Emerson Copeland CoreSense 571-0065-05 Manual

1
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
AE8-1384 R5
CoreSense™Communications for 20 to 40 Ton
Copeland Scroll™Air Conditioning Compressors
August 2016
Safety
Safety Instructions ...................................................2
Safety Icon Explanation...........................................2
Instructions Pertaining to Risk of Electrical
Shock, Fire, or Injury to Persons .............................3
Safety Statements ...................................................3
Introduction
Overview..................................................................4
Features ..................................................................4
Application Usage....................................................4
Part Numbers ..........................................................4
Agency Recognition.................................................4
ProductSpecications .............................................4
Installation
Mounting..................................................................4
Terminal Description and Basic Field Wiring ...........4
Dielectric (Hipot) Testing..........................................5
Operation
Warning Codes ........................................................5
Alert/Lockout Codes ...................................................5
Resetting Alert Codes..............................................6
TABLE OF CONTENTS
Section Page Section Page
Commissioning
Communications......................................................6
DIPSwitchConguration.........................................7
Jumper Setting ........................................................7
PC Interface Software .............................................7
Service
Field Service............................................................8
Troubleshooting .......................................................8
Tables
Module Part Numbers..............................................9
ModuleSpecications..............................................9
Accessory Parts.......................................................9
Modbus Map.....................................................10-12
DIP Switch Purpose...............................................13
LED Flash Code Information ............................13-14
Figures
Terminal Box Wiring Diagrams ..............................15
CoreSense Communications Module Photo..........16
Thermistor Circuit Cable........................................16
Modbus Addressing ............................................... 17
PC Interface Wiring ...............................................18

2
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
Safety Instructions
Copeland Scroll™compressors with CoreSense™Communications are manufactured according to the latest
U.S. and European Safety Standards. Particular emphasis has been placed on the user's safety. Safey icons are
explained below and safety instructions applicable to the products in this bulletin are grouped on page 3. These
instructions should be retained throughout the lifetime of the compressor. You are strongly advised to follow
these safety instructions.
Safety Instructions
Copeland Scroll™
compressors are manufactured according to the latest U.S. and European Safety
Standards. Particular emphasis has been placed on the user's safety. Safey icons are explained below
and safety instructions applicable to the products in this bulletin are grouped on Page 3. These
instructions should be retained throughout the lifetime of the compessor. You are strongly advised
to follow these safety instructions.
Safety Icon Explanation
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION, used with the safety alert symbol, indicates a hazardous
situation which, if not avoided, could result in minor or moderate injury.
NOTICE is used to address practices not related to personal injury.
CAUTION, without the safety alert symbol, is used to address practices
not related to personal injury.
DANGER
WARNING
CAUTION
NOTICE
CAUTION

3
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
ELECTRICAL SHOCK HAZARD
• Disconnect and lock out power before servicing.
• Discharge all capacitors before servicing.
• Use compressor with grounded system only.
• Molded electrical plug must be used when required.
• Refer to original equipment wiring diagrams.
•
• Failure to follow these warnings could result in serious personal injury.
PRESSURIZED SYSTEM HAZARD
• System contains refrigerant and oil under pressure.
• Remove refrigerant from both the high and low compressor side before
removing compressor.
•
• Never install a system and leave it unattended when it has no charge,
a holding charge, or with the service valves closed without electrically
locking out the system.
• Use only approved refrigerants and refrigeration oils.
• Personal safety equipment must be used.
• Failure to follow these warnings could result in serious personal injury.
BURN HAZARD
• Do not touch the compressor until it has cooled down.
• Ensure that materials and wiring do not touch high temperature areas of
the compressor.
• Use caution when brazing system components.
• Personal safety equipment must be used.
• Failure to follow these warnings could result in serious personal injury or
property damage.
COMPRESSOR HANDLING
• Use the appropriate lifting devices to move compressors.
• Personal safety equipment must be used.
• Failure to follow these warnings could result in personal injury or
property damage.
Safety Statements
• Refrigerant compressors must be employed only for their intended use.
•
install, commission and maintain this equipment.
•
• All valid standards and codes for installing, servicing, and maintaining electrical and
refrigeration equipment must be observed.
Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons
WARNING
WARNING
WARNING
CAUTION

4
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
INTRODUCTION
Overview
CoreSense™Communications is a breakthrough
innovation for 20 to 40 ton Copeland Scroll™
air conditioning compressors. The CoreSense
Communications module, installed in the compressor
electrical box, provides advanced diagnostics,
protection, and communications that enhance
compressor performance and reliability.
Features
CoreSense Communications has the following key
features:
1. Motor temperature protection
2. Scroll high temperature protection
3. Missing phase protection
4. Reverse phase protection
5. Low control circuit voltage protection
6. Short cycling detection and alert
7. Communication to system controller through
RS485/Modbus
8. Storage of operational history, runtime information,
fault counters, etc.
9. Display of status, warning, and alert information
via LEDs
CoreSense Communications provides compressor
and system protection through its proprietary lockout
feature. Depending on the severity and frequency of
the fault that caused the trip condition, the CoreSense
Communications module can lockout the compressor
contactor to prevent damage to the compressor and
system components. Less severe fault conditions
resulting in an occasional trip will not result in a lockout
condition.
Flashing red and green LEDs communicate Status,
Warning, and Alert codes to the service technician and
the master controller.
Application Usage
WARNING
CoreSense Communications modules are not
interchangeable with any other brand of motor
protection module that may have been previously
used with Copeland Scroll compressors.
CoreSense Communications modules are not intended
tobeusedaseldretrotsforothermotorprotection
modules that may have been previously used with
Copeland Scroll compressors. The motor and scroll
thermistor circuits are configured differently for
Copeland Scroll with CoreSense Communications and
are not compatible with motor protection modules that
were previously used.
Copeland Scroll compressors equipped with CoreSense
Communications will have an “E” in the electrical code.
An example is the 40-ton scroll, ZP485KCE-TED.
Module Part Numbers
OEM and service compressors will have the CoreSense
Communications module installed in the compressor
electrical box. Individually packaged modules are
available to the aftermarket for component replacement.
Part numbers for OEM and service applications are
listed in Table 1 at the end of this bulletin.
Agency Recognition
CoreSense Communications carries the following
agency recognitions:
U.L.leE253322,Volume7,SoftwareClassB
CBTestCerticate
Product Specications
CoreSensespecicationsareshowninTable 2. Many of
the electrical specifcations are the same as previously
used electronic motor protection modules.
INSTALLATION
Mounting
As mentioned above, CoreSense Communications will
be shipped already installed in the compressor electrical
box. Two holding tabs secure the module in the box.
To remove the module depress the holding tabs and
remove the module.
WARNING
Always disconnect and lockout the power supply
before removing the compressor electrical box
cover for servicing.
Terminal Description and Basic Field Wiring
Figure 2 at the end of this bulletin shows the CoreSense
Communications module. Figures 1a and 1b are the
terminal box wiring diagrams. An explanation of the
terminal designations follows:
T2-T1:Modulepowersupply,24or120/240VAC.
L1-L2-L3: Phase inputs corresponding to compressor
input power L1-L2-L3.

5
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
M2-M1: Normally open control circuit contacts; M2-
M1 should be wired in series with the compressor
contactor.
A (-), GND, B (+): RS485 communications.
Temperature Plug: See Figure 3foridenticationof
the PTC, NTC, and common connections.
When multiple CoreSense Communications modules
are networked, a shielded, twisted pair cable such
as Beldon #8761 (22 AWG) should be used for the
communication wiring.
NOTICE
The RS485 is polarity sensitive. When “daisy
chaining” modules the A (-) must connect to other
A (-) terminals and B (+) must connect to other B
(+) terminals.
Dielectric (Hipot) Testing
CAUTION
Use caution with high voltage and never hipot
when compressor is in a vacuum.
U.L. sets the requirement for dielectric strength testing
and should be consulted for the appropriate voltage
and leakage values. Emerson Climate Technologies
does not recommend hipot testing at voltages higher
than1,000VAC.
OPERATION
WARNING
The CoreSense Communications module is a
recognized safety device and must be used with
all compressors that have TE* electrical codes.
A solid green LED indicates the module is powered and
operation is normal. A solid red LED indicates an internal
problem with the module. See the Troubleshooting
section of this bulletin for more information on what to
do if the red LED is solid.
CoreSense Communications communicates Warning
codesviaagreenashingLED.Warningcodesdonot
result in a trip or lockout condition. Alert codes are
communicated via a red ashing LED. Alert codes
will result in a trip condition and possibly a lockout
condition.
Warning Codes (Green LED Flash Code)
Code 1 – Loss of Communication
ThemodulewillashthegreenWarning LED one
time indicating the module has not communicated
with the master controller for longer than 5 minutes.
Once communication is reinitiated, the Warning will
be cleared.
Code 2 – Reserved For Future Use
Code 3 – Short Cycling
ThemodulewillashthegreenWarning LED three
times indicating the compressor has short cycled more
than48timesin24hours.Ashortcycleisdenedas
compressor runtime of less than 3 minutes. The
Warning will be activated when the “Short Cycling”
dipswitch (#10) is "off" or in the "down" position. When
fewer than 48 short cycles are accumulated in 24
hours the Warning code will be cleared.
Code 4 – Open/Shorted Scroll Thermistor
ThemodulewillashthegreenWarning LED four
times indicating the scroll NTC thermistor has a
resistance value that indicates an open/shorted
thermistor (see Table 2). The Warning will be cleared
when the resistance value is in the normal range.
Alert/Lockout Codes (Red LED Flash Code)
Code 1 – Motor High Temperature
The module will ash the red Alert LED one time
indicating the motor PTC circuit has exceeded 4.5K
Ohms ± 25%. A code 1 Alert will open the M2-M1
contacts. The Alert will reset after 30 minutes and the
M2-M1 contacts will close if the resistance of the motor
PTC circuit is below 2.75K Ohms. Five consecutive
Code 1 Alerts will lockout the compressor. Once the
module has locked out the compressor, a power cycle
or Modbus reset command will be required for the
lockout to be cleared.
Code 2 – Open/Shorted Motor Thermistor
Themodulewill ash theredAlert LED two times
indicating the motor PTC thermistor circuit has a
resistance value that indicates an open/shorted
thermistor chain (see Table 2). A Code 2 Alert will
open the M2-M1 contacts. The Alert will reset after
30 minutes and the M2-M1 contacts will close if the
resistance of the motor PTC circuit is back in the
normal range. The module will lockout the compressor
if the trip condition exists for longer than 6 hours.

6
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
Once the module has locked out the compressor,
a power cycle or Modbus reset command will be
required to clear the lockout.
Code 3 – Short Cycling
ThemodulewillashtheredAlert LED three times
indicating the compressor is locked out due to short
cycling. A Code 3 Alert will open the M2-M1 contacts.
Code 3 will be enabled when the "Short Cycling"
dipswitch (#10) is "on" or in the "up" position and the
compressor has exceeded the number of short cycles
conguredbytheuserina24hourperiod.Oncethe
module has locked out the compressor, a power cycle
or Modbus reset command will be required to clear
the lockout.
Code 4 – Scroll High Temperature
ThemodulewillashtheredAlert LED four times
indicating the scroll NTC circuit is less than 2.4K
Ohms. A Code 4 Alert will open the M2-M1 contacts.
The Alert will reset after 30 minutes and the M2-
M1 contacts will close if the resistance of the scroll
NTC circuit is higher than 5.1K Ohms. The module
will lockout the compressor if the number of Code
4 Alerts exceeds the user congurable number of
Code 4 events within a 24 hour period. Once the
module has locked out the compressor, a power cycle
or Modbus reset command will be required to clear
the lockout.
Code 5 – Reserved for Future Use
Code 6 – Missing Phase
The module will ash the red Alert LED six times
indicating a missing phase in one of the three leads
to the compressor. A Code 6 Alert will open the M2-
M1 contacts. The Alert will reset after 5 minutes and
the M2-M1 contacts will close if the missing phase
condition is not present. The module will lockout the
compressor after 10 consecutive Code 6 Alerts.
Once the module has locked out the compressor,
a power cycle or Modbus reset command will be
required to clear the lockout.
Code 7 – Reverse Phase
ThemodulewillashtheredAlert LED seven times
indicating a reverse phase in two of the three leads
to the compressor. A Code 7 Alert will open the M2-
M1 contacts. The module will lockout the compressor
after one Code 7 Alert. A power cycle or Modbus
reset command will be required to clear the lockout.
Code 8 – Reserved For Future Use
Code9–ModuleLowVoltage
ThemodulewillashtheredAlert LED nine times
indicating low module voltage (see Table 2) on the
T2-T1 terminals for more than 5 seconds. A Code
9 Alert will open the M2-M1 contacts. The Alert will
reset after 5 minutes and the M2-M1 contacts will
close if the T2-T1 voltage is above the reset value
in Table 2.
Please see Table 6 for a summary of Warning and Alert
codes and troubleshooting information.
Resetting Alert Codes
Resetting Alert codes can be accomplished in two
different ways. First, Alert codes can be reset manually
by cycling power to the module (disconnect T2 or T1
for 5 seconds). The second way to reset Alert codes
is to send a Modbus reset command from the master
controller.
Power Up Delay
When CoreSense Communications is cycled off, there
isathirteentofteenseconddelaybeforethemodule
is active.
If the fault that initiated the Alert code is absent after
one of the above resets is performed, the Alert code will
be cleared and CoreSense will allow normal operation.
If the fault is still present after the reset is performed the
fault code will continue to be displayed via the green
orredashingLED.
COMMISSIONING
Communications
Programming knowledge and a familiarity with
Modbus will be required by the system designer
to use the communications features of CoreSense
Communications. CoreSense Communications
has opto-isolated RS485 for the physical layer. The
communication protocol is Standard Modbus and
Emerson Climate Technologies Modbus. CoreSense
Communications will act as the Modbus slave, while
the master will be implemented in a system controller,
PC software, or any other equivalent external device.
Use of the communications feature of CoreSense
Communications allows the master access to much of
the data that resides in the CoreSense Communications
module. Emerson Climate Technologies Modbus has
six message categories:
1. Device ID Messages
2. CoreSense Status Messages

7
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
3. CoreSense History Status Messages
4. CongurationMessages
5. Command Messages
6. Firmware Update Messages
CoreSense status, conguration, history, and device
information messages available to the master include
those listed in Table 4.
The history status messages give the order in which the
Warning/Alert has happened, with the total compressor
run time. Information about the Warning/Alert
occurrence during the last 7 days and the cumulative
Warning/Alert counter are also available.
For more information on CoreSense™Communications
features and to request Modbus maps please contact
your Application Engineer.
DIP Switch Conguration
DIP switch selection for the Modbus address, baud rate,
parity, and other operating conditions simplify service
and start-up procedures. Table 5 lists the purpose of
each switch.
NOTICE
The module must be reset after changing any of
the DIP switch settings for changes to take effect.
CoreSense Communications modules are shipped from
the factory with the DIP switches set to default settings
for standalone operation. Default settings are shown
in Table 5. Switch 1 is turned “on” as part of a quality
control check to verify communications capability of the
module before it leaves the compressor manufacturing
plant. Switch 9 is also turned “on” for TE* motor code. All
other DIP switch default settings are in the “off” position.
NOTICE
If DIP switch settings are inadvertently changed,
the compressor will operate, but could have some
loss of protection. Scroll temperature protection
and short cycle protection could be disabled.
The following steps cover the DIP switch settings
throughout the commissioning process for a multiple
compressor system with communications.
1. Switches 1 through 5 are used for setting
the device address. DIP switch 1 is the least
signicant bit (LSB) and switch 5 is the most
signicant bit (MSB). DIP switch addresses
0 through 31 are shown in Figure 4. Each
CoreSense Communications module that is daisy
chained and connected to a master controller
must have a unique node address (as determined
by the DIP switch settings).
2. Switch6denesthecommunicationbaudratefor
the CoreSense Communications module. If the
switch is “off”, the baud rate is 19200. If the switch
is “on” the baud rate is 9600. The baud rate of
each CoreSense Communications module should
be set to match the master controller baud rate.
3. Switch 7 denes the communications parity.
The default parity setting for the CoreSense
Communications module is no parity. If the switch
is set to “on” the module will communicate using
even parity. The parity setting must match the
parity setting of the master controller.
4. Switch 8 defines the control mode. The
default setting is standalone mode (off). If
communications with a master controller is
desired, switch 8 should be turned “on” to
network.
5. Switch9denesthethermistorconguration.If
the compressor has a voltage code of TE*, the
compressor has PTC and NTC thermistors for
motor and scroll temperature protection. If the
compressor voltage code is TW*, the compressor
has only PTC thermistors for motor and scroll
temperature protection. The default setting is “on”
for PTC and NTC thermistor types.
6. Switch 10 enables short cycling protection if
turned “on”. The default setting is “off”.
Jumper Setting
CoreSense Communications modules are shipped
with the jumper installed. For standalone operation
the jumper should remain installed. For daisy chained
applications the jumper should remain installed for
the modules on the ends of the daisy chain. All other
jumpers in the sequence of daisy chained modules
should be removed. The jumper can be removed using
miniature electronics needle nose pliers
PC Interface Software
PC interface software is available from Emerson Climate
Technologies, Inc. The PC interface software allows
the design engineer access to status, conguration,
history, and data logging via a computer. This method of
connecting and communicating with CoreSense is very
helpful during the unit development stage if CoreSense
is in stand-alone mode and not communicating with a
master controller.

8
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
The RS-485/USB adapter used to connect the laptop
to the CoreSense is B & B Electronics model number
USOPTL4. Figure 5 illustrates the wiring and DIP switch
settings necessary to enable communications.
For more information on the PC interface software, how
to obtain it, and a tutorial on its use, please contact your
Application Engineer.
SERVICE
Field Service
Service compressors will be shipped with the CoreSense
Communications module installed in the compressor
terminal box. Special attention should be given to the
module DIP switch settings of the compressor being
replaced so the DIP switch settings can be transferred
to the module of the replacement compressor. As
mentioned earlier, the CoreSense Communications
module is a recognized safety device and shall be used
only with approved compressors with TE* motor codes.
NOTICE
If a compressor with CoreSense Communications
fails in the eld, the CoreSense module should
remain with the failed compressor so Emerson
technicians can download the CoreSense data
to assist with determining the root cause of
compressor failure.
Troubleshooting
WARNING
Always disconnect and lockout the power supply
before removing the compressor electrical box
cover for servicing.
For troubleshooting purposes the scroll and motor
thermistor circuits are similar to those of other Copeland
Scrolls with one exception, the scroll thermistor is a
negativetemperaturecoefcient(NTC)typethermistor.
This means that as the discharge temperature
increases, the resistance of the thermistor decreases.
The motor has positive temperature coefficient
(PTC) type thermistors; as the motor temperature
increases, so does the resistance of the thermistor
chain. To measure the resistance of the PTC and NTC
circuits simply remove the temperature plug from the
CoreSense module and measure the resistance in the
appropriate pins shown in Figure 3. The measured
values should be in the ranges listed in Table 2. For
information on trouble shooting causes of high motor
and scroll temperatures please refer to the application
engineering bulletin for the compressor.
A loss of communications with the master controller for
morethanveminutesiscommunicatedviaagreen
ashcode1ifDIPswitch#8 isenabled.CoreSense
Communications has no provisions to detect incorrect
wiring neither between daisy chained modules nor to
the master controller. Ideally, the master controller will
contain advanced troubleshooting menus for help in
diagnosing communications issues between the master
controller and the CoreSense module.
NOTICE
In some rare cases communication between the
master controller and the CoreSense module is
problematic. Reversing the polarity will re-initiate
communication.
To reverse polarity:
1. Adjust CoreSense to negative
2. Adjust master controller to positive

9
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
Voltage OEM Part Number Service Part Number
24 571-0065-05 971-0065-04
120/240 571-0064-06 971-0064-05
Table 1
CoreSense Communications Module Part Numbers
Part Description Part Number
Scroll/Motor Thermistor Harness 529-0102-00
Table 3
CoreSense Communications Accessory Parts
Table 2
CoreSense Communications Module Specications
Module Part Number 571-0065-05 571-0064-06
ModuleVoltage&Frequency 24VAC,50/60HZ 120/240VAC,60HZ
115/230VAC,50HZ
AllowableVoltageRange 18-30VAC 85-265VAC
T2/T1LowVoltageTrip 18VAC 85/170VAC
T2/T1LowVoltageReset 19VAC 95/185VAC
Power Consumption 5VA 5VA
M1/M2 Contact Rating 2.5A Max 2.5A Max
Motor Temperature Trip Resistance >4.5KΩ±25% >4.5KΩ±25%
Open Motor Thermistor Trip Resistance >220KΩ >220KΩ
Shorted Motor Thermistor Trip Resistance <40Ω <40Ω
Motor Temperature Reset Resistance <2.75KΩ <2.75KΩ
Scroll Temperature Trip Resistance <2.4KΩ <2.4KΩ
Open Scroll Thermistor Trip Resistance >370KΩ >370KΩ
Shorted Scroll Thermistor Trip Resistance <1KΩ <1KΩ
Scroll Temperature Reset Resistance >5.1KΩ >5.1KΩ
Reset Time After Trip 30 minutes 30 minutes
Operating Temperature -40° to 150°F (-40° to 65°C) -40° to 150°F (-40° to 65°C)
Storage Temperature -60° to 175°F (-51° to 80°C) -60° to 175°F (-51° to 80°C)

10
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
Table 4 – CoreSense Modbus Map
Parameters can be read using Function code 4 (Read Input Register)
Location
in Hex Parameter
Message
Length
in Bytes
Message
Length
With Zero
Stufng
Description
300 CoreSense Module Firmware
Version 8 16
308 CoreSense Module Model Number 12 24
314 ASSET Serial Number 12 24
320 ASSET Model Number 18 36
332 CoreSense Module Serial Number 11 22
33D Division Name 29 58
35A Product Code 9 18
363 Product Name 7 14
36A Product type 1 2
36B Endian Convention 1 2
36C Dip switch Setting 2 2
Unused (18 bytes)
380 Alarm Code 1 2
0 - Normal Operation
1 - Loss of Communication to E2
2 - Open OR Short Spare Thermister Warning
3 - Open OR Shrt Scroll Thermister Warning
4 - Short Cycle Warning
5-ModuleLowVoltageTrip
6 - Spare High Temperature Trip
7 - Missing Phase Trip
8 - Scroll High Temperature Trip
9 - Motor Thermister Open OR Short Trip
10 - Motor High Temperature Trip
11 -Short Cycle Lockout
12 - Spare High Temperature Lockout
13 - Motor High Temperature Open OR Short Lockout
14 - Reverse Phase Lockout
15 - Missing Phase Lockout
16 - Scroll High Temperature Lockout
17 - Motor High Temperature Trip Lockout
18 - P47 Module Failure
Note: Numberofregistersvaluetobesendinthequery=Numberinthecolumn"MessageLengthWithZeroStufng"/2
(e.g. number of reg required to read "Seven day Warning history with cumulative count" is 36 (72/2)
Read Only Data
Read Write Data
Write Only Data

11
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
Unused (18 bytes) – continued
381 Input and Output status 4 4
0x0001 - PTC Status (OK-1/Not OK-0)
0x0002 - Scroll High Temp NTC Status (OK-1/Not OK-0)
0x0004 - Spare Temp NTC Status (OK-1/Not OK-0)
0x0008-L1VoltageStatus(Present-1/Absent-0)
0x0010-L2VoltageStatus(Present-1/Absent-0)
0x0020-L3VoltageStatus(Present-1/Absent-0)
0x0040-LinePhaseVoltageStatus(OK-1/NotOK-0)
0x0080-LineReverseVoltageStatus(OK-1/NotOK-0)
0x0100-PilotVoltageStatus(OK-1/NotOK-0)
385 ScrollTemperatureValue 2 2 (ScrollHighTempSensorValue)Range=-0°Cto
655.36°C
387 SpareTemperatureValue 2 2 (SpareTempSensorValue)Range=-0°Cto655.36°C
389 PilotVoltageValue 2 2 PilotVoltageValue–Range0to655.36V
Unused (117 bytes)
400 Ten most recent alarms with time
stamp 40 60
428 Compressor run history with
cumulative count 11 20
433 Compressor start history with
cumulative count 19 20
446 Short Cycle history with cumulative
count 11 20
Unused (30 bytes)
46F Seven day Warning history with
cumulative count 40 72
497 Seven day Trip history with
cumulative count 60 108
4D3 Seven day Lockout history with
cumulative count 70 126
Table 4 – CoreSense Modbus Map Continued

12
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
Parameters can be read using Function code 3 (Read Holding Register)
Location in Hex Parameter
Message
Length in
Bytes
Message
Length With
Zero Stufng
100 Customer Id Code 4 8
104 Customer Location 17 34
115 Customer Name 17 34
126 CompressorModelNumberModied 18 36
138 Compressor serial number 12 24
144 Application code 3 6
147 Temperature code 4 8
14B Refrigerant code 7 14
152 FunctionalConguration 2 2
154 Compressor run time to count as short cycle 1 2
155 Scroll High Temp Trip 2 2
157 Scroll High Temp Reset 2 2
159 No. of Events to Phase Loss Lockout 1 2
15A Future Use
15B Future Use
15D Future Use
15F No.of Events to Scroll High Temp Lockout 1 2
160 No.of Events to Short Cycling Warning 1 2
Table 4 – CoreSense Modbus Map Continued

13
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
Parameters can be write using Function code 16 (Preset Multiple Registers)
Location
in Hex Parameter
Message
Length in
Bytes
Message
Length
With Zero
Stufng
100 Customer Id Code 4 8
104 Customer Location 17 34
115 Customer Name 17 34
126 CompressorModelNumberModied 18 36
138 Compressor serial number 12 24
144 Application code 3 6
147 Temperature code 4 8
14B Refrigerant code 7 14
152 FunctionalConguration 2 2
154 Compressor run time to count as short
cycle 1 2 Range: 1 min to 6 min
155 Scroll High Temp Trip 2 2 Range: 110 deg C to 150 deg C
157 Scroll High Temp Reset 2 2
Note: Reset set point value should
be always (Trip set point value -
30 deg C)
159 No. of Events to Phase Loss Lockout 1 2 Range: 4 to 24
15A Future Use
15B Future Use
15D Future Use
15F No.of Events to Scroll High Temp
Lockout 1 2 Range: 4 to 36
160 No.of Events to Short Cycling Warning 1 2 Range: 20 to 200
16A Write Command 2 2 Options: 0x0800(Alarm Reset) &
0x8000(Module Reset)
Table 4 – CoreSense Modbus Map Continued

14
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
Table 6 – CoreSense™ Communications LED Flash Code Information
TheashcodenumbercorrespondstothenumberofLEDashes,followedbyapause,andthentheashcodeisrepeated.Alockout
conditionproducesaredash,followedbyapause,asolidred,asecondpause,andthenrepeated.
Status Fault Condition Code Fault Description Code Reset
Description Trouble Shooting Information
Solid Green Normal Operation Module is powered and
operation is normal N/A N/A
Solid Red Module
Malfunction Module has internal fault N/A
1) Reset module by removing
power from T2-T1
2)Replace module
Warning LED Flash
Green
Flash Code 1
Loss of
Communication
Module and master
controller have lost
communications with each
other for more than 5
minutes
When
communications are
conrmed
1)Check the control wiring
2)Verifydipswitch8is"on"
Green
Flash Code 2 Future Use N/A N/A N/A
Green
Flash Code 3 Short Cycling
Run time of less than 3
minutes; number of short
cycles exceeds 48 in 24
hours
< 48 short cycles in
24 hours
1) Check system charge and
pressure control setting
2) Adjust set-point of
temperature controller
3) Install anti-short cycling
control
Green
Flash Code 4
Open/Shorted
Scroll Thermistor Ω>370KorΩ<1K 5.1K<Ω<370K
1) Check for poor connections
at module and thermistor fusite
2) Check continuity of
thermistor wiring harness
Green
Flash Code 5 Future Use N/A N/A N/A
Table 5 – DIP Switch Purpose
DIP Switch Number On Off
1 through 5 Modbus Module Address
6 Baud Rate = 9600 Baud Rate = 19200
7 Even Parity No Parity
8 Network Mode Stand Alone
91TE*: NTC & PTC TW*: PTC ONLY
10 Enable Short Cycle Protection Disable Short Cycle Protection
1ThermistorConguration:TE*=PTC&NTC(3wireconnectors),TW*=PTConly(2wireconnectors)

15
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
Table 6 Continued
1This Alert does not result in a Lockout
Alert/Lockout LED Flash
Red
Flash Code 1
Motor High
Temperature
Ω>4.5K±25%;
Lockout after 5 Alerts
Ω<2.75Kand30
minutes
1) Check supply voltage
2) Check system charge &
superheat
3) Check contactor
Red
Flash Code 2
Open/Shorted
Motor Thermistor
Ω>220KorΩ<40;
Lockout after 6 hours
40<Ω<2.75Kand
30 minutes
1) Check for poor connections
at module and thermistor
fusite 2) Check continuity of
thermistor wiring harness
Red
Flash Code 3 Short Cycling
Run time of less than 3
minutes; Lockout if the
number of Alerts exceeds
thenumberconguredby
the user in 24 hours
Interrupt power to
T2-T1 or perform
Modbus reset
command
1) Check system charge and
pressure control setting
2) Adjust set-point of
temperature controller
3) Install anti-short cycling
control
Red
Flash Code 4
Scroll High
Temperature
Ω<2.4K;Lockoutifthe
number of Alerts exceeds
thenumberconguredby
the user in 24 hours
Interrupt power to
T2-T1 or perform
Modbus reset
command
1) Check system charge and
superheat
2) Check system operating
conditions
3) Check for abnormally low
suction pressure
Red
Flash Code 5 Future Use N/A N/A N/A
Red
Flash Code 6 Missing Phase Missing phase; Lockout
after 10 consecutive Alerts
After 5 minutes
and missing phase
condition is not
present
1) Check incoming power
2) Check fuses/breakers
3) Check contactor
Red
Flash Code 7 Reverse Phase Reverse phase; Lockout
after 1 Alert
Interrupt power to
T2-T1 or perform
Modbus reset
command
1) Check incoming phase
sequence
2) Check contactor
3) Check module phasing wires
A-B-C
Red
Flash Code 8 Future Use N/A N/A N/A
Red
Flash Code 9
Module Low
Voltage
Low voltage on T2-T1
terminals1
After 5 minutes and
the voltage is back in
the normal range
1)Verifycorrectmodulep/n2)
CheckVAratingoftransformer
3) Check for blown fuse in
transformer secondary

16
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
Figure 1b – ZP236/296 Terminal Box Wiring Diagram
2
3
1
4
4
2
ALERT CODE (RED)
/ CODIGO DE ALERTA (ROJO)
TYPE / TIPO EVENT / EVENTO
SOLID / SOLIDO LOCKOUT /
BLOQUEADO LOSS OF FUNCTION /
PERDIDA DE FUNCION
1
TRIP /
DISPARO MOTOR HIGH TEMPERATURE /
TEMPERATURA DEL MOTOR ELEVADA
2LOCKOUT/TRIP /
BLOQUEADO
/
DISPARO
SCROLL HIGH TEMPERATURE /
TEMPERATURA DEL SCROLL ELEVADA
3LOCKOUT /
BLOQUEADO
MISSING PHASE /
PERDIDA DE FASE
4LOCKOUT/TRIP /
BLOQUEADO
/
DISPARO
REVERSE PHASE /
INVERSIÓN DE FASE
5
OPEN / SHORT MOTOR THERMISTOR /
TERMISTOR DEL MOTOR EN CIRCUITO
ABIERTO O CORTOCIRCUITO
OPEN / SHORT SCROLL THERMISTOR /
TERMISTOR DEL SCROLL EN CIRCUITO
ABIERTO O CORTOCIRCUITO
6
N/AFUTURE USE / USO FUTURO
7
MODULE LOW VOLTAGE /
BAJO VOLTAJE AL M
Ó
DULO
9TRIP /
DISPARO
SHORT CYCLING /
CICLOS CORTOS
WARNING (GREEN) /
PRECAUCIÓN (VERDE)
TYPE / TIPOEVENT / EVENTO
SOLID / SOLIDO NORMAL /
NORMAL NORMAL OPERATION /
OPERACION NORMAL
1WARNING /
PRECAUCION
2FUTURE USE / USO FUTURO
3
LOSS OF COMMUNICATION /
PERDIDA DE COMUNICACIÓN
DIP SWITCH /
INTERRUPTORES “DIP”
PURPOSE / PROPOSITO UP = 1 /
PRENDIDO = 1
DOWN = 0 /
APAGADO = 0
1 -LSB 0
UNIQUE ADDRESS / DIRECCION UNICA
RANGE 1 TO 32 / RANGO DE 1 A 32
(EXAMPLE = 12) / (EJEMPLO = 12)
2
3
4
5 - MSB
6
7
8
9
10
0
TEMP. CONNECTOR CONFIGURATION /
CONFIG. DEL CONECTOR DEL SENSOR DE TEMPERATURA
BAUD RATE / FRECUENCIA DE TRANSMISIÓN EN BAUDIOS
PARITY / PARIDAD
COMMUNICATION / COMUNICACION
SHORT CYCLE PROTECTION /
PROTECCIÓN CONTRA CICLOS CORTOS
1
10
9,600 19,200
EVEN / PAR
STANDALONE /
INDEPENDIENTE
ENABLE /
ACTIVADO
DISABLE /
DESACTIVADO
TE* TW*
NONE / NINGUNA
LOCKOUT /
BLOQUEADO
WARNING /
PRECAUCION
WARNING /
PRECAUCION
WARNING /
PRECAUCION
NETWORK /
EN RED
LOCKOUT/TRIP /
BLOQUEADO /
DISPARO
4
5WARNING /
PRECAUCION FUTURE USE / USO FUTURO
SHORT CYCLING /
CICLOS CORTOS
8N/A FUTURE USE / USO FUTURO
SYMBOLS / SIMBOLOS
MOTOR WINDINGS
CONNECTIONS / CONEXIONES
DE DEVANADO DEL MOTOR
JUMPER / CONECTOR DE PUENTE
COMMUNICATION PORT /
PUERTO DE COMUNICACION
PROTECTOR MODULE VOLTAGE / VOLTAGE DEL MODULO DE PROTECCION
DIP SWITCHES /
INTERRUPTORES “DIP”
LED’S /
DIODOS LUMINOSOS
TEMP SENSORS /
SENSORES DE TEMPERATURA
USE COPPER CONDUCTORS ONLY.
USE MINIMUM 75º C WIRE FOR AMPACITY DETERMINATION.
USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY.
PRIMARY SINGLE PHASE FAILURE PROTECTION IS PROVIDED.
PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST
BE CONNECTED ONLY TO THEIR RATED VOLTAGE.
OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST
BE IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT APPROVALS
- SEE SYSTEM NAMEPLATE.
UTILICE CONDUCTORES DE COBRE ÚNICAMENTE.
UTILICE CABLE DE 75º C COMO MÍNIMO PARA DETERMINAR LA AMPACIDAD.
UTILICE ESTE EQUIPO EN SISTEMAS CONECTADOS A TIERRA SOLAMENTE.
SE PROVEE PROTECCION DE FALLA MONOFASICA EN EL CIRCUITO PRIMARIO.
EL MODULO DE PROTECCION Y EL CALENTADOR DE CARTER OPCIONAL DEBERAN
CONECTARSE A SU VOLTAJE NOMINAL RESPECTIVO.
EL TIPO Y LAS CARACTERISTICAS NOMINALES DEL DISPOSITIVO DE PROTECCIÓN DE
SOBRECORRIENTE DEBERÁN RESPETAR LAS APROBACIONES DE LA AGENCIA
REGLAMENTARIA PARA EL PRODUCTO FINAL
– VEA LA PLACA DE DATOS 02-14 052-2895-00
3
L1: RED / ROJO
L2: BLACK / NEGRO
L3: WHITE / BLANCO
TO CONTROL CIRCUIT / AL CIRCUITO DE CONTROL
THERMAL SENSORS DO NOT SHORT / SENSORES DE TEMPERATURA – NO CONECTAR
EN CORTO CIRCUITO
PHASE SENSING / SENSOR DE FASES
WARNING: GREEN FLASHING + PAUSE 2 SEC. /
PRECAUCIÓN: LUZ VERDE DESTELLANTE +PAUSA DE 2 SEG.
TRIP: RED FLASHING + PAUSE 2 SEC. /
DISPARO: LUZ ROJA DESTELLANTE + PAUSA DE 2 SEG.
LOCKOUT: RED FLASHING + PAUSE 2 SEC. + SOLID 3 SEC. + PAUSE 2 SEC. /
BLOQUEO: LUZ ROJA DESTELLANTE + PAUSA DE 2 SEG. + LUZ SOLIDA POR
3 SEG. + PAUSA DE 2 SEG.
S2
S1
3
1 2 3 4 5 6 7 8 9 10
T2 T1 L3
L2L1
M2 M1
14
L2L1
L3
4
L1
L2
L3
4
S2
S1
3
S3
2
3
1
4
4
2
1 2 3 4 5 6 7 8 9 10
T2 T1 L3
L2L1
M2 M1
ALERT CODE (RED)
/ CODIGO DE ALERTA (ROJO)
TYPE / TIPO EVENT / EVENTO
SOLID / SOLIDO LOSS OF FUNCTION /
PERDIDA DE FUNCION
1
TRIP /
DISPARO MOTOR HIGH TEMPERATURE /
TEMPERATURA DEL MOTOR ELEVADA
2LOCKOUT/TRIP /
BLOQUEADO / DISPARO
3
MISSING PHASE /
PERDIDA DE FASE
4
REVERSE PHASE /
INVERSI
Ó
N DE FASE
5
OPEN / SHORT MOTOR THERMISTOR /
TERMISTOR DEL MOTOR EN CIRCUITO
ABIERTO O CORTOCIRCUITO
6
N/AFUTURE USE / USO FUTURO
7
MODULE LOW VOLTAGE /
BAJO VOLTAJE AL MÓDULO
9TRIP /
DISPARO
SHORT CYCLING /
CICLOS CORTOS
WARNING (GREEN) /
PRECAUCIÓN (VERDE)
TYPE / TIPOEVENT / EVENTO
SOLID / SOLIDO NORMAL /
NORMAL NORMAL OPERATION /
OPERACION NORMAL
1WARNING /
PRECAUCIÓN
2FUTURE USE / USO FUTURO
3
LOSS OF COMMUNICATION /
PERDIDA DE COMUNICACIÓN
PURPOSE / PROPOSITO UP = 1 /
ARRIBA = 1
DOWN = 0 /
ABAJO = 0
1 -LSB 0
UNIQUE ADDRESS / DIRECCION UNICA
RANGE 1 TO 32 / RANGO DE 1 A 32
(EXAMPLE = 12) / (EJEMPLO: 12)
2
3
4
5 - MSB
6
7
8
9
10
0
TEMP. CONNECTOR CONFIGURATION /
CONFIG. DEL CONECTOR DEL SENSOR DE TEMPERAURA
BAUD RATE / FRECUENCIA DE TRANSMISIÓN EN BAUDIOS
PARITY / PARIDAD
COMMUNICATION / COMUNICACION
SHORT CYCLE PROTECTION /
PROTECCIÓN CONTRA CICLOS CORTOS
1
10
9,600 19,200
EVEN / PAR
STANDALONE /
INDEPENDIENTE
ENABLE /
ACTIVADO
DISABLE /
DESACTIVADO
TW*
LOCKOUT /
BLOQUEADO
WARNING /
PRECAUCIÓN
WARNING /
PRECAUCIÓN
NETWORK /
EN RED
4
5WARNING /
PRECAUCIÓN FUTURE USE / USO FUTURO
SHORT CYCLING /
CICLOS CORTOS
8N/A FUTURE USE / USO FUTURO
SYMBOLS / SIMBOLOS
MOTOR WINDINGS
CONNECTIONS / CONEXIONES
DE DEVANADO DEL MOTOR
JUMPER / CONECTOR DE PUENTE
COMMUNICATION PORT /
PUERTO DE COMUNICACION
PROTECTOR MODULE VOLTAGE / VOLTAJE DEL MODULO DE PROTECCION
DIP SWITCHES /
INTERRUPTORES "DIP"
LED’S /
DIODOS LUMINOSOS
TEMP SENSORS /
SENSORES DE TEMP.
USE COPPER CONDUCTORS ONLY.
USE MINIMUM 75º C WIRE FOR AMPACITY DETERMINATION.
USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY.
PRIMARY SINGLE PHASE FAILURE PROTECTION IS PROVIDED.
PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST
BE CONNECTED ONLY TO THEIR RATED VOLTAGE.
OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST
BE IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT APPROVALS
- SEE SYSTEM NAMEPLATE.
UTILICE CONDUCTORES DE COBRE ÚNICAMENTE.
UTILICE CABLE DE 75°C COMO MÍNIMO PARA DETERMINAR LA AMPACIDAD.
UTILICE ESTE EQUIPO EN SISTEMAS CONECTADOS A TIERRA SOLAMENTE.
SE PROVEE PROTECCION DE FALLA MONOFASICA EN EL CIRCUITO PRIMARIO.
EL MODULO DE PROTECCION Y EL CALENTADOR DE CARTER OPCIONAL DEBERAN
CONECTARSE A SU VOLTAJE NOMINAL RESPECTIVO.
EL TIPO Y LAS CARACTERISTICAS NOMINALES DEL DISPOSITIVO DE PROTECCIÓN DE
SOBRECORRIENTE DEBERÁN RESPETAR LAS APROBACIONES DE LA AGENCIA
REGLAMENTARIA PARA EL PRODUCTO FINAL
– VEA LA PLACA DE DATOS
14
3
L1: RED / ROJO
L2: BLACK / NEGRO
L3: WHITE / BLANCO
TO CONTROL CIRCUIT / AL CIRCUITO DE CONTROL
THERMAL SENSORS DO NOT SHORT / SENSORES DE TEMPERATURA – NO CONECTAR
EN CORTOCIRCUITO
PHASE SENSING / SENSOR DE FASES
WARNING /
PRECAUCIÓN
TE*
SCROLL HIGH TEMPERATURE /
ALTA TEMPERATURA DEL ESPIRALES
DIP SWITCH /
INTERRUPTOR "DIP"
LOCKOUT/TRIP /
BLOQUEADO / DISPARO
LOCKOUT/TRIP /
BLOQUEADO / DISPARO
LOCKOUT /
BLOQUEADO
LOCKOUT /
BLOQUEADO
OPEN / SHORT SCROLL THERMISTOR /
TERMISTOR DEL MOTOR ABIERTO
O EN CORTO
NONE / IMPAR
01-14 052-2820-00
WARNING: GREEN FLASHING + PAUSE 2 SEC. /
PRECAUCIÓN: LUZ VERDE DESTELLANTE + PAUSA DE 2 SEG.
TRIP: RED FLASHING + PAUSE 2 SEC. /
DISPARO: LUZ ROJA DESTELLANTE + PAUSA DE 2 SEG.
LOCKOUT: RED FLASHING + PAUSE 2 SEC. + SOLID 3 SEC. + PAUSE 2 SEC. /
BLOQUEO: LUZ ROJA DESTELLANTE + PAUSA DE 2 SEG. + LUZ SOLIDA POR
3 SEG. + PAUSA DE 2 SEG.
Figure 1a – 20 to 40 Ton Terminal Box Wiring Diagram (excluding ZP236/296)

17
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
Scroll NTC Thermistor
(black wire) Motor PTC Thermistor
(red wire)
Spare Connection
Common Connection
(blue wire)
View A
Terminal identification is from the end of the plug (View A)
Figure 3
Thermistor Circuit Cable
Figure 2 – CoreSense
Communications Module

18
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
Switch # 12345
On
Off
Switch # 12345
On
Off
= 23
= 22
= 31
= 30
= 29
= 28
= 27
= 26
= 25
= 24
Switch # 12345
On
Off
= 11
= 14
= 18
= 17
= 16
= 15
= 21
= 20
= 19
= 13
= 12
= 10
= 7
= 8
= 9
= 4
= 5
= 6
= 3
= 2
= 1
= 0
Figure 4
Modbus Addressing

19
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services
describedhereinortheiruseorapplicability.EmersonClimateTechnologies,Inc.reservestherighttomodifythedesignsorspecicationsofsuchproductsatanytimewithoutnotice.Emerson
Climate Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Climate
Technologies, Inc. product remains solely with the purchaser and end-user.
Figure 5
PC Interface Wiring
CoreSense
Isolated RS - 422/485 USB Adapter
Model USOPTL 4
RS-422
Echo ON
4-Wire
4-Wire
RS-485
Echo OFF
2-Wire
2-Wire
USB Serial Conversion
B & B Electronics
TDA (-)
TDB (+)
RDB (+)
GND
RDA (-)
A (-)
GND
B (+)
Laptop
USB
Cable
DIP Switch Settings
This manual suits for next models
3
Table of contents
Other Emerson Conference System manuals