EMC ModWeeihg MW61A User manual

Weigher Instrument MW61A
Instruction Manual ALL
MW61A_IM_ALL_SV6.09d_en EMC INDUSTRIAL GROUP LTD
APPLICA IONS
• Silo/ ank weighing
• Batch weighing
• Platform scales
FEA URES
• Digital high accuracy design (no pots or
DIP switches)
• Excitation for up to 10 x 350Ω loadcells
• 6 or 4 wire loadcell connection
• Update rate 100 times per second
• 4-20mA output
• Modbus communications (independent
RS232 and RS485 ports)
• USB Host & Device (memory stick & PC)
• Field software upgrades
• 12-24Vdc power supply
• Overall accuracy better than 0.01%
• otalising
• Peak reading
• Rate of change (flowrate)
MD2,MP2 INDICA OR
• IP54 Facia
• 2.8" (70mm) colour LCD
• 320 x 240 pixels
• Polyester film tactile keypad
• 4-20mA output, 1 digital input & 2 digi-
tal outputs
MO3 I/O for MP2
• 4 Digital inputs
• 4 Digital outputs
• 4-20mA input (or 0-10V)
• 4-20mA output
MD1,MP1 INDICA OR
• IP65 Facia
• 4.3" (109mm) colour LCD
• 480 x 272 pixels
• Silicone tactile keypad
M 1 RANSMI ER
• Size 136 x 66 x 50mm
• Optional removable P-Module holds cali-
bration settings
M 3 RANSMI ER
• Size 136 x 66 x 50mm
MR1 I/O
• Size 136 x 66 x 30mm
• 8 Digital inputs
• 8 Digital outputs
• 4-20mA input (or 0-10V)
• 4-20mA output x 2
• Pulse output
INCLUDES
• Installation
• Setting up principles
• Setup Summary
• I/O Function Table
• Operation
• Alarms
APPLIES O
• MW61A - Weigher P-Mo ule
• MT1,MT3 - Transmitters
• MD1,MD2 - Display
• MP1,MP2 - Processor
• MR1 - Remote IO
• Software v6.09 onwar s
MR1
MT3
MT1
MD2,MP2
MD1,MP1

EMC INDUS RIAL GROUP L D Features
MW61A_IM_ALL_SV6.09d_en 2/47
AVAILABLE DOCUMEN A ION
COPYRIGHT © 2019 by EMC In ustrial Group Lt
56 Tarn ale Grove, Albany, North Shore, Aucklan 0632
PO Box 101 444 North Shore, Aucklan 0745, New Zealan
Telephone +64-9-415 5110, Facsimile +64-9-415 5115
E-mail sales@emc.co.nz Web http://www.emc.co.nz
As we are continuously improving our pro ucts, changes to this specification may occur without notice.
(Document Details: g0 g1 g2 g3 g4 g5 g6 g7 g8 g9 g10 g11 g12 g13 g14 g15 MT1,MT3,MD1,MD2,MP1,MP2))
PRODUC DESCRIP ION DOCUMEN A ION
MW61 Weigher Instrument Technical Information
Instruction Manual
MW64 Batch Weigher Instrument Technical Information
Instruction Manual
MW65 Process Weigher Instrument Technical Information
Instruction Manual
MW93 Weight Change Instrument Technical Information
Instruction Manual
MW94 Impact Flowmeter Instrument Technical Information
Instruction Manual
MW95 Belt Weigher Instrument Technical Information
Instruction Manual
MW96 Weighfee er Instrument Technical Information
Instruction Manual

EMC INDUS RIAL GROUP L D Features
MW61A_IM_ALL_SV6.09d_en 3/47
Contents
IN RODUC ION ....................................................... 5
Features 5
Basic 5
Inputs 5
Internal Signals 5
Outputs 5
Communications & Display 6
IO Summary 6
Specifications 6
Loa cell Input AI1 6
Analog Input AI2 7
Analog Outputs AO1 & AO2 7
Digital Inputs INx 7
Digital Outputs OUTx 7
Communications COM1, COM2 & COM3 7
General 7
INS ALLA ION ......................................................... 8
Dimensions 8
MD2 Display 8
MP2 Processor 8
MD1 Display 8
MP1 Processor 8
MT1 Transmitter 8
MT3 Transmitter 8
MR1 Remote IO 8
Connections 8
Connection Principles 8
Connection Diagram – MP2 9
Connection Diagram – MP1 10
Connection Diagram – MT1 11
Connection Diagram – MT3 12
Loa cell Connections 12
Multi rop Systems 13
SE ING UP ........................................................... 14
Setup 14
Description 14
Keypa 15
Displaying the Setup Menus 16
Selecting a Menu Item 16
Description of Menus 16
To A just A Setting 17
Macros 18
Macro Co es 18
A justing a Macro 20
Software Up ating 21
Up ate with USB Drive 21
Up ate with a PC 22
SE ING UP GUIDE ................................................ 22
Settings 22
Quick Keys 22
Quick Keys Reference 22
Initial Setup 23
Engineering Units 23
Measuring Range 23
Display Resolution 23
Calibration 23
Calibrate Loa cell 23
SE UP – MW61A WEIGHER ..................................... 24
Basic Settings 24
Engineering units 24
Enter weighing units 24
Measuring range 24
Display resolution 24
Tra e setup 24
Weight change constants 25
Clock 25
Inputs 25
Digital inputs 25
Loa cell input (vessel weight) 26
Calibrate loa cell 26
Calibrate Using Loa cell Specifications 27
Current/Voltage input 27
Internal Signals 28
Weight 28
Flowrate 29
Totaliser 29
Limits 29
Events/Alarms/Faults 30
Memory Storage 30
User ata 31
Outputs 31
Analog output 1 (weight) 31
Analog output 2 (gross weight) 32
Digital outputs 32
Communications & Display 32
Comms port 1 - RS232 32
Comms port 2 - RS485 33
Comms port 3 - RS485 MR1 33
Interface registers 33
Printing & Macros 34
Display (MD1,MD2,MP1,MP2) 35
USB 38
Info, Resets & Final Cal 38
Pro uct Information 38
Reset settings 39
Reset macros 39
Final calibration 39
Loa cell calibration 39
SE UP – DISPLAY ................................................... 39
Basic Settings 39
Clock 39
Communications & Display 40
Comms port 1 – RS232 40
Comms port 2 – RS485 40
Display 40
CompactCom 40

EMC INDUS RIAL GROUP L D Features
MW61A_IM_ALL_SV6.09d_en 4/47
Information & Resets 40
Pro uct Information 40
Reset settings 40
Other display settings 40
I/O Function able 40
Mo bus Access 43
OPERA ION............................................................ 43
Display 43
Keys 44
Operator Menu 45
Actions 45
Settings 46
Alarm menu 46

EMC INDUS RIAL GROUP L D Features
MW61A_IM_ALL_SV6.09d_en 5/47
IN RODUC ION
Features
Basic
Units & Resolution
The units for each variable type (weight etc.) can be selecte from a list of metric an imperial units.
The resolution of each variable type can be a juste , this alters the count by e.g 100kg isplaye in
0.2kg increments.
OIML Design
The instrument is esigne to OIML stan ar s.
Language Support
Support is available for the following languages: English, Chinese, Korean, German, Spanish, French,
Italian an Polish.
Inputs
Digital Inputs INx
The igital inputs are programmable to a range of function inclu ing ‘acquire zero’, ‘print’ etc.
Direct Calibration
Direct calibration uses the loa cell capacity an loa cell sensitivity to calibrate the weight signal. Large
capacity weighing systems can be quickly an accurately calibrate without the nee for large test
weights.
Corner Adjustment (M 1 only)
The input sensitivity can be in ivi ually a juste for up to 4 loa cells, allowing ifferences in loa cell
sensitivities to be correcte .
Four Loadcell Inputs (M 1 only)
Separate inputs are available for 4 loa cells allowing the signal of each to be monitore sperately. This
provi e an ai for loa balancing across loa cells an also for fault fin ing.
Zeroing/ aring
The ZERO an TARE keys allow the weight rea ing to be set to zero. The SET TARE key allows a man-
ual tare weight to be entere .
Signal Filtering
Filtering for the weight can be a juste to get the optimum compromise between re uction of plant vi-
bration an response spee .
Internal Signals
Limits
The high an low limits have a justable setpoints which may be programme to operate on any internal
signal.
Event Collection
Process events are collecte for operation with external equipment (PLCs etc.)
otal Weight
The isplaye weight can be a e to a running total. The total can be reset at any time.
Peak Weight
A peak weight rea ing is maintaine of the highest absolute value of the weight measure . The peak
value can be reset to 0.
Memory Storage
Allows a group of settings to be store or recalle from memory. This can be use for example to store
settings for ifferent pro ucts. There are 20 memory locations with up to 4 settings in each.
Outputs
Analog Outputs AO1 & AO2
A 4-20mA output normally of weight may be programme to be any of the internal signals inclu ing
isplaye weight, gross weight an net weight.
Analog I/O Scaling
The analog output range can be a juste over the full 0 to 20mA range. The output will rive to a slight
negative mA, allowing a live zero to be achieve when using a 0 to 20mA range. A voltage output is
easily pro uce by connecting a resistor to the output.
In a ition the analog output signal is selectable to come from any internal signal in the instrument e.g
weight, flowrate etc.

EMC INDUS RIAL GROUP L D Specifications
MW61A_IM_ALL_SV6.09d_en 6/47
Digital Outputs OU x
The igital outputs are programmable to operate from any internal signal. These signals inclu e the
igital input states, status con itions (running, pause etc) an any fault con itions that are etecte .
This makes it easy connect into other systems.
Communications & Display
Comms
RS232 an RS485 ports are available. These are use to connect Mo Weigh units together an also to
connect to other systems. The protocol is either ASCII output for example to rive a printer or Mo bus
for interactive communications. Bau rates an no e a resses are programmable.
USB host an evice ports are available. This allows for example PC an USB flash rive connectivity. It
can be use to up ate the units software, for ata logging an for recor ing of the units settings.
Printouts & Macros
Printouts can be triggere by a key press or set up to occur at set times uring the ay or week. Data
may also be output continuously for ata collection purposes. Data is output on the COM1 RS232 port.
The content of the printouts is fully programmable using Macros.
Macros are programs use to customise printouts, but can also be use to perform arithmetic calcula-
tions. The Macro language also contains con itional terms for more a vance programming.
Display Customisation
Locks may be set to prevent unauthorise use of the operator keys an restrict entry to the operator
menu. The keys are in ivi ually lockable an optionally a passco e can be use to allow authorise op-
erators to use the keys. Alternatively a confirmation of the key action can be requeste .The operator
MENU can be customise to make a itional settings or signals available to the operator.
The contents of the main isplay can be set to suit any con ition, from a comprehensive isplay show-
ing all operating parameters to a simple isplay showing the basic signals.
Computer Connectivity
Mo Weigh instruments can be connecte to a computer withan RS232 connection. Data can be sent to
the PC at a preset rate. The ata sent can be set up using macros.
There is also a comman line interface which allows any of the settings an ata to be rea or written.
IO Summary
Digital Inputs
(inclu es pulse input)
Digital Outputs
(inclu es pulse output)
Isolate Pulse Output
Isolate 4-20mA Inputs
Isolate 4-20mA Outputs
RS232
RS485
USB Host (Memory Stick)
USB Device (PC Cable)
Corner a justment an bal-
ancing for 4 loa cells
Tra e approvals (MW95,
MW96)
MP2 1 2 1 0 1 1 1 1 1
MP2,MO3 1+4 2+4 1 1 1+1 1 1 1 1
MP1,MR1 1+8 9 1 1 2 2 1 1 1
MD1,MT1,MR1 2+8 1+9 1 1 2 2 2 1 1
MD2,MT1,MR1 2+8 1+9 1 1 2 2 2 1 1
MD1,MT3 2 1 0 0 1 2 1 1 1
MD2,MT3 2 1 0 0 1 2 1 1 1
MD1,MT3,MR1 2+8 8 1 1 3 2 1 1 1
MD2,MT3,MR1 2+8 8 1 1 3 2 1 1 1
Specifications
Loadcell Input AI1
Input Range ±4 mV/V (0-20mV)
Excitation 5 V c ±20 %, 250 mA maximum current

EMC INDUS RIAL GROUP L D Specifications
MW61A_IM_ALL_SV6.09d_en 7/47
Signal processing rate 100 Hz (response time setting≤ 0.5 s)
Input sensitivity 0.5 µV/ ivision maximum
Zero range ±3 mV/V (±15 mV)
Zero rift ±0.02 µV+0.0005 % of ea loa /°C typical
Span rift ±0.0005 %/°C typical
Non-linearity ‹0.002 % of FS
Input noise 0.15 µVp-p typical
Filtering 0.04 s to 32.0 s response time a justable
Sense voltage range 1-5 V
Analog Input AI2
4-20mA input resistance <60 Ω
0-10V input resistance ›100 kΩ
Isolation galvanically isolate to 50Vac
Analog Outputs AO1 & AO2
Output range 0 to 20 mA (-0.2 mA to 21 mA, inclu es stan ar 4-20mA)
Maximum loa 1000Ω
Resolution 0.4 µA
Response time Loa cell response time setting + 20 ms
Voltage output Use an external resistor to convert mA to volts.
For example 500Ω gives 10 V at 20 mA.
Non-linearity ‹0.01 %
Drift ‹2 µA/°C.
Isolation in epen ently galvanically isolate to 50Vac
High voltage › 8 V
Low voltage ‹ 4 V
Maximum voltage 32 V
Input loa 4 kΩ approximate
Digital Inputs INx
High voltage › 8 V
Low voltage ‹ 4 V
Maximum voltage 32 V
Input loa 6 kΩapproximate
Input type PNP output sensors
Digital Outputs OU x
Max output current Σ IIOx < 0.25 A
Output voltage same as supply voltage
Communications COM1, COM2 & COM3
COM1 Interface RS232
COM1 Han shake CTS can be enable
COM2/COM3 Interface RS485
Bau rates 9600, 19200, 38400, 57600, 115200 (230400 on COM2)
Settings 8 ata bits, no parity, 2 stop bits (8-N-2)
Protocol Mo bus RTU (MWBUS on COM2)
General
IP Rating IP20 (MD1,MP1 facia IP65) (MD2,MP2 facia IP54)
Operating temperature -10 to 45 °C
Supply voltage 10 to 28 V c
Power MT1 1.0 to 2.2 W + PTacho Excitation
Power MT3 1.0 to 2.2 W + PTacho Excitation
Power MR1 1.5 to 2.5 W + POUTx
Power MD1 1.8 W
Power MP1 1.8 to 3.0 W
Power MD2 1.4 W
Power MP2 1.4 to 3.1 W
Power MP2 + MO3 3.4 to 5.0 W + POUTx + PTacho Excitation
MP2 Restrictions PLoa cell Excitation + PAO1 + PAO2 < 1.5 W
ISupply < 0.5 A

EMC INDUS RIAL GROUP L D Dimensions
MW61A_IM_ALL_SV6.09d_en 8/47
INS ALLA ION
The instrumentation must be mechanically installe an then the electrical connections ma e. The im-
portant electrical connections are as follows.
Power supply connections: 24V c fuse or current limite to 5A.
Communications: A shiel e cable is recommen e to connect units together with COM2. It can exten
up to 500m. This leaves COM1 (RS232) free for other applications. For a cable length over 50m, MAT
line terminators must be fitte at each en of the cable.
Loa cell connections: For cable runs less than 20m, a 4 wire connection shoul be a equate. For longer
cable lengths, a 6 wire connection is recommen e .
Some a itional optional connections are as follows.
High an low limit outputs.
The 4-20mA weight output.
Dimensions
Following are the imensions of the har ware items that make up the system.
The isplays/processors are esigne for panel mounting.
MD2 Display
MP2 Processor
MD1 Display
MP1 Processor
M 1 ransmitter
M 3 ransmitter
MR1 Remote IO
Connections
Connection Principles
Mo Weigh instruments can be configure in many ifferent ways to suit any given application.
136mm
66mm
20mm
8mm
optional DIN rail mount
approx. 350g
156mm
86mm
136mm
66mm
20mm
50mm
8mm
optional DIN rail mount
approx. 35
0g
136mm
66mm
20mm
50mm
8mm
optional DIN rail mount
approx. 35
0g
PANEL cut out
186 x 92 mm
-0.0 + 1.0 mm
FACIA
208 x 104 mm
top view
approx. 450g
104mm
30mm
8mm
208mm
PANEL cut out
138 x 67 mm
-0.0 + 1.0 mm
FACIA
144 x 72 mm
top view
approx. 400g
72mm
80mm
9mm
144mm

EMC INDUS RIAL GROUP L D Connections
MW61A_IM_ALL_SV6.09d_en 9/47
The isplay is normally locate to suit an operator. The transmitter can be locate in the fiel to re uce
fiel wiring or can be locate with the isplay for a more conventional approach.
The I/O can conveniently be situate on a DIN rail in a cabinet.
Connection Diagram – MP2
D
1
D
2
D
3
D
4
D
5
Analog
+AO2
−
AO2
+VAI2
+mAAI2
−
AI2
limit 1 output
limit 2 output
motion
healthy
acquire zero
acquire tare
print
capture weight
MP2
2
3
4
5
6
7
8
2
3
4
6
7
20
RXD
DSR
SG
DTR
CTS
RTS
RXD
TXD
CTS
DSR
SG
DTR
P1
P2
P3
P4
P5
P6
RTS
TXD
0V
0V
RXD
CTS
RJ12
Loadcell
Power/COM2
+EX
−
EX/0V
+
SIG
−
SIG
+
SEN
−
SEN
24V
0V
COM1
MAC
MAP
DB25M
t
o
Printer
weight
LOADCELL
(s)
optional sense for 6 wire
connection
BEL SPEED ACHO
+
0
V
output
B
1
B
2
B
3
B
4
B
5
B
6
I/O
+AO1
−
AO1
+/~ OUT0
−
/~ OUT0
OUT9
IN9
B7
0V
C
1
C
2
C
3
C
4
C
5
C
6
C
7
C
8
C
9
Digital
I/O
OUT1
OUT2
OUT3
OUT4
{MT1}
IN1
IN2
IN3
IN4
24V
C10
0V
O ALISER
input
0
V
gross weight
POWER SUPPLY
+24V
0
V
A1
A2
limit 2 output
acquire zero
MO3 OP ION
24V
O ALISER
input
0V
I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
H1
H2
H3
V1
V2
V3
K1
K2
K3
K4
K5
O1
O2
O3
O4
O5
O6
O7
O8
O9
U1
U2
M1
M2
M3
M4
Digital Inputs
Power/COM2
Digital Ou tputs
Pulse Output
Analog Outputs
COM3
Analog Input 2
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
24V
0V
24V
0V
+
D
−
D
ADS
OUT1
OUT2
OUT3
OUT4
{MT1}
OUT5
OUT6
OUT7
OUT8
0V
+mAO2
−
mAO2
+mAO1
−
mAO1
+/~ OUT0
−
/~ OUT0
+D
−
D
0V
+VI2
+mAI2
−
AI2
limit 1 output
limit 2 output
motion
healthy
net mo e
at zero
weight fault
alarm alert
to
PC, PLC
or
Mo Weigh D isplay
MD1,MD2
gross weight
weight
acquire zero
acquire tare
print
capture weight
print total
reset total
totalise
hol flowrate
A3
A
4
A
5
+
D
−
D
IN0
t
o PC/PLC
TXD
MAD
DB9F
MR1
Address Select ADS
1
2
3
4
5
24V
0V
+
D
−
D
ADS
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
R
1k
2k2
4k7
10k
22k
47k
100k
4
5
6
7
8
9
10
1
2
3
Keep all wiring separate
from mains wiring
Use shiel e cable where
in icate

EMC INDUS RIAL GROUP L D Connections
MW61A_IM_ALL_SV6.09d_en 10/47
Connection Diagram – MP1
O ALISER
input
0V
I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
H1
H2
H3
V1
V2
V3
K1
K2
K3
K4
K5
O1
O2
O3
O4
O5
O6
O7
O8
O9
U1
U2
M1
M2
M3
M4
Digital Inputs
Power/COM2
Digital Ou tputs
Pulse Output
Analog Outputs
COM3
Analog Input 2
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
24V
0V
24V
0V
+
D
−
D
ADS
OUT1
OUT2
OUT3
OUT4
{MT1}
OUT5
OUT6
OUT7
OUT8
0V
+mAO2
−
mAO2
+mAO1
−
mAO1
+/~ OUT0
−
/~ OUT0
+D
−
D
0V
+VI2
+mAI2
−
AI2
limit 1 output
limit 2 output
motion
healthy
net mo e
at zero
weight fault
alarm alert
MP1
MR1
2
3
4
6
7
20
RXD
TXD
CTS
DSR
SG
DTR
MAC
MAP
DB25M
t
o
Printer
to
PC, PLC
or
Mo Weigh D isplay
MD1,MD2
gross weight
weight
acquire zero
acquire tare
print
capture weight
print total
reset total
totalise
hol flowrate
LOADCELL
(s)
optional sense for 6 wire
connection
Address Select ADS
1
2
3
4
5
24V
0V
+
D
−
D
ADS
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
R
1k
2k2
4k7
10k
22k
47k
100k
4
5
6
7
8
9
10
1
2
3
BEL SPEED ACHO
+
0
V
output
POWER SUPPLY
+24V
0
V
TXD
2
3
4
5
6
7
8
RXD
DSR
SG
DTR
CTS
RTS
MAD
DB9F
t
o PC/PLC
P1
P2
P3
P4
P5
P6
A1
A
2
A
3
A
4
A
5
RTS
TXD
0V
0V
RXD
CTS
RJ12
Loadcell
Power/COM2
+EX
−
EX/0V
+
SIG
−
SIG
+
SEN
−
SEN
24V
0V
+
D
−
D
IN0
COM1
Keep all wiring separate
from mains wiring
Use shiel e cable where
in icate
MP1 bus a ress set with
setting (Q2522).
MR1 bus a ress set with
ADS pin an must be same
as MP1.
Fit an MAT terminator to
each en of COM2 cable if
length excee s 50m.

EMC INDUS RIAL GROUP L D Connections
MW61A_IM_ALL_SV6.09d_en 11/47
Connection Diagram – M 1
BEL SPEED ACHO
+
output
0
V
POWER SUPPLY
+24V
0
V
O ALISER
input
0V
I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
H1
H2
H3
V1
V2
V3
K1
K2
K3
K4
K5
O1
O2
O3
O4
O5
O6
O7
O8
O9
U1
U2
M1
M2
M3
M4
Digital Inputs
Power/COM2
Digital Ou tputs
Pulse Output
Analog Outputs
COM3
Analog Input 2
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
24V
0V
24V
0V
+
D
−
D
ADS
OUT1
OUT2
OUT3
OUT4
{MT1}
OUT5
OUT6
OUT7
OUT8
0V
+mAO2
−
mAO2
+mAO1
−
mAO1
+/~ OUT0
−
/~ OUT0
+D
−
D
0V
+VI2
+mAI2
−
AI2
limit 1 output
limit 2 output
motion
healthy
net mo e
at zero
weight fault
alarm alert
MD1,MD2
MT1
MR1
L1
L
2
L
3
L
4
L
5
RTS
TXD
0V
0V
RXD
CTS
RJ12
Power/COM2
24V
0V
+
D
−
D
ADS
COM1
TXD
2
3
4
5
6
7
8
2
3
4
6
7
20
RXD
DSR
SG
DTR
CTS
RTS
RXD
TXD
CTS
DSR
SG
DTR
MAC
MAD
DB9F
t
o PC/PLC
MAP
DB25M
t
o
Printer
to
PC, PLC
or
Mo Weigh D isplay
MD1,MD2
gross weight
weight
acquire zero
acquire tare
print
capture weight
print total
reset total
totalise
hol flowrate
LOADCELL
(s)
optional sense for 6 wire
connection
Address Select ADS
1
2
3
4
5
24V
0V
+
D
−
D
ADS
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
R
1k
2k2
4k7
10k
22k
47k
100k
4
5
6
7
8
9
10
1
2
3
P1
P2
P3
P4
P5
P6
Q1
Q2
Q3
Q4
Q5
Q6
T1
T2
T3
T4
T5
J1
J2
J
3
J
4
J
5
R1
R2
R3
R4
R5
R
6
S
1
S
2
S
3
S4
S5
S6
RTS
TXD
0V
0V
RXD
CTS
RJ1
2
Loadcell 1
Loadcell 2
acho (I/O)
Loadcell 4
Loadcell 3
Power/COM2
+EX
−
EX/0V
+
SIG
−
SIG
+
SEN
−
SEN
+EX
−
EX/0V
+
SIG
−
SIG
+
SEN
−
SEN
+EX
−
EX/0V
+
SIG
−
SIG
+
SEN
−
SEN
24V
0V
+
D
−
D
ADS
24V
0V
IN0
IN9
OUT9
+EX
−
EX/0V
+
SIG
−
SIG
+
SEN
−
SEN
COM1
acquire zero
limit 2 output
Keep all wiring separate
from mains wiring.
Use shiel e cable where
in icate .
For in ivi ual loa cell sensi-
tivity a justment, use termi-
nals P, Q, R an S.
Display an transmitter can
alternatively be connecte
COM1 to COM1 using an MAC
cable.
MT1 bus a ress set with
ADS pin or a setting.
MR1 bus a ress set with
ADS pin an must be same
as MT1.
Fit an MAT terminator to
each en of COM2 cable if
length excee s 50m.

EMC INDUS RIAL GROUP L D Connections
MW61A_IM_ALL_SV6.09d_en 12/47
Connection Diagram – M 3
Loadcell Connections
The loa cell(s) may be wire irectly to the loa cell terminals or connecte together in the fiel with a
junction box an connecte to the Mo Weigh unit with a single cable.
When connecte to the terminals only a 4-wire connection is use , an igital corner a justments are
possible. (MT1 only)
When connecte with one cable an a junction box no corner a justments are possible. It is preferable
to use a 6-wire connection as this eliminates voltage rop errors in long cables cause by cable resis-
tance.
BEL SPEED ACHO
+
output
0
V
POWER SUPPLY
+24V
0
V
O ALISER
input
0V
I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
H1
H2
H3
V1
V2
V3
K1
K2
K3
K4
K5
O1
O2
O3
O4
O5
O6
O7
O8
O9
U1
U2
M1
M2
M3
M4
Digital Inputs
Power/COM2
Digital Ou tputs
Pulse Output
Analog Outputs
COM3
Analog Input 2
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
24V
0V
24V
0V
+
D
−
D
ADS
OUT1
OUT2
OUT3
OUT4
{MT1}
OUT5
OUT6
OUT7
OUT8
0V
+mAO2
−
mAO2
+mAO1
−
mAO1
+/~ OUT0
−
/~ OUT0
+D
−
D
0V
+VI2
+mAI2
−
AI2
limit 1 output
limit 2 output
motion
healthy
net mo e
at zero
weight fault
alarm alert
MD1,MD2
MR1
L1
L
2
L
3
L
4
L
5
RTS
TXD
0V
0V
RXD
CTS
RJ12
Power/COM2
24V
0V
+
D
−
D
ADS
COM1
TXD
2
3
4
5
6
7
8
2
3
4
6
7
20
RXD
DSR
SG
DTR
CTS
RTS
RXD
TXD
CTS
DSR
SG
DTR
MAC
MAD
DB9F
t
o PC/PLC
MAP
DB25M
t
o
Printer
to
PC, PLC
or
Mo Weigh D isplay
MD1,MD2
gross weight
weight
acquire zero
acquire tare
print
capture weight
print total
reset total
totalise
hol flowrate
LOADCELL
(s)
optional sense for 6 wire
connection
Address Select ADS
1
2
3
4
5
24V
0V
+
D
−
D
ADS
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
R
1k
2k2
4k7
10k
22k
47k
100k
4
5
6
7
8
9
10
1
2
3
MT3
P1
P2
P3
P4
P5
P6
E
1
E
2
T1
T2
T3
T4
T5
J1
J2
J
3
J
4
J
5
RTS
TXD
0V
0V
RXD
CTS
RJ1
2
Loadcell 1
Analog Output
acho (I/O)
Power/COM2
+EX
−
EX/0V
+
SIG
−
SIG
+
SEN
−
SEN
+AO1
−
AO1
24V
0V
+
D
−
D
ADS
24V
0V
IN0
IN9
OUT9
COM1
acquire zero
limit 2 output
weight
Keep all wiring separate
from mains wiring.
Use shiel e cable where
in icate .
Display an transmitter can
alternatively be connecte
COM1 to COM1 using an MAC
cable.
MT3 bus a ress set with
ADS pin or a setting.
MR1 bus a ress set with
ADS pin an must be same
as MT3.
Fit an MAT terminator to
each en of COM2 cable if
length excee s 50m.

EMC INDUS RIAL GROUP L D Connections
MW61A_IM_ALL_SV6.09d_en 13/47
Multidrop Systems
Mo Weigh instruments can be connecte using the COM2 RS485 bus. Up to 10 systems may be con-
necte on the bus. A Mo Weigh isplay can select any one of the systems on the bus to work with.
A multi rop connection can also be use with any other Mo bus master evice such as a PLC. If a non
Mo Weigh master is use on the bus, then the Mo Weigh instruments are unable to communicate with
one another. An external Mo bus master can alternatively be connecte to an RS232 COM1 port.
An MR1 unit cannot share the bus with a non Mo Weigh master such as a PLC. A PLC coul be con-
necte using the COM3 port on the MR1.
To connect in muti rop use the RS485 connection COM2. The wiring shoul be ma e in a aisy-chain,
with one instrument connecte to the next. If a stub connection is use to a main cable as shown in the
iagram, then make sure its length limit is a here to.
Two MAT line terminators must be fitte , one at each en of the cable run.
The +D, -D an a 0V terminal must all be connecte together through the ata cable.
…
L
i
L
][
40 m
n
Li ≤ ][500 mL
≤
if D = MD1,MD2 Display, then n ≤ 10
if D = PLC master, then n ≤ 32
Q1
Q2
Q3
Q4
Q5
Q6
Loadcell 2
+EX
−
EX/0V
+
SIG
−
SIG
+
SEN
−
SEN
P1
P2
P3
P4
P5
P6
Loadcell 1
+EX
−
EX/0V
+
SIG
−
SIG
+
SEN
−
SEN
R
1
R
2
R
3
R
4
R
5
R
6
Loadcell 3
+EX
−
EX/0V
+
SIG
−
SIG
+
SEN
−
SEN
S
1
S
2
S
3
S
4
S
5
S
6
Loadcell 4
+EX
−
EX/0V
+
SIG
−
SIG
+
SEN
−
SEN
4
3
2
1
Loa cells Wire to
Directly to Terminals
Allows corner a justment an in ivi ual
monitoring of loa cell outputs
M 1
P1
P2
P3
P4
P5
P6
Loadcell 1
+EX
−
EX/0V
+
SIG
−
SIG
+
SEN
−
SEN
LOADCELL
(s)
optional sense for 6 wire
connection
1
+E
1
−
E
+S
−
S
2
+E
1
−
E
+S
−
S
3
+E
1
−
E
+S
−
S
4
+E
1
−
E
+S
−
S
Loa cells Wire to Junction Box
For best accuracy use a 6-wire connec-
tion to controller

EMC INDUS RIAL GROUP L D Setup
MW61A_IM_ALL_SV6.09d_en 14/47
Setting the COM1 Modbus Address
Before a multi rop system will operate, the a resses in each of the Mo Weigh units will nee to be set
ifferently. This can be one by wiring a link or resistor to the ADS terminal where available. See the
table on the connection iagram. Alternatively the a ress setting can be change in each unit using a
isplay connecte to its COM1.
The following proce ure is use to set a units a ress.
1. Press the Q key to access the setup menu.
2. Key in the quick key co e 2512 to select the ‘COM1&2 mo bus a ress’ step.
3. Press the EDIT key. (If e iting is locke , key in the passwor 111 an press ENTER).
4. Enter the esire a ress (1, 2 or 3 etc.) an press ENTER.
5. Press an hol the BACK key to return to normal operation.
6. Repeat for each of the units which are to be use on the bus.
When the multi rop system is then connecte an powere , the isplay shoul be able to see each of
the Mo Weigh systems. This is one by pressing the SELECT key on the isplay.
SE ING UP
Setup
Mo Weigh instruments must be calibrate for each specific application. The parameters store are col-
lectively known as the Setup.
Description
Press the Q key to access the setup menu.
The setup is ivi e into sections as shown in the following iagram.
SE UP
Basic Settings
AI1 AO1
AI2 AO2
IN1 OUT1
IN2 OUT2
IN3 OUT3
IN4 OUT4
IN5 OUT5
IN6 OUT6
IN7 OUT7
IN8
Inputs
Internal Signals
Outputs
OUT8
COM1
Communications & Display
COM2
Information, Resets & Final Calibration
Setup Diagram
The Setup contains
Settings
an
Macros
which are escribe next.
Settings
Most of the setup for a system involves setting calibration constants which for example calibrate the
loa cell input, the 4-20mA outputs an the operation of relays etc. These settings are simple numeric
values.
Macros
Macros are use to store short programs which are use to construct text strings to output to the
printer, perform arithmetic calculations an other special control functions. Macros are a collection of
program segments which can call one another as subroutines. They have structure if/then/else state-
ments an program looping constructs.
A macro is a sequence of numbers (bytes with values of 0 to 255).
Menus
All the setup parameters are containe within a menu structure which follows the setup sections.
Basic Settings
Inputs
Internal Signals
Outputs
Communications & Display
Information, Resets & Final Calibration
Factory Settings
Loa cell
Calibration
Ma
c
ros

EMC INDUS RIAL GROUP L D Setup
MW61A_IM_ALL_SV6.09d_en 15/47
Basic Settings
The basic settings are settings which generally must be set first an often affect other settings through
the controller. For example, they set the engineering units an measuring range for the application.
Inputs
The inputs are settings an calibration which effect the basic inputs signals. For example the loa cell
input, tacho input (where use ) an igital inputs.
Internal Signals
This section contains the main calculations for the instrument. Most signals are here, for example the
weight, zero weight, total weight etc. Much of the instruments configuration is one in this section.
Outputs
The output are settings an calibration which effect the basic output signals. For example the 4-20mA
outputs an igital outputs. These change the calibration range an select the signal to appear on the
igital outputs.
Communications & Display
This section sets the bau rates etc for the communications ports. It sets the key locks for the
MD1,MD2 Display. It also contains the Macros for the instrument.
These settings are not available in ‘B’ mo el instruments.
Information, Resets & Final Calibration
This section contains information about the unit, inclu ing its serial number, the pro uct type etc.
These settings allow all the settings & macros to be reset back to their efault values. The final calibra-
tion is also one here.
Factory Settings
The factory settings are use to calibrate the basic instrument in the factory. These are passwor pro-
tecte an are not usually require once the instrument has left the factory.
Keypad
MD1,MP1 Keypad
MD2,MP2 Keypad
SOF keys
The function of the 5 soft keys is in icate on the isplay.
ALARM key
Use to access the alarm list menu.
SELEC key
Use to select a system to isplay if more than one unit is connecte on the network.
DISPLAY key
Allows the operator to select the isplay layout.
ALARM
SELEC
DISPLAY
SE UP
UP
LEF
RIGH
DOWN
SOF KEYS
BACK
EN ER
SOF KEYS
BACK
EN ER
ALARM
SELEC
DISPLAY
SE UP
UP
LEF
RIGH
DOWN

EMC INDUS RIAL GROUP L D Setup
MW61A_IM_ALL_SV6.09d_en 16/47
SE UP key
Press to view the setup menus.
ALPHANUMERIC keypad
Use to enter numerical ata values.
UP and DOWN keys
Use these keys to move up an own a menu, or to increase or ecrease a setting when e iting is en-
able .
LEF and RIGH keys
Use to step thorugh macros an the selection of some other items.
EN ER key
Use this key to move forwar s through the menu, or to confirm a change to a setting.
BACK key
Use this key to move backwar s through the menu, or to cancel a change to a setting. Hol the key to
exit completely out of the menus an back to normal operation.
Displaying the Setup Menus
Press the SETUP key (Q) to isplay the setup menus.
Selecting a Menu Item
To the left of each menu item is a single igit. This is the Quick Key number. Simply key in this number
to select the correspon ing menu item. Items which have a + to the left will then isplay a sub-menu in
the same format. Continue pressing Quick Keys to navigate to the esire setting. Refer to the Setup
Summary for the sequence of Quick Keys to go irectly to each setting.
Alternatively, repeate ly press the ENTER key to step through all the menus, sub-menus an settings in
turn.
You can use the UP an DOWN keys to highlight a menu or sub-menu item, then press the ENTER key
to continue from there. When viewing a setting, the UP an DOWN keys will move between the set-
tings.
1
Menu name.
2
Quick Key number. Press key with same number to irectly enter the name menu.
3
Menu item escriptor.
Element Description
Selecting this menu item will open a sub-menu.
(blank) Selecting this menu item will isplay the correspon ing setting, or will
return from a sub-menu
The action escribe will be implemente irectly either if the ENTER
key is presse when item is highlighte or when the item’s Quick Key is
presse . (Quick Key number is the left most number shown in the item
line)
4
Name of menu item.
Description of Menus
Quick setup
Quick setup menu contains the most important settings, an is a shortene version of the Main setup
menu. Use the Quick setup menu for initial setup of the unit. In many applications, no further setup will
be nee e . The quick setup settings are marke with an asterix in the Setup Summary. (*)
Main setup
Main setup menu contains all stan ar information an settings. Use this menu to view the units infor-
mation (eg serial number), an a apt the unit for the application (eg change the spee eman output
to 0 to 20mA). The main setup settings are liste in the Setup Summary.
1
2
3
4

EMC INDUS RIAL GROUP L D Setup
MW61A_IM_ALL_SV6.09d_en 17/47
Service
Service menu contains all stan ar settings as well as settings for a vance configuration an iagnos-
tics. Use this menu if there are special application requirements, or if special iagnostics are require .
This menu inclu es the Factory settings, for which certifie equipment is require . These settings are
not ocumente in this manual, contact the factory for further information.
Altered settings
Altere settings menu lists all settings that are ifferent from the efault. Use this menu to fill in the
fiel settings on the Setup Summary
o Adjust A Setting
Press the EDIT key to allow changes to the selecte setting.
If e iting is locke , a passwor will be requeste . For Quick setup an Main setup, the passwor is
111. For Service setup the passwor is 9713. For Altered setup there is no passwor as settings are
isplay only.
Use the keypa an /or UP an DOWN arrow keys to increase or ecrease the isplaye setting. Some
settings allow only one metho , an some are isplay only.
Hol ing either key own will automatically continually increase or ecrease the value.
1
Menu item.
2
Setting name.
3
Gives information about the settings an in icates active keys or the preferre metho of making a
value change while e iting.
Icon Description
The setting is locke . Passwor must be entere to e it.
The setting can only be viewe .
The setting has been change from the efault.
An important setting.
The setting is being e ite .
Use numbere keys to change setting value.
Use UP & DOWN keys to scroll through selection list.
Use UP & DOWN keys to turn setting on or off.
Use the arrow keys to move through the bits of a control or status register.
4
Sequence of quick-keys use to reach this setting. Not e itable. The left-most igit i entifies the
current menu as follows: 1 for Quick setup, 2 for Main setup, 3 for Service setup, an 4 for Altere
setup.
5
Hint line which reveals extra information about the setting.
6
Setting value. To change press EDIT key. If e iting is locke , a passwor will be requeste . Key in
the passwor an press the ENTER key. The setting will become highlighte by a black back-
groun . Key in changes then press ENTER key. For Quick setup an Main setup, the passwor is
111. For Service the passwor is 9713.
7
Engineering unit setting is isplaye in.
8
Mo bus a ress of this setting. Not e itable.
9
Soft keys use with settings.
Icon Description
Press key for menu of special functions.
Press EDIT key to e it the macro.
Use the soft key to start an stop an operation.
1
5
3
2
7
8
4
6
9

EMC INDUS RIAL GROUP L D Macros
MW61A_IM_ALL_SV6.09d_en 18/47
Macros
A macro is a list of numbers representing text characters an instructions co es. Each number is e ite
separately, an is entere either as a number using the numeric keys, or as an text character using the
letter keys much like a cell phone. There are three ata entry mo es, instruction, lower case text an
upper case text.
Macro Codes
Code Description
0 en of macro Terminates execution of macro or returns from subroutine.
1 - 127 stan ar ASCII characters
128 - 187 exten e ASCII characters
Characters are sent out COM1 (RS232).
Alternate Instructions
Use to enco e printable characters (Unico e values 0 to 65536) outsi e the ASCII range.Sen s the
Unico e characters out COM1 with UTF8 enco ing. Some characters can be use in the “system name
macro” to appear on a Mo Weigh isplay.
arg0 an arg1 must be in the range 1 to 128.
188 ALT0 ‹arg1› ‹arg0› UC = (arg0 - 1) + (arg1 - 1) × 128
189 ALT1 ‹arg1› ‹arg0› UC = (arg0 - 1) + (arg1 - 1) × 128 + 16384
190 ALT2 ‹arg1› ‹arg0› UC = (arg0 - 1) + (arg1 - 1) × 128 + 32768
191 ALT3 ‹arg1› ‹arg0› UC = (arg0 - 1) + (arg1 - 1) × 128 + 49152
Register Instructions
192 NOP no operation
193 RECALL “register” “register” is an ASCII Mo bus a ress (8000 to 8992).
194 RECALL ‹argument› ‹argument› register
1 weight
2 gross weight
3 net weight
4 zero weight
5 tare weight
6 total weight
7 running total
8 peak weight
9 flow rate
10 belt spee
11 current setpoint
12 spee eman
13 COM 2 mo bus a ress
14 print settings & macros
15 pro uct serial number
16 flowrate raw
17 temp 1
18 temp 2
19 perm 1
20 perm 2
21 P_Mo ule serial number
22 perm3
23 perm4
24 perm5
25 temp3
26 temp4
27 temp5
28 batch setpoint
29 batche weight
30 batch number
31 last batche weight
32 number to batch
101 with a ress in VALUE
102 efault_value
103 minimum_value
104 maximum_value
105 column
106 memory
107 register_number
108 port
109 slave_a ress
Other aruments are invali an not all arguments
available in all pro ucts.
195 STORE “register” “register” is an ASCII Mo bus register (8000 to 8992).
196 STORE ‹argument› ‹argument› selects register. See RECALL instruction.

EMC INDUS RIAL GROUP L D Macros
MW61A_IM_ALL_SV6.09d_en 19/47
Register Instructions
197 MENU ‹argument› ‹argument› action
1 start_menu
3 next_quick
5 next_service
6 next_factory
7 next_altere
198 MACRO ‹argument› ‹argument› action
1 start_macro
2 next_macro
3 next_ altere _macro
Print Instructions
200 PRINT_VALUE
201 PRINT_NAME
202 PRINT_UNITS
203 PRINT_HINT
204 PRINT_DATE
205 PRINT_TIME
206 PRINT_SECONDS
207 PRINT_MENU_HEADING
208 PRINT_MENU_PATH
209 PRINT_QUICK_KEY
212 FORMAT “format”
213 NEWLINE
214 NEWPAGE
215 TAB ‹column›
218 LIST ‹macro›
219 DUMP ‹macro›
“format” is an ASCII format co e of the form CcD Bb. c is the column
wi th, is the number of ecimal places an b is the count by. Any one
or combination of the three parts can be inclu e . (e.g. C10 2b5 sets the
column wi th to 10, the ecimal places to
2 an the count by to 5; C10
sets column wi th to 10). The efault is 0.
‹column› is a number 1 to 99. Columns are numbere from 0.
‹macro› is number 1 to 99. If ‹macro› = 101, lists macro
number in
VALUE.
Calculation Instructions
Calculations are one on a stack in RPN (reverse polish notation). When a value is entere onto the
stack with a RECALL or VALUE instruction, the other values on the stack are move up first.
An instruction like ADD or MUL opera
tes on the values in VALUE an Y an places the result in VALUE. Z
is move to Y an T is copie to Z.
The operation follows the values. e.g RECALL ‹weight› VALUE “2” MUL., this multiplies the weight by 2.
e.g. 2 + 3 x weight =
VALUE “2” VALUE “3” RECALL ‹weight› MUL ADD
S ACK
RECALL or VALUE ROLL ADD, SUB, MUL, DIV, MOD
T T lost copie
Z
Y
VALUE RESULT (using VALUE & Y)
220 VALUE “number” “number” is an ASCII number (e.g. 123.4) If there is no number, then the
stack is pushe up.
221 ADD VALUE = VALUE + Y
222 SUB VALUE = VALUE + Y
223 MUL VALUE = VALUE + Y
224 DIV VALUE = VALUE + Y
225 MOD VALUE = VALUE + Y
226 SWAP_VALUE&Y VALUE an Y swappe
227 ROLL stack rolle own
230 CLEAR_VALUE VALUE is set to zero
231 CLEAR_ALL VALUE, Y, Z an T all set to 0
232 INC_ VALUE VALUE = VALUE + 1
233 DEC_ VALUE VALUE = VALUE – 1
235 CHANGE_SIGN sign of VALUE change , plus an minus
236 ABS absolute value of VALUE (e.g. ABS(-12.54) = 12.54)
237 INT integer value of VALUE (e.g. INT(12.54) = 12)
238 FIX fixe value of VALUE (e.g. INT(12.54) = 13)

EMC INDUS RIAL GROUP L D Macros
MW61A_IM_ALL_SV6.09d_en 20/47
Looping and Control Instructions
239 DRIVE_BIT ‹bit›
240 IF ‹con ition›
241 IF_EVENT ‹event con ition›
242 NOT
243 AND ‹con ition›
244 OR ‹con ition›
245 ELSE
246 END_IF
247 SET_BIT ‹bit›
248 CLEAR_BIT ‹bit›
249 TOGGLE_BIT ‹bit›
250 GOSUB ‹macro›
251 STOP
252 STACK
253 LOOP
254 EXIT_WHEN ‹con ition›
255 END_LOOP
value test
1-150 See I/O Function Table
value test value test
151 VALUE›=0 163 VALUE_ALTERED
152 VALUE›0 164 VALUE_NOT_ALTERED
153 VALUE=0 165 VALUE_VIEW_ONLY
154 VALUE‹›0 166 DEC_temp1=0
155 VALUE‹0 180 with_stack
156 VALUE‹=0 181 en _of_macro
157 Y›=VALUE 182 en _of_menus
158 Y›VALUE 183 new_menu_hea ing
159 Y=VALUE 184 new_menu_path
160 Y‹›VALUE 185 macro_altere
161 Y‹VALUE 186 clock_active
162 Y‹=VALUE
operator result
AND true if both values are true
OR true if either value is true
‹con ition› is a logical expression ma e up of one or more values an operators evaluate from left
to right. e.g. ‹IN3› OR NOT ‹IN4›
‹con ition› = value [NO ] [operator] [value] [NO ] [operator]
NO reverses the sense of the value, (e.g. true becomes false).
STACK stacks the current value. The stacke value is use with an operator followe by ‹with_stack›.
DRIVE_BIT sets the bit to the value evaluate by the con ition.
e.g. IF ‹IN1› AND ‹IN2› STACK ‹IN3› AND ‹IN4› OR ‹with_stack› DRIVE_BIT ‹user bit 1›
‹event con ition› has a value of 1-150, an is true if the bit in the I/O Function table has change
since the “event macro” last ran.
‹bit› is a value from 1 to 187 from the I/O Function Table. Use Output Functions shoul not be set.
‹macro› is a macro number from 1 to 99. If macro = 101, calls subroutine number in VALUE.
The con itional an looping structures are as follows. Any sequence of instructions may be place
where
INST
appears.
IF ‹con ition›
INST
ENDIF IF_EVENT ‹event con ition›
INST
ENDIF
IF ‹con ition›
INST
ELSE
INST
ENDIF IF_EVENT ‹event con ition›
INST
ELSE
INST
ENDIF
IF ‹con ition›
INST
DRIVE_BIT ‹bit› IF_EVENT ‹event con ition›
INST
DRIVE_BIT ‹bit›
LOOP
INST
EXIT_WHEN ‹con ition›
INST
END_LOOP
Adjusting a Macro
1
Menu item.
2
Setting name.
3
Gives information about the macro an in icates active keys or the prefere metho of
making a value change while e iting.
Icon Description
The macro is locke . Passwor must be entere to e it.
The macro has been change from the efault.
Use the 1 & 2 keys to move the cursor back an forth through
the macro.
Shows which numeric keys are use to enter lower case letters.
5
6
3
2
7
8
4
1
9
Table of contents
Other EMC Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Build Equinox
Build Equinox CERV2 Option manual

Tronair
Tronair 01-0597-0000 Operation & service manual

Ortlinghaus
Ortlinghaus TPI 1060 EN Translation of original operating manual

Piranha
Piranha MegaFab P-120 Instructions and parts manual

Schmalz
Schmalz X-Pump - SXPi operating instructions

Geotech
Geotech SitePro Installation and operation manual