
sub rack
2 One captive screw per module is used to fix it to the sub rack Component part of the
module
3.4 Optional Equipment:
Optional equipment according to the following table is available:
Description Material Code
Cover plate (with handle), necessary to cover empty slots, 1/4 x 19’’, 2U,
colour RAL 7035 881-MEC-BPL.02.21.B
1
1
2 2 2
1
1
2

AC Rack
ACR INV222-6.75 LV
User Manual
Page 10 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
3.5 Cooling/Air Flow Direction
The INV222 (INV215) and STS207 units are cooled with internal fans. The airflow is from the front to
rear side. The fans are monitored and speed controlled dependent on module temperature. To provide
sufficient air flow, a minimum space (see item “A” in figure 3) of 50 mm is required between the back-
plane of the rack and the rear cabinet wall as well as an unobstructed supply of air to the front of the
modules.
Figure 3) - Sub rack airflow

AC Rack
ACR INV222-6.75 LV
User Manual
Page 11 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
4. Handling
4.1 Storage
AC racks must be stored in a dry, dust free environment with a storage temperature in accordance
with the specific technical data (see section 6).
4.2 Commissioning
Carefully unpack the unit and integrate it in your power supply cabinet with 4 screws M6 (1) at
the front side.
Figure 4) - Front view of the empty rack
4.2.1 Assembling
Assemble the modules into the slots of the sub rack.
Fill the rack beginning with the left slot (slot 1 to 3 for INV222/INV215, slot 4 for STS207)
Fix the modules with the captive screws.
Not used slots must be covered with cover plates (see section “Optional Equipment”).
1
Slot1
INV222
Slot2
INV222
Slot3
INV222
Slot4
STS207
1
11

AC Rack
ACR INV222-6.75 LV
User Manual
Page 12 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
4.2.2
Communication Interface/Termination
The AC rack is equipped with a serial data interface in accordance with the Controller Area Network
(CAN) specification.
Several racks and/or modules in a system can be controlled and monitored through the CAN-Bus by a
central DC controller unit UPC3.
Two CAN-Bus connectors (X21= CAN 1; X22= CAN 2) are located at the rear of the sub rack
(see figure 5).
4.2.3 CAN-BUS Addresses
All modules within a system must have a specific CAN-BUS address for a clear identification through
the central controller unit.
The CAN-BUS addresses of the installed inverters are automatically designated by the AC rack.
4.2.4 Termination
The CAN-Bus must be terminated at both ends.
If no other rack and/or module is connected (CAN 2 not used), the CAN-Bus termination resis-
tor must be activated with the plugged jumper at the rear of the backplane of the AC rack (see
figure 6).
If CAN 2 is connected, the CAN-Bus termination resistor must be deactivated (the jumper must
be removed).
Not more than two termination resistors should be activated on one bus and these should be
located at both ends of the bus.
ATTENTION: Missing terminations or too many terminations within the system can disturb the CAN-Bus
communication.
X21 X22
Figure 5) - Rear view of the rack
Figure 6) - Detail: Jumper
REMARK: Figure 5) shows the rack without the serial plexiglass cover!

AC Rack
ACR INV222-6.75 LV
User Manual
Page 13 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
4.2.5
Rear View/Electrical Connectors
Figure 7) - Rear side connectors
Connect the terminals according to the connection tables on the following pages.
REMARK: The rack itself must be grounded with the cabinet frame (common PE of the system) on the
special grounding bolt “PE” (screw thread M5).
4.2.6 Connection Tables
Assignment of the rear side connectors according to figure 7).
DC input voltage of the inverters 24, 48, 60VDC
Connector Function Recommended
external fuses
Recommended
wire cross section
X1 (+) DC input inverter 1
X2 (-) DC input inverter 1 63A 16mm2
X3 (+) DC input inverter 2
X4 (-) DC input inverter 2 63A 16mm2
X5 (+) DC input inverter 3
X6 (-) DC input inverter 3 63A 16mm2

AC Rack
ACR INV222-6.75 LV
User Manual
Page 14 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
Connector Function Recommended
external fuses
Recommended wire
cross section
X11 AC output of inverter 1
1 Neutral 1.5 mm2
2 Line output 10A 1.5 mm2
X12 AC output of inverter 2
1 Neutral 1.5 mm2
2 Line output 10A 1.5 mm2
X13 AC output of inverter 3
1 Neutral 1.5 mm2
2 Line output 10A 1.5 mm2
X41 AC line input to STS (coming from
inverters)
1 Line from inverter
2 Line from inverter
3 Line from inverter
No
3 x 1.5 mm2
(All three lines must
be connected)
X42
1 Neutral connection to STS (only
measuring)
No 1.5 mm2
2 AC line input to STS (coming from
mains)
3 AC line input to STS (coming from
mains)
32A (@230VAC)
2 x 2.5 mm2
(both lines must be
connected)
4 Line output of the STS (to the load)
5 Line output of the STS (to the load) 32A (@230VAC)
2 x 2.5 mm2
(both lines must be
connected)
X43 DC input to STS
(redundant circuitry supply)
1 minus
2 plus MCB C2 0.75mm2
X23 Common Alarm Relay output of STS
1 NO (normally open) contact No 0.5mm2
2 COM (common) contact No 0.5mm2
3 NC (normally closed) contact No 0.5mm2
X21 CAN 1 (RJ11, 6-pole) Cord Set
X22 CAN 2 (RJ11, 6-pole) Cord Set

AC Rack
ACR INV222-6.75 LV
User Manual
Page 15 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
4.2.7 Schematic Diagram (Example of use)
Figure 8) - Schematic diagram (example of use)
We recommend an individual fuse for each input!
With this fuse you can switch ON/OFF each module individually.
Recommended input fuses and output fuses: See the tables on previous pages.

AC Rack
ACR INV222-6.75 LV
User Manual
Page 16 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
5. Maintenance
In general, the system is maintenance-free.
A yearly inspection with following checks is recommended:
Correct fan operation (modules)
Mechanical inspection
Removal of dust and dirt
Check for internal dust or humidity
Attention! Dust combined with moisture or water may influence or destroy the internal electronic
circuits.
Dust inside the unit can be blown out with dry compressed air.
The interval between the checks depends on the ambient conditions of the installed system.
To exchange defective fans in the inverter modules, an additional instruction manual is available on
request.

AC Rack
ACR INV222-6.75 LV
User Manual
Page 17 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
6. Technical Specifications
Type designation ACR INV222-6.75 LV
Material code 502-222-315.LV
Main Data:
Modules Designed for the use of 1 up to max. 3 DC/AC inverters of series INV215
(Vi= 24VDC) or INV222 (Vi= 48; 60VDC) and 1 static transfer switch
STS207 (24; 48/60V version)
Input voltage 24, 48, 60VDC, depending on the used inverters
Internal input fuses There are no internal fuses, we recommend an individual fuse for each
input.
Output voltage 230VAC
Output power INV215: 1.5 up to 4.5kVA @ cos phi= 0,8;
INV222: 2.25 up to 6.75kVA @ cos phi= 0,8
Electric connectors:
DC input 3 x input (1 for each module), screw thread M5
PE bolt screw thread M5
DC input for STS207
(redundant DC supply)
screw terminals
AC mains bypass input to
STS
230VAC, 50/60Hz, screw terminals
AC line input to STS (from
inverters)
230VAC, 50/60Hz, screw terminals
AC outputs of inverters 3 x (screw terminals)
AC output of STS (to the
load)
230VAC, 50/60Hz, screw terminals
Signalling contacts 1 x potential free relay output COM, NO, NC; (STS207 common alarm)
Communication interfaces 2 x isolated CAN-Bus connectors (RJ11, 6-pole)
Environmental:
Max. installation altitude 1500 m
Ambient temperature operation: -20°C...+55°C; storage: -40°C...+85°C
Audible noise 45dB(A) at 1m distance

AC Rack
ACR INV222-6.75 LV
User Manual
Page 18 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
Mechanical:
Type of construction Sub rack, 19’’, 2U
Cooling The modules are fan-cooled (front-to-rear airflow), temperature-
regulated and monitored
Surfaces powder coating RAL 7035 (front only), constructive parts: anodized
metal
W/H/D 483/88.5/350mm (19”, 2U)
Minimum installation
depth
400mm
Weight approx. 4.9 kg (excluding INV and STS modules)
Applicable standards:
Mechanical construction acc. to VDE 0160 edition 5.88 chapter 7.2.2
Protection class IP20
Climatic conditions acc. to IEC 721-3-3 class 3K3/3Z1/3B1/3C2/3S2/3M2
RFI suppression/
immunity
CE-label, (EN50081-1, EN55011/55022 class „B“, EN50082-2, EN61000-
4 part 2/3/4/5)
Compliance to safety
standards
acc. to EN60950-1, VDE0100 T410, VDE0110, EN60146
6.1 Dimensional Drawings:
Figure 9) - Rack dimensions

AC Rack
ACR INV222-6.75 LV
User Manual
Page 19 (20)
ELTEK VALERE INDUSTRIAL ©2008 UM_ACR_INV222_6.75_LV_E_R1.0
7. Notes

Supplier:
ELTEK VALERE INDUSTRIAL GmbH
Schillerstraße 16
D-32052 Herford
+ 49 (0) 5221 1708-210
FAX + 49 (0) 5221 1708-222
Internet http://www.eltekvalere-industrial.de
Copyright ELTEK VALERE INDUSTRIAL 2008. All rights reserved.
Table of contents
Other Eltek Valere Rack & Stand manuals
Popular Rack & Stand manuals by other brands

Tuff Mount
Tuff Mount TM-200HD Owner's manual & safety instructions

ClipperCreek
ClipperCreek CS EVSE Pedestal installation guide

Actiforce
Actiforce Aluforce Pro 140 M Assembly manual

PEERLESS
PEERLESS IM740P Installation and assembly

LEVENGER
LEVENGER HARLEQUIN LIBRARY STAND manual

SMART
SMART WSE-400 user guide