EMKO TRANS-ATS.D User manual

Introduction Brochure. ENG TRANS-ATS_D 01 V05 04/21
1. Introduction
1.1 General Specifications
1.2 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.3 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
The unit provides the voltage monitoring for both sources and automatic transfer switching. In
the event of any Source voltage failure, the remote start relay output is energized(
) and the unit automatically transfers the load from one source to other .
if generator
application selected
If a fault is detected, the unit shuts down the engine(if generator application selected), transfers
load to the other source and shows the failure message on the LCD display.
Both automatic and manual control is possible. A test mode is also available which allows the
generator with the higher priority to be run.
The unit is extensively programmable through the front panel, with password protection on
two levels. Operational parameters can also be monitored and controlled from a PC via a
built-in USB port.
The unit monitors both sources and gives warning of any faults that are detected.
TRANS-ATS.D
AUTOMATIC TRANSFER SWITCH

Ýçindekiler
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical
and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit , power off
the system and seperate the electrical connection of the device from the system.
Keep the power off until all of the wiring is completed so that electric shock and trouble with
the unit can be prevented.
Before beginning installation of this product, please read the instruction
manual and warnings below carefully.
2. Installation
Ýçindekiler
2.1 Unit Configuration
Ýçindekiler
2.2 Panel Mounting
The unit is designed for panel mounting. Fixing is by two screw fixings.
Insert the unit in the panel cut-out from the front.
Insert the fixings in the slotted at the corners of the unit and tighten the fixing screws to secure
the unit against the panel.
1-
2-
During the equipment is putted in hole on the metal panel while mechanical
installation some metal burrs can cause injury on hands, you must be careful.
Figure 2.1 Front View Figure 2.2 Panel Cut-Out
The unit can be programmed using the buttons and LCD display on the front panel or PC
Software.
2
182mm
135mm
152mm
229mm
!
!
ü
S2S1
ATS.D

2.3 Electrical Connection
3
TRANS-ATS.D three phase connections schematic
1- Connect the unit as shown in the appropriate diagram. Be sure to connect the battery
supply the right way round and battery negative should be grounded.
2- Current transformers secondary should be grounded.
!
35 21
22
BATTERY -
BATTERY +
40
42 41
5A
BATTERY +
34 33
BATTERY -
32 31 30 29 28
Configurable Input-2
Remote Start 2 or
Configurable Output-6
5A
USB
FUSE-7
FUSE-8
Configurable Output-3
39 38 37 36
Configurable Output-4
TRANSISTOR OUTPUTS
MAX. 1 A
BATTERY +
Emergency Stop or
Configurable Input-1
62
73
8
8A
8A
14
910 5
L1
L2
L3
N
LOAD
L1
L2
L3
N
Electrical interlock
Mechanical interlock
13 14 15 16
Source 1
Contactor
Relay
Source 2
Contactor
Relay
FUSE 1-
FUSE 2-
FUSE 3-
FUSE-4
FUSE-5
FUSE-6
Output-1Configurable
Max. 300VVMax. 300VV
BATTERY +
Configurable Input-6
Source 2 Ready or
Configurable Input-8
Configurable Input-5
Output-2Configurable
Configurable Input-3
Configurable Input-4
L1
L2
L3
N
1
!
2
!
FUSE FUSE FUSE-5, FUSE-6 FUSE-3, FUSE-4 8A. T
FUSE-7 6A. T
FUSE-8 Max. 10A. T
-1, -2, 2A. T
Remote Start 1 or
Configurable Output-5
Configurable Input-7
S1
S2: (GENERATOR)
S1: (MAINS)
S2

4
3. Changing And Saving Parameters Values
S1: MAINS
V12: 380V V1 V
Source 1 okay
: 220
V23: 380V V2: 220V
V31: 380V V3: 220V
ü
Operation Screen
When the Prog button is
pressed, the parameters
section is asked for
accessing to parameters.
ü
ü ü
üü
ü ü
ü ü
üü
Press the Up or
Down buttons to
select the section
you wish to
view/change.
Press the
Enter
button.
Enter password
with cursor (Right,
Left,
) .
Up and
Down buttons
Press the Enter button to confirm
password. If the password is
incorrect, the unit will drop out of
program mode.
Press the Up or
Down buttons to
select the main
parameter group
you wish to
view/change.
Note1: If Enter button is pressed
and the technician password is
zero, Password screen is ignored.
Press Enter button to access to
all parameters page in currently
main parameter group.
Parameter can be
changed with Up
and Down buttons.
Press Enter button to
confirm the changed value.
PROGRAM
Operator setting
Technician setting
Factory adjustment
PROGRAM
Operator setting
Technician setting
Factory adjustment
TECHNICIAN SETTING
Password
0162
TECHNICIAN SETTING
Password
0000
TECHNICIAN SETTING
System
Source 1
Source 2
Load
TECHNICIAN SETTING
System
Source 1
Source 2
Load
SOURCE 2
Volt level
Frequency level
Actions
SOURCE 2 VOLT LEVEL
Under volt set
320 Vac
SOURCE 2 VOLT LEVEL
Under volt set
Under volt reset
Over volt set
Over volt reset
Press the Enter
button to view
parameter value.
Press Enter button to
access to all parameters in
currently parameter page.
SOURCE 2 VOLT LEVEL
Under volt set
325 Vac
SOURCE 2 VOLT LEVEL
Under volt set
Under volt reset
Over volt set
Over volt reset
Operation
Screen
SOURCE 2
Volt level
Frequency level
Actions
When the Escape button is
pressed any time, previous
page can be accessed.
S1: MAINS
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
Source 1 okay
To exit from
programming mode any
time, press Prog button.

5
Note: dis = disable
600
60
60
60
600
600
600
VV
VV
VV
VV
60
Min DefaultSOURCE 1 VOLT LEVEL (Source 1 )->Volt level Max
Source 1 Under Voltage
Source 1 Under Voltage Reset
Source 1 Over Voltage
Source 1 ResetOver Voltage
320
340
440
420
Under volt trip
4.1 Operator Parameters
Under volt reset
Over volt trip
Over volt reset
Unit
4. Parameters
Min DefaultSOURCE 1 Source 1FREQ. LEVEL ( )-> levelFrequency Max
Source 1 Under Frequency
Hz
Hz
Hz
Hz
20.0 75.0
20.0 75.0
20.0 75.0
20.0 75.0
45.0
48.0
55.0
52.0
Source 1 ResetUnder Frequency
Source 1 Over Frequency
Source 1 ResetOver Frequency
Under freq trip
Under freq reset
Over freq trip
Over freq reset
Unit
4.1.1 Source 1 (Mains)
4.1.2 Source 2 (Generator)
600
60
60
60
600
600
600
VV
VV
VV
VV
60
Min DefaultSOURCE 2 VOLT LEVEL (Source 2 )->Volt level Max
Source 2 Under Voltage
Source 2 Under Voltage Reset
Source 2 Over Voltage
Source 2 ResetOver Voltage
320
340
440
420
Under volt trip
Under volt reset
Over volt trip
Over volt reset
Unit
Min DefaultSOURCE 2 Source 2FREQ. LEVEL ( )-> levelFrequency Max
Source 2 Under Frequency
Hz
Hz
Hz
Hz
20.0 75.0
20.0 75.0
20.0 75.0
20.0 75.0
45.0
48.0
55.0
52.0
Source 2 ResetUnder Frequency
Source 2 Over Frequency
Source 2 ResetOver Frequency
Under freq trip
Under freq reset
Over freq trip
Over freq reset
Unit

6
Note: = The device must be restarted after changing this parameter.*1
4.2 Technician Parameters
Min Default
Max
Current Transformer Ratio
Voltage Transformer Ratio
Select AC system;
Phase Sequence (dis, L123 or L321)
Generator kVA rating set
CT ratio
PT ratio
Type of AC system
Phase sequence
Generator kVA rating
Unit
SYSTEM NETWORK ( )System->Network
2
9999
100
kVA
0
0
1
1
300
1
DISBL
0- 1 Phase 2 Wire
1- 3 Phase 4 Wire
2- 2 Phase 3 Wire L1-L2
3- 2 Phase 3 Wire L1-L3
DISBL, L123,
L321
99995 100
4.2.1 System
Min Default
Max Unit
SYSTEM OPTIONS ( )System->Options
Source selection
Operation type
Source priority
Source 1 dual time
Source 2 dual time
Early start time
Source selection *1
Operation type
Source priority
Source 1 dual time
Source 2 dual time
Early start time
2
1
1
9999
9999
999
Min.
Min.
sec
0
0
0
0
0
0
0
0
0
60
60
10
0-Mains-Gen
1-Gen-Gen
2-Mains-Mains
0-Duty - standby
1-Dual
0-Source 1
1-Source 2

Min Default Unit
LCD DISPLAY ( )System->LCD display Max
Language Selection
Contrast Setting
Auto Backlight Off
ENGLISH/CHINESE
5
4 9
Contrast
Auto backlight off
Language
Auto Scroll Time
Auto Scroll Number
Scroll Time For Error Messages
0
0 (dis) 250 Sec
5
14
2
1 250
Auto scroll number
Err. mesg scroll time
Auto scroll time
Sec
1
ENGLISH
ENA DISBLBL/ DISBL
7
Min Default Unit
BREAKERS ( )System->Breakers
Max
Hardware Breaker Selection
Source 2 Close Breaker Contact Type
Source 2 Close Breaker Relay Type
Source 2 Close Timer
0
Source 2 Open Breaker Relay Type
0 2
Source 2 Open Timer
Source 1 Close Breaker Contact Type
Source 1 Close Breaker Relay Type
Source 1 Close Timer
NO / NC 0
NOR / PULS
5
1 250
0
Sec
0
NOR / PULS
0
1 250 5
0
NOR / PULS
0
1 250 5
5
NOR / PULS
0.0
0.0
0
10.0
10.0
250 2
Source 1 Open Breaker Relay Type
Source 1 Open Timer
Breaker Close Pulse Time
Breaker Open Pulse Time
Transfer Time
Spring Loading Time
Retry Number
NO / NC
S2 brk.cls.contact
S2 brk.cls.relay
S2 brk.cls.time
S2 brk.open relay
S2 brk.open time
Type of Breaker
S1 brk.cls.relay
S1 brk.cls.time
S1 brk.open relay
S1 brk.open time
Break.close puls.time
S1 brk.cls.contact
Transfer time
Spring loading time
Retry number
Break.open pulse time
Sec
Sec
1 250
0.5
0.5
Sec
Sec
Sec
Sec
Sec
3
5
1 250
1 250
Note: NO / NC : Normally Open / Normally Close
NOR / PULS : Normal / Pulse
Min DefaultDATE & TIME SET ( )System->Date & time set Max
Year
Month
0 99
112
Date 131
Day of week 17
Hour 023
Minute 059
Second 059
Year
Month
Day
Week
Hour
Minute
Second
Unit
Min Default Unit
COMMUNICATION ( )System->Communication Max
Slave Address 1
1 247
05 3
Baud Rate: 0 - 1200 baud
1 - 2400 baud
2 - 4800 baud
3 - 9600 baud
4 - 19200 baud
5 - 38400 baud
Datalog Period
Timeout
ModBus ASCII/RTU Selection
Stop Bit (0-> 1 stop bit,1-> 2 stop bit)
020
0.0(dis)
0(dis)
0
999.9
999
1
1.0
3
ASCII
0
Slave address
Baud rate
Parity
Datalog period
Timeout
ASCII/RTU selection
Stop bit
Parity: 0-> None, 1-> Odd, 2-> Even
Min
Min
ASCII / RTU

4.2.2 Source 1 (Mains)
Min Default Unit
SOURCE 1 (Source 1 )ACTIONS ->Actions Max
Look Failure at Stop Mode En/DisSource 1
Always Look Source 1 Return Delay
Source 1 return delay
Source 1 fail delay
S1 fail.stop mode
S1 always return delay
S1 return delay
S1 fail delay
ENABL/DISBL
ENABL/DISBL
ENABL
DISBL
8
Min Default Unit
PASSWORD SETTINGS ( )System->Password settings Max
Operator Password
Technician Password
0
0 9999
09999 0
Operator password
Technician password
Min Default Unit
DEFAULT SETTINGS ( )System->Default settings Max
Save setting to default
Reset default sets
Save setting to def.
Reset default sets
YES / NO NO
Reset factory sets
Reset factory sets
YES / NO NO
YES / NO NO
600
60
60
60
600
600
600
VV
VV
VV
VV
60
Min DefaultSOURCE 1 VOLT LEVEL (Source 1 )->Volt level Max
Source 1 Under Voltage
Source 1 Under Voltage Reset
Source 1 Over Voltage
Source 1 ResetOver Voltage
320
340
440
420
S1 Under volt trip
S1 Under volt reset
S1 Over volt trip
S1 Over volt reset
Unit
Min DefaultSOURCE 1 Source 1FREQ. LEVEL ( )-> levelFrequency Max
Source 1 Under Frequency
Hz
Hz
Hz
Hz
20.0 75.0
20.0 75.0
20.0 75.0
20.0 75.0
45.0
48.0
55.0
52.0
Source 1 ResetUnder Frequency
Source 1 Over Frequency
Source 1 ResetOver Frequency
S1 Under freq trip
S1 Under freq reset
S1 Over freq trip
S1 Over freq reset
Unit
4.2.3 Source 2(Generator)
600
60
60
60
600
600
600
VV
VV
VV
VV
60
Min DefaultSOURCE 2 VOLT LEVEL (Source 2 )->Volt level Max
Source 2 Under Voltage
Source 2 Under Voltage Reset
Source 2 Over Voltage
Source 2 ResetOver Voltage
320
340
440
420
S2 Under volt trip
S2 Under volt reset
S2 Over volt trip
S2 Over volt reset
Unit
sec
sec
0
0
99
99
2
2
Min Default Unit
SYSTEM GENERAL (System )->General Max
All Warnings Are Latched En/Dis
All warning are latch ENABL/DISBL DISBL
Min DefaultSOURCE 2 Source 2FREQ. LEVEL ( )-> levelFrequency Max
Source 2 Under Frequency
Hz
Hz
Hz
Hz
20.0 75.0
20.0 75.0
20.0 75.0
20.0 75.0
45.0
48.0
55.0
52.0
Source 2 ResetUnder Frequency
Source 2 Over Frequency
Source 2 ResetOver Frequency
S2 Under freq trip
S2 Under freq reset
S2 Over freq trip
S2 Over freq reset
Unit

9
Min Default
Max
Load Under Current Pre-Alarm Reset
Load Under Current Actions Delay Time
Load Over Current Set
Load Over Current Pre-Alarm
Load Over Current Pre-Alarm Reset
Load Over Current Actions Delay Time
Load Short Circuit Current Set
Under cur. reset
Under cur. act.
Under act. delay time
Over cur. set
Over cur. prealarm
Over cur. reset
Over cur. act.
Over act. delay time
Short circuit cur.
Unit
LOAD CUR LEVEL & ACT Load( )->Current level & act.
Load Under Current Set
Under cur. set
Under cur. prealarm Load Under Current Pre-Alarm
0
0(dis)
0
0
9999
3
99
9999
9980
dis
2
9999
AV
AV
0
0(dis)
0
0(dis)
0
0
0(dis)
9999
9999
9999
3
99
9999
9999
1
dis
5
dis
2
9999
9990
AV
AV
AV
AV
AV
Sec
Sec
Load
0 -
1 -
2 -
3 -
Under Current Actions
Disable
Warning (Alarm Only, No Shutdown)
Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
Shutdown (Alarm And Shutdown)
Load
0 -
1 -
2 -
3 -
Over Current Actions
Disable
Warning (Alarm Only, No Shutdown)
Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
Shutdown (Alarm And Shutdown)
9999
9999
9999
9999
9999
9999
kVA
kVA
kVA
kVA
0(dis)
0(dis)
0
0(dis)
0(dis)
0
Min Default
Max
Load PowerUnder Shutdown
Load PowerUnder Pre-Alarm
Load PowerUnder Pre-Alarm Reset
Load PowerOver Shutdown
Load PowerOver Pre-Alarm
dis
5
Load PowerOver Pre-Alarm Reset
kVA
kVA
Under shutdownpower
Under prealarmpower
Under resetpower
Over shutdownpower
Over prealarmpower
Over resetpower
Unit
Shutdown delay time
Reverse power set
Reverse power act.
Rv.pow.act.delay time
Load Power Shutdown Delay Time
Reverse Power Set
Reverse Power Action Delay Time
LOAD POWER LEVEL (Load )->Power level
0
-9999
0(dis)
0
99
0
3
99
2
0
0(dis)
2
Sec
kW
Sec
dis
dis
0
dis
Reverse Power Actions
Disable
Warning (Alarm Only, No Shutdown)
Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
Shutdown (Alarm And Shutdown)
0 -
1 -
2 -
3 -
4.2.4 Load
Min Default Unit
SOURCE 2 (Source 2 )ACTIONS ->Actions Max
Look Failure at Stop Mode En/DisSource 2
Always Look Source 2 Return Delay
Source 2 return delay
Source 2 fail dlelay
S2 fail.stop mode
S2 always return delay
S2 return delay
S2 fail delay
ENABL/DISBL
ENABL/DISBL
ENABL
DISBL
sec
sec
0
0
99
99
2
2
Note: dis = disable

4.2.5 Power Supply
10
Min Default
Max
Working Calendar Disable or Enable
Working Calendar Work Start Time on Monday
Working Calendar Work Stop Time on Monday
Working Calendar Work Start Time on Tuesday
Working Calendar Work Stop Time on Tuesday
Working Calendar Work Start Time on Wednesday
Working Calendar Work Start Time on Thursday
Working Calendar Work Start Time on Friday
Working Calendar Work Start Time on Saturday
Working Calendar Work Start Time on Sunday
Disable/enable select
Start time on monday
Stop time on monday
Start time on tues.
Stop time on tuesday
Start time on wednes.
Start time on thurs.
Start time on friday
Start time on satur.
Start time on sunday
Unit
Stop time on wednes.
Stop time on thursday
Stop time on friday
Stop time on saturday
Stop time on sunday
Working Calendar Work Stop Time on Wednesday
Working Calendar Work Stop Time on Thursday
Working Calendar Work Stop Time on Friday
Working Calendar Work Stop Time on Saturday
Working Calendar Work Stop Time on Sunday
WORKING CALENDAR (Engine )->Working calendar
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
23.59
23.59
23.59
23.59
23.59
23.59
23.59
DISBL ENABL/ DISBL
Min Default
ENGINE PLANT BATTERY ( )Engine->Plant battery Max
Battery Undervolts Warning
Battery Undervolts Warning Reset
Battery Undervolts Volts Delay
Battery Overvolts Warning
10.0
Battery Overvolts Warning Reset
6.0(dis) 30.0
10.5
6.0
1.0
0.0 9.9
30.0
29.5
30.0
30.0
6.0 30.0
Battery Overvolts Delay 1.0
0.0 9.9
6.0(dis)
Under volt
Under volt reset
Under volt delay
Over volt
Over volt reset
Over volt delay
Unit
VZ
VZ
VZ
VZ
Sec
Sec
Min Default
EXERCISE ( )Engine->Exercise Max
0(dis) 99 dis
1
7
0.0 23.59 0.00
1
Time of Period
Week
Start time
Generator exercise working period on related day
Generator exercise working day of week
Generator exercise work start time on related day
Unit
Min
H.Min
Min Default
LOAD TEST ( )Engine->Load test Max Unit
1-NO LOAD
Disable/enable select Disable, No Load or On Load Selection 0-DISABLE
1-NO LOAD
2-ON LOAD
4.2.6 Engine
Sec
Min Default Unit
ENGINE START OPTIONS ( )Engine->Starting options Max
Number Of Start Attempts
Cranking Time
Crank Rest Time
3
5
1
1
10
99
10
5 99
No. of crank attemp
Cranking time
Crank rest time Sec
Min Default Unit
ENGINE GENERAL ( )Engine->General Max
Stop Solenoid Time 1 1099
Stop solenoid time Sec
Engine Running Voltage 60(dis)
25.0
300
30.0
600
75.0
Engine Running Frequency
Engine running volt
Engine running freq.
VV
Hz

11
Note-1 :
Note-2 :
Note-3 :
x = 1(input-1), 2(input-2), 3(input-3), 4(input-4), 5(input-5), 6(input-6), 7(input-7) or 8(input-8)
25 - Emergency Stop (for only input-1)
dis = disable
Min Default Unit
CONF. INPUT-X ( )Inputs->Conf. input-x Max
20(dis)
10
4
20
0
2500 Sec
0
Dis,user conf.or list
Polarity
Indication
Activation
Select from list
Active delay
0- Disable
1- User Configured
2- Select From List
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
If User Configured
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
If User Configured
0- Active From Starting
1- Active From Safety On
2- Always Active
Input active delay
in =27
in2=26
in3=26
in4=26
in5=26
in6=26
in7=26
In8=26
1 In =27
in2=13
In3=11
in4=19
in5=3
in6=7
In7=23
in8=24
1
in1=2
in2,3=0
in4, 5=0
in6,7=0
in8=0
in1=0
in2=0
in3=4
in4=0
in5=0
in6=0
in7=0
in8=0
in1, 2=2
in3, 4=2
in5, 6=2
in7, 8=2
in1=0
in2, 3, 4=1
in5, 6, 7=1
In8=1
in1, 3=1
in2, 4=0
in5, 6=0
in7, 8=0
If Select From List
0-Remote Start On Load
1-Remote Start Off Load
2-Auxiliary S1 Fail
3-Auxiliary S2 Fail
4-Simulate Horn Reset Button
5-Simulate Alarm Reset Button
6-Simulate Auto Button
7-Simulate Test Button
8-Simulate Manual Button
9-Simulate Start Button
10-Simulate Stop Button
11-S2 Closed Auxiliary
12-S2 Load Inhibit
13-S1 Closed Auxiliary
14-S1 Load Inhibit
15-Auto Restore Inhibit
16-Auto Start Inhibit
17-Panel Lock
18-Scheduled Run Inhibit
19-Reserved
20-Transfer Source 1 To Source 2
21-Transfer Source 2 To Source 1
22-Remote Inhibit
23-Auxiliary S1 Ready
24-Auxiliary S2 Ready
25-Simulate S1 Available
26-Simulate S2 Available
27-Emergency Stop (for only input-1)
4.2.7 Inputs

12
Min Default Unit
Max
0
2
20(dis)
10
4
20
2
2500 Sec
0
1
0
21 2
5
0- Disable
1- User Configured
2- Select From List
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
If User Configured
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
If User Configured
0- Active From Starting
1- Active From Safety On
2- Always Active
If Select From List
2-Auxiliary S1 Fail
3-Auxiliary S2 Fail
4-Simulate Horn Reset Button
5-Simulate Alarm Reset Button
6-Simulate Auto Button
7-Simulate Test Button
8-Simulate Manual Button
9-Simulate Start Button
10-Simulate Stop Button
11-S2 Closed Auxiliary
12-S2 Load Inhibit
13-S1 Closed Auxiliary
14-S1 Load Inhibit
15-Auto Restore Inhibit
16-Auto Start Inhibit
17-Panel Lock
18-Scheduled Run Inhibit
19-Reserved
20-Transfer Source 1 To Source 2
21-Transfer Source 2 To Source 1
Input active delay
010
0- ( To )
1- ( To )
> -Ve Switched Battery -
> +Ve Switched Battery +
CONF. EXP. INPUT-X ( )Inputs->Conf. exp. input-x
Dis,user conf.or list
Polarity
Indication
Activation
Select from list
Active delay
Hardware type
Note-1 : x = 1(exp. input ), 2( ), 3( ), 4( ), 5( ), 6(
)
exp. input exp. input exp. input exp. input exp.
input , 7(exp. input ) or 8(exp. input )
dis = disableNote-2 :
-1 -2 -3 -4 -5
-6 -7 -8

13
Min Default Unit
CONF. OUTPUT-1 ( )Outputs->Conf. output-1 Max
010
1290 71
Polarity
Function
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
4.2.8 Outputs
0-NOT USED
1-AIR FLAP CONTROL
2-ALARM RESET
3-AUDIBLE ALARM
4-AUTO START INHIBIT
5-AUXILIARY SOURCE 1 FAILURE
6-BATTERY HIGH VOLTAGE
7-BATTERY LOW VOLTAGE
8-CALLING FOR SCHEDULED RUN(EXERCISE)
9-AUXILIARY SOURCE 2 FAILURE
10-RESERVED
11-RESERVED
12-COMMON ALARM
13-COMMON ELECTRICAL TRIP ALARM
14-COMMON SHUTDOWN ALARM
15-COMMON WARNING ALARM
16-RESERVED
17-RESERVED
18-RESERVED
19-SOURCE 1 CRANK RELAY ENERGISED (For generator application)
20-COOLING DOWN TIMER IN PROGRESS
21-SOURCE 2 CRANK RELAY ENERGISED (For generator application)
22-DELAYED ALARM ACTIVE
23-DIGITAL INPUT1 ACTIVE
24-DIGITAL INPUT2 ACTIVE
25-DIGITAL INPUT3 ACTIVE
26-DIGITAL INPUT4 ACTIVE
27-DIGITAL INPUT5 ACTIVE
28-DIGITAL INPUT6 ACTIVE
29-DIGITAL INPUT7 ACTIVE
30-EXPANSION INPUT1 ACTIVE
31-EXPANSION INPUT2 ACTIVE
32-EXPANSION INPUT3 ACTIVE
33-EXPANSION INPUT4 ACTIVE
34-EXPANSION INPUT5 ACTIVE
35-EXPANSION INPUT6 ACTIVE
36-EXPANSION INPUT7 ACTIVE
37-EXPANSION INPUT8 ACTIVE
38-DIGITAL INPUT8 ACTIVE
39-EMERGENCY STOP
40-FAILED TO START SOURCE 2 (For generator application)
41-FAILED TO STOP SOURCE 2(For generator application)
42-FAILED TO START SOURCE 1 (For generator application)
43-FAILED TO STOP SOURCE 1(For generator application)
44-RESERVED
45-SOURCE 2 AT REST(For generator application)
46-SOURCE 2 AVAILABLE
47-SOURCE 2 CLOSED AUXILIARY
48-SOURCE 2 FAIL TO CLOSE
49-SOURCE 2 FAIL TO OPEN
50-SOURCE 2 HIGH FREQUENCY
51-SOURCE 2 FAILURE
52-SOURCE 2 HIGH VOLTAGE
53-RESERVED
54-SOURCE 2 LOAD INHIBIT
55-SOURCE 2 LOW FREQUENCY
56-RESERVED
57-SOURCE 2 LOW VOLTAGE
58-RESERVED
59-SOURCE 2 STOPPING(For generator application)
60-SOURCE 2 OPEN BREAKER
61-HORN OUT LATCHED
62-HORN OUT PULSED
63-LAMP TEST
64-RESERVED
65-SOURCE 1 AVAILABLE
66-SOURCE 1 AT REST (For generator application)
67-SOURCE 1 STOPPING (For generator application)
68-SOURCE 1 CLOSED AUXILIARY
69-SOURCE 1 FAIL TO CLOSE
70-SOURCE 1 FAIL TO OPEN
71-SOURCE 1 FAILURE
72-SOURCE 1 HIGH FREQUENCY
73-SOURCE 1 HIGH VOLTAGE
74-SOURCE 1 LOAD INHIBIT
75-SOURCE 1 LOW FREQUENCY
76-SOURCE 1 LOW VOLTAGE
77-SOURCE 1 OPEN BREAKER
78-SOURCE 2 NO LOADING COMMAND
79-SOURCE 1 NO LOADING COMMAND
80-SOURCE 1 OVER CURRENT PREALARM
81-SOURCE 1 OVER CURRENT
82-SOURCE 1 OVER POWER PREALARM
83-SOURCE 2 OVER CURRENT PREALARM
84-SOURCE 2 OVER CURRENT
85-SOURCE 2 OVER POWER PREALARM
86-SOURCE 2 OVER POWER SHUTDOWN
87-SOURCE 1 OVER POWER SHUTDOWN
88-RESERVED
89-PANEL LOCK
90-RESERVED
91-RESERVED
92-RESERVED
93-REMOTE START SOURCE 1 (For generator application)
94-REMOTE START SOURCE 2 (For generator application)
95-SOURCE 1 SHORT CIRCUIT
96-SOURCE 2 SHORT CIRCUIT
97-RESERVED
98-SOURCE 1 STOP RELAY ENERGISED (For generator application)
99-STARTING ALARM ARMED
100-SOURCE 2 STOP RELAY ENERGISED (For generator application)
101-SYSTEM AUTO MODE
102-SYSTEM MANUAL MODE
103-SYSTEM STOP MODE
104-SYSTEM TEST MODE
105-SOURCE 2 UNDER CURRENT PREALARM
106-SOURCE 2 UNDER CURRENT
107-SOURCE 2 UNDER POWER PREALARM
108-SOURCE 2 UNDER POWER SHUTDOWN
109-RESERVED
110-WAITING FOR SOURCE 1 (For generator application)
111-WAITING FOR SOURCE 2 (For generator application)
112-RESERVED
113-LOAD SUPPLY SOURCE 2
114-LOAD SUPPLY SOURCE 1
115-SOURCE 1 UNDER CURRENT PREALARM
116-SOURCE 1 UNDER CURRENT
117-SOURCE 1 UNDER POWER PREALARM
118-SOURCE 1 UNDER POWER SHUTDOWN
119-RESERVED
120-RESERVED
121-RESERVED
122-REMOTE CONTROL ACTIVE
123-SOURCE 2 REVERSE POWER
124-SOURCE 1 REVERSE POWER
125-RESERVED
126-RESERVED
127-RESERVED
128-RESERVED
129-REMOTE OUTPUT

14
Min
Min
Min
Min
Min
Min
Min
Min
Min
Min
Min
Default
Default
Default
Default
Default
Default
Default
Default
Default
Default
Default
Unit
Unit
Unit
Unit
Unit
Unit
Unit
Unit
Unit
Unit
Unit
Max
Max
Max
Max
Max
Max
Max
Max
Max
Max
Max
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
129
129
129
129
129
129
129
129
129
129
129
0
0
0
0
0
0
0
0
0
0
0
51
62
12
93
94
12
12
12
12
12
12
The same as Configurable Output-1 options
The same as Configurable Output-1 options
The same as Configurable Output-1 options
The same as Configurable Output-1 options
The same as Configurable Output-1 options
The same as Configurable Output-1 options
The same as Configurable Output-1 options
The same as Configurable Output-1 options
The same as Configurable Output-1 options
The same as Configurable Output-1 options
The same as Configurable Output-1 options
CONF. OUTPUT-2 ( )Outputs->Conf. output-2
CONF. OUTPUT-3 ( )Outputs->Conf. output-3
CONF. OUTPUT-4 ( )Outputs->Conf. output-4
CONF. OUTPUT-5 ( )Outputs->Conf. output-5
CONF. OUTPUT-6 ( )Outputs->Conf. output-6
CONF. EXP. OUTPUT-1 ( )Outputs->Conf. exp. output-1
CONF. EXP. OUTPUT-2 ( )Outputs->Conf. exp. output-2
CONF. EXP. OUTPUT-3 ( )Outputs->Conf. exp. output-3
CONF. EXP. OUTPUT-4 ( )Outputs->Conf. exp. output-4
CONF. EXP. OUTPUT-5 ( )Outputs->Conf. exp. output-5
CONF. EXP. OUTPUT-6 ( )Outputs->Conf. exp. output-6
Polarity
Polarity
Polarity
Polarity
Polarity
Polarity
Polarity
Polarity
Polarity
Polarity
Polarity
Function
Function
Function
Function
Function
Function
Function
Function
Function
Function
Function
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)

15
Min Default
START TIMERS ( )Timers->Start timers Max
Remote Start Delay
Generator fail delay
4
0 3600
45
0 250
Horn Duration 60
0 (dis) 999
Remote start delay
Generator fail delay
Horn duration
Generator Start Delay 0
0 9999
Generator start dely
Unit
Sec
Sec
Sec
Sec
4.2.9 Timers
Warmup Time
5
0 250
Warming up time Sec
Note: dis = disable
Min Default
STOPPING TIMERS ( )Timers->Stopping timers Max
Remote Stop Delay
Cooling Time
4
0 250
60
0 (dis) 3600
Fail To Stop Time 30
15 999
Remote stop delay
Cooling time
Fail to stop delay
Unit
Sec
Sec
Sec
4.2.10 Expansion Modules
DIAL-UP & ETHERNET ( )Expansion modules->Dial-up & Ethernet
Expansion Module SelectionDal-up&Ethernet
Call Back Selection
Disable/enable select
Call back selection
Min Default
Max
DISBL
DISBL
ENABL/DISBL
ENABL/DISBL
Unit
Min
Min
Default
Default
Unit
Unit
Max
Max
0
0
1
1
0
0
129
129
0
0
12
12
The same as Configurable Output-1 options
The same as Configurable Output-1 options
CONF. EXP. OUTPUT-7 ( )Outputs->Conf. exp. output-7
CONF. EXP. OUTPUT-8 ( )Outputs->Conf. exp. output-8
Polarity
Polarity
Function
Function
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
Can Fault Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
0
0 2
0
0(dis) 4
CAN fault activation
CAN fault actions
SecCan Fault Delay 10
2 250
CAN fault delay
Can Fault Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
IO (1-8) MODULE ( )Expansion modules->IO (1-8)
Expansion I/O Module Selection
Disable/enable select
Default
Max
Min
DISBL
ENABL/DISBL
Unit

16
4.2.11 User Adjustment
Min Default Unit
SOURCE 1 VOLTAGE OFFSET ( )User adjustment->Source 1 voltage offset Max
0
0
0
-20
-20
-20
Source 1 V1 offset
Source 1 2V offset
Source 1 3V offset
Source 1 V1 Offset
Source 1 2V Offset
Source 1 3V Offset
20
20
20
VV
VV
VV
Min Default Unit
SOURCE 2 VOLTAGE OFFSET ( )User adjustment->Source 2 voltage offset Max
0
0
0
-20
-20
-20
Source 2 V1 offset
Source 2 2V offset
Source 2 3V offset
Source 2 V1 Offset
Source 2 2V Offset
Source 2 3V Offset
20
20
20
VV
VV
VV
Min Default Unit
CURRENT OFFSET ( )User adjustment-> offsetCurrent Max
0
0
0
-20
-20
-20
Current I1 offset
Current I offset2
Current I offset3
Current I1 Offset
Current I Offset2
Current I Offset3
20
20
20
AV
AV
AV
Min Default Unit
BATTERY OFFSET ( )User adjustment->Battery offset Max
0- 05.
Batt.volt offset
Battery Voltage Offset
5.0
VZ
GPRS MODULE ( )Expansion modules->GPRS
Expansion Module SelectionGPRS
Call Back Selection
Cell info refresh rate
Location data
Location warning
Disable/enable select
Call back selection
Cell inf refresh rate
Location data
Location warning
Min Default
Max
1- SERVERGPRS
DISBL
2
1(dis)
0-DISABLE
1- SERVER
2- CLIENT
3-SMS
GPRS
GPRS
ENABL/DISBL
0(dis)
1(dis)
Unit
999
999
Min
Km
DISBL
ENABL/DISBL
GPRS WEB MODULE (Expansion modules->GPRS Web)
GPRS-Web Module Selection
Disable/enable select
Min Default
Max
ENABL
ENABL/DISBL
Unit

Error Messages And Explanations:
Battery high warning! : Battery high error
Battery low warning! : Battery low error
Can bus warning! : Can bus error
Emergency stop! : Emergency stop error
Exp.spare-1 alarm! : Expansion module spare 1 error
Exp.spare-2 alarm! : Expansion module spare 2 error
Exp.spare-3 alarm! : Expansion module spare 3 error
Exp.spare-4 alarm! : Expansion module spare 4 error
Exp.spare-5 alarm! : Expansion module spare 5 error
Exp.spare-6 alarm! : Expansion module spare 6 error
Exp.spare-7 alarm! : Expansion module spare 7 error
Exp.spare-8 alarm! : Expansion module spare 8 error
S1 fail to start! : Fail to start alarm for Source 1 (for generator application)
S1 ready! : Source 1 is ready (for generator application)
S1 stop fail! : Source 1 stop error (for generator application)
S2 fail to start! : Fail to start alarm for Source 2 (for generator application)
S2 ready! : Source 2 is ready (for generator application)
S2 stop fail! : Source 2 stop error (for generator application)
S1 Over cur. prealr! : Over current pre-alarm for source 1
S1 Over cur. warn.! : Over current warning for source 1
S1 Over current trip! : Over current error for source 1
S1 Over pow. prealr! : Over power error for source 1
S1 Over power trip! : Over power Error for source 1
S1 Ovr cur.trip cool! : Over current electrical trip for source 1
S1 Rev. power warnng! : Reverse power Warning for source 1
S1 Rev.pow.trip cool! : Reverse power Electrical Trip for source 1
S1 Rever. power trip! : Reverse power Error for source 1
S1 Short cir. trip! : Short circuit error for source 1
S1 Und.cur.trip cool! : Under current electrical trip for source 1
S1 Under cur. prealr! : Under current pre-alarm for source 1
S1 Under cur. trip!: Under Current Error for source 1
S1 Under cur. warnng! : Under Current Warning for source 1
S1 Under pow. prealr! : Under power prealarm for source 1
S1 Under pow. trip! : Under power Error for source 1
S1 break.close fail! : Source 1 breaker not closed alarm
S1 breaker open fail! : Source 1 breaker not opened alarm
S1 over frequency! : Source 1 over frequency
S1 over voltage! : Source 1 over voltage
S1 phase seq.wrong! : Source 1 phase sequence wrong
S1 under frequency! : Source 1 under frequency
S1 under voltage! : Source 1 under voltage
S2 Over cur. prealr! : Over current pre-alarm for source 2
S2 Over cur. warn.! : Over current warning for source 2
S2 Over current trip! : Over current error for source 2
S2 Over pow. prealr! : Over power error for source 2
S2 Over power trip! : Over power Error for source 2
S2 Ovr cur.trip cool! : Over current electrical trip for source 2
S2 Rev. power warnng! : Reverse power Warning for source 2
S2 Rev.pow.trip cool! : Reverse power Electrical Trip for source 2
S2 Rever. power trip! : Reverse power Error for source 2
S2 Short cir. trip! : Short circuit error for source 2
S2 Und.cur.trip cool! : Under current electrical trip for source 2
S2 Under cur. prealr! : Under current pre-alarm for source 2
S2 Under cur. trip!: Under Current Error for source 2
S2 Under cur. warnng! : Under Current Warning for source 2
S2 Under pow. prealr! : Under power prealarm for source 2
S2 Under pow. trip! : Under power Error for source 2
S2 break.close fail! : Source 2 breaker not closed alarm
S2 breaker open fail! : Source 2 breaker not opened alarm
S2 over frequency! : Source 2 over frequency
S2 over voltage! : Source 2 over voltage
S2 phase seq.wrong! : Source 2 phase sequence wrong
S2 under frequency! : Source 2 under frequency
S2 under voltage! : Source 2 under voltage
Source 1 fail! : Source 1 error
Source 2 fail! : Source 2 error
Spare-1 alarm! : Spare 1 error
Spare-2 alarm! : Spare 2 error
Spare-3 alarm! : Spare 3 error
Spare-4 alarm! : Spare 4 error
Spare-5 alarm! : Spare 5 error
Spare-6 alarm! : Spare 6 error
Spare-7 alarm! : Spare 7 error
Spare-8 alarm! : Spare 8 error
17

Event Messages And Explanations:
Battery high warning : Battery high error
Battery low warning : Battery low error
Can bus warning : Can bus error
Changed mode to auto : Changed mode to auto
Changed mode to man : Changed mode to manual
Changed mode to stop : Changed mode to off
Changed mode to test : Changed mode to test
Emergency stop : Emergency stop error
Exp.spare-1 alarm : Expansion module spare 1 error
Exp.spare-2 alarm : Expansion module spare 2 error
Exp.spare-3 alarm : Expansion module spare 3 error
Exp.spare-4 alarm : Expansion module spare 4 error
Exp.spare-5 alarm : Expansion module spare 5 error
Exp.spare-6 alarm : Expansion module spare 6 error
Exp.spare-7 alarm : Expansion module spare 7 error
Exp.spare-8 alarm : Expansion module spare 8 error
S1 fail to start alrm : Fail to start source 1 (for generator application)
S2 fail to start alrm : Fail to start source 2 (for generator application)
GPRS IP not found : Gprs no IP alarm
GPRS reset fail : Gprs reset fail
S1 stop fail : Source 2 stop error (for generator application)
S2 stop fail : Source 2 stop error (for generator application)
Modem response: error : Gprs error response alarm
No respons.from modem : Gprs no response alarm
S1 Over cur. prealr! : Over current pre-alarm for source 1
S1 Over current alarm : Over current alarm for source 1
S1 Over pow. alarm : Over power error for source 1
S1 Over pow. prealarm : Over power pre-alarm for source 1
S1 Reverse pow. alarm : Reverse power alarm for source 1
S1 Short circuit alrm : Short circuit alarm for source 1
S1 Under cur. alarm : Under current error for source 1
S1 Under cur. prealr : Under current pre-alarm for source 1
S1 Under pow. alarm : Under power error for source 1
S1 Under pow.prealarm : Under power pre-alarm for source 1
S1 break.close fail : Source 1 breaker not closed alarm
S1 breaker open fail : Source 1 breaker not opened alarm
S1 over frequency : Source 1 over frequency
S1 over voltage : Source 1 over voltage
S1 phase seq.wrong : Source 1 phase sequence wrong
S1 under frequency : Source 1 under frequency
S1 under voltage : Source 1 under voltage
S2 Over cur. prealr! : Over current pre-alarm for source 2
S2 Over current alarm : Over current alarm for source 2
S2 Over pow. alarm : Over power error for source 2
S2 Over pow. prealarm : Over power pre-alarm for source 2
S2 Reverse pow. alarm : Reverse power alarm for source 2
S2 Short circuit alrm : Short circuit alarm for source 2
S2 Under cur. alarm : Under current error for source 2
S2 Under cur. prealr : Under current pre-alarm for source 2
S2 Under pow. alarm : Under power error for source 2
S2 Under pow.prealarm : Under power pre-alarm for source 2
S2 break.close fail : Source 2 breaker not closed alarm
S2 breaker open fail : Source 2 breaker not opened alarm
S2 over frequency : Source 2 over frequency
S2 over voltage : Source 2 over voltage
S2 phase seq.wrong : Source 2 phase sequence wrong
S2 under frequency : Source 2 under frequency
S2 under voltage : Source 2 under voltage
SMS was not sent : Sms wasn't sent
SMS was sent : Sms was successfully sent
Source 1 OK : Source 1 OK
Source 1 fail : Source 1 error
Source 2 OK : Source 2 OK
Source 2 fail : Source 1 error
Spare-1 alarm : Spare 1 error
Spare-2 alarm : Spare 2 error
Spare-3 alarm : Spare 3 error
Spare-4 alarm : Spare 4 error
Spare-5 alarm : Spare 5 error
Spare-6 alarm : Spare 6 error
Spare-7 alarm : Spare 7 error
Spare-8 alarm : Spare 8 error
18

19
5. Specifications
Equipment use
Housing & Mounting
Panel Cut-Out
Protection
Weight
Environmental rating
Operating/Storage Temperature
Operating/Storage Humidity
Installation Over Volt. Category
Pollution Degree
Mode of Operation
Cranking Dropouts
Battery Voltage Measurement
Source 1 Voltage Measurement
Source 1 Frequency
Source 2 Voltage Measurement
Source 2 Frequency
CT secondary
Communication interface
Optional Expansion I/O Module
Optional Comm. Modules
Relay Outputs
Transistor Outputs
: Electrical control equipment for generating sets.
: 229 mm x 152 mm x 41 mm. (including connectors)
.
: 182mm x 135mm.
:
: Approximately 0,53 Kg.
:
with non-condensing humidity
: -20°C to +70°C / -30°C to +80°C
: 90 % max. (non-condensing)
: II Appliances, portable equipment
: II, Normal office or workplace, non conductive pollution
: Continuous.
: 8 to 32 V . Max. operating current is 360 mA.
: Battery voltage can be “0” VDC for max. 50 ms during
cranking (battery voltage should be at least nominal
voltage before cranking).
: 8 to 32 V , accuracy: 1 % FS, resolution: 0,1 V
: 3
Resolution: 1 V.
: 5 to 99.9Hz (min. 20 VAC Ph-N) Accuracy: 0,25 % FS,
Resolution: 0,1 Hz.
: 3
Resolution: 1 V.
: 5 to 99.9Hz (min. 20 VAC Ph-N) Accuracy: 0,25 % FS,
Resolution: 0,1 Hz.
: 5A.
: USB programming and communication port.
: Expansion I/O module including 8 inputs and 8 outputs.
: Ethernet/Dial-up, GSM/GPRS and Web Server modules.
: Source 1 contactor relay output 8A 250V
Source 2 contactor relay output 8A 250V
Configurable output-5 5A 250V
Configurable output-6 5A 250V
: Configurable output-1 1A at DC supply voltage
Configurable output-2 1A at DC supply voltage
Configurable output-3 1A at DC supply voltage
Configurable output-4 1A at DC supply voltage
All transistor ouputs supplied from DC supply terminal 22
. Plastic
housing for panel mounting
IP65 at front panel.
Standard, indoor at an altitude of less then 2000 meters
.
to 300 VAC Ph-N, 5 to 99.9 Hz. Accuracy: 1 % FS,
to 300 VAC Ph-N, 5 to 99.9 Hz. Accuracy: 1 % FS,
DC Battery Supply Voltage Z
Z
V
V
V
V
@
@
@
@

20
6. Other Informations
Manufacturer Information:
Emko Elektronik Sanayi ve Ticaret A.Þ.
Demirtaþ Organize Sanayi Bölgesi Karanfil Sk. No:6 16369
BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Repair and maintenance service information:
Emko Elektronik Sanayi ve Ticaret A.Þ.
Demirtaþ Organize Sanayi Bölgesi Karanfil Sk. No:6 16369
BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Thank you very much for your preference to use Emko Elektronik
products, please visit our web page to download detailed user
manual.
Your Technology Partner www.emkoelektronik.com.tr
Other manuals for TRANS-ATS.D
1
Table of contents
Other EMKO Switch manuals
Popular Switch manuals by other brands

ATEN
ATEN Master View CS-82A user manual

Comtrol
Comtrol RocketLinx ES8108 Quick installation guide

Comnet
Comnet CNGE11FX3TX8MS Installation and operation manual

Eaton
Eaton COOPER POWER LS4R Series installation instructions

Cypress
Cypress CHDMI-41AT Operation manual

Allied Telesis
Allied Telesis AT-8000S/48 datasheet